SPEC. ITEM
Item Description UNIT QTY RATE AMOUNT
NO.
A LIGHT FIXTURES:-
Supply, install, connect and test light fixtures including all lamps including all
mounting devices and brackets as shown on the drawings, specification and as
scheduled. All light fixtures will be supplied and installed by Contractor .
2 Weather proof (IP54) wall mounted oblique with 100w lamp No 8 17300
B LIGHT SWITCHES
Supply, install and connect light switches complete including, conduits, conduit
fittings, switches, terminations, earthing, wiring from switches to branch circuit
according to specifications and as shown on drawings.
Switches should be products of :-
- GEWISS ( PLAYBUS RANGE )
- BTICHINO
- LEGRAND
2 Water proof two pole, one way 10A modular switch No 60 17300
C SOCKET OUTLETS
Supply, install, connect and test socket outlets complete including conduits,
conduit fittings, wiring, earthing back to panel board or to branch circuit complete
including plaster rings, wiring, earthing, terminations, socket plate, cover, plugs
all necessary accessories and ancillary work according to specification and
schedules.
Supply, install, connect and test switch fuses complete including conduits, conduit
fittings, wiring, earthing back to panel board or to branch circuit complete
including plaster rings, wiring, earthing, terminations, socket plate, cover, plugs
all necessary accessories and ancillary work according to specification and
schedules.
Sockets should be products of :-
- GEWISS ( PLAYBUS RANGE )
- BTICHINO
- LEGRAND
TOTAL
E BRANCH CIRCUITS
Supply, install, connect and test PVC insulated 450/750V stranded copper
conductor wires from branch circuit panelboards to light & power outlets
including raceways, termination, glands and all necessary accessories and
ancillary works required for complete operative system.
Embeded or concealed surface mounted conduits should be rigid PVC. Exposed
mounted conduits should be galvanized steel.
- PVC conduits should be products of MARSHAL TUFFLEX CO. or approved
equal.
10 3x4 mm² copper conductor branch circuit, for feeding 1 No. power Receptacles No 180 17300
11 3x6 mm² copper conductor branch circuit, for feeding 1 No. power Receptacles No 30 17300
12 3x10 mm² copper conductor branch circuit, for feeding 1 No. power Receptacles No 30 17300
13 3x4 mm² copper conductor branch circuit, for feeding 2 No. power Receptacles No 30 17300
14 3x4 mm² copper conductor branch circuit, for feeding 4 No. power Receptacles No 35 17300
15 3x4 mm² copper conductor branch circuit, for feeding 5 No. power Receptacles No 31 17300
16 3x4 mm² copper conductor branch circuit, for feeding 6 No. power Receptacles No 2 17300
Supply, install, connect and test the following panel boards complete with circuit
breakers, bus bars cabinets, conductors relays, residual current devices, indicator
lamps and all necessary accessories and ancillary works required in accordance
with the specification, construction drawings & attached schedules.
2 BCP-SR No 1 17300
Supply, install, connect and test main distribution boards with all necessary
accessories circuit breakers, contractors, relays, indicator lamps, cable terminals
& all ancillary works required for complete operative system according to the
specifications & as shown on drawings.
1 SMB No 1 17300
2 SMDB-ST No 1 17300
TOTAL
CABLE FEEDERS
Supply, install, connect and test PVC insulated, PVC sheathed 600/1000V
stranded copper cables from main feeder distribution panelboard to branch circuit
panels & starter panels including raceways, termination, glands and all necessary
accessories and ancillary works required for complete operative system..
2 Pvc/Pvc condactor [(4x1x10)mm2 + 10mm2] and all necessary accessories and MT 300 17300
ancillary works required as specified and as shown on drawings.
3 Pvc/PvC condactor [(4x1x50)mm2 + 25mm2] and all necessary accessories and MT 250 17300
ancillary works required as specified and as shown on drawings.
4 Pvc/Pvc condactor [(4x240)mm2 + 120mm2] and all necessary accessories and MT 200 17300
ancillary works required as specified and as shown on drawings.
NB
Earthing impedance must be <= 2 ohm
Grounding system components shall be products :-
- Furse Co. or approved equal
TELECOMMUNICATION SYSTEM
Supply, install, connect and test Telephone System complete including conduits,
conduit fittings,(2x0.6mm) cabling, earthing complete including plaster rings,
wiring, earthing, terminations, socket plate, cover, plugs all necessary accessories
and ancillary work according to specification and Design
Supply, install, connect and test socket RJ-11 telephone outlets complete
including conduits, conduit fittings, (2x0.6mm) cabling, earthling complete
including plaster rings, wiring, earthling, terminations, socket plate, cover, plugs
all necessary accessories and ancillary work according to specification and Design
1 NO 180 17200
Sockets should be products of :-
'legrand
avaya
TOTAL
Supply, install, connect and test of MF frame complete as specified and indicated
2 in the drawings with all necessary termination, conduits, raceways, patch cords, NO 1 17200
cables and all necessary accessories required to complete operative system
Supply, install, connect and test of 10 pair wall mount telephone frames complete
as specified and indicated in the drawings with all necessary termination,
3 NO 30 17200
conduits, raceways, patch cords, cables and all necessary accessories required to
complete operative system
Supply, install, connect and test of 10 pair jelly filled cable complete as specified
4 and indicated in the drawings with all necessary termination, conduits, MT 700 17200
raceways,and all necessary accessories required to complete operative system
Supply, install, connect and test central dishes System complete including
conduits, conduit fittings, coaxial cable, distribution amplifiers , splitters ,
earthing complete including wiring, earthing terminations and all necessary
accessories and ancillary work according to specification and Design
5 complete Coaxial cable network including all necessar cabling, raceways & LS LS 17200
accessories. The item shall be complete with all necessary works according to the
specifications & the tender drwings.
TOTAL
ELECTRICITY WORKS
Page 1
Page 2
Page 3