Catalogue sm6 1508140048
Catalogue sm6 1508140048
Catalogue | 2013
SM6
Modular units
Air insulated switchgear up to 36 kV
Safety
Continuity of Service & Complete Safety
Reliability
● Type-tested solution which complies with the IEC62271-200
standard
● Design by the most accurate three-dimensional computer
techniques
● Manufacturing & Testing according to ISO 9001:2000
quality standard
Simplicity
● Easy installation - All cubicles with the same engineering
dimensions
● On-site information retrieval
● Possibility of remote management
● Maintenance with power on (LSC2A), very simple
● Compartmentalization of MV parts
(insulated partitions)
Schneider Electric has developed protection, monitoring and control solutions specifically
dedicated to Medium Voltage networks for over 40 years.
SM6 switchgear has been specifically designed on the basis of that extensive experience.
It also incorporates some very new solutions, giving the best in terms of continuity of service
and operators’ safety.
kA
25
A comprehensive solution
SM6 switchgear is fully compatible with
● PowerMeter metering units.
● Sepam multi-function protection relays
- Protection
- Measurements and diagnosis.
● VIP protection self powered relay for protection.
SM6 swithchboards can thus be easily integrated into any monitoring
and control system.
- Local & remote indication and operation.
installed
PM103193
world-wide.
SM6 General contents
Presentation 3
General characteristics 11
Characteristics
49
of the functional units
Connections 83
Installation 91
Appendices
101
Order form
AMTED398078EN 1
2 AMTED398078EN
Presentation Contents
Quality assurance 9
AMTED398078EN 3
Presentation The experience of a world leader
built cubicles and over thirty years in SF6 breaking technology for Medium
Voltage switchgear.
This experience means that today Schneider Electric can propose
a complementary range: vacuum type circuit breaker cubicles up to 24 kV
and standard or enhanced internal arc withstand cubicles to reinforce
the safety of people according to the IEC standard.
This gives you the advantage of unique experience, that of a world leader,
with over 2,500 000 SF6 Medium Voltage units installed throughout
the world.
1975: innovation
Sulphur hexafluoride (SF6) is first used in an MV switch for an MV/LV
transformer substation, with the VM6.
1989: experience
Over 300,000 VM6 cubicles equipped networks throughout the world.
4 AMTED398078EN
Presentation The range’s advantages
Upgradability
SM6, a comprehensive range
bb A comprehensive offer covering your present and future requirements
bb A design adapted to the extension of your installations
bb A catalogue of functions for all your applications
bb A product designed to be in compliance with standards constraints
bb Options to anticipate the control and monitoring of your installations.
Compactness
SM6, an optimised range
bb Compact units, with low increment cubicles
bb Rationalised space requirement for switchboard installation
bb Reduction of civil works costs
bb Easy integration in factory-built outdoor substations for which the SM6
is particularly well designed.
Maintenance
SM6, a range with reduced maintenance
bb The active parts (breaking and earthing) are integrated in an SF6-filled, “sealed for
life” unit
bb The control mechanisms, are intented to function with reduced maintenance
under normal operating conditions
bb Enhanced electrical endurance when breaking.
Ease of installation
SM6, a simple range to incorporate
bb Reduced dimensions and weights
bb Only one civil works layout
bb A solution adapted to cable connection
bb Simplified switchboard busbar design.
AMTED398078EN 5
Presentation Protecting the environment
61051N
for SF6 products is part of a rigorous
management process.
24 kV 36 kV
Switch Circuit breaker Switch Circuit breaker
unit unit unit unit
Ferrous metal 84% 65% 74% 82 %
01
ISO 140
6 AMTED398078EN
Presentation A full range of services
61052N
either associated or not with the supply of the SM6 unit.
AMTED398078EN 7
Presentation The references of a leader
SM6, a world-wide product
Asia/Middle East
PE57234
Africa
bb ONAFEX, Hilton Hotel, Algeria
bb Yaounde University, Cameroon
bb Karoua Airport, Cameroon
bb Libreville Airport, Gabon
bb Ivarto Hospital, CORIF, Madagascar
bb Central Bank of Abuja, ADEFEMI, Nigeria
bb OCI Dakar, Oger international, CGE, Senegal
bb Bamburi cement Ltd, Kenya
bb Ivory Electricity Company, Ivory Coast
bb Exxon, New Headquarters, Angola
South America/Pacific
bb Lamentin Airport, CCIM, Martinique
bb Space Centre, Kourou, Guyana
bb Mexico City Underground System, Mexico
bb Santiago Underground System, Chile
bb Cohiba Hotel, Havana, Cuba
bb Iberostar Hotel, Bavaro, Dominican Republic
bb Aluminio Argentino Saic SA, Argentina
bb Michelin Campo Grande, Rio de Janeiro, Brazil
bb TIM Data Center, São Paulo, Brazil
bb Light Rio de Janeiro, Brazil
bb Hospital Oswaldo Cruz, São Paulo, Brazil
Europe
bb Stade de France, Paris, France
bb EDF, France
bb Eurotunnel, France
bb Nestlé company headquarters, France
bb TLM Terminal , Folkestone, Great Britain
bb Zaventem Airport, Belgium
bb Krediebank Computer Centre, Belgium
bb Bucarest Pumping station, Romania
bb Prague Airport, Czech Republic
bb Philipp Morris St Petersburg, Russia
bb Kremlin Moscow, Russia
bb Madrid airport, Spain
bb Dacia Renault, Romania
bb Lafarge cement Cirkovic, Czech Republic
bb Caterpillar St Petersburg, Russia
bb Ikea Kazan, Russia
bb Barajas airport, Spain
bb Coca-cola Zurich, Switzerland
8 AMTED398078EN
Presentation Quality assurance
Quality certified to ISO 9001
A major advantage
Schneider Electric has integrated a functional organisation into each
of its units. The main mission of this organisation is to check the quality
and the compliance with standards.
This procedure is:
bb Uniform throughout all departments
bb Recognised by many customers and approved organisations.
But it is above all its strict application that has enabled recognition
to be obtained by an independent organisation:
The French Quality Assurance Association (FQAA).
The quality system for the design and manufacture of SM6 units
has been certified in conformity with the requirements of
the ISO 9001: 2000 quality assurance model.
MT55054
MT55055
900 1 ISO
ISO 9002
During manufacture, each SM6 is subject to systematic routine testing which aims to
check the quality and conformity:
bb Sealing testing
bb Filling pressure testing
bb Opening and closing rate testing
bb Switching torque measurement
bb Dielectric testing
bb Conformity with drawings and plans.
The results obtained are written and reported on the test certificate for each device
by the quality control department.
61003N
AMTED398078EN 9
General characteristics Contents
Field of application 12
Operating conditions 20
Standards 21
Main characteristics 22
Compartments description 26
Safety of people 28
By switchgear 28
By operating mechanism safety 30
By internal arc protection 31
Ammeter 39
AMTED398078EN 11
General characteristics Field of application
SM6 units are used for the MV section in MV/LV transformer substations in public
distribution systems and MV consumer or distribution substations up to 36 kV.
DE59670EN
Other standards
MV consumer substations
(MV metering)
IM IM DM1-D GBC-A QM DM1-S
MT55146
12 AMTED398078EN
General characteristics Field of application
HV/MV substation
DE59200EN
Distribution switchboard
DM1-A GBC-B QM QM IM IM IMB GBM QM DM1-S GBC-B DM1-A
61004N
Incoming Incoming
line ATS line
Unit definitions
Below is the list of SM6 units used in MV/LV
transformer substations and industrial distribution
substations:
bb IM, IMC, IMB switch
bb PM fused switch
bb QM, QMC, QMB fuse-switch combination
bb CVM contactor and contactor with fuses
bb DM1-A, DM1-D, DM1-S single-isolation
disconnectable SF6 type circuit breaker
bb DMV-A, DMV-D, DMV-S single-isolation Standby Standby
vacuum type circuit breaker frontal generator source source
bb DMVL-A, DMVL-D single-isolation disconnectable
vacuum type circuit breaker lateral
bb DM1-W, DM1-Z withdrawable single-isolation
SF6 type circuit breaker for SM6-24 Distribution switchboard
bb DM2 double-isolation disconnectable SF6 type QM QM GBC-B IM IMB GBM IM GBC-B DM1-S DM1-S
circuit breaker
bb CM, CM2 voltage transformers
bb GBC-A, GBC-B current and/or voltage measurements
bb NSM-cables for main incoming and standby
bb NSM-busbars for main incoming and cables
for standby
bb GIM intermediate bus unit
bb GEM extension unit
bb GBM connection unit
bb GAM2, GAM incoming cable connection unit
bb SM disconnector
bb TM MV/LV transformer unit for auxiliaries ATS
bb Other units, consult us Incoming Incoming
bb Special function EMB busbar earthing only for line line
SM6-24.
ATS: Automatic Transfer System
AMTED398078EN 13
General characteristics Units for switching function
Switching
See in
DE59671
DE59672
DE59673
details
on page
50 IM IMC IMB
Switch unit Switch unit Switch unit
SM6-24: 375 or 500 mm SM6-24: 500 mm with earthing disconnector
SM6-36: 750 mm SM6-36: 750 mm right or left outgoing line
SM6-24: 375 mm
SM6-36: 750 mm
DE59693
51 NSM-cables NSM-busbars
Cables power supply Busbars power supply
for main incoming line for main incoming line on right or left
and standby line and cables for standby line
SM6-24: 750 mm SM6-24: 750 mm
14 AMTED398078EN
General characteristics Units for protection function
Fuse-switch
See in
DE59674
DE59675
DE59676
details
on page
52 QM QMC QMB
Fuse-switch combination unit Fuse-switch combination unit Fuse-switch combination unit
SM6-24: 375 or 500 mm SM6-24: 625 mm right or left outgoing line
SM6-36: 750 mm SM6-36: 1000 mm SM6-24: 375 mm
SM6-36: 750 mm
DE59677
53 PM
Fuse-switch unit
SM6-24: 375 mm
SM6-36: 750 mm
SF6 circuit-breaker
DE59678
DE59679
54 DM1-A DM1-D
Single-isolation, disconnectable Single-isolation, disconnectable
circuit breaker unit circuit breaker unit
SM6-24: 750 mm right or left outgoing line
SM6-36: 1000 mm SM6-24: 750 mm
SM6-36: 1000 mm
AMTED398078EN 15
General characteristics Units for protection function
SF6 circuit-breaker
See in
DE59681
DE53487
DE53490
details
on page
55 DM2
Double-isolation, disconnectable
circuit breaker unit right or left outgoing line
SM6-24: 750 mm
SM6-36: 1500 mm
Vacuum circuit-breaker
DE53491
DE53492
DE53493
16 AMTED398078EN
General characteristics Units for protection function
Vacuum circuit-breaker
See in
DE53485
DE59694
details
on page
58 DMVL-A DMVL-D
Single-isolation, disconnectable Single-isolation, disconnectable
circuit breaker unit circuit breaker unit right outgoing line
SM6-24: 750 mm SM6-24: 750 mm
DE59232
59 CVM CVM
Fuse-contactor unit Contactor unit
SM6-24: 750 mm SM6-24: 750 mm
AMTED398078EN 17
General characteristics Units for metering function
See in
DE59863
DE59684
details
on page
60 CM CM2
Voltage transformers for mains Voltage transformers for mains
with earthed neutral system with insulated neutral system
SM6-24: 375 mm SM6-24: 500 mm
SM6-36: 750 mm SM6-36: 750 mm
DE53496
DE53497
61 GBC-A GBC-B
Current and/or voltage Current and/or voltage
measurement unit measurement unit
right or left outgoing line SM6-24: 750 mm
SM6-24: 750 mm SM6-36: 750 mm
SM6-36: 750 mm
18 AMTED398078EN
General characteristics Units for other functions
See in
DE59686
DE53498
DE59685
details
on page
DE59688
DE53498
DE59690
64 SM TM EMB
Disconnector unit MV/LV transformer unit Busbar earthing compartment
SM6-24: 375 mm or 500 (1) mm for auxiliaries SM6-24: 375 mm
SM6-36: 750 mm SM6-24: 375 mm
(1) only for 1250 A units. SM6-36: 750 mm
* For other switchboard extension (Modularc 36, Unifluorc or Fluokit M24), please consult us.
AMTED398078EN 19
General characteristics Operating conditions
In addition to its technical characteristics, SM6 units are designed for indoor installations.
SM6 meets requirements concerning safety Their compact dimensions are:
bb 375 to 1500 mm width
of life and property as well as ease bb 1600 to 2250 mm height
of installation, operation and protecting bb 840 to 1400 mm depth…
the environment. … this makes for easy installation in small rooms or prefabricated substations.
Cables are connected via the front.
All control functions are centralised on a front plate, thus simplifying operation.
PE57152
20 AMTED398078EN
General characteristics Standards
AMTED398078EN 21
General characteristics Main characteristics
The hereunder values are for working temperatures from -5°C up to +40°C
PE57150
Electrical characteristics
Rated voltage Ur kV 7.2 12 17.5 24 36
Insulation level
Insulation Ud 50/60 Hz, 1 min (kV rms) 20 28 38 50 70
Isolation Ud 50/60 Hz, 1 min (kV rms) 23 32 45 60 80
Insulation Up 1.2/50 µs (kV peak) 60 75 95 125 170
Isolation Up 1.2/50 µs (kV peak) 70 85 110 145 195
Breaking capacity
Transformer off load A 16
Cables off load A 31.5 50
Rated current Ir A 400 - 630 -1250 630-1250
Short-time withstand current Ik/tk (1) kA /1 s 25 630 - 1250 1250
20 (2) 630 - 1250
16 630 - 1250
12.5 400 - 630 - 1250 630-1250
Making capacity (50 Hz) Ima kA 62.5 630 NA
50 630
40 630
31.25 400 - 630 630
Maximum breaking capacity (Isc)
Units IM, IMC, IMB A 630 - 800 (3) 630
NSM-cables, NSM-busbars A 630 - 800 (3) NA
QM, QMC, QMB kA 25 20 20
PM kA 25 20
CVM kA 6.3 NA
CVM with fuses kA 25 NA
SF6 circuit breaker range
DM1-A, DM1-D, DM1-W (4) kA 25 630-1250 1250
20 630-1250
DM1-S kA 25 630 NA
DM1-Z 25 1250 NA
DM2 kA 20 630
25 630 1250
Vacuum circuit breaker range
DMV-A, DMV-D, DMV-S kA 25 630-1250 NA
DMVL-A kA 20 630 NA
DMVL-D kA 25 630 NA
NA: Non Available
(1) 3 phases
(2) In 20 kA / 3 s, consult us
(3) In 800 A, consult us.
(4) NA for SM6-36
22 AMTED398078EN
General characteristics Main characteristics
Endurance
PE57150
Protection index:
bb Classes: PI (insulating partition)
bb Loss of service continuity classes: LSC2A (LSC1 for metering functions)
bb Units in switchboard: IP3X
bb Between compartments: IP2X for SM6-24, IP2XC for SM6-36
bb Cubicle: IK08 for SM6-24, IK07 for SM6-36.
Electro-magnetic compatibility:
bb Relays: 4 kV withstand capacity, as per recommendation IEC 60801.4
bb Compartments:
vv electrical field:
-- 40 dB attenuation at 100 MHz
-- 20 dB attenuation at 200 MHz
vv magnetic field: 20 dB attenuation below 30 MHz.
Temperatures:
The cubicles must be stored and installed in a dry area free from dust and with
limited temperature variations.
bb For stocking: from – 40°C to +70°C
bb For working: from – 5°C to +40°C
bb Other temperatures, consult us.
AMTED398078EN 23
General characteristics Factory-built cubicles
description
5 low voltage: installation of a terminal block (if motor option installed), LV fuses
and compact relay devices.
If more space is required, an additional enclosure may be added on top of the cubicle.
5 low voltage: installation of compact relay devices (Statimax) and test terminal
4 boxes. If more space is required, an additional enclosure may be added on top
of the cubicle.
24 AMTED398078EN
General characteristics Factory-built cubicles
description
1 switchgear: load break switch and earthing switch(es), in enclosure filled with
2 SF6 and satisfying and one vacuum circuit breaker, “sealed pressure system”
1 5 requirements.
2 busbars: all in the same horizontal plane, thus enabling later switchboard
4 extensions and connection to existing equipment.
5 low voltage: installation of compact relay devices (VIP) and test terminal boxes.
If more space is required, an additional enclosure may be added on top of the cubicle.
5 low voltage: installation of compact relay devices (VIP) and test terminal boxes.
If more space is required, an additional enclosure may be added on top of the cubicle.
Contactor cubicles
1 switchgear: disconnector and earthing switch and contactor in enclosures filled
DE58650
2 2 busbars: all in the same horizontal plane, thus enabling later switchboard
extensions and connection to existing equipment.
1 5
3 connection and switchgear: accessible through front.
This compartment is also equipped with an earthing switch downstream.
4 The contactor may be equipped with fuses.
2 types may be used:
bb Vacuum with magnetic holding
bb Vacuum with mechanical latching.
3 4 operating mechanism: contains the elements used to operate
the disconnector(s), the contactor and the earthing switch and actuate
the corresponding indications.
5 low voltage: installation of compact relay devices and test terminal boxes.
With basic equipment, an additional enclosure is added on top of the cubicle.
4
Options: please, refer to the chapter “Characteristics of the functional units”.
AMTED398078EN 25
General characteristics Compartments description
Busbar compartment
DE53507
61007N The three insulated busbars are parallel-mounted. Connection is made to the upper
pads of the enclosure using a field distributor with integrated captive screws.
Ratings 400 (for SM6-24 only) - 630 - 1250 A.
Switch compartment
DE53508
61006N
This compartment is separated from the busbar compartment and the connection
compartment by the enclosure surrounding the switch, the disconnector and
the earthing switch.
A stud incorporated in the field distributor makes it possible to position and secure
the cable-end lug with a single hand.
26 AMTED398078EN
General characteristics Compartments description
Operating-mechanism cover
DE57173
PE57230
These covers contain the various operating functions for the:
bb switch and earthing switch
bb disconnector(s)
bb circuit breaker
bb contactor
and the voltage presence indicator.
The operating-mechanism cover may be accessed with the cables and busbars
energised and without isolating the substation.
It also enables easy installation of padlocks, locks and standard LV accessories
(auxiliary contacts, trip units, motors, etc.).
A - LV cover B - LV wiring duct C - LV control cabinet Low-voltage monitoring control cabinet for SM6-24
h = 1600 mm h = 1690 mm h = 2050 mm
It enables the cubicle to be equipped with low voltage switchgear providing
PE57153
DE57195
section to be installed such as indication buttons, push
buttons or protection relays. C
The total height of the cubicle is then 1600 mm.
B
B - LV wiring duct and cabinet: enables a large A
majority of low voltage configurations to be installed.
It also takes the Sepam series 20 or series 40.
The total cubicle height is then 1690 mm.
A - LV cover
h = 2250 mm
Low-voltage monitoring control cabinet for SM6-36
A - LV cover: enables a very simple low voltage 215 mm
PE58270
AMTED398078EN 27
General characteristics Safety of people
By switchgear
bb Gas tightness
The three rotating contacts are placed in an enclosure filled with gas to a relative
pressure of 0.4 bar (400 hPa) for SM6-24 and 1 bar (1000 hPa) for SM6-36.
It satisfies “sealed pressure system” requirements and seal tightness is always
factory checked, and leakage rate is less than 0.1% for 30 years life span.
bb Operating safety
vv the switch may be in one of three positions: “closed”, “open”, or “earthed”,
representing a natural interlocking system that prevents incorrect operation.
Moving-contact rotation is driven by a fast-acting mechanism that is independent
Switch-disconnector for 24 kV of the action of the operator.
vv the device combines the breaking and disconnection functions.
vv the earthing switch placed in the SF6 has a short-circuit making capacity,
PE57226
Switch-disconnector for 36 kV
28 AMTED398078EN
General characteristics Safety of people
By switchgear
bb Gas tightness
The SF1 circuit breaker is made up of three separate poles mounted
on a structure supporting the operating mechanism. Each pole-unit houses
all the active elements in an insulating enclosure filled with gas to a relative pressure
of 0.5 bar (500 hPa) for 24 kV and 2 bar (2000 hPa) for 36 kV. It satisfies “sealed
pressure system” requirements and seal tightness is always checked in the factory.
bb Operating safety
Accidental over-pressures are eliminated by the opening of the safety membrane.
DE53514
bb Operating safety
The magnetic field is applied along the contact axis of the vacuum type circuit breaker.
This process diffuses the arc in a regular manner with high currents.
It ensures optimum distribution of the energy along the compact surface
so as to avoid local hot spots.
The advantages of this technique:
vv a simplified vacuum type circuit breaker which is consequently very reliable,
vv low dissipation of arcing energy in the circuit breaker,
vv highly efficient contacts which do not distort during repeated breaking,
vv significant reduction in control energy.
AMTED398078EN 29
General characteristics Safety of people
By operating mechanism safety
For combined switch fuses, the opening mechanism is armed at the same time
as the contacts are closed.
bb Opening: the switch is opened using the same quick acting mechanism,
operated in the opposite direction.
For circuit breakers and the combined switch fuses, opening is controlled by:
vv a push-button,
vv a fault.
bb Earthing: a specific control shaft enables the opening or closing of the earthing
contacts. Access to this shaft is blocked by a cover that can be slid back if the switch
is open but which remains locked in place if it is closed.
VPIS complies with 62271-206 standard allowing to indicate the voltage presence on
each phase with LEDs. Designed for harsh environments so that to guarantee high
reliability in MV/LV susbstations worldwide.
Exits in Voltage Output version to provide voltage presence information to VD23
voltage presence relay.
30 AMTED398078EN
General characteristics Safety of people
By internal arc protection
Standard IEC 62271-200 appendix A To enhance the safety of people, it is desirable to provide as high a degree
indicates a method for testing switchgear of protection as possible by evacuating the effects of internal arc using:
bb Evacuation systems which direct gases towards the top or the bottom
in metal enclosures under internal arc of the switchboard enabling over pressure to be limited in the case
conditions. The aim of this test is to show of an internal fault in the compartments
that an operator situated in front of bb Channelling and evacuating hot gases towards an external area, which is not
a switchboard would be protected hazardous for the operator
bb Materials which are non-inflammable in the cubicles
against the effects of an internal fault. bb Reinforced panels.
Consequently:
The SM6 is designed to offer a good level of safety
bb Control of the architecture:
vv compartment type enclosure.
bb Technological control:
vv electrotechnical: modelling of electrical fields,
DE59732
vv 16 kA 1 s, IAC: A-FL.
AMTED398078EN 31
General characteristics MV electrical network
management
Easergy T200 S for SM6-24
PE56423
32 AMTED398078EN
General characteristics MV electrical network
management
Easergy T200 I
PE56422
PE56824
AMTED398078EN 33
General characteristics MV electrical network
management
Automation systems
Current Easergy T200 automation systems are factory predefined. No on-site programming
DE40552EN
Voltage
b Switches can be controlled manually in the following circumstances:
drop v automation system switched off
v switch in local mode.
Sectionaliser (SEC)
The sectionaliser automation system opens the switch after a predefined number of
b Configurable parameters: Time faults (1 to 4) during the voltage dip in the reclosing cycle of the top circuit breaker.
v Number of faults: from 1 to 4 b The automation system counts the number of times a fault current followed
v Execution time: from 20 s to 4 mins configurable
in 5 s steps
by a voltage loss is detected. It sends an open order if:
v Automation system valid/invalid. v the switch is closed
v the fault has disappeared
DE59320EN
DE56654
Network ATS version: control of two MV network channels.
C
TR T1 TR
The network ATS automatic transfer system requires use of
O SW2 SW1 SW2
the VD23 relay for detection of voltage presence/absence.
Network ATS - Semi-Auto Mode Generator ATS version: control of one network channel and
(without paralleling upon automatic return) one generating set channel (not available on T200 E).
TR: switch response time
Note: ATS automatic transfer system is available only on channels
Vn
SW1 voltage 1 and 2 of each CONTROL module. Generator ATS automatic
transfer system is available only on the first CONTROL module
O
(channels 1 to 4).
C
T1 TR SW1 T2 TR Operating modes
O The operating mode is selected from the T200 Web server.
Mode SW1VSW2 or SW2VSW1 (or SWVSWG if Generator ATS):
C
TR SW2 TR Automatic transfer system executes only one changeover from the priority channel
O
to the backup channel. Automatic transfer system then remains on that channel.
Network ATS - Auto Mode SW1 Semi-Auto mode SW1XVSW2 (or SWXVSWG if Generator ATS):
(with paralleling upon automatic return)
TR: switch response time
In the event of a voltage loss on the active channel, automatic transfer system
switches to the other channel after a time delay T1. Automatic transfer system
executes no return, except in case of voltage loss on the new active channel.
DE59321EN
Vn
SW1 voltage Auto SW1 or Auto SW2 mode (or Auto SW if Generator ATS):
0
After a changeover, return to the priority channel occurs if the MV voltage on that
1 channel is restored. The channel that has priority can be defined according to
T1 GE Command 6s
0
the state of a dedicated digital input.
Vg
Tg1 GE voltage Tg2 Changeover sequences:
0 Network ATS: in the event of voltage loss on the normal channel, changeover involves
opening the normal channel after time delay T1 and then closing the backup channel.
C TR Note: in “Auto” mode, the sequence of return to the normal channel depends on
TR SW
O configuration of the “Paralleling upon auto return” option (see below).
Generator ATS: in the event of voltage loss on the network channel, changeover
C
TR T2 TR SWG involves sending the order for opening the network channel and at the same time
O the Generator start-up order, after time delay T1.
C The remainder of the changeover sequence depends on the management of
TR T2 TR SWG
O
Generator channel closing (configurable option):
bb Case of Generator channel closing after start-up order:
Generator ATS - Auto SW mode After the Generator start-up order, the closing order is given to the Generator
(Without paralleling upon Auto return) channel, without waiting until the Generator is actually started.
TR: Switch response time bb Case of Generator closing after Generator power on:
Tg1: Generator starting time (maximum 60 s) The Generator channel closing order is sent only when Generator voltage is detected.
Tg2: Generator stopping time
Case : Generator channel closing after Generator power on
(configurable option)
Case : Generator channel closing after Generator start-up
command (configurable option)
34 AMTED398078EN
General characteristics MV electrical network
management
Automation systems
Source transfer locking 1 bb When the automatic transfer system is configured with auto return on the network
2 channel, Generator stoppage is requested 6 s after the changeover sequence
DO 1 3 is completed.
4
+5
Stop/start generator order
–6
AMTED398078EN 35
General characteristics MV electrical network
management
Automation systems
The BTA (Bus Tie Automatism) is an automation system for switching sources
SW1 SW3 SW2 between two incoming lines (SW1 and SW2) and a busbar coupling switch (SW3).
It must be used in conjunction with VD23 type voltage presence detectors and the fault
current detection function on the busbar incoming lines.
Operating mode
Two operating modes can be configured:
b Standard mode:
“Normal” position
If the voltage is lost on one busbar, the automation system opens the incoming line
(SW1 or SW2) and closes the coupling switch SW3. Coupling is conditional upon
the absence of a fault current on the main source.
b Interlock on loss of voltage after switching mode:
After execution of the automation system in standard mode, the voltage presence is
SW1 SW3 SW2 checked for a configurable period. If the voltage is lost during this period,
the coupling switch SW3 is opened and the automation system interlocked.
Coupling sequence
b Coupling takes place if the following conditions are met:
v the automation system is switched on
v the switches on incoming channels SW1 and SW2 are closed
Active coupling
v the earthing switches SW1, SW2 and SW3 are open
v there is no voltage on an incoming line SW1 or SW2
v there is no fault current detection on SW1 and SW2
v there is no transfer interlock
v voltage is present on the other incoming line.
DE59322EN
36 AMTED398078EN
General characteristics Fault passage indicators
Flair 21D, 22D and 23DM
Flair 21D, 22D, 23DM is a family of DIN Applications and main features
format fault passage indicators. They are The Flair range increases your power availability by providing indicators
small in size, self-powered and adapt suitable for fault locating and MV network load management.
automatically to the network. b Indication of phase-phase and phase-earth faults
b Display of settings
These devices use cutting-edge technology b Indication of the faulty phase
to detect earth faults on underground MV b Display of the load current including peak demand and frequency
networks with isolated, resistor-earthed or b Fault passage indication and voltage detection combination (Flair 23DM)
directly earthed neutral and overcurrents on b RJ45 communication (Flair 23DM only).
all networks. These fault passage indicators are reliable and easy to use.
b Self-powered, the fault current passage b Automatic setting on the site
detection and indication system operates b Fault indication with LED or outdoor lamp
continuously b 15-year battery life for Flair 22D
b More accurate fault detection if Flair 22D or 23DM is connected to voltage
b Adjustment-free, they are immediately
presence indication system (VPIS) voltage output
operational (numerous manual adjustments b Can be factory-mounted in Premset cubicles or added on the site
are however possible) b Easy on-site addition without removing MV cables using split-type current sensor.
b Compact, their DIN format easily fits
in MV cubicles Fault detection functions
b Smart, they offer an ammeter/digital
maximeter function Overcurrent detection
b Comprehensive, the Flair 23DM version b Automatic mode for adjustment-free calibration of detection thresholds
b Manual mode for special override settings:
incorporates a highly sophisticated voltage
□ Flair 21D: 4 detection thresholds from 200 A to 800 A, in 200 A increments,
presence/absence relay function with RJ45 selectable via microswitches
Modbus communication. □ Flair 22D and Flair 23DM: 8 detection thresholds from 100 A to 800 A, in 50 A
increments, confi gurable via the front panel keypad.
b Fault acknowledge time:
□ Flair 21D: 40 ms
□ Flair 22D and Flair 23DM (configurable via the front panel keypad)
PE57783
□ Flair 22D and Flair 23DM (configurable via the front panel keypad):
- Type A from 20 to 200 A, in 10 A increments
- Type B from 5 to 30 A in 5 A increments and 30 to 200 A in 10 A.
b Inrush function: prevents unnecessary detection in the event of load switch-on.
Incorporates a 3 s time delay for fault fi ltering at network power up.
The Inrush function can be disabled via confi guration on Flair 22D and 23DM.
Indication reset
b Automatic reset upon load current recovery (configurable time delay on Flair 22D
and Flair 23DM)
b Manual reset via front panel button
b Reset via external Reset input
b Reset by time delay: fixed (4 hr) for Flair 21D and adjustable using front
panel keypad (2 hr to 16 hr) for Flair 22D and Flair 23DM.
AMTED398078EN 37
General characteristics Fault passage indicators
Flair 21D, 22D and 23DM
L1
Power supply Self-powered b b b
L2
A
I max.
L3
Dual-powered b (1) b
Esc
Easergy
Flair 22D Detection Overcurrent b b
EMS58352
Earth-fault b b
Display Ammeter b b
(4 digit LCD) Maximeter b b
SCADA interface (relay) b b
External lamp b b
External reset b b
Extended setting (keypad) b b
Connection diagrams Communication 2-voltage output relays b
Serial communication port b
DM1000048
L3
(1) By lithium battery
L2
L1
Characteristics per product
Model Description
Fault passage indicator with single power supply (self-powered)
Flair 23DM Detector with 24-48 Vdc external and autonomous power supply
External indicator lamp output powered by the Flair (BVE)
Zero sequence CT option (type B or C setup)
FLAIR 22D
Reset Indication Voltage presence and absence detector (same as for VD23)
L3 Interface with VPIS-VO needed for the voltage presence
L2
L1
VPIS-VO Standard applications
-
option +
SCADA Reset Flair 21D Maintenance-free, adjustment-free fault detector
Flair 22D Fault detector for networks with very low load current (< 2 A) with
(1) possibility of manual adjustments
Flair 23DM Adapted to Feeder Automation. Forwarding of current measurement,
fault passage indication and voltage outage information to the SCADA
FLAIR 23DM via a serial communication port.
Reset Indication Voltage
relays Combination fault passage indicator and voltage detector, ideal for use
(1) Com RS485 with an Automatic Transfer System
38 AMTED398078EN
General characteristics Ammeter
Current sensors
bb Split core CT for mounting on MV cables.
Technical data
Application
Frequency 50 Hz and 60 Hz
Load current Minimum current ≥ 3A
Measurement
Range Phase current 3 to 630 A (resolution 1 A)
DE58404
AMTED398078EN 39
General characteristics Protection and control monitoring
Sepam selection guide for all applications
(1) LPCT: low-power current transformer complying with standard IEC 60044-8.
(2) Control matrix for simple assignment of information from the protection,
control and monitoring functions.
(3) Logipam ladder language (PC programming environment) to make full use
of Sepam series 80 functions.
(4) Standard lithium battery 1/2 AA format, 3.6 V, front face exchangeable.
40 AMTED398078EN
General characteristics Protection and control monitoring
Sepam selection guide for all applications
Series 40 Series 60
Protections
Current b b b b b b
Voltage b b b b b b
Frequency b b b b b b
Specifics Directional Directional Directional Directional
earth fault earth fault earth fault earth fault
and phase and phase
overcurrent overcurrent
Applications
Substation S40 S41, S43 S42 S60 S62
Busbar
Transformer T40 T42 T60 T62
Motor M41 M61
Generator G40 G60 G62
Capacitor C60
Characteristics
Logic inputs 0 to 10 0 to 28
Logic outputs 4 to 8 4 to 16
Temperature sensors 0 to 16 0 to 16
Channel
Current 3 I + Io 3 I + Io
Voltage 3V, 2U + Vo 3V, 2U + Vo or Vnt
LPCT (1) b b
Communication ports 1 to 2 1 to 2
IEC61850 Protocol b b
Control
Matrix (2) b b
Logic equation editor b b
Logipam (3)
Other
Backup battery 48 hours Lithium battery (4)
Front memory cartridge b
with settings
(1) LPCT: low-power current transformer complying with standard IEC 60044-8.
(2) Control matrix for simple assignment of information from the protection, control and monitoring functions.
(3) Logipam ladder language (PC programming environment) to make full use of Sepam series 80 functions.
(4) Standard lithium battery 1/2 AA format, 3.6 V, front face exchangeable.
AMTED398078EN 41
General characteristics Protection and control monitoring
Sepam selection guide for all applications
Series 80
Protections
Current b b b b b b b b
Voltage b b b b b b b b
Frequency b b b b b b b b
Specifics Directional Directional Disconnection Transformer Machine Voltage and frequency Capacitor-bank
earth fault earth fault by rate of & transformer- differential protection for 2 sets unbalance
and phase change of machine unit of busbars
overcurrent frequency differential
Applications
Substation S80 S81 S82 S84
Busbar B80 B83
Transformer T81 T82 T87
Motor M81 M88 M87
Generator G82 G88 G87
Capacitor C86
Characteristics
Logic inputs 0 to 42 0 to 42 0 to 42 0 to 42
Logic outputs 5 to 23 5 to 23 5 to 23 5 to 23
Temperature sensors 0 to 16 0 to 16 0 to 16 0 to 16
Channel
Current 3 I + 2 x Io 2 x 3 I + 2 x Io 3 I + Io 2 x 3 I + 2 x Io
Voltage 3V + Vo 3V + Vo 2 x 3V + 2 x Vo 3V + Vo
LPCT (1) b b b b
Communication ports 2 to 4 2 to 4 2 to 4 2 to 4
IEC61850 Protocol b b b b
Control
Matrix (2) b b b b
Logic equation editor b b b b
Logipam (3) b b b b
Other
Backup battery Lithium battery (4) Lithium battery (4) Lithium battery (4) Lithium battery (4)
Front memory cartridge b b b b
with settings
(1) LPCT: low-power current transformer complying with standard IEC 60044-8.
(2) Control matrix for simple assignment of information from the protection, control and monitoring functions.
(3) Logipam ladder language (PC programming environment) to make full use of Sepam series 80 functions.
(4) Standard lithium battery 1/2 AA format, 3.6 V, front face exchangeable.
42 AMTED398078EN
General characteristics Protection and control monitoring
VIP 35 protection relay
VIP 300 LL protection relay
AMTED398078EN 43
General characteristics Protection and control monitoring
Sepam series 10 with CRa/CRb sensors
44 AMTED398078EN
General characteristics Protection and control monitoring
Protection and sensor selection table
AMTED398078EN 45
General characteristics Protection and control monitoring
LPCT protection chain
Advantages
bb Consistent protection chain with the same sensor measures phase currents
Demanding from 5 A to 630 A
applications
bb Simple to install and implement:
vv installation of LPCT sensors
PE88011
5.00
4.75
Custom 4.50
applications 4.25
4.00
3.75
PE88010
3.50
3.25 Protective class 5P
3.00
2.75 Measuring class 0.5
2.50
2.25
2.00
1.75
1.50
1.25
1.00
Sepam series 60 and 80 0.75
0.50
0.25 A
loss).
Connections
1 LPCT sensor, equipped with a shielded cable fitted with an RJ45 connector
to be connected directly to the card 3
2 Sepam series 20, 40, 60 and 80 protection unit
3 Card interface that adapts the voltage delivered by the LPCT sensors,
with microswitch setting of rated current.
vv CCA671 card for series 60 and 80
vv CCA670 card for series 20 and 40.
46 AMTED398078EN
General characteristics PS100 high-availability power
supply
Backup solution for MV switchgear power needs PS100 backup power supply for MV substations
in the event of micro outages and power
interruptions. Applications
bb Easy maintenance with only one battery The power supply unit supplies backup operating power for:
bb MV switchgear motor mechanisms and circuit breaker coils
bb Remote battery monitoring
bb Transmission equipment (e.g. radio)
bb High level of insulation to protect the electronic bb Control units such as RTU or Automatic Transfer System
devices in harsh MV environments bb Protection relays, Fault Passage Indicators and others electronic devices.
bb End-of-life alarm possible via Modbus
communication High availabilty power supply
A battery ensures uninterrupted operation of the whole substation in the event of loss
bb Compliant with standards IEC 60 255-5
of the main supply. The backup power supply unit:
(10 kV level).
bb Includes a regulated and temperature-compensated charger
bb Stops the battery before deep discharge
bb Carries out a battery check every 12 hours
bb Measures battery ageing
PM100592
PS100 benefits
Only one battery
Traditional backup power supplies require a set of 2 or 4 batteries to produce
24 V or 48 V, with complicated replacement and adjustment of the battery pack.
The PS100 needs only one battery, simplifying replacement.
The battery is a standard sealed lead-acid 12 V battery with a 10-year service.
PS100
It can be purchased easily, anywhere in the world.
Main features
bb DIN rail mounting for easy integration in any LV cabinet or MV/LV substation
bb 2 power supply outputs:
vv 12 Vdc - 18 W continuous - 100 W 20 s (for modem, radio, RTU, etc.)
vv 48 Vdc or 24 Vdc - 300 W /1 minute (for switchgear operating mechanism motors)
and 90 W / continuous for protection relays, electronic devices, etc.
bb RJ45 Modbus communication port
bb 2 output relays (AC supply ON, Battery ON)
bb Diagnosis with LEDs
bb 1 sealed lead-acid 12 V battery with a 10-year service life (from 7 Ah to 40 Ah)
bb Power supply paralleling available with a 2nd PS100
bb - 40°C to +70°C operating temperature.
Range
bb PS100-48V 48 Vdc power supply and battery charger
bb PS100-24V 24 Vdc power supply and battery charger
bb Bat24AH 24 Ah long life battery
bb Bat38AH 38 Ah long life battery.
AMTED398078EN 47
48 AMTED398078EN
Characteristics of Contents
the functional units
Operating mechanisms 65
Auxiliaries 68
Protection of transformers 77
Interlocks 79
AMTED398078EN 49
Characteristics of Functional units selection
the functional units Switching
IM IMC IMB
Switch unit Switch unit Switch unit with earthing switch
Right or left outgoing
DE59700
DE53518
DE53519
Electrical characteristics
DE59710
DE59711
kA Ik/1s kA Ima
25 62.5
20 50
Ir = 630 A
Ir = 630 A
16 40
Basic equipment:
bb switch and earthing switch
bb three-phase busbars
bb CIT operating mechanism
bb voltage presence indicator
bb 150 W heating element for SM6-36
bb connection pads for dry-type cables bb three-phase bottom busbars
for outgoing lines (right or left)
bb one to three CTs for SM6-24
bb three CTs for SM6-36
Versions:
bb CI2 operating mechanism
bb CI1 operating mechanism bb CI1 operating mechanism for SM6-36 bb CI1 operating mechanism
bb in 800 A version for SM6-24, consult us
Optional accessories:
bb motor for operating mechanism bb 630 A three-phase upper busbars for severe operating conditions for SM6-24
bb auxiliary contacts bb visibility of main contacts
bb key-type interlocks bb pressure indicator device
bb release units (coil) bb enlarged low-voltage control cabinet for SM6-24
bb operation counter bb 50 W heating element for SM6-24
bb 1250 A three-phase upper busbars bb 630 A cable connection by the top (no internal arc withstand if selected)
bb fault indicators
bb Connection pads for two dry-type single-core cables for 36 kV
bb digital ammeter
bb surge arresters (for SM6-36 and for SM6-24 in 500
mm width cubicle)
bb 630 A busbars earthing switch cabinet for SM6-24
(not available for internal arc IEC62271-200)
50 AMTED398078EN
Characteristics of Functional units selection
the functional units Switching
Automatic Transfer System for SM6-24
DE58401
DE53561
Electrical characteristics
DE59212
DE59218
kA Ik/1s kA Ima
25 62.5
20 50
Ir = 630 A
Ir = 630 A
16 40
Basic equipment:
bb switches and earthing switches
bb three-phase busbars
bb connection pads for dry-type cables
bb voltage presence indicator
bb mechanical interlocking
bb motorised operating mechanism CI2 with open/close coils
bb additional enclosure
bb automatic-control equipment (T200 S)
Optional accessories:
bb auxiliary contacts
bb key-type interlocks
bb 50 W heating element
bb control and monitoring
bb visibility of main contacts
bb pressure indicator device
bb 1250 A three-phase upper busbars
bb 630 A three-phase upper busbars for severe operating conditions
AMTED398078EN 51
Characteristics of Functional units selection
the functional units Protection
Fuse-switch
QM QMC QMB
Fuse-switch combination unit Fuse-switch combination unit Fuse-switch combination unit
Outgoing line right or left
DE59701
DE53523
DE53524
Electrical characteristics
DE59712
DE59713
kA Ik/1s kA Isc
25 25
20 20
Ir = 200 A Ir = Ir = 200 A Ir =
16 63 A 16 63 A
12.5 12.5
Ur Ur
Basic equipment:
bb switch and earthing switch
bb three-phase busbars
bb CI1 operating mechanism
bb voltage presence indicator
bb equipment for three DIN striker fuses
bb mechanical indication system for blown fuses
bb 150 W heating element for SM6-36
bb connection pads for dry-type cables bb three-phase bottom busbars for
bb downstream earthing switch 2 kA rms making capacity outgoing lines (right or left)
bb one to three CTs for SM6-24
bb three CTs for SM6-36
Version:
bb equipment for three UTE striker fuses for SM6-24
bb CI2 operating mechanism bb CI2 operating mechanism for SM6-36
Optional accessories:
bb motor for operating mechanism
bb auxiliary contacts
bb key-type interlocks
bb auxiliary contact for blown fuses
bb DIN striker fuses
bb release units (coil)
bb digital ammeter
bb 1250 A three-phase upper busbars
bb 630 A cable connection by the top (no internal arc withstand if selected)
bb visibility of main contacts
bb pressure indicator device
bb 630 A three-phase upper busbars for severe operating conditions for SM6-24
bb enlarged low-voltage control cabinet for SM6-24
bb 50 W heating element for SM6-24
52 AMTED398078EN
Characteristics of Functional units selection
the functional units Protection
Fuse-switch
PM
Fused-switch unit
DE53526
Electrical characteristics
DE59714
25
20
Ir = 200 A Ir =
16 63 A
12.5
Ur
7.2 12 17.5 24 36 kV
Basic equipment:
bb switch and earthing switch
bb three-phase busbars
bb CIT operating mechanism
bb voltage presence indicator
bb connection pads for dry-type cables
bb downstream earthing switch 2 kA rms making capacity
bb equipment for three UTE (for SM6-24) or DIN striker fuses
bb 150 W heating element for SM6-36
Version:
bb CI1 operating mechanism
bb CI2 operating mechanism for SM6-36
Optional accessories:
bb motor for operating mechanism
bb auxiliary contacts
bb digital ammeter
bb key-type interlocks
bb mechanical indication system for blown fuses
bb 1250 A three-phase upper busbars
bb 630 A cable connection by the top (no internal arc withstand if selected)
bb UTE (for SM6-24) or DIN striker fuses
bb visibility of main contacts
bb pressure indicator device
bb 630 A three-phase upper busbars for severe operating conditions for SM6-24
bb enlarged low-voltage control cabinet for SM6-24
bb 50 W heating element for SM6-24
bb Release units for SM6-36
AMTED398078EN 53
Characteristics of Functional units selection
the functional units Protection
SF6 type circuit breaker
DE53532
DE53533
Electrical characteristics
DE59715
Ir =
25
1250 A
20
Ir = 630 - 1250 A
16
7.2 12 17.5 24 36 kV
Basic equipment:
bb SF1 disconnectable circuit breaker
bb disconnector and earthing switch
bb three-phase busbars
bb circuit breaker operating mechanism RI
bb disconnector operating mechanism CS
bb voltage presence indicator
bb three CTs
bb auxiliary contacts on circuit breaker
bb mechanical interlocking between circuit breaker and disconnector
bb 150 W heating element for SM6-36
bb connection pads for dry-type cables bb three-phase bottom busbars
bb downstream earthing switch 2 kA rms making
capacity at 630 A and 25 kA rms making capacity
at 1250 A
Version:
bb LPCT (only with Sepam series 20, 40, 60, 80)
bb SFset circuit breaker disconnectable (only for 400-630 A performances and SM6-24)
Optional accessories:
bb cubicle: vv 630 A three-phase upper busbars for severe operating conditions for SM6-24
vv auxiliary contacts on the disconnector vv enlarged low-voltage control cabinet for SM6-24
vv protection using Sepam programmable electronic unit vv 50 W heating element for SM6-24
vv three voltage transformers vv connection pads for two dry-type single-core cables for SM6-36
vv key-type interlocks
vv 1250 A three-phase upper busbars at Ir 630 A
vv 630 A cable connection by the top (no internal arc
withstand if selected)
vv surge arresters
vv 630 A busbars earthing switch cabinet for SM6-24
(not available for internal arc IEC62271-200)
54 AMTED398078EN
Characteristics of Functional units selection
the functional units Protection
SF6 type circuit breaker
DE53536
DE53537
Electrical characteristics
DE59212-Isc
DE59721
Ir =
25 25
1250 A
20 20
Ir = 630 A Ir = 630
16 16
Basic equipment:
bb SF1 disconnectable circuit breaker
bb disconnector and earthing switch
bb three-phase busbars
bb circuit breaker operating mechanism RI
bb disconnector operating mechanism CS
bb auxiliary contacts on circuit breaker
bb mechanical interlocking between circuit breaker and disconnector
bb VIP relay bb three CTs
bb three CR sensors for VIP relay protection bb 150 W heating element for SM6-36
bb voltage presence indicator
bb connection pads for dry-type cables
bb downstream earthing switch 2 kA rms making capacity
Version:
bb Sepam series 10 with auxiliary supply and
three CR sensors
Optional accessories:
bb cubicle: bb cubicle:
vv key-type interlocks vv protection using Sepam programmable electronic unit
vv auxiliary contacts on disconnectors
vv 2 voltage transformers phase-to-phase or 3 voltage transformers phase-to-earth
vv 1250 A three-phase upper busbars at Ir 630 A bb 630 A cable connection by the top (no internal arc withstand if selected)
vv 630 A three-phase upper busbars for severe vv 50 W heating element for SM6-24
operating conditions for SM6-24
vv enlarged low-voltage control cabinet for SM6-24
bb circuit breaker:
vv motor for operating mechanism
vv release units (coil)
vv operation counter on manual operating mechanism
AMTED398078EN 55
Characteristics of Functional units selection
the functional units Protection
SF6 type circuit breaker
DM1-W DM1-Z
Withdrawable single-isolation Withdrawable single-isolation CB unit
circuit breaker unit Outgoing line on right
DE53538
DE53539
Electrical characteristics
DE59715
DE59226
25 25
20 20
Ir = 630 - 1250 A Ir = 1250 A
16 16
Basic equipment:
bb SF1 withdrawable circuit breaker
bb disconnector and earthing switch
bb three-phase busbars
bb circuit breaker operating mechanism RI
bb disconnector operating mechanism CS
bb voltage presence indicator
bb three CTs
bb auxiliary contacts on circuit breaker
bb mechanical interlocking between circuit breaker and disconnector
bb earthing switch operating mechanism CC bb three-phase busbars
bb connection pads for dry-type cables
bb downstream earthing switch 25 kA rms making capacity
Version:
bb LPCT (only with Sepam series 20, 40, 60 and 80)
Optional accessories:
bb cubicle: bb circuit breaker:
vv auxiliary contacts on the disconnector vv motor for operating mechanism
vv protection using Sepam programmable electronic unit vv release units (coil)
vv key-type interlocks vv operation counter on manual
vv three voltage transformers for SM6-24 operating mechanism
vv connection enclosure for cabling from above for
SM6-24
vv 50 W heating element for SM6-24
vv enlarged low-voltage control cabinet for SM6-24
vv 1250 A three-phase upper busbars at Ir 630 A
vv 630 A three-phase upper busbars for severe
operating conditions for SM6-24
vv surge arresters (only for 630 A and SM6-24)
56 AMTED398078EN
Characteristics of Functional units selection
the functional units Protection
Vacuum type circuit breaker
DE53542
DE53543
Electrical characteristics
DE59227
25
20
Ir = 630 - 1250 A
16
7.2 12 17.5 24 kV
Basic equipment:
bb Evolis circuit breaker frontal
bb switch and earthing switch for 400 - 630 A
bb disconnector and earthing switch for 1250 A
bb three-phase busbars
bb circuit breaker operating mechanism P2
bb disconnector and switch operating mechanism CIT
bb voltage presence indicator
bb auxiliary contacts on circuit breaker
bb three CTs bb 3 CR sensors for VIP relay
bb Sepam series 20 programmable electronic unit bb VIP protection relay
bb connection pads for dry-type cables
bb connection pads for dry-type cables bb downstream earthing switch
bb downstream earthing switch 25 kA rms making capacity 25 kA rms making capacity
Optional accessories:
bb cubicle: bb circuit breaker:
vv auxiliary contacts on the disconnector vv motor for operating mechanism
vv three voltage transformers vv release units (coil)
vv key-type interlocks vv operation counter on manual operating mechanism
vv 50 W heating element
vv 1250 A three-phase upper busbars at Ir 630 A
vv 630 A three-phase upper busbars for severe operating conditions
vv enlarged low-voltage control cabinet
vv 630 A cable connection by the top
(no internal arc withstand if selected)
AMTED398078EN 57
Characteristics of Functional units selection
the functional units Protection
Vacuum type circuit breaker
DMVL-A DMVL-D
Single-isolation disconnectable circuit breaker unit Single-isolation disconnectable circuit breaker unit
Outgoing line on right
DE53535
DE59703
Electrical characteristics
DE59228
DE59717
25 25
20 20
Ir = 630 A
16 Ir = 630 A 16
12.5 12.5
Ur Ur
Basic equipment:
bb Evolis circuit breaker lateral disconnectable
bb disconnector and earthing switch
bb mechanical interlocking between circuit breaker and disconnector
bb three-phase busbars
bb circuit breaker operating mechanism RI
bb disconnector operating mechanism CS
bb voltage presence indicator
bb auxiliary contacts on circuit breaker
bb 3 CTs
bb connection pads for dry-type cables
bb downstream earthing switch 2 kA rms making
capacity
Optional accessories:
bb cubicle: bb circuit breaker:
vv auxiliary contacts on the disconnector vv motor for operating mechanism
vv three voltage transformers vv release units (coil)
vv key-type interlocks vv operation counter on manual operating mechanism
vv 50 W heating element
vv 1250 A three-phase upper busbars at Ir 630 A
vv 630 A three-phase upper busbars for severe operating conditions
vv enlarged low-voltage control cabinet
vv Sepam relay protection
vv surge arresters
58 AMTED398078EN
Characteristics of Functional units selection
the functional units Protection
Contactor (Direct Motor Starter) for SM6-24
CVM CVM
Disconnectable contactor unit Disconnectable contactor unit with fuses
DE53527
DE53528
Electrical characteristics
DE59220
DE59221
25
10 20
Ir = 250 A
8
16
6.3
Ir = 400 A
12.5
Ur Ur
7.2 12 kV 7.2 12 kV
Basic equipment:
bb vacuum contactor
bb disconnector and earthing switch
bb three-phase busbars
bb contactor operating mechanism with magnetic holding or contactor with mechanical latching
bb disconnector operating mechanism CS
bb one to three current transformers
bb auxiliary contacts on contactor
bb connection pads for dry-type cables
bb voltage presence indicator
bb downstream earthing switch 2 kA rms making capacity
bb operation counter on contactor
bb enlarged low-voltage control cabinet
bb mechanical interlocking between contactor and disconnector/earthing switch
bb equipment for three DIN striker fuses
bb mechanical indication system for blown fuses
bb auxiliary contact for blown fuses
Version:
bb LPCT (only with Sepam series 20, 40, 60, 80)
Optional accessories:
bb cubicle:
vv auxiliary contacts on the disconnector
vv protection using Sepam programmable electronic unit
vv one to three voltage transformers
vv key-type interlocks
vv 50 W heating element
vv 1250 A three-phase upper busbars
vv 630 A three-phase upper busbars for severe operating conditions
bb contactor:
vv mechanical interlocking
bb DIN striker fuses
AMTED398078EN 59
Characteristics of Functional units selection
the functional units Metering
CM CM2
Voltage transformers unit for network Voltage transformers unit for network
with earthed neutral system with insulated neutral system
DE53546
DE53547
Electrical characteristics
DE59722
kA Ik/1s
25
20
Ir = 50 A
16
12.5
Ur
7.2 12 17.5 24 36 kV
Basic equipment:
bb disconnector and earthing switch
bb three-phase busbars
bb operating mechanism CS
bb LV circuit isolation switch
bb LV fuses
bb three 6.3 A UTE or DIN type fuses
bb 150 W heating element for SM6-36
bb three-voltage transformers bb two voltage transformers
(phase-to-earth) (phase-to-phase)
Optional accessories:
bb auxiliary contacts
bb mechanical signalling for blown fuses
bb auxiliary contact for blown fuses for SM6-24
bb 1250 A three-phase upper busbars
bb 630 A cable connection by the top (no internal arc withstand if selected)
bb 50 W heating element for SM6-24
bb 630 A three-phase upper busbars for severe operating conditions for SM6-24
bb enlarged low-voltage control cabinet for SM6-24
60 AMTED398078EN
Characteristics of Functional units selection
the functional units Metering
DE53550
DE53551
Electrical characteristics
DE59709
kA Ik/1s
Ir =
25
1250 A
20
Ir = 630 - 1250 A
16
7.2 12 17.5 24 36 kV
Basic equipment:
bb one to three CTs for SM6-24
bb three CTs for SM6-36
bb connection bars
bb three-phase busbars
bb 150 W heating element for SM6-36
Optional accessories:
bb 1250 A three-phase upper busbars at Ir 630 A for SM6-24
bb enlarged low-voltage control cabinet for SM6-24
bb three voltage transformers (phase-to-earth) or two voltage transformers (phase-to-phase) for SM6-24
bb 50 W heating element for SM6-24
bb 630 A cable connection by the top for SM6-36 (no internal arc withstand if selected)
AMTED398078EN 61
Characteristics of Functional units selection
the functional units Other functions
DE53552
DE53552
DE58361
Electrical characteristics
DE59709
DE59212
DE59709_2
DE59214
kA Ik/1s kA Ik/1s kA Ik/1s kA Ik/1s
Ir =
25 25 25 25
1250 A
20 20 20 20
Ir = 630 - 1250 A Ir = 630 A Ir = 630 A
Ir =
16 16 16 16
630 A
12.5 Ir = 400 - 630 - 1250 A 12.5 Ir = 400 - 630 A 12.5 12.5 Ir = 400 - 630 A
Ur Ur Ur Ur
Basic equipment:
bb connection bars bb metallic envelop bb metallic bb metallic envelop
bb three-phase busbars for outgoing lines bb three-phase busbars envelop
right or left bb three-phase
bb 150 W heating element for SM6-36 busbars
Optional accessories:
bb 1250 A three-phase upper busbars at Ir bb LV-continuity
630 A
bb enlarged low-voltage control cabinet
for SM6-24
bb 630 A cable connection by the top for
SM6-36 (no internal arc withstand if
selected)
62 AMTED398078EN
Characteristics of Functional units selection
the functional units Other functions
GAM2 GAM
Incoming-cable-connection unit Incoming-cable-connection unit
DE53554
DE53555
Electrical characteristics
DE59719
DE59709
kA Ik/1s kA Ik/1s
Ir = Ir =
25 25
1250 A 1250 A
20 Ir = 630 A 20
Ir = Ir = 630 - 1250 A
630 -
16 1250 A 16
Basic equipment:
bb three-phase busbars
bb voltage presence indicator
bb connection pads for dry-type cables
bb connection bars
bb 150 W heating element for SM6-36
bb downstream earthing switch 25 kA rms making capacity
bb operating mechanism CC for SM6-24
bb operating mechanism CS for SM6-36
Optional accessories:
bb fault indicator
bb digital ammeter
bb 1250 A three-phase upper busbars at Ir 630 A
bb enlarged low-voltage control cabinet for SM6-24
bb 630 A cable connection by the top (no internal arc withstand if selected)
bb 50 W heating element for SM6-24
bb surge arresters for SM6-36 bb auxiliary contacts
bb key-type interlocks
bb surge arresters for SM6-24
AMTED398078EN 63
Characteristics of Functional units selection
the functional units Other functions
SM TM EMB
Disconnector unit MV/LV transformer unit Busbars earthing switch
for auxiliaries cabinet
DE59704
DE53557
DE53558_N
Electrical characteristics
DE59709
DE59722
DE59212
kA Ik/1s kA Ik/1s kA Ik/1s
Ir =
25 25 25
1250 A
20 20 20
Ir = 630 - 1250 A Ir = 630 A
Ir = 50 A
16 16 16
Basic equipment:
bb disconnector and earthing switch bb earthing switch
bb three-phase busbars bb connection bars three phase
bb operating mechanism CS bb operating mechanism CIT
bb 150 W heating element for SM6-36 bb installation on 630 A IM 375 mm or
DM1-A units (not available for internal
bb connection pads for dry-type cables bb two 6.3 A fuses, UTE (for SM6-24) arc IEC 62271-200)
bb voltage presence indicator or DIN type bb require a key-type interlocks
bb LV circuit isolating switch adapted to the switchboard network
bb one voltage transformer (phase-to-phase)
Optional accessories:
bb auxiliary contacts bb auxiliary contacts
bb key-type interlocks
bb 1250 A three-phase upper busbars at Ir 630 A
bb 630 A cable connection by the top (no internal arc withstand if selected)
bb enlarged low-voltage control cabinet for SM6-24
bb 50 W heating element for SM6-24
bb 630 A three-phase upper busbars for severe operating conditions for SM6-24
bb digital ammeter for SM6-24 bb mechanical signalling for blown fuses
bb surge arrester for SM6-36 bb auxiliary contact for blown fuses for
SM6-24
64 AMTED398078EN
Characteristics of Operating mechanisms
the functional units
The control devices required for the unit Units Type of operating mechanism
operating mechanisms are centralised Switch/disconnector / Circuit breaker
downstream earthing
on the front panel. The different types switch
of operating mechanism are presented CIT CI1 CI2 CS CC RI P2
in the table opposite. IM, IMB b v v
Operating speeds do not depend IMC b v v
on the operator, except for the CS. PM b v v (1)
QM b v
QMC, QMB b v
CM, CM2, CVM b
DM1-A, DM1-D, DM1-S, DM1-Z, DM2, b b
DMVL-A, DMVL-D
DM1-A (2), DM1-W b b b
DMV-A, DMV-D, DMV-S b b
NSM-cables, NSM-busbars b
GAM 24 kV b
SM, TM, GAM 36 kV b
EMB b
b Provided as standard
v Other possibility
(1) Only SM6-36
(2) 1250 A version
bb Switch function
Independent-operation opening or closing by lever or motor.
bb Earthing-switch function
Independent-operation opening or closing by lever.
Operating energy is provided by a compressed spring which, when released,
causes the contacts to open or close.
bb Auxiliary contacts
vv switch (2 O + 2 C) *,
vv switch (2 O + 3 C) and earthing switch (1 O + 1 C),
vv switch (1 C) and earthing switch (1 O + 1 C) if motor option.
bb Mechanical indications
Fuses blown in unit PM.
bb Motor option
AMTED398078EN 65
Characteristics of Operating mechanisms
the functional units
bb Switch function
vv independent-operation closing by lever or motor.
Operating energy is provided by a compressed spring which, when released, causes
the contacts to open or close.
vv independent-operation opening by push-button (O) or trip units.
bb Earthing-switch function
Independent-operation closing and opening by lever.
Operating energy is provided by a compressed spring which, when released,
causes the contacts to open or close.
bb Auxiliary contacts
vv switch (2 O + 2 C) *,
vv switch (2 O + 3 C) and earthing switch (1 O + 1 C),
vv switch (1 C) and earthing switch (1 O + 1 C) if motor option,
vv fuses blown (1 C).
bb Mechanical indications
Fuses blown in units QM.
bb Opening releases
vv shunt trip,
vv undervoltage for unit QM.
bb Motor option
66 AMTED398078EN
Characteristics of Operating mechanisms
the functional units
AMTED398078EN 67
Characteristics of Auxiliaries
the functional units
Un DC AC (50 Hz)*
Power supply (V) 24 48 110 125 220 120 230
Motor option
(W) 200
(VA) 200
Operating time for CIT 1 to 2 (s) 1 to 2 (s)
Charging time for CI1, CI2 4 to 7 (s) 4 to 7 (s)
Opening releases
Shunt trip (W) 200 250 300 300 300
(VA) 400 750
Response time (ms) 35 35
Undervoltage
Pick-up (W) 160
(VA) 280 550
Hold (W) 4
(VA) 50 40
Response time (ms) 45 45
Closing release
Shunt trip (W) 200 250 300 300 300
(VA) 400 750
Response time (ms) 55 55
* Please consult us for other frequencies.
Un DC AC (50 Hz)*
Power supply (V) 24 48 110 125 220 120 230
Motor option
(W) 300
(VA) 380
Charging time (s) 15 15
Opening releases
Mitop (low energy) (W) 3
Response time (ms) 30 30
Shunt trip (W) 85
(VA) 180
Response time (ms) 45 45
Undervoltage
Pick-up (W) 160
(VA) 280 550
Hold (W) 10
(VA) 50 40
Response time (ms) 55 55
Closing release
Shunt trip (W) 85
(VA) 180
Response time (ms) 65 65
* Please consult us for other frequencies.
68 AMTED398078EN
Characteristics of Auxiliaries
the functional units
17.5 kV frontal
Charging motor and associated mechanism (P2)
Power supply (Vac 50/60 Hz) 48/60 100/130 200/240
(Vdc) 24/30 48/60 100/125 200/250
Threshold 0.85 to 1.1 Ur
Consumption (VA or W) 180
Motor overcurrent 2 to 3 Ir during 0.1 s
Charging time 6 s max.
Switching rate 3 cycles per minute max.
CH contact 10 A 240 V
Opening release (MITOP low energy)
Power supply Direct current
Threshold 0.6 A < I < 3 A
Response time 50 ms (protection relay setting)
to the circuit breaker at Ur
Opening release (MX)
Power supply (Vac 50/60 Hz) 24 48 100/130 200/250
(Vdc) 24/30 48/60 100/130 200/250
Threshold 0.7 to 1.1 Ur
Consumption (VA or W) Pick-up: 200 (during 200 ms)
Hold: 4.5
Response time 50 ms ± 10
to the circuit breaker at Ur
Closing release (XF)
Power supply (Vac 50/60 Hz) 24 48 100/130 200/250
(Vdc) 24/30 48/60 100/130 200/250
Threshold 0.85 to 1.1 Ur
Consumption (VA or W) Pick-up: 200 (during 200 ms)
Hold: 4.5
The auxiliary contacts are of the changeover type with a common point.
The following are available:
bb 3 NO + 3 NC for the electrically held version (optional 3 NO & 3 NC additional
auxiliary contacts),
bb 5 NO + 6 NC for the mechanically latched version as standard.
Characteristics
Operating voltage Minimum 48 V
Maximum 480 V
Rated current 10 A
Breaking capacity Vdc 60 W (L/R 150 ms)
Vac 700 VA (power factor 0.35)
AMTED398078EN 69
Characteristics of Current transformers
the functional units
for SM6-24
Transformer ARJP1/N2F
bb characteristics according to IEC standard 61869-2
bb single primary winding
ARJP1
Transformer ARJP1/N2F
bb characteristics according to IEC standard 61869-2
bb single primary winding
bb double secondary winding for measurement and protection.
Short-time withstand current Ith (kA)
ARJP1
Transformer ARM3/N2F
bb characteristics according to IEC standard 61869-2
bb double primary winding
bb single secondary winding for measurement and protection.
Short-time withstand current Ith (kA)
I1n (A) 10/20 20/40 50/100 100/200 200/400 300/600
Ith (kA) 5 12.5 12.5/21* 12.5/25* 12.5/25* 25
ARM3
t (s) 1 0.8 1
Measurement and 5 A 7.5 VA - class 0.5
protection 1A 1 VA - 10P30
5A 5 VA - 5P10 5 VA - 5P15
* For 5 A protection
Transformer ARM4
bb characteristics according to IEC standard 61869-2
bb single or double primary winding
bb up to 3 secondary windings (for measure and/or for protection)
bb rated highest voltage 7,2 - 12 - 17,5 - 24kV
bb rated primary current up to 630A (for SM6 cubicles)
bb secondary currents 5A or 1A
bb version with one secondary winding: ARM4/N1F
bb version with two secondary windings: ARM4/N2F
bb version with three secondary windings: ARM4/N3F
(*) Consult us for further characteristics please consult us.
70 AMTED398078EN
Characteristics of Current transformers
the functional units
Characteristics of for SM6-24
the functional units
Transformer ARJP2/N2F
ARJP2
Transformer ARJP3/N2F
bb characteristics according to IEC standard 61869-2
bb single primary winding
bb double secondary winding for measurement and protection.
Short-time withstand current Ith (kA)
I1n (A) 1000 1250
Ith (kA) 25
t (s) 1
Measurement 1A 30 VA - class 0.5
and protection 1A 10 VA - 5P20
Measurement 5A 30 VA - class 0.5
and protection 5A 10 VA - 5P20
PE55661
AMTED398078EN 71
Characteristics of Current transformers
the functional units
for SM6-36
72 AMTED398078EN
Characteristics of Voltage transformers
the functional units
for SM6-24
AMTED398078EN 73
Characteristics of Voltage transformers
the functional units
for SM6-24
Surge arresters
DE58408
74 AMTED398078EN
Characteristics of Voltage transformers
the functional units
for SM6-36
For units TM
Transformer VRC3/S1 (phase-to-phase)
bb single primary winding
bb single secondary
bb characteristics according to IEC standard 61869-3
Rated voltage (kV) 36
Primary voltage (kV) 30
Secondary voltage (V) 220
Thermal power (VA) 1000
DE58408
Surge arresters
For units IM, DM1-A, SM, GAM2
In (A) 630
Un (kV) 36
AMTED398078EN 75
Characteristics of Motors protection units
the functional units
The current rating of fuses installed in units Selection of fuses for CVM units
depends on:
bb motor current rating In
bb starting current Id Service Starting Rated operational Starting time (s)
voltage (kV) current (A) current 5 10 30
bb frequency of starts. (continous duty)
The fuses rating is calculated such that a current equal (A) Number of starts per hour
to twice the starting current does not blow the fuse Id = 6 x Ie Ie 3 6 3 6 3 6
within period equal to the starting time.
3.3 1100 183 250 250 250
The adjacent table indicated the ratings which should
942 157 250 250 250 250 250 250
be used, based on the following assumptions:
bb direct on-line startup 785 131 200 200 200 200 200 250
bb Id/In y 6 6.6 628 105 160 160 160 200 200 200
bb pf = 0.8 (P y 500 kW) or 0.9 (P > 500 kW) 565 94 160 160 160 160 160 160
bb η = 0.9 (P y 500 kW) or 0.94 (P > 500 kW). 502 84 125 160 160 160 160 160
The indicated values are for Fusarc fuses 439 73 125 125 125 160 160 160
(to DIN standard 43-625). 377 63 100 125 100 125 125 160
314 52 100 100 100 100 100 125
Example:
251 42 100 100 100 100 100 100
Consider a 950 kW motor at 5 kV.
P 188 31 80 100 100 100 100 100
In = = 130 A 126 21 50 50 63 80 80 80
pf
Id = 6 x In = 780 A
Fuse selection method:
Then select the next higher value, i.e. 790 A.
bb if Id ≥ 6 x Ie, use Id to select the fuses
For six 5-second starts per hour, select fuses
bb if Id < 6 x Ie, use Ie to select the fuses.
rated 200 A.
Note:
Note: the same motor could not be protected for 12 starts Fuses are 292 mm long (Fusarc fuses).
per hour since the maximum service voltage for the required Fuses are only for short circuit protection.
250 A rated fuses is 3.3 kV. For 250 A fuses, it is necessary to delay the opening of the contactor.
76 AMTED398078EN
Characteristics of Protection of transformers
the functional units
Fuse ratings for SM6 protection units such as PM, QM, QMB and QMC depend,
PE57161
30 10 10 16 20 25 31.5 31.5 50 50 63 63 36
31.5 10 10 16 20 25 25 31.5 50 50 63 63
33 6.3 10 16 20 25 25 31.5 40 50 50 63
34.5 6.3 10 16 20 25 25 31.5 40 50 50 63
Fusarc CF oil immersed type transformers (2)
30 10 10 16 20 25 31.5 31.5 40 40 50 63 36
31.5 10 10 16 20 25 31.5 31.5 40 40 50 63
33 10 10 16 20 25 25 31.5 31.5 40 40 50
34.5 10 10 16 20 25 25 31.5 31.5 40 40 50
(1) SIBA fuses
(2) This selection table has been prepared according to the technical characteristics of France Transfo.
The characteristics of transformers and fuses may change according to manufactures and standards.
AMTED398078EN 77
Characteristics of Protection of transformers
the functional units
Fuses dimensions
Solefuse (UTE standards)
DE53563
ø 55 ø6 Ur Ir L Ø Weight
(kV) (A) (mm) (mm) (kg)
7.2 6.3 to 125 450 55 2
12 100 450 55 2
17.5 80 450 55 2
450 23 24 6.3 to 63 450 55 2
35 35
Fusarc CF (DIN standards)
DE57467
ø 45 Ø ø6 Ur Ir L Ø Weight
(kV) (A) (mm) (mm) (kg)
7.2 125 292 86 3.3
12 6.3 292 50.5 1.2
10 292 50.5 1.2
16 292 50.5 1.2
L 23 20 292 50.5 1.2
33 33 25 292 57 1.5
31.5 292 57 1.5
40 292 57 1.5
50 292 78.5 2.8
63 292 78.5 2.8
80 292 78.5 2.8
100 292 78.5 2.8
24 6.3 442 50.5 1.6
10 442 50.5 1.6
16 442 50.5 1.6
20 442 50.5 1.6
25 442 57 2.2
31.5 442 57 2.2
40 442 57 2.2
50 442 78.5 4.1
63 442 78.5 4.1
80 442 86 5.3
36 10 537 50.5 1.8
16 537 50.5 1.8
25 537 57 2.6
31.5 537 78.5 4.7
40 537 78.5 4.7
50 537 86 6.4
63 537 86 6.4
SIBA
DE57467
ø 45 Ø ø6 Ur Ir L Ø Weight
(kV) (A) (mm) (mm) (kg)
7.2 160 292 85 3.8
200 292 85 5.4
12 125 292 67 2
160 292 85 3.8
L 23 200 292 85 3.8
33 33 17.5 125 442 85 5.4
24 100 442 85 5.4
125 442 85 5.4
78 AMTED398078EN
Characteristics of Interlocks
the functional units
O
Outgoing units
Aim:
O bb to prevent the closing of the earthing switch on a transformer protection unit
unless the LV circuit breaker is locked in “open” or “disconnected” position.
C1 type bb to prevent the access to the transformer if the earthing switch for transformer
DE53566
C4 type bb to prevent the closing of the earthing switch on a transformer protection unit
DE53567
AMTED398078EN 79
Characteristics of Interlocks
the functional units
O
Aim:
bb to prevent the closing of the earthing switch of a load-side cubicle
unless the line-side switch is locked “open”.
O
O O
A5 type bb to prevent the closing of the earthing switch of the casing unit unless
DE53570
O the downstream and the upstream switches are locked in the “open” position.
S
O
S
80 AMTED398078EN
Characteristics of Interlocks
the functional units
P1 type bb to prevent the closing of an earthing switch if the switch of the other unit
DE53572
X O
P2 type bb to prevent on-load operation of the disconnector unless the switch is locked “open”
DE53573
X O O bb to prevent the closing of the earthing switches unless the disconnector and
the switch are locked “open”.
P3 type bb to prevent on-load operation of the disconnector unless the switch is locked “open”
DE53574
AX O bb to prevent the closing of the earthing switches with the unit energised, unless
the disconnector and the switch are locked “open”
bb to allow off-load operation of the switch.
O X
P5 type bb to prevent the closing of the earthing switch of the incoming unit unless
DE53575
O O
Prevents
bb on-load switching of the disconnectors.
O
Allows
bb off-load operation of the circuit breaker with the disconnectors open (double isolation).
bb off-load operation of the circuit breaker with the disconnector open (single isolation).
Type 52 Prevents
DE59203
O Allows
bb off-load operation of the contactor with the disconnectors open (double isolation).
bb off-load operation of the contactor with the disconnector open (single isolation).
AMTED398078EN 81
82 AMTED398078EN
Connections Contents
AMTED398078EN 83
Connections Connections with dry-type
cables for SM6-24
Selection table
Note:
b The cable end terminals, covered by a field distributor, can be square,
b PM/QM type cubicle, round end connections Ø 30 mm max.
84 AMTED398078EN
Connections Cable-connection from below
for SM6-24
Cable positions
DE58676
DE58677
DE58678
630 A 1250 A
IM, NSM-cables, NSM-busbars 945
SM 945 945
IMC 400
PM, QM 400
QMC 400
CVM 430
DM1-A 430 320 H
DMVL-A 430
DMV-S 320 H
H
DM1-W 370 320
GAM2 760
GAM 470 620 200 200 200 200 200 200
420 420 420
DMV-A 320 313
DM1-S 543
DE53581
H
H
200 200
420 165 165 275
313
DE58656
H
H H
200 200 X
510,5 420 313
AMTED398078EN 85
Connections Cable-connection from below
for SM6-24
Trenches depth
500 b Through trenches: the trench depth P is given in the following table for usual dry
375 single-core cables type (for tri-core cables consult us).
b With stands: to reduce depth P or avoid trenches, by placing the units on 400 mm
concrete footings.
b With floor void: the trench depth is given in the following table for usual types of
cables.
630 A 1250 A
Cable All cubicles Other cubicles
section expect ... DMVA CVM DM1A, DM1S, DM1W, DMVLA SM, DM1A, DMV-A,
(mm2) GAM DM1-W
12.5 16 12-16 12.5 16 12.5 kA/1s 16 12-16 12-16 kA/1s
kA/1s kA/1s kA/1s kA/1s kA/1s kA/1s kA/1s
Depth P (mm)
S < 120 330 550 550 330 550 330 550 – –
120 < S < 240 330 550 800 – – Opposite to Under the 550 – –
circuit breaker: circuit breaker:
330 450
S > 400 – – – – – – – – 1000 1400
187.5
DE57177
DE57178
DE57179
100 100 100 100
100
445
P P
P P
480
86 AMTED398078EN
Connections Cable-connection from below
for SM6-24
Trench diagrams example for installation
IAC: A-FL classified
Units represented without switchboard side panels
DE57181
100
P
P2 P1
P3
600
25 25
25
IM IM
QMC
IM IM
IM
DM1 DM1
IM
DE57180
DE57182
On each 630 A unit of the range, except those including a low-voltage control cabinet
Height: and EMB compartment, the connection is made with dry-type and single-core cables.
450 mm
Remarks:
bb Not available for internal arc IEC 62271-200.
bb Not available in 1250 A.
AMTED398078EN 87
Connections Cable-connection from below
for SM6-24
Trench diagrams and floor void drawings
example
Installation with floor void
DE57188
for 16 kA 1 s downwards exhaust
5
minimu50
m 70
50
50
70
740
110 min
.
90 min
930 .
120
DE57196
bb Position of fixing holes b depends on the width of the unit:
Cubicle width (mm) b (mm)
125 95
375 345
500 470
625 595
750 720
21
minimu50
m
4 x M8
3
minimu30
m b
100
50
740
600
88 AMTED398078EN
Connections Connections with dry-type
cables for SM6-36
Selection table
Single-core cables Units 630 A The ageing resistance of the equipment in an MV/LV substation
Cable- Bending IM, IMC, QM, CM, CM2, depends on three key factors:
section radius PM, DM1-A, GAM, GAM2, b the need to make connections correctly
(mm2) (mm) SM, TM New cold fitted connection technologies offer ease of installation that favours
Depth P (mm) resistance over time. Their design enables operation in polluted environments
P1 P2 under severe conditions.
1 x 35 525 350 550 b the impact of the relative humidity factor
1 x 50 555 380 580 The inclusion of a heating element is essential in climates with high humidity levels
1 x 70 585 410 610 and with high temperature differentials.
1 x 95 600 425 625 b ventilation control
1 x 120 630 455 655 The dimension of the grills must be appropriate for the power dissipated
1 x 150 645 470 670 in the substation. They must only traverse the transformer area.
1 x 185 675 500 700
Network cables are connected:
1 x 240 705 530 730
bb on the switch terminals
Note: the unit and the cables requiring the greatest depth bb on the lower fuse holders
must be taken into account when determining the depth P bb on the circuit breaker’s connectors.
for single-trench installations. In double-trench installations
must be taken into account to each type of unit and cable
The bimetallic cable end terminals are:
orientations. bb round connection and shank for cables y 240 mm2.
Crimping of cable lugs to cables must be carried out by stamping.
The end connectors are of cold fitted type
Schneider Electric’s experience has led it to favour this technology wherever
possible for better resistance over time.
The maximum admissible copper(*) cable cross section:
bb 2 x (1 x 240 mm2 per phase) for 1250 A incomer and feeder cubicles
bb 240 mm2 for 630 A incomer and feeder cubicles
bb 95 mm2 for transformer protection cubicles with fuses.
Access to the compartment is interlocked with the closing of the earthing disconnector.
The reduced cubicle depth makes it easier to connect all phases.
A 12 mm Ø pin integrated with the field distributor enables the cable end terminal
to be positioned and attached with one hand. Use a torque wrench set to 50 mN.
(*) Consult us for alu cable cross sections
Trench diagrams
Cable entry or exit through Rear entry or exit with conduits Front entry or exit with conduits
right or left side
DE59723
DE59724
DE59725
P2 Ø 200 P1 P2 P2 Ø 200
QM QM QM 100
100 100 100
100 100
IM Ø 200 IM IM
IM Ø 200 IM IM Ø 200
AMTED398078EN 89
Connections Cable-connection from below
for SM6-36
Cable positions
Side view
IM, SM units QM, PM units DM1-A units GAM2 unit
DE59727
DE57183
DE57184
DE59730
1210
540 632
456
400
Front view
IM, SM QMC GAM GAM2 QM, PM DM1-A
DE57185
1200
90 AMTED398078EN
Installation Contents
AMTED398078EN 91
Installation Dimensions and weights
for SM6-24
D
Dimensions and weights
DE57186
(1) Add to height 450 mm for low-voltage enclosures for control/monitoring and protection functions.
To ensure uniform presentation, all units (except GIM and GEM) may be equipped with
low-voltage enclosures.
(2) Depending on the busbar configuration in the VM6 unit, two types of extension units may be
used:
b to extend a VM6 DM12 or DM23 unit, use an extension unit with a depth of 1060 mm
b for all other VM6 units, a depth of 930 mm is required.
(3) For the 1250 A unit.
92 AMTED398078EN
Installation Units dimensions for SM6-24
IM, IMB, PM, QM, QMB, SM, IMC, QMC, CM, CM2 NSM-cables, NSM-busbars, CVM GBM, GAM2
DE58661
DE58662
DE58663
450 450
DE58665
DE58666
1600 1600 1600
DE58668
450 503
1600 1600
AMTED398078EN 93
Installation Units dimensions for SM6-24
DMVL-A, DMVL-D, DM1-A, DM1-D, DM1-W, DM1-Z, DM1-A 630 A with EMB option DM1-A, DM1-W 1250 A
DM1-S, DM2 630 A
DE58669
DE58670
DE58671
450 503 450
200 200
330
90 840 100 90 840 100
832 200
90 840 100
100
150 85 445
85
90 100 74
840
90 840 100
DMV-D DMV-S
DE58674
DE58675
1680 1600
100
90
150
85 85
94 AMTED398078EN
Installation Civil engineering
for SM6-24
Ground preparation
To obtain the internal arc performance, ground implementation must comply with
the following requirements:
bb Straightness: 2 mm / 3 m (Rep.1)
bb Flatness: 3 mm maximum (Rep.2)
All the elements allowing the evacuation of the gas (duct, casing, etc.) must be able
to bear a load of 250 kg/m2.
DE100520
1
Cubicle
front face
Fixing of units
With each other
The units are simply bolted together to form the MV switchboard (bolts supplied).
Busbar connections are made using a torque wrench set to 28 mN.
On the ground
bb For switchboards comprising up to three units, the four corners of the switchboard
must be secured to the ground with using:
vv M8 bolts (not supplied) screwed into nuts set into the ground using a sealing pistol
vv screw rods grouted into the ground.
bb For switchboards comprising more than three units, each unit may be fixed to
the ground
bb In circuit-breaker or contactor units, fixing devices are installed on the opposite
side of the switchgear.
AMTED398078EN 95
Installation Layout examples for SM6-24
DE58657
10
930
300
25 (minimum)
(minimum)
300
(minimum)
930
300
25 (minimum)
(minimum)
or 50 (evacuation by the top)
Duct
(not supplied)
Coupling flange
(supplied)
96 AMTED398078EN
Installation Dimensions and weights
for SM6-36
Dimensions
IM, SM, IMC, QM, PM, IMB, CM, CM2 units DM1-A, DM1-D, DM2 units
GBM, GAM, GAM2, GBC-A,GBC-B
QMB, QMC units
100 215 215
DE59662
DE59663
DE59664
AMTED398078EN 97
Installation Civil engineering
for SM6-36
Ground preparation
Units may be installed on ordinary concrete grounds, with or without trenches
depending on the type and cross-section of cables.
Required civil works are identical for all units.
A Fixing of units
150
B 50 With each other
The units are simply bolted together to form the MV switchboard (bolts supplied).
DE5961
98 AMTED398078EN
Installation Layout examples for SM6-36
DE59666
100
100
2550 (1) min.
(2)
2650 min.
5200 min.
1770 min.
100
100 100
Top view
DE59667
3430 min.
100
AMTED398078EN 99
100 AMTED398078EN
Appendices Contents
Order form
Appendices
Trip curves for VIP 300 LL or LH relays 102
Order form
SM6 - Switching 106
Switching 106
Automatic Transfer System 107
AMTED398078EN 101
Appendices Trip curves for VIP 300 LL
or LH relays
DE53614
t> t>
t >> t >>
With lower definite time threshold With lower inverse definite time threshold
10 10
1 1
0.6
0.4 0.6
0.3 0.4
0.2 0.3
0.1 0.15 0.1 0.2
0.1 0.15
0.07 0.1
0.05 0.07
0.05
I/Is I/Is
0.01 0.01
1 1.2 10 100 1 1.2 10 100
EI curve RI curve
t (s) t (s)
1000 10
DE53616
100
1
10
0.6
0.4
0.3
1 0.2
0.15
0.1
0.1
0.07
0.6 0.05
0.1 0.4
0.3
0.2
0.15
0.1
0.07 I/Is I/Is
0.01 0.05 0.01
1 1.2 10 100 1 10 100
102 AMTED398078EN
Appendices Trip curves for VIP 35 relays
DE53617EN
The trip curve shows the time
before the relay acts, to which
must be added 70 ms to obtain
the breaking time.
10
Type
0.01 I/Is
0 1.2 5 10 15 20 25 30
AMTED398078EN 103
Appendices Fusarc CF fuses
Fuse and limitation curves
4A
6.3 A
10 A
16 A
20 A
25 A
31.5 A
40 A
50 A
63 A
80 A
100 A
125 A
160 A
200 A
250 A
1000
8
DE53618
6
4
100
8
6
4
10
8
6
4
1
8
6
4
0.1
8
6
4
0.01
2 4 6 8 2 4 6 8 2 4 6 8
10 100 1000 10000
Current (A)
1
8 4A
0.1
6 8 2 4 6 8 2 4 6 8 2 4 6 8
0.1 1 10 100
Rms value of the presumed broken current (kA)
104 AMTED398078EN
Appendices Solefuse fuses
Fuse and limitation curves
6.3 A
10 A
16 A
20 A
25 A
31.5 A
43 A
63 A
80 A
100 A
125 A
1000
8
DE53620
6
4
100
8
6
4
10
8
6
4
1
8
6
4
0.1
8
6
4
0.01
2 4 6 8 2 4 6 8 2 4 6 8
10 100 1000 10000
Current (A)
The diagram shows the maximum limited broken current value 100
DE53621
1
8
6
0.1
2 4 6 8 2 4 6 8 2 4 6 8
0.1 1 10 100
Rms value of the presumed broken current (kA)
AMTED398078EN 105
Order form SM6
Switching
Options
Common options
Replacement of CIT by CI1 CI2
Electrical driving motorization 24 Vdc 110 Vdc 120/127 Vac (50 Hz)
and/or coil voltage 32 Vdc 120-125 Vdc 220/230 Vac (50 Hz)
(not applicable on SM cubicle)
48 Vdc 137 Vdc 120/127 Vac (60 Hz)
60 Vdc 220 Vdc 220/230 Vac (60 Hz)
Signalling contact 1 C on SW and 1 O & 1 C on ES (not applicable on SM cubicle)
2 O & 2 C on SW 2 O & 3 C on SW and 1 O & 1 C on ES
Interlocking
Tubular key type Flat key type
SM6-24 options
Remote control signalling
2 lights 2 lights and 2 PB 2 lights and 2 PB + 1 switch
Voltage of the lights (must be the same than electrical driving mechanism)
24 V 48 V 110/125 V 220 V
Roof configuration (A, B or C only one choice possible)
A - Cable connection by the top (cable maxi 240 mm2 with VPIS)
Single core 2 x single core
B - Low voltage control cabinet (h = 450 mm) With unpunched door
C - Wiring duct
Cable connection by the bottom (not applicable on IMB, cable maxi 240 mm2)
Three core Single core 2 x single core
50 W heating element
Surge arresters for IM 500
7.2 kV 10 kV 12 kV 17.5 kV 24 kV
Operation counter
CTs for IMC (quantity) 1 2 3
Busbar field distributors for severe conditions (only for 630 A)
Internal arc version (not possible with “top incomer” option) 16 kA 1 s 20 kA 1 s
Gaz exhaust direction Downwards (only for 16 kA 1s) Upwards
SM6-36 options
Cable connection by the top (single core cable maxi 240 mm2 with VPIS)
Cable connection by the bottom (2 x single core, cable maxi 240 mm2, not applicable on IMC)
Surge arresters (not applicable on IMB, IMC cubicles) 36 kV
106 AMTED398078EN
Order form SM6
Switching
Automatic Transfer System
Options
Common options
Signalling contact 1 C on SW and 1 O & 1C on ES
Operation counter
Interlocking SM6-SM6
Tubular key type Flat key type
SM6-24 options
2 heating elements
Busbar field distributors for severe conditions (only for 630 A)
Internal arc version (not possible with “top incomer” option) 16 kA 1 s 20 kA 1 s
Gaz exhaust direction Downwards (only for 16 kA 1s) Upwards
AMTED398078EN 107
Order form SM6
Protection
Circuit breaker
36 kV For SF1 circuit breaker DM1-A 1000 DM1-D left 1000 DM1-D right 1000
DM2 left 1500 DM2 right 1500
Basic SM6-24
Busbar (Ir u Ir cubicle)
For DM1-A, DM1-S, DM1-W, DMVL-A, DMVL-D ,DM1-D, DM2
400 A 630 A 1250 A
For DM1-A, DM1-D, DM1-W, DM1-Z 1250 A
For DMV-A, DMV-D 630 A 1250 A
For DMV-S 630 A
Protection
For DM1-S, DMV-S VIP35 with CRc VIP300LL with CRa
VIP300LL with CRb
For DM1-S Sepam series 10 with CRa Sepam series 10 with CRb
For DMV-A, DMV-D Sepam series 20/40
Control for DMV-A and DMV-D
Local (shunt trip coil compulsory)
Remote (opening coil and closing coil compulsory)
Local and remote (opening coil and closing compulsory)
Voltage of the auxiliaries 48/60 Vdc 110/125 or 220/250 Vdc
110/130 or 220/240 Vac (50 Hz)
Voltage of signalling 48/60 Vdc 110/125 Vdc 220/250 Vdc
110/130 Vac (50 Hz) 220/240 Vac (50 Hz)
Cable connection by the bottom
For DM1-A, DM1-W, DMVL-A
3 x single core cable maxi 240 mm2 6 x single core cable maxi 240 mm2
Current sensors CT LPCT ring type for DM1-A 630 A
LPCT MV type for DM1-D
Basic SM6-36
Current sensors CT LPCT ring type for DM1-A 630 A
108 AMTED398078EN
Order form SM6
Protection
Circuit breaker
SM6-24 options
Roof configuration (not applicable on DMV-A, DMV-S, DMV-D)
(A, B or C only one choice possible)
A - Cable connection by the top (cable maxi 240 mm2 with VPIS)
Single core 2 x single core
DM2 1 set 2 sets
B - Low voltage control cabinet
DM2 1 cabinet 2 cabinets
C - Wiring duct DM2 1 set 2 sets
Other cubicles 1 set
Surge arrester
50 W heating element
Replacement of 630 A upper busbars 400-630 A by 1250 A
Busbar field distributors for severe conditions (only for 630 A)
Internal arc version (not possible with “top incomer” option) 16 kA 1 s 20 kA 1 s
Gaz exhaust direction Downwards (only for 16 kA 1s) Upwards
SM6-36 options
Cable connection by the top (single core cable maxi 240 mm2 with VPIS)
Cable connection by the bottom (for DM1-A only)
3 x 2 x single core cable maxi 240 mm2
Surge arrester 36 kV
Sepam relay protection See specific order form
AMTED398078EN 109
Order form SM6
Protection
Fuse switch
Electrical driving motorization 24 Vdc 110 Vdc 120/127 Vac (50 Hz)
32 Vdc 120-125 Vdc 220/230 Vac (50 Hz)
48 Vdc 137 Vdc 120/127 Vac (60 Hz)
60 Vdc 220 Vdc 220/230 Vac (60 Hz)
Shunt trip Opening (on CI1) Closing and opening (on CI2)
110 AMTED398078EN
Order form SM6
Protection
Vacuum contactor (Direct Motor Starter)
for SM6-24
Options
MV fuses 25 A 31.5 A 40 A 50 A 63 A
80 A 100 A 125 A 160 A 200 A 250 A
Busbar field distributors for severe conditions (only for 630 A)
Key interlockings for C1 type
Tubular key type Flat key type
Contactor
Vacuum contactor Magnetic hold Mechanical latching
Open release 48 Vdc 125 Vdc 250 Vdc
Closing coil 110 Vac/dc 120 Vac/dc 125 Vac/dc
220 Vac/dc 240 Vac/dc 250 Vac/dc
AMTED398078EN 111
Order form SM6
Metering
Basic SM6-24
VTs for GBC (to see price structure) Phase/phase Phase/earth
CTs for GBC (to see price structure) Quantity 1 2 3
Ratio choice for GBC
Protections 1 secondary 1 high secondary
2 secondaries 1 low secondary
Basic SM6-36
Voltage transformers See specific order form
Options
SM6-24 options
Roof configuration (A, B or C only one choice possible)
A - Cable connection by the top (cable maxi 240 mm2 with VPIS)
Single core 2 x single core
B - Low voltage control cabinet (h = 450 mm) With unpunched door
C - Wiring duct
SM6-36 options
Current transformers and voltage transformers for GBC See specific order form
Cable connection by the top (single core cable maxi 240 mm2 with VPIS)
Replacement of 630 A busbar by 1250 A (for CM, CM2 and TM only)
112 AMTED398078EN
Order form SM6
Other functions
Type of cubicle for SM6-36 GAM 750 GAM2 750 GBM 750
Options
SM6-24 options
Roof configuration (A, B or C only one choice possible)
A - Cable connection by the top (cable maxi 240 mm2 with VPIS)
Single core 2 x single core
B - Low voltage control cabinet (h = 450 mm) With unpunched door
C - Wiring duct
A3 SM6-SM6 P5 SM6-SM6
Localisation of 2nd lock for P5 Cubicle no.
SM6-36 options
Cable connection by the top (single core cable maxi 240 mm2 with VPIS)
Replacement of 630 A busbar by 1250 A (for GAM2 only)
Surge arresters for GAM2
AMTED398078EN 113
Order form SF1
Lateral disconnectable or withdrawable
Only one of the boxes (ticked X or filled by Basic circuit breaker Quantity
the needed value) have to be considered between each
Rated voltage Ur (kV)
horizontal line.
Green box X corresponds to none priced functions. Service voltage (kV)
Frequency 60 Hz 50 Hz
Remote control
Electrical motor M 24…32 Vdc 110…127 Vdc/ac
48…60 Vdc/ac 220…250 Vdc/ac
Shunt closing release YF
24 Vdc 60 Vdc 220 Vdc 220 Vac (50 Hz)
30 Vdc 110 Vdc 48 Vac (50 Hz) 120 Vac (60 Hz)
48 Vdc 125 Vdc 110 Vac (50 Hz) 240 Vac (60 Hz)
114 AMTED398078EN
Order form SFset
Lateral disconnectable
for SM6-24
Only one of the boxes (ticked X or filled by Basic circuit breaker Quantity
the needed value) have to be considered between each
Rated voltage Ur (kV)
horizontal line.
Green box X corresponds to none priced functions. Service voltage (kV)
Frequency 60 Hz 50 Hz
Mechanism position A1 B1
Remote control
Electrical motor M 24…32 Vdc 110…127 Vdc/ac
48…60 Vdc/ac 220…250 Vdc/ac
Shunt closing release YF
24 Vdc 60 Vdc 220 Vdc 220 Vac (50 Hz)
30 Vdc 110 Vdc 48 Vac (50 Hz) 120 Vac (60 Hz)
48 Vdc 125 Vdc 110 Vac (50 Hz) 240 Vac (60 Hz)
AMTED398078EN 115
Order form Evolis
Frontal fixed version
for SM6-24 (up to 17.5 kV)
Only one of the boxes (ticked X or filled by Basic fixed circuit breaker Quantity
the needed value) have to be considered between each
Rated voltage Ur (kV) 12 17.5
horizontal line.
Green box X corresponds to none priced functions. Service voltage (kV)
116 AMTED398078EN
Order form Evolis
Lateral disconnectable version
for SM6-24 (up to 24 kV)
Only one of the boxes (ticked X or filled by Basic circuit breaker Quantity
the needed value) have to be considered between each 24 (kV)
Rated voltage Ur
horizontal line.
Green box X corresponds to none priced functions. Service voltage (kV)
Mechanism position B1
AMTED398078EN 117
Notes
118 AMTED398078EN
ART16044 © Schneider Electric Industries SAS - All rights reserved
AMTED398078EN 12-2013