Presentation Electrical switchboards up to

630 A

System design has been validated by type tests as per standard


IEC 61439-1 & 2 and benefits from the combined experience of
Schneider Electric over many years.
PB115632_73.eps

Electrical characteristics
Comply with IEC 62208 and EN 62208 standards:
b rated insulation of main busbars at rear of enclosure:
1000 V
b InA: 630 A
b rated peak withstand current Ipk: 53 kÂ
b rated short-time withstand current Icw:
25 kA rms / 1 second
b short-circuit current: 50 kA
b frequency: 50/60 Hz.

Mechanical characteristics
b Steel sheet metal
b (OHFWURSKRUHVLVWUHDWPHQWKRWSRO\PHULVHGSRO\HVWHU
epoxy powder, white colour RAL 9001.
b Enclosures supplied in kit form, totally dismountable,
designed to be assembled and wired horizontally on a work
station.
b Can be combined side by side and one on top of another
b Degree of protection:
v IP30: without door
v IP40: with door
v ,3ZLWKGRRUFDQRS\
v ,3ZLWKGRRUJDVNHWFDQRS\
v IP55: IP55 Prisma G offer, supplied in kit form
b degree of protection against mechanical impacts:
v IK07: without door
Readly available close by v IK08: with door (transparent)
v IK10: with plain door
v IK10: for Prisma G IP55
The kit concept makes handling and transport easier
b Seismic characteristics: 2G without accessories
DQG\RXJHWWREHQH¿WIURP6FKQHLGHU(OHFWULF¶VHI¿FLHQW
b Enclosure dimensions:
international logistics. Your distributor, hand-picked by
v 3 widths:
Schneider Electric, can give you the very best advice.
- W = 300: duct
10 modules width
- : :DOOPRXQWHGDQGÀRRUVWDQGLQJHQFORVXUHV
24 modules width
- W = 850: Floor-standing enclosure
36 modules width
v depth with door:
- enclosures G IP30: 250 mm
- enclosures G IP55: 260 mm
v heights:
- Prisma G IP30: 12 heights: 330 mm to 1980 mm
- Prisma G IP55: 7 heights: 450 mm to 1750 mm
b Inside switchboards.

Electrical switchboards built using the Prisma functional system and


Schneider Electric recommendations fully comply with international standard
IEC 61439-1&2.

23
1 2 3 4 5 6 7 8 9 10

K88-P5-0037-06-MAT-ELE-450-0005-03
A
IJ dar al-handasah
Confirmation DATA sheet
lhair il1lf partnm

showing the BB S.C and Size 0


0
CON l: APPROVED
C®£ I: APPIOVED AS NOTED

to be delivered with MIR/ WIR.


IW MY IIICIIIIIIlKTlO
IIICOIINMtll Of EIIOIIID
B co.um.
D conE c: RlYISIAaiiSUBIIT
IOIIIIAY lOTPIOCUD
D COD! DI RE-JECTED
By:AKamar D•te:26-09-22
~ ......... Centrlctor

--............
of., of 1111 IJIIItils- the
Colltract. Clllllfllllllllltallall
C of..., . . . " Cenlract Deaalls.
Contrlctoris,...... ..

withotJ.trMn.

I
D
I
I
I
I

3 18-09-2022
08-09-2022 JOB ORDER Drawing No Scale Sheet Total Sheets
G 21-08-2022
07-08-2022
1 2 3 4 5 6 7 8 9 10

3 [typical]

G
1 2 3 4 5 6 7 8 9 10

G
1 2 3 4 5 6 7 8 9 10

G
1 2 3 4 5 6 7 8 9 10

Contractor is requested to coordinate


A the panel's dimensions with its relevant
spaces (room/closet)
1500mm
250mm
600mm 300mm 600mm

Electric Electric Electric

1380mm
1380

G
1 2 3 4 5 6 7 8 9 10

1500mm

600mm 300mm 600mm 600mm 300mm 600mm

1380mm
D

-Bus-bars rating, S.C, dimensions...shall be provided,


however bus-bar shall be included in the calculation note
verifying all c/c's (SC, rating, IP, range...)
-All panel components to withstand panel short circuit level
F

G
1 2 3 4 5 6 7 8 9 10

BB Data sheet does not include 20X5


A Clarify.

G
1 2 3 4 5 6 7 8 9 10

-Contractor/Supplier should coordinate with BMS/SCADA suppliers and system requirements and
B confirm compatibility of communication method/protocols, number and type of I/O points and should
also provide any necessary interfaces, relays, transducers, all terminals blocks, etc. necessary to
achieve proper system operation.

G
1 2 3 4 5 6 7 8 9 10

G
1 2 3 4 5 6 7 8 9 10

G
1 2 3 4 5 6 7 8 9 10

G
1 2 3 4 5 6 7 8 9 10

G
1 2 3 4 5 6 7 8 9 10

G
1 2 3 4 5 6 7 8 9 10

G
1 2 3 4 5 6 7 8 9 10

G
1 2 3 4 5 6 7 8 9 10

G
1 2 3 4 5 6 7 8 9 10

G
1 2 3 4 5 6 7 8 9 10

G
1 2 3 4 5 6 7 8 9 10

G
1 2 3 4 5 6 7 8 9 10

G
1 2 3 4 5 6 7 8 9 10

G
1 2 3 4 5 6 7 8 9 10

G
1 2 3 4 5 6 7 8 9 10

A
BILL OF MATERIALS

G
Transmittal to DAR (Shop Drawings)

To : From :
Dar-Al-Handasah MACC

Project Code Project Title Trans. No Date :


DAR S20066-K88
K88 - Project K88-5013-TR-SHD-ELE-0130 21-Sep-22
MACC 5013-P5
Discipline Action required
ARC CIV/STR ELE ICT VRD MEC Submittal for Approval
Submittal for Information

No. of
S/N Drawings Title / Description / Subject Drawings number
copies
K88-P5-0037-06-SDW-ELE-450-0601-03
1 BUILDING 0037 SWITCHBOARD B37-TK-LP 1
5013-2-450-0037-601-C_00
2

THIS LIST CONTINUES IN NEXT PAGE YES NO 


Submitted by :
ANM Soeab Document Control

Name Title Signature


Dar-Al-Handasah Use
S/N 1 2 3 4 5 6 7 8
Action Code B
Reviewed by WGhasoup
Action Code:
A: Reviewed - Work may proceed;
B: Reviewed with comments. Work may proceed subject to incorporation of comments:
C: Objection - Revise and resubmit. Work may not proceed;
D: Rejected
Special Instructions :

-Refer to comments on SDW and FSD.


-All comments shall be sorted out .

Reviewed by: Date:


Wael Ghasoup Sr. Elec. Eng. WGhasoup 28/9/2022
Name Title Signature
Signed off by: Date:
Raed Attaya Resident Engineer
28/9/2022
Name Title Signature
1 2
CLIENT :
NOTES : LEGEND :

PROJECT MANAGEMENT & COST CONSULTANCY :


A

REVISED AS PER UPDATED IFC


03 20/09/2022

IJ dar al-handasah REVISED AS PER CONSULTANT COMMENTS CONSULTANT DESIGN REVIEWER :


02 03/07/2022
REVISED AS PER CONSULTANT COMMENTS
lhair il1lf partnm 01 20/06/2022
FIRST ISSUE
00 09/03/2022
0 CON l: APPROVED
REV.
0 C®£ I: APPIOVED AS NOTED NO. DESCRIPTION DATE
IW MY IIICIIIIIIlKTlO
IIICOIINMtll Of EIIOIIID
co.um. SHOP DRAWING DESIGNER :
D conE c: RlYISIAaiiSUBIIT
IOIIIIAY lOTPIOCUD
D COD! DI RE-JECTED CIVIL/LS ARCHITECT STRUCTURAL
By:WGhasoup D•te: 28/9/22
- - -
~ ......... Centrlctor

--............
of., of 1111 IJIIItils- the
Colltract. Clllllfllllllllltallall ELECTRICAL MECHANICAL ICT
of..., . . . " Cenlract Deaalls.
B Contrlctoris,...... ..
- - - CONTRACTOR :
withotJ.trMn. DRAWN BY CHECKED BY APPROVED BY

I O.B M.AMER O.I

I -Refer to comments on SDW and FSD. SITE KEY PLAN :


MODERN ARCH

-All commens shall be fulfilled.


I
I SUBCONTRACTOR :
I
N

BUILDING KEY PLAN :


N
BUILDING 0037 5013 2 450 0037 601 C_00
PROJECT CODE PHASE TRADE BUILDING DOC. NUMBER REVISION
PROJECT TITLE : DRAWING TITLE :

C K88_PROJECT BUILDING 0037


BUILDING NUMBER & NAME : SWITCHBOARD
0037 B37-TK-LP
SCALE - SHEET SIZE DATE CAD FILE
CENTRAL PRODUCTION NTS 09/03/2022 K88-P5-0037-06-SDW-ELE-450-0601-03

BUILDING 0037 DOCUMENT NUMBER :


K88 P5 0037 06 SDW ELE 450 0601 03
PROJECT PROGRAM BUILDING PHASE DOC. TYPE DISCIPLINE TRADE DOC. NUMBER REVISION

1 2
?
NSX100N Micrologic 2.2
100A, 3P-3D

back up calculation shall be


4 provided

VD% = 0.21
(4Cx10mm² + 1Cx10mm² (G)) L = 10m
refer comment on revision-1
and fulfill, however back up

CU/XLPE/LS0H + CU/PVC
calculation for SC and VD shall
be provided

37-UPS
LOAD: 15 KVA
3
loads shall be provided [typical]
2x2.5 2X10A

16
DRY STORE + POULTRY PREP + MEAT PREP 180 - - 180 LS0H 3G2.5 2X16A TK-LP-L1 IC60N

0.08
2.22
PUSH BUTTON - - - - LS0H 2x2.5 - TK-LP-L2T -
T

28
CORRIDOR - 452 - 452 LS0H 3G2.5 2X16A TK-LP-L2 IC60N

0.14
2.28
1X16A

24
EMERGENCY LIGHTING - - - - LS0H 5x2.5 - TK-LP-L2S -

0.01
2.15

AMBIANT LIGHTING - - - - LS0H 2x2.5 - TK-LP-L2A -

PUSH BUTTON - - - - LS0H 2x2.5 - TK-LP-L3T -


T

26

CORRIDOR - - 240 240 LS0H 3G2.5 2X16A TK-LP-L3 IC60N


0.17
2.31
1X16A

AMBIANT LIGHTING - - - - LS0H 2x2.5 - TK-LP-L3A -


33

BEVERAGE STORE 60 - - 60 LS0H 3G2.5 2X16A TK-LP-L4 IC60N


0.05
2.19

PUSH BUTTON - - - - LS0H 2x2.5 - TK-LP-L5T -


T

50

DINING ROOM - 452 - 452 LS0H 3G2.5 2X16A TK-LP-L5 IC60N


0.57
2.71
1X16A

36

EMERGENCY LIGHTING - - - - LS0H 5x2.5 - TK-LP-L5S -


0.02
2.16

AMBIANT LIGHTING - - - - LS0H 2x2.5 - TK-LP-L5A -

be provided with RCD [typical]

PUSH BUTTON - - - - LS0H 2x2.5 - TK-LP-L6T -


T

41

DINING ROOM - - 384 384 LS0H 3G2.5 2X16A TK-LP-L6 IC60N


0.42
2.56
1X16A

AMBIANT LIGHTING - - - - LS0H 2x2.5 - TK-LP-L6A -


circuits serving wet areas/kitchen/toilets shall
46

TOILETS MALE 150 - - 150 LS0H 3G2.5 2X16A TK-LP-L7 IC60N


0.18
2.32

45

TOILETS FEMALE 150 - - 150 LS0H 3G2.5 2X16A TK-LP-L8 IC60N


0.18
2.32

PUSH BUTTON - - - - LS0H 2x2.5 - TK-LP-L9T -


T

31

KITCHEN - - 300 300 LS0H 3G2.5 2X16A TK-LP-L9 IC60N


0.24
2.38
1X16A

31

EMERGENCY LIGHTING - - - - LS0H 5x2.5 - TK-LP-L9S -


0.01
2.15

AMBIANT LIGHTING - - - - LS0H 2x2.5 - TK-LP-L9A -

PUSH BUTTON - - - - LS0H 2x2.5 - TK-LP-L10T -


T

34

KITCHEN 144 - - 144 LS0H 3G2.5 2X16A TK-LP-L10 IC60N


0.13
2.27
1X16A

AMBIANT LIGHTING - - - - LS0H 2x2.5 - TK-LP-L10A -


provided e.g. (fixtures ...etc.),

fixtures per circuit matching the


approved lighting SDW [typical]
the approved material submittal

indicate number, type, load... of


moreover load designation shall
reference for mentioned loads to be
26
SEAFOOD PREP + FRUIT & VEG PREP - 156 - 156 LS0H 3G2.5 2X16A TK-LP-L11 IC60N

0.11
2.25
RECEIVING+DISPATCH OFFICE + WASTE ROOM - - 348 348 LS0H 3G2.5 2X16A TK-LP-L12 IC60N

32
0.29
2.43
+ RECEIVING. DEBOX & SANITIZATION

40
TROLLEY PARKING AREA + OS&E STORE 318 - - 318 LS0H 3G2.5 2X16A TK-LP-L13 IC60N

0.34
2.48
CHEF OFFICE

44
DISH&POT WASH AREA + DISHES DROP-OFF - 248 248 LS0H 3G2.5 2X16A 0.28 TK-LP-L14 IC60N
2.42

45
EMERGENCY LIGHTING - - - - LS0H 5x2.5 - TK-LP-L14S -
0.01
2.15

PUSH BUTTON - - - - LS0H 2x2.5 - TK-LP-L15T -


T

40

CORRIDOR - 144 - 144 LS0H 3G2.5 2X16A TK-LP-L15 IC60N


0.15
2.29
1X16A

EMERGENCY LIGHTING - - - - LS0H 5x2.5 - TK-LP-L15S -

AMBIANT LIGHTING - - - - LS0H 2x2.5 - TK-LP-L15A -

PUSH BUTTON - - - - LS0H 2x2.5 - TK-LP-L16T -


T

39

CORRIDOR - - 96 96 LS0H 3G2.5 2X16A TK-LP-L16 IC60N


0.10
2.24
1X16A

59

TOILET + STAFF CHANGING FACILITY - 225 - 225 LS0H 3G2.5 2X16A TK-LP-L17 IC60N
0.35
2.49

EMERGENCY LIGHTING - - - - LS0H 5x2.5 - TK-LP-L17S -

PUSH BUTTON - - - - LS0H 2x2.5 - TK-LP-L18T -


T

40

BEVERAGE STATION + CORRIDOR - - 300 300 LS0H 3G2.5 2X16A TK-LP-L18 IC60N
0.30
2.44
1X16A

44

EMERGENCY LIGHTING - - - - LS0H 5x2.5 - TK-LP-L18S -


0.01
2.15

AMBIANT LIGHTING - - - - LS0H 2x2.5 - TK-LP-L18A -


49

ROOF (Controlled by Photo Cell & Timer) - 150 - 150 LS0H 3G2.5 2X16A TK-LP-L19 IC60N
0.19
2.33

56

ROOF (Controlled by Photo Cell & Timer) 210 - - 210 LS0H 3G2.5 2X16A TK-LP-L20 IC60N
0.31
2.45

FEMALE TOILETS MIRROR - LIGHTING 50 - - 50 LS0H 3G2.5 2X16A TK-LP-L21 IC60N


53
0.07
2.21

MALE TOILETS MIRROR - LIGHTING - - 50 50 LS0H 3G2.5 2X16A TK-LP-L22 IC60N


54
0.07
2.21

TOILETS MIRROR - LIGHTING - - 50 50 LS0H 3G2.5 2X16A TK-LP-L23 IC60N


55
0.07
2.21

UNEQUIPPED SPARE - - - - - - - - -

- -
UNEQUIPPED SPARE - - - - - - -

- -
UNEQUIPPED SPARE - - - - - - -

- -
UNEQUIPPED SPARE - - - - - - -
provided [typical]
control wiring shall be
spare shall be provided)
apre circuits [typical] (min. 20%
16A, breakers shall be added for
RECEIVING +DISPATCH OFFICE 680 - - 680 LS0H 3G2.5 2X16A TK-LP-S1 IC60N

33
0.59
2.73
SOCKETS
30mA

CHEF OFFICE - 680 - 680 LS0H 3G2.5 2X16A TK-LP-S2 IC60N

45
0.8
2.94
SOCKETS
30mA

DINING ROOM - 680 - 680 LS0H 3G2.5 2X16A TK-LP-S3 IC60N

47
0.84
2.98
SOCKETS
30mA

DINING ROOM 680 - - 680 LS0H 3G2.5 2X16A TK-LP-S4 IC60N

57
1.02
3.16

SOCKETS
FEMALE TOILETS - 420
- 420 LS0H 3G2.5 2X16A TK-LP-S5 IC60N
53
0.59
2.73

SOCKETS
MALE TOILETS 420
- - 420 LS0H 3G2.5 2X16A TK-LP-S6 IC60N
54
0.60
2.74

SOCKETS
STAFF CHANGING + TOILETS 680 - - 680 LS0H 3G2.5 2X16A TK-LP-S7 IC60N
55
0.98
3.12

SOCKETS
30mA 30mA 30mA 30mA

SPARE EQUIPPED - - - - - - 2X16A TK-LP-S10 IC60N

SPARE EQUIPPED - - - - - - 2X16A TK-LP-S11 IC60N


30mA 30mA

UNEQUIPPED SPARE - - - - - - - - -
circuit matching the approved power SDW[typical]
load designation shall indicate number, type, load... of sockets per
23
MOTORIZED DOOR SW100 - 30 - 30 LS0H 3G2.5 2X16A TK-LP-P1 IC60N

0.02
2.16

24
MOTORIZED DOOR SW100 - 30 - 30 LS0H 3G2.5 2X16A TK-LP-P2 IC60N

0.02
2.16

25
MOTORIZED DOOR SW100 - 30 - 30 LS0H 3G2.5 2X16A TK-LP-P3 IC60N

0.02
2.16

28
MOTORIZED DOOR SW100 - - 30 30 LS0H 3G2.5 2X16A TK-LP-P4 IC60N

0.02
2.16

34
MOTORIZED DOOR SW100 - - 30 30 LS0H 3G2.5 2X16A TK-LP-P5 IC60N

0.03
2.17

33
MOTORIZED DOOR SW100 - - 30 30 LS0H 3G2.5 2X16A TK-LP-P6 IC60N

0.03
2.17

33
MOTORIZED DOOR SW100 - - 30 30 LS0H 3G2.5 2X16A TK-LP-P7 IC60N

0.03
2.17

37
MOTORIZED DOOR SL500 - - 310 310 LS0H 3G2.5 2X16A 0.31 TK-LP-P8 IC60N
2.45

37
MOTORIZED DOOR SW100 - - 30 30 LS0H 3G2.5 2X16A TK-LP-P9 IC60N
0.03
2.17

40

MOTORIZED DOOR SW100 30 - - 30 LS0H 3G2.5 2X16A TK-LP-P10 IC60N


0.03
2.17

39

MOTORIZED DOOR SW100 30 - - 30 LS0H 3G2.5 2X16A TK-LP-P11 IC60N


0.03
2.17

44

MOTORIZED DOOR SW100 30 - - 30 LS0H 3G2.5 2X16A TK-LP-P12 IC60N


0.04
2.18

44

MOTORIZED DOOR SL500 - - 310 310 LS0H 3G2.5 2X16A TK-LP-P13 IC60N
0.41
2.55

50

MOTORIZED DOOR SL500 - - 310 310 LS0H 3G2.5 2X16A TK-LP-P14 IC60N
0.33
2.47

49

MOTORIZED DOOR SW100 30 - - 30 LS0H 3G2.5 2X16A TK-LP-P15 IC60N


0.04
2.18

47

MOTORIZED DOOR SW100 30 - - 30 LS0H 3G2.5 2X16A TK-LP-P16 IC60N


0.04
2.18

33

MOTORIZED DOOR SW100 30 - - 30 LS0H 3G2.5 2X16A TK-LP-P17 IC60N


0.03
2.17

SPARE EQUIPPED - - - - - - 2X16A TK-LP-C10 IC60N

SPARE EQUIPPED - - - - - - 2X16A TK-LP-C11 IC60N

UNEQUIPPED SPARE - - - - - - - - -
load per circuit matching the approved SDW
motorized doors ...etc.), moreover load designation shall indicate number, type,
the approved material submittal reference for mentioned loads to be provided e.g.
X
3

??

3 3
I
F

7.5
B37-TK-LP

8
HCU CLOSET
HCU CLOSET HCU CLOSET

9
1 2 3 4 5 6
NOTES : CLIENT :

PROJECT MANAGEMENT & COST CONSULTANCY :


CONDUIT FILLING RATIO CALCULATION

A A

MK MK MK

F.F.L
CONSULTANT DESIGN REVIEWER :

Kitchen area classified as a

400

400

1500
hazard & service area any 1 TYPICAL INSTALLATION HEIGHTS
raised WIR not mentioned - SCALE: NTS

WALL MOUNTED SOCKET


that the Conduit is RGS will 2 INSTALLATION DETAIL
SCALE: NTS
DESIGNER :

be rejected. 3 DISCONNECT SWITCH INSTALLATION DETAIL


- SCALE: NTS

H=1800mm H=1800mm
CONTRACTOR :
AFFL AFFL DS 16A
H=1100mm H=1100mm 4P, IP43
AFFL AFFL TK-PP1-73 @1500mm AFFL
(4C,2.5+ SC,2.5)mm² LS0H CABLE IN
3/4"Ø EMT CONDUIT EXPOSED ABOVE
FALSE CEILING

B
A RDS-12 Potato & Carrot Peeler =0.55 KW
H=600mm
AFFL
B
00-67a J H=600mm
AFFL
MODERN ARCH

00-69b 00-95a J

According to the attached


H=1100mm
AFFL
00-69 00-98
TK-PP1-74
(3C,2.5mm²) LS0H CABLE IN 3/4"Ø EMT 00-74 TK-LP-S4

H C
(3C,2.5mm²) LS0H CABLE

D
TO TK-PP1 TK-PP1-67 CONDUIT EXPOSED ABOVE FALSE CEILING TK-PP1-92
(4C,2.5+ SC,2.5)mm² LS0H CABLE IN RDS-16 Rox Electrolyzing = 0.2 KW TK-PP1-83 TK-PP1-91 IN 3/4"Ø EMT CONDUIT EXPOSED
(3C,2.5mm²) LS0H CABLE IN

VD calculation some of
3/4"Ø EMT CONDUIT EXPOSED (4C,2.5+ SC,2.5)mm² LS0H CABLE IN 3/4"Ø EMT (4C,2.5mm²+1C2.5mm²) LS0H CABLE IN ABOVE FALSE CEILING
3/4"Ø EMT CONDUIT EXPOSED
DS 16A ABOVE FALSE CEILING CONDUIT EXPOSED ABOVE FALSE CEILING ABOVE FALSE CEILING Ø 25mm PVC CONDUIT RUNNING UNDER
4P, IP43 DSP-5 DISPATCH CHILLER = 1.76 KW
EXISTING DOOR TO BE WST-7 WASTE CHILLER = 1.76 KW CHF-2 = 1.5 KW H=400mm TILES
00-69a
FIRE RATED 45°
@ABOVE CEILING TK-PP1-71
(3C,2.5mm²) LS0H CABLE IN 3/4"Ø EMT
H=1100mm
AFFL
H=1100mm
AFFL
AFFL SUBCONTRACTOR :
CONDUIT EXPOSED ABOVE FALSE H=300mm DS 16A

H C
H=1100mm AFFL
CEILING, RDS-5.2 Spare Socket = 1 KW

D
4P, IP43

H C
the cable been changed
AFFL
@ABOVE CEILING

D
TK-PP1-87

H C
TK-PP1-65

D
TK-PP1-90 (3C,2.5mm²) LS0H CABLE
(3C,2.5mm²) LS0H CABLE IN 3/4"Ø (4C,2.5mm²+1C2.5mm²) LS0H CABLE IN IN 3/4"Ø EMT CONDUIT EXPOSED
EMT CONDUIT EXPOSED ABOVE
FALSE CEILING
00-94 TK-PP1-85 Ø 25mm PVC CONDUIT RUNNING UNDER ABOVE FALSE CEILING
H=1600mm (3C,6mm²) LS0H CABLE IN 1"Ø TILES DPW-25 ROX ELECTROLYZING = 0.2KW
WST-1 AIR CURTAIN = 0.22 KW H=400mm
AFFL TK-PP1-70 EMT CONDUIT EXPOSED ABOVE
AFFL

Contractor has to return


TK-PP1-68 FALSE CEILING
00-73a (3C,2.5mm²) LS0H CABLE IN 3/4"Ø
3C,6mm² LS0H CABLE IN 1"Ø EMT
CONDUIT EXPOSED ABOVE FALSE Spare Socket = 3KW
EMT CONDUIT EXPOSED ABOVE

H C
CEILING, Spare Sockets = 3 KW
00-67 H=1500mm

D
ABOVE DOOR FALSE CEILING AFFL
TK-PP1-64 WST-9 Front Load Baler = 1.1 KW TK-PP1-69
TK-PP1-91
(3C,2.5mm²) LS0H CABLE IN 3/4"Ø (3C,2.5mm²) LS0H CABLE IN 3/4"Ø EMT
(4C,6mm²+1C6mm²) LS0H CABLE IN 1"Ø EMT

back them to the


EMT CONDUIT EXPOSED ABOVE H=1500mm H=400mm CONDUIT EXPOSED ABOVE FALSE
AFFL CONDUIT EXPOSED ABOVE FALSE CEILING
FALSE CEILING AFFL CEILING, RDS-2 INSECT KILLER = 0.03 KW H=1500mm H=2200mm
DPW-14 U/C POTS & PAN WAREWASHER = 6.9KW

IJ dar al-handasah
H=2400mm AFFL
WST-2 INSECT KILLER = 0.03 KW TK-PP1-77 AFFL
AFFL
Ø 3/4" EMT CONDUIT DOWN TO (3C,6mm²) LS0H CABLE IN 1"Ø EMT

H=400mm RUNNING UNDER TILES . H=2200mm


AFFL
CONDUIT EXPOSED ABOVE FALSE CEILING
Spare Socket = 3 KW
00-97 H=1100mm
TK-PP1-88
00-75
B
H=1600mm (4C,4mm²+1C4mm²) LS0H CABLE IN 3/4"Ø EMT
AFFL Ø 3/4" EMT CONDUIT UP TO H=1500mm AFFL

mentioned sizes:
AFFL CONDUIT EXPOSED ABOVE FALSE CEILING
AFFL
RUNNING EXPOSED UNDER H=400mm TK-PP1-75 DPW-4 U/C Glass Wash Machine = 8.4KW
LEGEND :
AFFL (4C,2.5+ SC,2.5)mm² LS0H CABLE IN 3/4"Ø EMT TK-PP1-96
CEILING . CONDUIT EXPOSED ABOVE FALSE CEILING TK-LP-S2 (3C,2.5mm²) LS0H CABLE
RDS-15 Salad & VEG. Dryer = 1.10 KW (3C,4mm²) LS0H CABLE 00-75a IN 3/4"Ø EMT CONDUIT EXPOSED
H=1500mm IN 3/4"Ø EMT CONDUIT EXPOSED TK-PP1-90 ABOVE FALSE CEILING
H=1100mm

lhair il1lf partnm AFFL


AFFL
ABOVE FALSE CEILING (4C,6mm²+1C6mm²) LS0H CABLE IN 1"Ø EMT DPW-2 INSECT KILLER = 0.03KW 13 AN4

TK-PP1-51 3X10
CONDUIT EXPOSED ABOVE FALSE CEILING
H=400mm
TK-PP1-100 00-95 DPW-12 PASS THROUGH DISHWASH = 10.6KW TK-PP1-95 SINGLE SOCKET OUTLET
AFFL (3C,2.5mm²) LS0H CABLE
00-73 3C,6mm² LS0H CABLE IN 1"Ø EMT
CONDUIT EXPOSED ABOVE H=1500mm TK-PP1-93 IN 3/4"Ø EMT CONDUIT EXPOSED 79 AE4
DS 16A ABOVE FALSE CEILING
Ø 3/4" EMT CONDUIT UP TO FALSE CEILING 4P, IP43 AFFL (3C,6mm²) LS0H CABLE IN 1"Ø
DPW-3.2 Spare Socket = 1KW
@1500mm FFL EMT CONDUIT EXPOSED ABOVE
RUNNING EXPOSED UNDER TK-PP1-61
16 AN24
Ø 3/4" EMT CONDUIT DOWN TO FALSE CEILING, CHF-1.1 = 3KW

TK-PP1-58 3X4mm
(3C,6mm²) LS0H CABLE IN 1"Ø TK-PP1-24 TK-PP1-14
J
C
CEILING . H=1600mm EMT CONDUIT EXPOSED ABOVE 3C,4mm² LS0H CABLE IN 3/4"Ø (3C,2.5mm²) LS0H CABLE IN 3/4"Ø
TWIN BRITISH STANDARD SOCKET OUTLET
RUNNING UNDER TILES . AFFL FALSE CEILING
TK-PP1-25
EMT CONDUIT EXPOSED ABOVE EMT CONDUIT EXPOSED ABOVE
(4C,16mm²+1C16mm²) LS0H CABLE IN H=400mm
Spare Socket = 3 KW FALSE CEILING FALSE CEILING
00-93 Ø 38 mm PVC CONDUIT RUNNING 23 AE24

0
TK-PP1-76 ARB-7 U/C CHILLER = 0.5KW DS 16A AFFL H=1600mm
TK-PP1-99 Spare Socket = 3KW

CON l: APPROVED H=2200mm (4C,2.5+ SC,2.5)mm² LS0H CABLE IN UNDER TILES 4P, IP43 AFFL
ABOVE DOOR 3C,4mm² LS0H CABLE IN 3/4"Ø TK-PP1-15
AFFL 3/4"Ø EMT CONDUIT EXPOSED ARB-4 Combi Duo Steamer = 18.9KW TK-PP1-23 @1500mm AFFL
TK-PP1-60 EMT CONDUIT EXPOSED (3C,2.5mm²) LS0H CABLE IN 3/4"Ø EMT

TK-PP1-92 3X4mm
ABOVE FALSE CEILING (4C,6mm²+1C6mm²) LS0H CABLE IN Ø 32mm
(3C,2.5mm²) LS0H CABLE IN 3/4"Ø ABOVE FALSE CEILING TK-PP1-84
PVC CONDUIT RUNNING UNDER TILES CONDUIT EXPOSED ABOVE FALSE CEILING TK-PP1-49 15 TERMINAL BOX FOR SINGLE-PHASE CABLE
RDS-15 Salad & VEG. Dryer = 1.10 KW (4C,6mm²+1C6mm²) LS0H CABLE IN (4C,4mm²+1C4mm²) LS0H CABLE IN
EMT CONDUIT EXPOSED ABOVE ARB-7 U/C CHILLER = 0.5KW

0 Ø 32 mm PVC CONDUIT RUNNING ARB-10 ELEC. Tandoor Oven = 11KW 1"Ø EMT CONDUIT EXPOSED ABOVE

C®£ I: APPIOVED AS NOTED


FALSE CEILING TK-PP1-16
WST-2 INSECT KILLER = 0.03 KW UNDER TILES TK-PP1-29 FALSE CEILING
ARB-4 Combi Duo Steamer = 10.8KW (3C,2.5mm²) LS0H CABLE IN 3/4"Ø EMT LCS-17 GYROS GRILL = 7.2KW 07 TERMINAL BOX FOR 3P+N+E CABLE
(3C,2.5mm²) LS0H CABLE IN 3/4"Ø CONDUIT EXPOSED ABOVE FALSE CEILING
EMT CONDUIT EXPOSED ABOVE ARB-20 U/C CHILLER = 0.5KW TK-PP1-45

IW MY IIICIIIIIIlKTlO FALSE CEILING


ARB-12 HOOD MARVEL = 0.236KW TK-PP1-72
(3C,2.5mm²) LS0H CABLE IN 3/4"Ø EMT
(4C,2.5mm²+1C2.5mm²) LS0H CABLE IN
3/4"Ø EMT CONDUIT EXPOSED ABOVE
FALSE CEILING
03 FAN COIL UNIT POWER SUPPLY (DS 2X20A)

IIICOIINMtll Of EIIOIIID 029 TK-LP-S1


TK-PP1-55
(3C,2.5mm²) LS0H CABLE IN 3/4"Ø EMT
CONDUIT EXPOSED ABOVE FALSE
00-96
H=600mm H=600mm H=1100mm H=600mm TK-PP1-22
CONDUIT EXPOSED ABOVE FALSE CEILING
ARB-20 U/C CHILLER = 0.5KW
LCS-2 ELEC. Tepanyaki = 6KW

TK-PP1-46 05 HOOD POWER SUPPLY

co.um.
(3C,2.5)mm² LS0H CABLE IN 1"Ø H=1100mm AFFL AFFL AFFL AFFL
CEILING, FRV-8 VEG. Slicer = 0.55 KW (3C,2.5mm²) LS0H CABLE IN 3/4"Ø (3C,2.5mm²) LS0H CABLE IN
EMT CONDUIT EXPOSED ABOVE AFFL
H=1100mm EMT CONDUIT EXPOSED ABOVE 3/4"Ø EMT CONDUIT EXPOSED ABOVE FALSE TK-PP1-47
AFFL
FALSE CEILING H=2200mm
H=600mm FALSE CEILING CEILING, LCS-5 HOOD MARVEL = 0.33KW (3C,2.5mm²) LS0H CABLE IN 02 LOW CURRENT POWER SUPPLY
C H=1100mm
Spare Sockets = 0.54 KW
TK-PP1-58
AFFL
TK-PP1-56
J J J J
ARB-15 U/C CHILLER = 0.5KW AFFL

J J J J
3/4"Ø EMT CONDUIT EXPOSED ABOVE FALSE
CEILING, LCS-5 HOOD LIGHT = 0.138KW
C
D conE c: RlYISIAaiiSUBIIT
AFFL (3C,2.5)mm² LS0H CABLE IN 3/4"Ø (3C,2.5mm²) LS0H CABLE IN 1"Ø EMT H=600mm (4C,2.5mm²+1C2.5mm²) LS0H CABLE
EMT CONDUIT EXPOSED ABOVE CONDUIT EXPOSED ABOVE FALSE AFFL IN Ø 25 mm PVC CONDUIT RUNNING 01 WATER HEATER POWER SUPPLY
FALSE CEILING H=1100mm 1
ARB-10 ELEC. TANDOOR OVEN
H=1100mm CEILING, FRV-11 U/C Chiller = 0.5 KW 0

UNDER TILES
AFFL 11 KW/ 3 PH @ 1500mm AFFL
FRV-10 Food Processor = 1.5 KW AFFL H=1100mm H=1500mm DS 16A
ARB-4 COMBI DUO STEAMER
J
1

H=1100mm AFFL 0

AFFL 4P, IP43 TK-PP1-51 01


IOIIIIAY lOTPIOCUD EMERGENCY STOP PUSH BUTTON
18.9 KW/ 3 PH @ 1500mm AFFL
AFFL TK-PP1-57 TK-PP1-27 4C,25mm²+1C16mm² LS0H (3C,6mm²) LS0H CABLE
00-92 ARB-4 COMBI DUO STEAMER
1

0
@1500mm AFFL
(3C,2.5)mm² LS0H CABLE IN 3/4"Ø EMT CABLE IN Ø 50 mm PVC CONDUIT 10.8 KW/ 3 PH @ 1500mm AFFL
IN 1"Ø EMT CONDUIT EXPOSED ABOVE
00-91 1

ARB-8 20 RACK COMBI STEAMER TK-PP1-98 ISOLATOR SWITCH /1 PHASE


TK-PP1-94 CONDUIT EXPOSED ABOVE FALSE RUNNING UNDER TILES 0

37.2 KW/ 3 PH @ 1500mm AFFL


(3C,4mm²) LS0H CABLE IN J FALSE CEILING 15
(3C,6)mm² LS0H CABLE IN 1"Ø CEILING LCS-20 High Speed Panini = 3.6KW 3 PHASE ROTARY TYPE

D COD! DI RE-JECTED
3/4"Ø EMT CONDUIT EXPOSED
EMT CONDUIT EXPOSED ABOVE TK-PP2-32 FRV-9 Vegetable Preparation = 0.55 KW ABOVE FALSE CEILING TK-PP1-50
FALSE CEILING (4C,2.5+ SC,2.5)mm² LS0H CABLE IN H=1100mm H=1100mm H=From Below
(3C,2.5mm²) LS0H CABLE IN 3/4"Ø EMT
14 1 PHASE SWITCH
3/4"Ø EMT CONDUIT EXPOSED TK-PP1-59 AFFL AFFL
RDO-1.1 ELECTRICAL = 3 KW CONDUIT EXPOSED ABOVE
ABOVE FALSE CEILING (3C,2.5)mm² LS0H CABLE IN 3/4"Ø H=1100mm
FALSE CEILING
H=600mm TK-PP1-44 24
FRV-15 Fruit & VEG. Chiller = 2.15 KW EMT CONDUIT EXPOSED ABOVE AFFL
AFFL LCS-13 U/C CHILLER = 0.5KW (3C,4mm²) LS0H CABLE IN 3/4"Ø
J JUNCTION BOX

D
FALSE CEILING REVISED AS PER CONSULTANT REMARKS

28/07/22
TK-PP1-66 EMT CONDUIT EXPOSED ABOVE
TK-PP1-54 05 20/07/2022
By:AKamar D•te:
FRV-13 U/C CHILLER = 0.5 KW
(3C,6mm²) LS0H CABLE IN 1"Ø (3C,2.5mm²) LS0H CABLE IN 3/4"Ø FALSE CEILING 03
DS 16A EMT CONDUIT EXPOSED ABOVE TK-PP1-43 LCS-3 U/C Heated Cabinet = 3KW
RECESSED ELECTRICAL BOX CABINET
EMT CONDUIT EXPOSED
4P, IP43 H=600mm
FALSE CEILING (3C,2.5mm²) LS0H CABLE IN REVISED AS PER CONSULTANT REMARKS
@ABOVE CEILING AFFL
ABOVE FALSE CEILING
ARB-17 HOOD LIGHT = 0.138 KW 3/4"Ø EMT CONDUIT EXPOSED
ARB-20 U/C CHILLER
04 OUTLET POWER FOR MOTORIZED DOOR
04 26/06/2022
Spare Sockets = 3 KW 0.50 KW/ 1PH
3PH CABLE

H=1100mm
TM

ABOVE FALSE CEILING 1PH CABLE


BOX EMBEDDED IN WALL; ROOTING AND
ARB-7 U/C CHILLER
00-65a REVISED AS PER CONSULTANT REMARKS

~ ......... Centrlctor
LCS-7 Induction Warmer = 0.5KW SOCKETS INSIDE COUNTERS BY 2 OUTLET POWER FOR TEMPERATURE
AFFL 05 03 01/06/2022

H C
0.50 KW/ 1PH
TK-PP1-26
00-75b
3PH CABLE
1PH CABLE

00-90 ELECTRICAL CONTRACTOR. KEC TO

D
heat lamp heat lamp TK-PP1-13 ARB-7 U/C CHILLER
(3C,2.5mm²) LS0H CABLE IN 3/4"Ø EMT
ARRANGE CHASE FOR CABLE ROOTING MONITORING SYSTEM 13A 3-PIN SOCKET
00-88

H C
028 CONDUIT EXPOSED ABOVE FALSE CEILING (3C,2.5mm²) LS0H CABLE IN 3/4"Ø EMT 3PH CABLE
0.50 KW/ 1PH
REVISED AS PER CONSULTANT REMARKS

--............
J
1PH CABLE

D
AND BOXES FOR SOCKET INSTALLATION
H=2400mm
H=1400mm
AFFL
ARB-17 HOOD MARVEL = 0.047 KW CONDUIT EXPOSED ABOVE FALSE CEILING
TK-PP1-42
ARB-20 U/C CHILLER ALL POINTS MUST BE 20cm ABOVE FALSE CEILING 02 09/05/2022
0.50 KW/ 1PH

of., of 1111 IJIIItils- the


ARB-5 SALADETTE UNIT = 0.175KW
TM

3PH CABLE
AFFL TK-PP1-28 1PH CABLE

H=1100mm (3C,2.5mm²) LS0H CABLE IN


(3C,2.5mm²) LS0H CABLE IN 3/4"Ø EMT TK-PP1-21 3/4"Ø EMT CONDUIT EXPOSED REVISED AS PER CONSULTANT REMARKS
CONDUIT EXPOSED ABOVE FALSE CEILING
AFFL
(3C,4mm²) LS0H CABLE IN 3/4"Ø ABOVE FALSE CEILING TK-PP1-41
01 25/04/2022
ARB-12 HOOD LIGHT = 0.24 KW TK-PP1-12 EMT CONDUIT EXPOSED ABOVE LCS-7 Induction Warmer = 0.5KW (3C,2.5mm²) LS0H CABLE IN

Colltract. ClllllfllllllllltallallE
H=1600mm FIRST ISSUE
TK-PP1-19 (3C,2.5mm²) LS0H CABLE IN 3/4"Ø FALSE CEILING 3/4"Ø EMT CONDUIT EXPOSED
(3C,6mm²) LS0H CABLE IN 1"Ø EMT CONDUIT EMT CONDUIT EXPOSED ABOVE
AFFL TM

ABOVE FALSE CEILING


00 19/04/2022
TK-PP1-53 TK-PP1-40
(3C,2.5)mm² LS0H CABLE IN 3/4"Ø EMT EXPOSED ABOVE FALSE CEILING FALSE CEILING LCS-4 U/C FREEZER = 0.24KW
(3C,2.5mm²) LS0H CABLE IN
ARB-19.1 Heated Strip Lamp = 2 KW ARB-21.6 SPARE SOCKET = 1KW
CONDUIT EXPOSED ABOVE FALSE CEILING
FRV-3 Knife Sterilizer = 0.015 KW TK-PP1-18 TK-PP1-5
3/4"Ø EMT CONDUIT EXPOSED REV. DESCRIPTION DATE
TK-PP1-30 ABOVE FALSE CEILING NO.
of..., . . . " Cenlract Deaalls. (3C,10mm²) LS0H CABLE IN 1 1/4"Ø EMT (3C,2.5mm²) LS0H CABLE IN 3/4"Ø (3C,2.5mm²) LS0H CABLE IN TM

LCS-7 Induction Warmer = 0.5KW


TK-PP1-39

H C
TK-PP2-37 TK-PP1-52 CONDUIT EXPOSED ABOVE FALSE CEILING EMT CONDUIT EXPOSED ABOVE TK-PP1-20 (3C,2.5mm²) LS0H CABLE IN
00-65

D
3/4"Ø EMT CONDUIT EXPOSED
(3C,2.5)mm² LS0H CABLE IN 3/4"Ø (3C,2.5)mm² LS0H CABLE IN 3/4"Ø EMT ARB-19 Ceiling Shelf + Socket = 3 KW FALSE CEILING (3C,4mm²) LS0H CABLE 3/4"Ø EMT CONDUIT EXPOSED
TK-PP1-17 LCS-3 U/C Heated Cabinet = 1.5KW ABOVE FALSE CEILING
EMT CONDUIT EXPOSED ABOVE IN 3/4"Ø EMT CONDUIT ABOVE FALSE CEILING

Contrlctoris,...... ..
CONDUIT EXPOSED ABOVE FALSE CEILING H=1100mm LCS-11.5 Spare Socket = 1KW TK-PP1-38
FALSE CEILING (3C,4mm²) LS0H CABLE IN 3/4"Ø EXPOSED ABOVE LCS-7 Induction Warmer = 0.5KW
FRV-2.5 Spare Socket = 1 KW AFFL (3C,2.5mm²) LS0H CABLE IN
EMT CONDUIT EXPOSED ABOVE
TK-PP2-33
(3C,4)mm² LS0H CABLE IN 3/4"Ø TK-PP2-35
(3C,2.5)mm² LS0H CABLE IN 3/4"Ø
FALSE CEILING
TK-PP1-101
(3C,6mm²) LS0H CABLE IN 1"Ø
FALSE CEILING
TK-PP2-54
TM

3/4"Ø EMT CONDUIT EXPOSED


ABOVE FALSE CEILING
CONDUITS LEGEND
EMT CONDUIT EXPOSED EMT CONDUIT EXPOSED ABOVE H=400mm (3C,6)mm² LS0H CABLE IN 1"Ø EMT
EMT CONDUIT EXPOSED ABOVE TK-PP2-36 AFFL CONDUIT EXPOSED ABOVE FALSE LCS-7 Induction Warmer = 0.5KW
ABOVE FALSE CEILING FALSE CEILING Ø 25 mm PVC CONDUIT RUNNING UNDER TILES.
FALSE CEILING (4C,2.5+ SC,2.5)mm² LS0H CABLE IN CEILING
IBC-13 TILTING BRATT PAN TK-PP1-37
TK-PP2-34 3/4"Ø EMT CONDUIT EXPOSED TK-PP2-55&56 AND CONDUIT AS INDICATED ON DRAWINGS
13.50 KW/ 3 PH @ 1500mm AFFL
(3C,2.5)mm² LS0H CABLE IN 3/4"Ø ABOVE FALSE CEILING (3C,10) mm² LS0H CABLE IN TK-PP2-53 00-75c TM
(3C,2.5mm²) LS0H CABLE IN
026 Disc. Switch, Non-Fusibe, 32A, 4PST, 400V - IP43
EMT CONDUIT EXPOSED ABOVE
TK-PP2-57
(4C,2.5+ SC,2.5)mm² LS0H CABLE
1,1/4"Ø EMT CONDUIT EXPOSED (3C,2.5)mm² LS0H CABLE IN 1"Ø EMT 3/4"Ø EMT CONDUIT EXPOSED 3C2.5mm2 CABLE RUNNING INSIDE EMT

withotJ.trMn.
IBC-14 ELEC BOILING PAN ABOVE FALSE CEILING
FALSE CEILING ABOVE FALSE CEILING CONDUIT EXPOSED ABOVE FALSE CEILING Ø 3/4 '' EXPOSED CONDUIT ABOVE FALSE
18.0 KW/ 3 PH @ 1500mm AFFL H=2300mm IN Ø 25 mm PVC CONDUIT LCS-7 Induction Warmer = 0.5KW
027 Disc. Switch, Non-Fusibe, 40A, 4PST, 400V - IP43 AFFL RUNNING UNDER TILES
MagnaWave TM

CEILING. OTHERWISE THE CABLE SIZE AND CONDUIT

heat lamp
IBC-15 VARIO COOKING CENTER AS INDICATED ON DRAWINGS
19.0 KW/ 3 PH @ 1500mm AFFL 00-87
F
Disc. Switch, Non-Fusibe, 40A, 4PST, 400V - IP43
IBC-16 20 RACK COMBI STEAMER TK-PP2-13 H C heat lamp heat lamp J EXPOSED CABLE CLIPPED TO CEILING EXPOSED
D ABOVE FALSE CEILING
37.20 KW/ 3 PH @ 1500mm AFFL
38.90
Disc. Switch, Non-Fusibe, 80A, 4PST, 400V - IP43
(3C,2.5)mm² LS0H CABLE IN 3/4"Ø H=1500mm
AFFL H=1500mm
J H=1100mm
AFFL SIZE AS INDICATED ON DRAWINGS
EMT CONDUIT EXPOSED ABOVE IBC-7 INDUCTION HOB
1

TK-PP2-59 TK-PP2-51 0
H=1100mm
IBC-24 ROLL-IN BLAST CHILLER 20.0 KW/ 3 PH @ 1500mm AFFL
FALSE CEILING AFFL AFFL
H=2200mm 3C4mm² LS0H CABLE IN Ø (3C,2.5mm²) LS0H CABLE IN 3/4"Ø 1
IBC-7 INDUCTION HOB LCS-7 INDUCTION WARMER
5.20 KW/ 3 PH @ 1500mm AFFL MP-3.5 Spare Socket = 1 KW TK-PP2-30 0

Disc. Switch, Non-Fusibe, 16A, 4PST, 400V - IP43


C H AFFL 25 mm PVC CONDUIT EMT CONDUIT EXPOSED ABOVE
20.0 KW/ 3 PH @ 1500mm AFFL
0.50 KW/ 1PH VIA BOX H=1800mm
(4C,2.5+ SC,2.5)mm² LS0H CABLE IN D
1

IBC-9 ELEC SALAMANDER TK-PP1-36 BOX EMBEDDED IN WALL; ROOTING AND


LCS-7 INDUCTION WARMER
0

TK-PP2-12 RUNNING UNDER TILES FALSE CEILING 4.0 KW/ 3 PH @ 1500mm AFFL

SHOP DRAWING
IBC-27 6 RACK COMBI STEAMER 3/4"Ø EMT CONDUIT EXPOSED (3C,2.5mm²) LS0H CABLE IN AFFL
(3C,2.5)mm² LS0H CABLE IN 3/4"Ø IBC-5 HOOD MARVEL = 1.204KW
1

IBC-10 ELECTRIC GRIDDLE


0.50 KW/ 1PH VIA BOX SOCKETS INSIDE COUNTERS BY ELECTRICAL
5.70 KW/ 3 PH @ 1500mm AFFL ABOVE FALSE CEILING TK-PP2-53 0

12.0 KW/ 3 PH @ 1500mm AFFL 3/4"Ø EMT CONDUIT EXPOSED


EMT CONDUIT EXPOSED ABOVE H=1100mm IBC-11 DEEP FAT FRYER TK-PP1-31 LCS-4 U/C FREEZER CONTRACTOR.
(3C,2.5mm²) LS0H CABLE IN 3/4"Ø
1

Disc. Switch, Non-Fusibe, 16A, 4PST, 400V - IP43 MPP-2 Meat & Poultry Chiller =1.76KW 0 H=600mm ABOVE FALSE CEILING
FALSE CEILING AFFL 15.0 KW/ 3 PH @ 1500mm AFFL
AFFL (3C,4mm²) LS0H CABLE IN 3/4"Ø 0.24 KW/ 1PH VIA BOX KEC TO ARRANGE CHASE FOR CABLE
EMT CONDUIT EXPOSED ABOVE 1

IBC-11 DEEP FAT FRYER LCS-8 Inset Chilled Top = 1.1KW


MP-2 Knife Sterilizer = 0.015KW DS 16A
0

EMT CONDUIT EXPOSED LCS-7 INDUCTION WARMER ROOTING AND BOXES FOR SOCKET
TK-PP2-43 FALSE CEILING 15.0 KW/ 3 PH @ 1500mm AFFL
4P, IP43 ABOVE FALSE CEILING 0.50 KW/ 1PH VIA BOX INSTALLATION
(4C,16mm²+1C16)mm² LS0H IBC-5 HOOD LIGHT = 0.414KW TK-PP1-4
@ABOVE CEILING TK-PP2-41
(4C,25mm²+1C16)mm² LS0H
CABLE IN Ø 32 mm PVC CONDUIT
H=600mm
AFFL TK-PP1-32 (3C,6mm²) LS0H CABLE IN 1"Ø
LCS-7 INDUCTION WARMER
0.50 KW/ 1PH VIA BOX
00-76a
TK-PP2-46 (3C,4mm²) LS0H CABLE IN 3/4"Ø EMT CONDUIT EXPOSED
TK-PP2-38 RUNNING UNDER TILES LCS-7 INDUCTION WARMER
025 H=2200mm CABLE IN Ø 50 mm PVC CONDUIT (4C,10mm²+1C10mm²) LS0H TK-PP2-52 EMT CONDUIT EXPOSED ABOVE ABOVE FALSE CEILING 00-76

LCU CLOSET
AFFL (3C,4)mm² LS0H CABLE IN RUNNING UNDER TILES 00-65b CABLE IN Ø 32 mm PVC CONDUIT (3C,2.5mm²) LS0H CABLE IN 3/4"Ø EMT FALSE CEILING
0.50 KW/ 1PH VIA BOX
3/4"Ø EMT CONDUIT EXPOSED
ABOVE FALSE CEILING
00-89 RUNNING UNDER TILES CONDUIT EXPOSED ABOVE FALSE CEILING DS 16A
TK-PP1-35
LCS-7 INDUCTION WARMER
0.50 KW/ 1PH VIA BOX
IBC-30 U/C CHILLER = 0.5KW 4P, IP43 H=1800mm
HCU CLOSET

H=2200mm (3C,10mm²) LS0H CABLE IN 1 1/4"Ø EMT LCS-8 INSET CHILLED TOP
H=1100mm H=1100mm @600mm FFL AFFL
AFFL CONDUIT EXPOSED ABOVE FALSE CEILING 1.1 KW/ 1PH VIA BOX
H=1400mm
AFFL
AFFL AFFL J LCS-9 Conveyor Toaster = 5.04 KW LCS-1.2 SNEEZE GUARD TK-LP-21

D 001
J J J J J J H=1100mm TK-PP1-33
3 KW/ 1PH VIA BOX H=1100mm (3C,2.5mm²) LS0H CABLE
D
H C

TK-PP2-11 H=400mm AFFL AFFL IN 3/4"Ø EMT CONDUIT EXPOSED


D

AFFL
(3C,6mm²) LS0H CABLE IN 3/4"Ø EMT
(3C,4)mm² LS0H CABLE IN ABOVE FALSE CEILING
CONDUIT EXPOSED ABOVE FALSE CEILING
3/4"Ø EMT CONDUIT EXPOSED
ABOVE FALSE CEILING H=1600mm J J J Spare Sockets = 3 KW
AFFL H=600mm 00-76b 00-76c
B37-TK-PP2 00-86
TK-PP2-15
(3C,4)mm² LS0H CABLE IN 3/4"Ø
EMT CONDUIT EXPOSED
TK-PP2-42 4C,16mm²+1C16mm²
LS0H CABLE IN Ø 32 mm PVC
TK-PP2-44&45
4C,10mm²+1C10mm² LS0H CABLE
IN Ø 32 mm PVC CONDUIT TK-PP2-48
TK-PP2-50
(4C,16mm²+1C16mm²) LS0H
CABLE IN Ø 38 mm PVC CONDUIT
AFFL

H=400mm
TK-PP1-34
(3C,2.5mm²) LS0H CABLE IN 3/4"Ø EMT
CONDUIT EXPOSED ABOVE FALSE CEILING TK-LP-S5
(3C,2.5mm²) LS0H CABLE
5013 2 450 0037 201 E_00
TK-PP2-6 H=1100mm ABOVE FALSE CEILING CONDUIT RUNNING UNDER RUNNING UNDER TILES (4C,2.5+1C2.5)mm² LS0H CABLE IN
RUNNING UNDER TILES AFFL H=1100mm
LCS-13 U/C CHILLER = 0.5 KW
IN 3/4"Ø EMT CONDUIT EXPOSED
PROJECT CODE PHASE TRADE BUILDING DOC. NUMBER REVISION
(3C,2.5)mm² LS0H CABLE IN 3/4"Ø TILES Ø 32 mm PVC CONDUIT RUNNING TK-PP2-49 TK-PP2-26 AFFL TK-PP1-11
AFFL ABOVE FALSE CEILING
TK-PP2-14 UNDER TILES (4C,16mm²+1C16mm²) LS0H (3C,2.5mm²) LS0H CABLE IN 3/4"Ø EMT
EMT CONDUIT EXPOSED ABOVE (3C,6)mm² LS0H CABLE IN 1"Ø
H=1100mm (4C,2.5+ SC,2.5)mm² LS0H CABLE IN CONDUIT EXPOSED ABOVE FALSE CEILING
CABLE IN Ø 38 mm PVC CONDUIT
FALSE CEILING
PP-3.5 Spare Socket = 1 KW
H=1400mm AFFL 3/4"Ø EMT CONDUIT EXPOSED 00-80 TK-PP2-47 4C,6mm²+1C6mm² LS0H
RUNNING UNDER TILES
EMT CONDUIT EXPOSED
ABOVE FALSE CEILING LCS-22 Heated Plated Dispenser = 0.9 KW CIVIL/LS ARCHITECT STRUCTURAL
AFFL H=1100mm ABOVE FALSE CEILING CABLE IN Ø 25 mm PVC CONDUIT
H=1100mm TK-PP1-10
AFFL STR-3 Defrost Chiller Room = 1.76 KW RUNNING UNDER TILES
H=600mm AFFL (3C,4mm²) LS0H CABLE IN 3/4"Ø

G
AFFL EMT CONDUIT EXPOSED ABOVE
FALSE CEILING
B37-TK-PP1 - - -
TK-PP2-5 00-85
H C

H=2200mm TK-PP2-17
D

TK-PP1-2
HCU CLOSET

(3C,2.5)mm² LS0H CABLE IN 3/4"Ø TK-PP2-27

LCU CLOSET
AFFL (3C,4)mm² LS0H CABLE IN 3/4"Ø (3C,2.5)mm² LS0H CABLE IN 3/4"Ø EMT (4C,6mm²+1C6mm²) LS0H CABLE IN 1"Ø EMT
EMT CONDUIT EXPOSED ABOVE
EMT CONDUIT EXPOSED CONDUIT EXPOSED ABOVE FALSE CEILING CONDUIT EXPOSED ABOVE FALSE CEILING 00-75d
FALSE CEILING
PP-2 Knife Sterilizer = 0.015KW
TK-PP2-16
(4C,2.5+ SC,2.5)mm² LS0H TK-PP2-18
ABOVE FALSE CEILING 00-78 LCS-29 Upright Bottle Cooler = 0.25 KW
H=2200mm
AFFL
LCS-26 Extractor Coffee Brewer = 11.44 KW ELECTRICAL MECHANICAL ICT
CABLE IN 3/4"Ø EMT CONDUIT (4C,2.5+ SC,2.5)mm² LS0H CABLE
EXPOSED ABOVE FALSE CEILING TK-PP1-9
H=600mm IN 3/4"Ø EMT CONDUIT EXPOSED
AFFL STR-5 General Freezer Room = 2.96 KW (3C,6mm²) LS0H CABLE IN 1"Ø
DS 16A DS 16A ABOVE FALSE CEILING
H=1100mm 4P, IP43 4P, IP43 STR-6 General Chiller Room = 2.09 KW DS 16A
4P, IP43 H=2200mm TK-PP2-28 DS 16A
DS 25A
EMT CONDUIT EXPOSED ABOVE
FALSE CEILING
- - -
AFFL @ABOVE CEILING @ABOVE CEILING
H=1100mm @ABOVE CEILING AFFL TK-PP2-20 (3C,2.5)mm² LS0H CABLE IN 3/4"Ø EMT 4P, IP43
4P, IP43
@600mm FFL
Spare Socket = 3KW 00-77a
AFFL (3C,2.5)mm² LS0H CABLE IN
3/4"Ø EMT CONDUIT EXPOSED
CONDUIT EXPOSED ABOVE FALSE CEILING @600mm FFL 00-77b 00-77c
LCS-29 Upright Bottle Cooler = 0.25 KW
H=400mm
AFFL
ABOVE FALSE CEILING DRAWN BY CHECKED BY APPROVED BY
TK-PP2-4 TK-PP1-8
(3C,4)mm² LS0H CABLE IN TK-PP2-22 (3C,2.5mm²) LS0H CABLE IN 3/4"Ø EMT
3/4"Ø EMT CONDUIT EXPOSED H=2200mm (3C,2.5)mm² LS0H CABLE IN CONDUIT EXPOSED ABOVE FALSE CEILING
H=2200mm
B37-TK-LP ABOVE FALSE CEILING
Spare Sockets = 3 KW
AFFL 3/4"Ø EMT CONDUIT EXPOSED
ABOVE FALSE CEILING
AFFL LCS-28 INSET CHILLED TOP = 1.1KW TK-LP-S6
(3C,2.5mm²) LS0H CABLE TBT A.B M.AMER O.I
HCU CLOSET

LCU CLOSET
H=400mm TK-PP2-21 TK-PP1-3 IN 3/4"Ø EMT CONDUIT EXPOSED
TK-PP2-3 H=1500mm
AFFL (3C,2.5)mm² LS0H CABLE IN H=600mm
(3C,2.5)mm² LS0H CABLE IN 00-82 3/4"Ø EMT CONDUIT EXPOSED
TK-PP2-23
AFFL (4C,2.5+ SC,2.5)mm² LS0H CABLE IN 3/4"Ø EMT
CONDUIT EXPOSED ABOVE FALSE CEILING H=1100mm H=1100mm AFFL
ABOVE FALSE CEILING
3/4"Ø EMT CONDUIT EXPOSED ABOVE FALSE CEILING AFFL AFFL TK-LP-22
TK-PP2-1 (3C,2.5)mm² LS0H CABLE IN H=400mm LCS-25 Automatic Coffee Machine = 7.10 KW TK-PP1-7
ABOVE FALSE CEILING
PP-7 U/C CHILLER = 0.5 KW
(3C,6)mm² LS0H CABLE IN 3/4"Ø EMT CONDUIT EXPOSED AFFL TK-PP1-6 (3C,2.5mm²) LS0H CABLE IN 3/4"Ø EMT
(3C,2.5mm²) LS0H CABLE
IN 3/4"Ø EMT CONDUIT EXPOSED 00-77 SITE KEY PLAN : PROJECT TITLE :
1"Ø EMT CONDUIT EXPOSED ABOVE FALSE CEILING (3C,2.5mm²) LS0H CABLE IN 3/4"Ø EMT CONDUIT EXPOSED ABOVE FALSE CEILING ABOVE FALSE CEILING
ABOVE FALSE CEILING CONDUIT EXPOSED ABOVE FALSE CEILING LCS-26.2 40 LTS Container Coffee = 0.07 KW
Spare Sockets = 3 KW LCS-26.2 40 LTS Container Coffee = 0.07 KW

K88_PROJECT
TK-LP-S3

022 00-84 00-79 (3C,2.5mm²) LS0H CABLE


00-81 TK-PP2-24 IN 3/4"Ø EMT CONDUIT EXPOSED
ABOVE FALSE CEILING
(3C,6)mm² LS0H CABLE IN 1"Ø
EMT CONDUIT EXPOSED
H=2200mm
AFFL 00-75e
00-83 ABOVE FALSE CEILING

020 H=1100mm
AFFL
N
TK-PP1-1
(3C,2.5mm²) LS0H CABLE IN 3/4"Ø EMT
CONDUIT EXPOSED ABOVE FALSE CEILING BUILDING NUMBER & NAME :
LCS-16 INSECT KILLER = 0.03KW
H=1800mm

023
AFFL H=1800mm
AFFL 0037
024
BUILDING 0037
CENTRAL PRODUCTION
021
BUILDING KEY PLAN : DRAWING TITLE :

E
OUT OF SCOPE 00-34
N

BUILDING 37 E

013 SOCKET & POWER

SCALE - SHEET SIZE DATE CAD FILE

004 BUILDING 0037


1/50 - A0 19/04/2022 K88-P5-0037-06-SDW-ELE-450-0201-05

DOCUMENT NUMBER :

007 003 K88 P5 0037 06 SDW ELE 450 0201 05


PROJECT PROGRAM BUILDING PHASE DOC. TYPE DISCIPLINE TRADE DOC. NUMBER REVISION

1 2 3 4 5 6