Professional Documents
Culture Documents
F CKE Design
For D i
y Scope
The guidelines apply to electrical installations for non-residential buildings
either it is a conventional design or design and build such as the peak design
rate of electrical energy usage for all purposes is greater than 10W/m² of gross
floor area.
y Ob
Objective
The objective of these guidelines is to ensure that electrical system design
comply with the minimum requirements of MS 1525:2007-
1525:2007 Code of Practice on
Energy Efficiency and Use of Renewable Energy for Non-Residential Buildings
(First Revision).
y Responsibility
Head of Design Team (HODT) is responsible for ensuring adherence to these
guidelines.
y Method of Compliance
HODT shall use the EE checklist as in Appendix 3 together with these
guidelines. This checklist shall be submitted during Design Verification and
attached with JKR.PK Form(O).02-2 (Form Review / Verification / Validation).
Passive and Active Design
Passive Design Elements
y Building Orientation Helps
H l in
i reducing
d i
y Building Envelope cooling & lighting
Natural Air Ventilation
load demand
y
y Interior Space Layout Design
Active Design
g Elements
• Air Conditioning & Mechanical Ventilation Helps in
• Innovative Lighting System reducing
• Energy Efficient Office Appliances & Plug Loads
electrical
• Comprehensive Energy Management System
demand
Building Energy Intensity (BEI)
Conventional KeTTHA-LEO
300
kWh / m² per yr 275
200
120
100 93 100
64 62
25
11
0
Cooling Lights Other Total
Lighting Design
y Types of lighting
Lighting Design
y Electronic Ballast for Fluorescent Lighting
- reducing power consumption by around 25%
- last 10 to 15 years lifetime with long burning times
- more compact and 60% lighter weight than
electromagnetic ballasts.
- give
i freedom
f d from
f the
h 50Hz
50H lamp
l fli
flicker
k
- lower heat generation
- lamp starting is instantaneous
y Electromagnetic Ballast
- ballast loss not to exceed 6
6.0
0 W in accordance to MS IEC 60929:1995
60929:1995.
Lighting Design
Design Criteria
Illuminance of immediate
Task illuminance lux
surrounding lux
≥ 750 500
500 300
300 200
≤ 200 Same as task illuminance
Restaurants 15
Offices 15
Supermarkets / Department
Stores / Shops 25
Car Park 5
Illuminance
Levels
Illuminance
Levels
Lighting Design
Design Criteria
Lighting Zone & Controls
• Automatic
A lighting
l h controll for
f lighting
l h loads
l d exceeding
d 100kW.
100kW
• Lighting zone control to take into account:
- separate circuit where day light can be use and alternate switching to optimize the use
g g
of lighting
- 1 switch for max. 1kW on lighting load
- 1 switch for each task or group of task within an area less than 30m2
Sub Metering
y Electrical energy meters shall be provided
for all energy uses of ≥ 100kVA and shall
be installed at strategic load centres to
monitor energy consumption of key
building services such as the outgoing sub-
circuits serving, but not limited to the
following:
◦ Central air-conditioning system
◦ Lifts
◦ Major water pumping system
◦ Plug loads
◦ Lightings
g g
Transformers Design
All transformers in the building’s electrical system shall have efficiencies
not lower than 98% for size below 1000kVA and not less than 99% for
sizes equal to or greater than 1000kVA at full load conditions.
y Dry-type Oil-Filled
Rated Power No Load On-Load Loss Total Losses Rated Power No-Load On-Load Total Losses
(kVA) Loss (W)* (W)* (W)* (kVA) Loss (W)* Loss (W)* (W)*
400 810 4520 5330 100 300 1500 1800
ption
For the installations taking supply at 11kV and above from TNB, it is
recommended to install the EMS complete with maximum demand (MD) limiting
controller for controlling and reducing MD in TNB bill.
Energy Efficiency
Ch kli
Checklist
(Electrical
A
Aspects Only)
O l )
Energy Efficiency
Ch kli
Checklist
(Electrical
A
Aspects Only)
O l )
Energy Efficiency
Ch kli
Checklist
(Electrical
A
Aspects Only)
O l )
Th k Y
Thank You…
Building Orientation
- M j it off windows
Majority i d fface th
the N
North
th and
dSSouth
th
- Minimum no. of windows in the East and West facing wall. Thus,
√ Reduce direct sunlight from entering the building (as the sun
rises from the East and sets in the West)
9 Minimise heat gain from sunlight
9 Reduce cooling load
N
Building Envelope Insulation
y INSULATION OF WALL AND ROOF
◦ Common Insulation Materials
x TYPE OF WALL-BRICK & AERATED CONCRETE
x TYPE OF ROOF-POLYSTYRENE & MINERAL WOOL
Natural Air Ventilation Thermal Flue
Stack
SPACE PLANNING
To maximise the p
penetration of daylight
y g into inner space
p
• The offices along the perimeter have primarily glazed partition walls
towards the inner parts of the building, such that daylight will filter
through
g to those areas too.
Reduced Office Lighting
g g Load