Professional Documents
Culture Documents
Rla - Hotel Project - Roof Health Club Floor - Lux Level Report - 25.01.2024
Rla - Hotel Project - Roof Health Club Floor - Lux Level Report - 25.01.2024
2024
Description
The nominal values shown in the calculation report are the result of
precision calculations, based upon precisely positioned luminaires in
a fixed relationship to each other and to the area under examination.
In practice the values may vary due to tolerances on luminaires,
luminaire position, reflection properties of room walls, ceilings, floor,
furniture texture and finishes, road surface variances, declared
lumen output and intensity of luminaire are nominal values which are
subject to +/- 10% variation as per BIS guidelines. There could be
further tolerance of +/- 7% due to various reasons like tolerance in
Supply voltage (as per BIS norms), ambient temperature, dirt
accumulation in luminaire surfaces. Lighting calculations are usually
done for open area without any obstructions. Any obstructions like
trees, buildings or furniture, racks, general building elements will
impact lighting levels and shadow patterns. Such inputs are generally
not considered during design estimation.
1
RLA_HOTEL PROJECT_ROOF HEALTH CLUB FLOOR _25.01.2024
2
RLA_HOTEL PROJECT_ROOF HEALTH CLUB FLOOR _25.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.12
1.88 W/m²/100 lx
Luminaire list
1 Not yet a LD1082- Shallow Recessed Low Glare Fixed LED – 13.3 W 905 lm 68.0 lm/W
DIALux 700-LW30- Downlight
member WB
3
RLA_HOTEL PROJECT_ROOF HEALTH CLUB FLOOR _25.01.2024
4
RLA_HOTEL PROJECT_ROOF HEALTH CLUB FLOOR _25.01.2024
Working planes
Working plane (01 HANDICAPPED TOILET) 147 lx 17.7 lx 442 lx 0.12 0.040 WP1
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m
5
RLA_HOTEL PROJECT_ROOF HEALTH CLUB FLOOR _25.01.2024
6
RLA_HOTEL PROJECT_ROOF HEALTH CLUB FLOOR _25.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.12
2.08 W/m²/100 lx
Luminaire list
4 Not yet a LD1082- Shallow Recessed Low Glare Fixed LED – 13.3 W 905 lm 68.0 lm/W
DIALux 700-LW30- Downlight
member WB
7
RLA_HOTEL PROJECT_ROOF HEALTH CLUB FLOOR _25.01.2024
8
RLA_HOTEL PROJECT_ROOF HEALTH CLUB FLOOR _25.01.2024
Working planes
Working plane (02 FEMALE TOILET) 158 lx 19.2 lx 324 lx 0.12 0.059 WP2
Perpendicular illuminance (adaptive)
Height: 0.000 m, Wall zone: 0.000 m
9
RLA_HOTEL PROJECT_ROOF HEALTH CLUB FLOOR _25.01.2024
10
RLA_HOTEL PROJECT_ROOF HEALTH CLUB FLOOR _25.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.060
1.21 W/m²/100 lx
Luminaire list
11
RLA_HOTEL PROJECT_ROOF HEALTH CLUB FLOOR _25.01.2024
12
RLA_HOTEL PROJECT_ROOF HEALTH CLUB FLOOR _25.01.2024
Working planes
Working plane (03 CORRIDOR ) 140 lx 8.36 lx 361 lx 0.060 0.023 WP4
Perpendicular illuminance (adaptive)
Height: 0.000 m, Wall zone: 0.000 m
13
RLA_HOTEL PROJECT_ROOF HEALTH CLUB FLOOR _25.01.2024
14
RLA_HOTEL PROJECT_ROOF HEALTH CLUB FLOOR _25.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.45
1.68 W/m²/100 lx
Luminaire list
15
RLA_HOTEL PROJECT_ROOF HEALTH CLUB FLOOR _25.01.2024
16
RLA_HOTEL PROJECT_ROOF HEALTH CLUB FLOOR _25.01.2024
Working planes
Working plane (04 GSM RM) 480 lx 217 lx 677 lx 0.45 0.32 WP3
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m
17
RLA_HOTEL PROJECT_ROOF HEALTH CLUB FLOOR _25.01.2024
18
RLA_HOTEL PROJECT_ROOF HEALTH CLUB FLOOR _25.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.054
1.27 W/m²/100 lx
Luminaire list
19
RLA_HOTEL PROJECT_ROOF HEALTH CLUB FLOOR _25.01.2024
20
RLA_HOTEL PROJECT_ROOF HEALTH CLUB FLOOR _25.01.2024
Working planes
Working plane (05 HOUSE KEEPING) 241 lx 12.9 lx 772 lx 0.054 0.017 WP5
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m
21
RLA_HOTEL PROJECT_ROOF HEALTH CLUB FLOOR _25.01.2024
22
RLA_HOTEL PROJECT_ROOF HEALTH CLUB FLOOR _25.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.30
1.26 W/m²/100 lx
Luminaire list
23
RLA_HOTEL PROJECT_ROOF HEALTH CLUB FLOOR _25.01.2024
24
RLA_HOTEL PROJECT_ROOF HEALTH CLUB FLOOR _25.01.2024
Working planes
Working plane (06 GYM) 555 lx 168 lx 883 lx 0.30 0.19 WP6
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m
25
RLA_HOTEL PROJECT_ROOF HEALTH CLUB FLOOR _25.01.2024
26
RLA_HOTEL PROJECT_ROOF HEALTH CLUB FLOOR _25.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.18
1.41 W/m²/100 lx
Luminaire list
27
RLA_HOTEL PROJECT_ROOF HEALTH CLUB FLOOR _25.01.2024
28
RLA_HOTEL PROJECT_ROOF HEALTH CLUB FLOOR _25.01.2024
Working planes
Working plane (07 PASSGE) 175 lx 32.1 lx 351 lx 0.18 0.091 WP7
Perpendicular illuminance (adaptive)
Height: 0.000 m, Wall zone: 0.000 m
29