Description

The nominal values shown in the calculation report are the result of
precision calculations, based upon precisely positioned luminaires in
a fixed relationship to each other and to the area under examination.
In practice the values may vary due to tolerances on luminaires,
luminaire position, reflection properties of room walls, ceilings, floor,
furniture texture and finishes, road surface variances, declared
lumen output and intensity of luminaire are nominal values which are
subject to +/- 10% variation as per BIS guidelines. There could be
further tolerance of +/- 7% due to various reasons like tolerance in
Supply voltage (as per BIS norms), ambient temperature, dirt
accumulation in luminaire surfaces. Lighting calculations are usually
done for open area without any obstructions. Any obstructions like
trees, buildings or furniture, racks, general building elements will
impact lighting levels and shadow patterns. Such inputs are generally
not considered during design estimation.

1
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 01 IT RM (Light scene 1)


Summary

Ground area 60.00 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

2
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 01 IT RM (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 464 lx

Uo (g1 ) 0.37

Energy estimation(2) Consumption 928 kWh/a

Room Lighting power density 6.25 W/m²

1.35 W/m²/100 lx

(1) Based on a rectangular space of 8.800 m x 7.100 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

15 Regent ZEN22 – 25.0 W 2500 lm 100.0 lm/W

3
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 01 IT RM (Light scene 1)


Calculation objects

4
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 01 IT RM (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (01 IT RM) 464 lx 170 lx 605 lx 0.37 0.28 WP1
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 8.800 m x 7.100 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

5
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 02 PASSGE (Light scene 1)


Summary

Ground area 5.22 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

6
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 02 PASSGE (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 193 lx

Uo (g1 ) 0.72

Energy estimation(2) Consumption 74.3 kWh/a

Room Lighting power density 5.75 W/m²

2.98 W/m²/100 lx

(1) Based on a rectangular space of 1.800 m x 2.900 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

2 Regent Blaire – 15.0 W 1501 lm 100.1 lm/W

7
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 02 PASSGE (Light scene 1)


Calculation objects

8
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 02 PASSGE (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (02 PASSGE) 193 lx 139 lx 237 lx 0.72 0.59 WP2
Perpendicular illuminance (adaptive)
Height: 0.000 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 1.800 m x 2.900 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

9
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 03 PASSAGE (Light scene 1)


Summary

Ground area 10.26 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

10
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 03 PASSAGE (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 176 lx

Uo (g1 ) 0.51

Energy estimation(2) Consumption 111 kWh/a

Room Lighting power density 4.39 W/m²

2.49 W/m²/100 lx

(1) Based on a rectangular space of 1.800 m x 5.700 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

3 Regent Blaire – 15.0 W 1501 lm 100.1 lm/W

11
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 03 PASSAGE (Light scene 1)


Calculation objects

12
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 03 PASSAGE (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (03 PASSAGE) 176 lx 89.3 lx 225 lx 0.51 0.40 WP3
Perpendicular illuminance (adaptive)
Height: 0.000 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 1.800 m x 5.700 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

13
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 04 FEMALE TOILET (Light scene 1)


Summary

Ground area 3.15 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

14
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 04 FEMALE TOILET (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 202 lx

Uo (g1 ) 0.089

Energy estimation(2) Consumption 32.9 kWh/a

Room Lighting power density 4.22 W/m²

2.09 W/m²/100 lx

(1) Based on a rectangular space of 2.250 m x 1.400 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

1 Not yet a LD1082- Shallow Recessed Low Glare Fixed LED – 13.3 W 905 lm 68.0 lm/W
DIALux 700-LW30- Downlight
member WB

15
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 04 FEMALE TOILET (Light scene 1)


Calculation objects

16
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 04 FEMALE TOILET (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (04 FEMALE TOILET) 202 lx 17.9 lx 596 lx 0.089 0.030 WP4
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 2.250 m x 1.400 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

17
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 05 MALE TOILET (Light scene 1)


Summary

Ground area 4.54 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

18
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 05 MALE TOILET (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 158 lx

Uo (g1 ) 0.056

Energy estimation(2) Consumption 32.9 kWh/a

Room Lighting power density 2.93 W/m²

1.85 W/m²/100 lx

(1) Based on a rectangular space of 2.250 m x 2.150 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

1 Not yet a LD1082- Shallow Recessed Low Glare Fixed LED – 13.3 W 905 lm 68.0 lm/W
DIALux 700-LW30- Downlight
member WB

19
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 05 MALE TOILET (Light scene 1)


Calculation objects

20
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 05 MALE TOILET (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (05 MALE TOILET) 158 lx 8.77 lx 586 lx 0.056 0.015 WP5
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 2.250 m x 2.150 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

21
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 06 MALE ABLUTION RM (Light scene 1)


Summary

Ground area 19.07 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

22
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 06 MALE ABLUTION RM (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 214 lx

Uo (g1 ) 0.091

Energy estimation(2) Consumption 198 kWh/a

Room Lighting power density 4.18 W/m²

1.95 W/m²/100 lx

(1) Based on a rectangular space of 5.900 m x 3.450 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

6 Not yet a LD1082- Shallow Recessed Low Glare Fixed LED – 13.3 W 905 lm 68.0 lm/W
DIALux 700-LW30- Downlight
member WB

23
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 06 MALE ABLUTION RM (Light scene 1)


Calculation objects

24
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 06 MALE ABLUTION RM (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (06 MALE ABLUTION RM) 214 lx 19.5 lx 627 lx 0.091 0.031 WP6
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 5.900 m x 3.450 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

25
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 07 MALE PRAYER RM (Light scene 1)


Summary

Ground area 12.59 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

26
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 07 MALE PRAYER RM (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 286 lx

Uo (g1 ) 0.40

Energy estimation(2) Consumption 149 kWh/a

Room Lighting power density 4.76 W/m²

1.66 W/m²/100 lx

(1) Based on a rectangular space of 3.450 m x 3.650 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

4 Regent Blaire – 15.0 W 1501 lm 100.1 lm/W

27
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 07 MALE PRAYER RM (Light scene 1)


Calculation objects

28
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 07 MALE PRAYER RM (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (07 MALE PRAYER RM) 286 lx 114 lx 380 lx 0.40 0.30 WP7
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 3.450 m x 3.650 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

29
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 08 FEMALE PRAYER RM (Light scene 1)


Summary

Ground area 26.75 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

30
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 08 FEMALE PRAYER RM (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 309 lx

Uo (g1 ) 0.12

Energy estimation(2) Consumption 322 kWh/a

Room Lighting power density 4.86 W/m²

1.57 W/m²/100 lx

(1) Based on a rectangular space of 3.400 m x 8.800 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

3 Not yet a LD1082- Shallow Recessed Low Glare Fixed LED – 13.3 W 905 lm 68.0 lm/W
DIALux 700-LW30- Downlight
member WB

6 Regent Blaire – 15.0 W 1501 lm 100.1 lm/W

31
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 08 FEMALE PRAYER RM (Light scene 1)


Calculation objects

32
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 08 FEMALE PRAYER RM (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (08 FEMALE PRAYER RM) 309 lx 36.0 lx 671 lx 0.12 0.054 WP8
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 3.400 m x 8.800 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

33
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 09 FEMALE TOILET (Light scene 1)


Summary

Ground area 14.22 m² Clearance height 2.600 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.600 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

34
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 09 FEMALE TOILET (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 249 lx

Uo (g1 ) 0.14

Energy estimation(2) Consumption 165 kWh/a

Room Lighting power density 4.68 W/m²

1.88 W/m²/100 lx

(1) Based on a rectangular space of 6.775 m x 2.362 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

5 Not yet a LD1082- Shallow Recessed Low Glare Fixed LED – 13.3 W 905 lm 68.0 lm/W
DIALux 700-LW30- Downlight
member WB

35
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 09 FEMALE TOILET (Light scene 1)


Calculation objects

36
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 09 FEMALE TOILET (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (09 FEMALE TOILET) 249 lx 34.7 lx 553 lx 0.14 0.063 WP9
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 6.775 m x 2.362 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

37
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 10 ADA TOILET (Light scene 1)


Summary

Ground area 6.14 m² Clearance height 2.600 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.600 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

38
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 10 ADA TOILET (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 122 lx

Uo (g1 ) 0.088

Energy estimation(2) Consumption 32.9 kWh/a

Room Lighting power density 2.16 W/m²

1.77 W/m²/100 lx

(1) Based on a rectangular space of 2.482 m x 2.475 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

1 Not yet a LD1082- Shallow Recessed Low Glare Fixed LED – 13.3 W 905 lm 68.0 lm/W
DIALux 700-LW30- Downlight
member WB

39
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 10 ADA TOILET (Light scene 1)


Calculation objects

40
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 10 ADA TOILET (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (10 ADA TOILET) 122 lx 10.7 lx 517 lx 0.088 0.021 WP10
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 2.482 m x 2.475 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

41
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 11 MALE TOILET (Light scene 1)


Summary

Ground area 16.08 m² Clearance height 2.600 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.600 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

42
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 11 MALE TOILET (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 262 lx

Uo (g1 ) 0.13

Energy estimation(2) Consumption 198 kWh/a

Room Lighting power density 4.96 W/m²

1.90 W/m²/100 lx

(1) Based on a rectangular space of 3.650 m x 6.750 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

6 Not yet a LD1082- Shallow Recessed Low Glare Fixed LED – 13.3 W 905 lm 68.0 lm/W
DIALux 700-LW30- Downlight
member WB

43
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 11 MALE TOILET (Light scene 1)


Calculation objects

44
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 11 MALE TOILET (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (11 MALE TOILET) 262 lx 33.3 lx 560 lx 0.13 0.059 WP11
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 3.650 m x 6.750 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

45
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 12 LUGGAGE RM (Light scene 1)


Summary

Ground area 20.40 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

46
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 12 LUGGAGE RM (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 384 lx

Uo (g1 ) 0.47

Energy estimation(2) Consumption 297 kWh/a

Room Lighting power density 5.88 W/m²

1.53 W/m²/100 lx

(1) Based on a rectangular space of 6.800 m x 3.000 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

8 Regent Blaire – 15.0 W 1501 lm 100.1 lm/W

47
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 12 LUGGAGE RM (Light scene 1)


Calculation objects

48
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 12 LUGGAGE RM (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (12 LUGGAGE RM) 384 lx 182 lx 501 lx 0.47 0.36 WP12
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 6.800 m x 3.000 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

49
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 13 SERVICE LIFT RM (Light scene 1)


Summary

Ground area 36.50 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

50
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 13 SERVICE LIFT RM (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 248 lx

Uo (g1 ) 0.35

Energy estimation(2) Consumption 446 kWh/a

Room Lighting power density 4.93 W/m²

1.99 W/m²/100 lx

(1) Based on a rectangular space of 4.700 m x 14.800 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

12 Regent Blaire – 15.0 W 1501 lm 100.1 lm/W

51
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 13 SERVICE LIFT RM (Light scene 1)


Calculation objects

52
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 13 SERVICE LIFT RM (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (13 SERVICE LIFT RM) 248 lx 87.6 lx 371 lx 0.35 0.24 WP13
Perpendicular illuminance (adaptive)
Height: 0.000 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 4.700 m x 14.800 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

53
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 14 TEL. RM (Light scene 1)


Summary

Ground area 5.04 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

54
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 14 TEL. RM (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 361 lx

Uo (g1 ) 0.51

Glare valuation(1) RUG, max 24

Energy estimation(2) Consumption 99.0 kWh/a

Room Lighting power density 7.94 W/m²

2.20 W/m²/100 lx

(1) Based on a rectangular space of 1.600 m x 3.150 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

1 Regent Stark 24 40.0 W 4800 lm 120.0 lm/W

55
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 14 TEL. RM (Light scene 1)


Calculation objects

56
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 14 TEL. RM (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (14 TEL. RM) 361 lx 183 lx 518 lx 0.51 0.35 WP14
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 1.600 m x 3.150 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

57
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 15 SERVICE KIT CHEN (Light scene 1)


Summary

Ground area 18.36 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

58
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 15 SERVICE KIT CHEN (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 533 lx

Uo (g1 ) 0.51

Glare valuation(1) RUG, max 17

Energy estimation(2) Consumption 371 kWh/a

Room Lighting power density 8.17 W/m²

1.53 W/m²/100 lx

(1) Based on a rectangular space of 3.600 m x 5.100 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

6 Regent LED 0799 Kosher Eco 16 25.0 W 2500 lm 100.0 lm/W

59
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 15 SERVICE KIT CHEN (Light scene 1)


Calculation objects

60
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 15 SERVICE KIT CHEN (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (15 SERVICE KIT CHEN) 533 lx 272 lx 640 lx 0.51 0.43 WP15
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 3.600 m x 5.100 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

61
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 16 AIR LOCK (Light scene 1)


Summary

Ground area 14.52 m² Clearance height 4.100 m

Reflection factors Ceiling: 70.0 %, Mounting height 4.100 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

62
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 16 AIR LOCK (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 298 lx

Uo (g1 ) 0.29

Glare valuation(1) RUG, max 13

Energy estimation(2) Consumption 149 kWh/a

Room Lighting power density 4.13 W/m²

1.39 W/m²/100 lx

(1) Based on a rectangular space of 4.400 m x 3.300 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

6 Regent 2005.7524 NOVO 13 10.0 W 1005 lm 100.5 lm/W

63
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 16 AIR LOCK (Light scene 1)


Calculation objects

64
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 16 AIR LOCK (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (16 AIR LOCK) 298 lx 87.4 lx 452 lx 0.29 0.19 WP16
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 4.400 m x 3.300 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

65
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 17 HOTEL MANAGER (Light scene 1)


Summary

Ground area 15.27 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

66
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 17 HOTEL MANAGER (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 395 lx

Uo (g1 ) 0.62

Energy estimation(2) Consumption 248 kWh/a

Room Lighting power density 6.55 W/m²

1.66 W/m²/100 lx

(1) Based on a rectangular space of 4.300 m x 3.550 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

4 Regent ZEN22 – 25.0 W 2500 lm 100.0 lm/W

67
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 17 HOTEL MANAGER (Light scene 1)


Calculation objects

68
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 17 HOTEL MANAGER (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (17 HOTEL MANAGER) 395 lx 246 lx 491 lx 0.62 0.50 WP17
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 4.300 m x 3.550 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

69
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 18 ADMIN OFFICE (Light scene 1)


Summary

Ground area 69.00 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

70
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 18 ADMIN OFFICE (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 440 lx

Uo (g1 ) 0.33

Energy estimation(2) Consumption 990 kWh/a

Room Lighting power density 5.80 W/m²

1.32 W/m²/100 lx

(1) Based on a rectangular space of 9.000 m x 9.500 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

16 Regent ZEN22 – 25.0 W 2500 lm 100.0 lm/W

71
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 18 ADMIN OFFICE (Light scene 1)


Calculation objects

72
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 18 ADMIN OFFICE (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (18 ADMIN OFFICE) 440 lx 144 lx 587 lx 0.33 0.25 WP18
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 9.000 m x 9.500 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

73
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 19 DINING AREA (Light scene 1)


Summary

Ground area 298.64 m² Clearance height 3.800 m – 4.100 m

Reflection factors Ceiling: 56.6 %, Mounting height 3.500 m – 4.100 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

74
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 19 DINING AREA (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 298 lx

Uo (g1 ) 0.072

Glare valuation(1) RUG, max 14

Energy estimation(2) Consumption 3148 kWh/a

Room Lighting power density 4.26 W/m²

1.43 W/m²/100 lx

(1) Based on a rectangular space of 21.501 m x 18.700 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

84 Modular 11463032 Minude 45 adjustable jack 1x LED 2700K lens -1 8.5 W 565 lm 66.5 lm/W
Lighting medium GE black struc
Instruments

39 Regent 2005.7524 NOVO 14 10.0 W 1005 lm 100.5 lm/W

6 Regent TEA TEA 12 28.0 W 3069 lm 109.6 lm/W

75
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 19 DINING AREA (Light scene 1)


Calculation objects

76
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 19 DINING AREA (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (19 DINING AREA) 298 lx 21.6 lx 1667 lx 0.072 0.013 WP19
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 21.501 m x 18.700 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

77
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 20 LIVING AREA (Light scene 1)


Summary

Ground area 33.75 m² Clearance height 3.800 m

Reflection factors Ceiling: 53.3 %, Mounting height 3.500 m – 3.800 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

78
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 20 LIVING AREA (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 174 lx

Uo (g1 ) 0.23

Glare valuation(1) RUG, max 13

Energy estimation(2) Consumption 248 kWh/a

Room Lighting power density 2.96 W/m²

1.70 W/m²/100 lx

(1) Based on a rectangular space of 4.570 m x 7.400 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

1 Not yet a L07633.06 WILLY 60 LED 11 40.0 W 3587 lm 89.7 lm/W


DIALux 0.0402
member

6 Regent 2005.7524 NOVO 13 10.0 W 1005 lm 100.5 lm/W

79
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 20 LIVING AREA (Light scene 1)


Calculation objects

80
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 20 LIVING AREA (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (20 LIVING AREA) 174 lx 40.6 lx 471 lx 0.23 0.086 WP20
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 4.570 m x 7.400 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

81
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 21 HOTEL LOBBY+CORRIDOR (Light scene 1)


Summary

Ground area 226.78 m² Clearance height 4.000 m – 4.100 m

Reflection factors Ceiling: 65.7 %, Mounting height 3.800 m – 4.100 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

82
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 21 HOTEL LOBBY+CORRIDOR (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 159 lx

Uo (g1 ) 0.14

Glare valuation(1) RUG, max 14

Energy estimation(2) Consumption 1099 kWh/a

Room Lighting power density 1.96 W/m²

1.23 W/m²/100 lx

(1) Based on a rectangular space of 14.657 m x 33.152 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

36 Regent 2005.7524 NOVO 14 10.0 W 1005 lm 100.5 lm/W

3 Regent TEA TEA 12 28.0 W 3069 lm 109.6 lm/W

83
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 21 HOTEL LOBBY+CORRIDOR (Light scene 1)


Calculation objects

84
RLA_HOTEL PROJECT_FRIST FLOOR_25.01.2024

Building 1 · Storey 1 · 21 HOTEL LOBBY+CORRIDOR (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (21 HOTEL LOBBY+CORRIDOR) 159 lx 22.2 lx 497 lx 0.14 0.045 WP21
Perpendicular illuminance (adaptive)
Height: 0.000 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 14.657 m x 33.152 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))