Professional Documents
Culture Documents
TXV Selection Methodology-DANFOSS
TXV Selection Methodology-DANFOSS
PH Diagram
Figure 1. A conventional
thermostatic expansion valve (TXV
or TEV) is controlled by springs,
bellows, and push rods. (Graphics
courtesy of Sporlan Valve Co.)
© Subros Limited. All rights reserved
Thermal Expansion Valve
universal charge
Maximum operating pressure (MOP) charge.
MOP charge with ballast (standard for Danfoss expansion valves with MOP).
Expansion valves with MOP ballast charges are used mainly in refrigeration
systems with "high dynamic" evaporators, such as in air conditioning systems
and plate heat exchangers with high heat transfer.
Remember: the TXV controls only one thing: the rate of flow of liquid
refrigerant into the evaporator.
The TXV is not designed to control air temperature, head pressure, capacity,
suction pressure, or humidity. Attempts to use the TXV to control any of these
system variables will lead to poor system performance and possible compressor
failure.
This is how the TXV keeps the system in balance and operating properly
Liquid refrigerant enters the TXV under high pressure. As the flow of liquid
refrigerant is reduced, its pressure drops.
The refrigerant leaving the TXV is now a combination of low-pressure liquid and
vapor.
As the flow is restricted, several things happen:
The pressure on the liquid refrigerant drops;
A small amount of the liquid refrigerant is converted to gas, in response to the
drop in pressure;
This "flash gas" represents a high degree of energy transfer, as the sensible heat
of the refrigerant is converted to latent heat;
The low-pressure liquid and vapor combination moves into the evaporator,
where the rest of the liquid refrigerant "boils off" into its gaseous state as it
absorbs heat from its surroundings.
Changes in gas temperature at the evaporator outlet are detected by the sensing
bulb, which then causes the valve pin to move in or out, regulating the flow of
refrigerant through the TXV.
In this way, the valve allows just enough refrigerant into the evaporator, to
maintain the correct level of superheat in the suction line.
© Subros Limited. All rights reserved
Thermal Expansion Valve
Installation Procedures
The expansion valve must be installed in the liquid line, ahead of the evaporator, with bulb
fastened to the suction line as close to the evaporator as possible. If there's external pressure
equalization, the equalizing line must be connected to the suction line immediately after the
bulb. (Figure 1)
The bulb is best mounted on a horizontal suction line tube and in a position corresponding to
between 1 o'clock and 4 o'clock.
The location depends on the outside diameter of the tube. (Figure 2)
© Subros Limited. All rights reserved
Thermal Expansion Valve
Note: The bulb must never be located at the bottom of the suction line due to the
possibility of oil laying in the bottom of the pipe causing false signals.
The bulb must be able to sense the temperature of the superheated suction vapour and must
therefore not be located in a position that will expose it to extraneous heat/cold.
The bulb must not be installed after a heat exchanger. In this position it will give false
signals to the expansion valve (Figure 4). Additionally, the bulb must not be installed close
to components of large mass, as this also will give rise to false signals to the expansion
valve.
As previously mentioned, the bulb must be installed to the horizontal part of the suction line
immediately after the evaporator. It must not be installed to a collection tube or a riser after
an oil pocket. The expansion valve bulb must always be installed ahead of any liquid lock.
© Subros Limited. All rights reserved
Thermal Expansion Valve - Alco
Operating Principles
Alco thermo expansion valves control the superheat of refrigerant vapour at the outlet of the
evaporator.
They act as a throttle device between the high pressure & the low pressure sides of the
system & ensure that the rate of refrigerant flow into the evaporator exactly matches the rate
of evaporation of the liquid refrigerant in the evaporator.
Thus the evaporator is fully utilised & no liquid refrigerant may reach the compressor.
Evaporator pressures are limited to a maximum value to protect the compressor from
overload conditions.
MOP selection should be within the maximum allowed evaporating temperature of the
compressor.
© Subros Limited. All rights reserved
Thermal Expansion Valve
Dimensioning
To correctly size a thermo expansion valve on a system, the following design conditions
must be available.
- Cooling capacity Qo
- Nett pressure differential across the TEV Dp
- Evaporating temperature/pressure
- Lowest possible condensing temperature/pressure
- Liquid temperature
- Refrigerant
- Vertical liquid line lift from the receiver to the TEV (see below)
Selection Example - 1
1. Establish Kt factor.
Referring to the following Correction Tables, a Kt factor is established from
the R407C chart of 0.98 for this example.
2. Establish nett pressure differential.
Determine the pressure differential across the valve using the data previously
shown.
Dp = 15.5 - (4.61 + 0.2 + 0.7 + 2) = 7.99 = ~ 8 bar
The next stage is to select the KDp factor, again from the following Correction
Tables for R407C. For this particular example the factor of 1.18 will need to
be applied.
3. Calculate Qn the nominal valve capacity.
Qn = 18 x 0.98 x 1.18 = 20.82kW
Looking at the TI(E) Series nominal duties, it can be seen that this family is
not large enough. Therefore referring to T Series we can establish that valve
TCLE 550 @ 24kW nominal should be selected.
Optimised % = (20.82/24) x 100 = 86.7% loaded @ design conditions.
Selection Example - 2
To select a valve, the valve nett pressure drop has to be calculated, from this
it’s a simple matter of referring to the valve capacity charts to find the
appropriate valve.
Selection Example - 2
Guidelines
Guidelines
Obviously small single circuit coils will have little pressure drop, followed by venturi
distributors then the pressure drop type (versions fitted with an orifice). This is an
estimation & will vary with each application.
5. When selecting a valve it should be noted that generally the maximum capacity
of the valve is usually 20% above nominal.
Sometimes this may mean sizing the valve marginally above 100% rather than
having a valve in the system operating at a value far below its rated capacity.
Figure 2. A cutaway of an
electronic expansion valve (EEV)
with step motor and drive assembly
© Subros Limited. All rights reserved
Expansion Valve Sizing for Wind tunnel cascade System
Pressure
equalization
(optional)
DpL
pC Evaporating
Estimated pressure pressure
Condensing drop in evaporator
pressure (and distributor)
pE
0.5 bar
14.5 bar Evaporating
pressure
Estimated pressure
Condensing drop in evaporator
pressure (and distributor) 4 bar
R22
R22
Refrigerant R22
Q0,REQ = 5.0 kW
pC = 14.2 bar
pE = 5.8 bar TE = +10 °C pE = 5.8 bar
DpL = 0.4 bar
Dp = ?
© Subros Limited. All rights reserved
A note on subcooling
Q0,REQ
Q0,CONV
Correction factor
© Subros Limited. All rights reserved
Features
• Changeable orifice
– Can change the maximum capacity of the valve
• Internal or external pressure equalization
– If the pressure drop in evaporator is significant or if liquid distributor is
used
• Maximum operating pressure (MOP)
– To protect the compressor by limiting the evaporating pressure
• Change of superheat setting
– To adapt valve to different evaporator types
The AKV's are electrically operated expansion valves designed for refrigeration
plants. They are suitable for HCFC and HFC refrigerants.
The following article was published in ASHRAE Journal, February 2009. ©Copyright 2009
American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for
educational purposes only. This article may not be copied and/or distributed electronically or in
paper form without permission of ASHRAE.