RLA_HOTEL PROJECT_GROUND FLOOR_24.01.

2024

Description

The nominal values shown in the calculation report are the result of
precision calculations, based upon precisely positioned luminaires in
a fixed relationship to each other and to the area under examination.
In practice the values may vary due to tolerances on luminaires,
luminaire position, reflection properties of room walls, ceilings, floor,
furniture texture and finishes, road surface variances, declared
lumen output and intensity of luminaire are nominal values which are
subject to +/- 10% variation as per BIS guidelines. There could be
further tolerance of +/- 7% due to various reasons like tolerance in
Supply voltage (as per BIS norms), ambient temperature, dirt
accumulation in luminaire surfaces. Lighting calculations are usually
done for open area without any obstructions. Any obstructions like
trees, buildings or furniture, racks, general building elements will
impact lighting levels and shadow patterns. Such inputs are generally
not considered during design estimation.

1
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 01 GARBAGE RM (Light scene 1)


Summary

Ground area 50.63 m² Clearance height 3.000 m

Reflection factors Ceiling: 70.0 %, Mounting height 3.000 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

2
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 01 GARBAGE RM (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 318 lx

Uo (g1 ) 0.56

Glare valuation(1) RUG, max 31

Energy estimation(2) Consumption 594 kWh/a

Room Lighting power density 4.74 W/m²

1.49 W/m²/100 lx

(1) Based on a rectangular space of 6.500 m x 12.732 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

6 Regent Stark 31 40.0 W 4800 lm 120.0 lm/W

3
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 01 GARBAGE RM (Light scene 1)


Calculation objects

4
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 01 GARBAGE RM (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (01 GARBAGE RM) 318 lx 179 lx 426 lx 0.56 0.42 WP1
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 6.500 m x 12.732 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

5
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 02 MAIN TEL. RM (Light scene 1)


Summary

Ground area 10.85 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

6
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 02 MAIN TEL. RM (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 448 lx

Uo (g1 ) 0.62

Glare valuation(1) RUG, max 27

Energy estimation(2) Consumption 198 kWh/a

Room Lighting power density 7.37 W/m²

1.65 W/m²/100 lx

(1) Based on a rectangular space of 3.500 m x 3.100 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

2 Regent Stark 26 40.0 W 4800 lm 120.0 lm/W

7
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 02 MAIN TEL. RM (Light scene 1)


Calculation objects

8
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 02 MAIN TEL. RM (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (02 MAIN TEL. RM) 448 lx 279 lx 594 lx 0.62 0.47 WP2
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 3.500 m x 3.100 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

9
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 03 PASSAGE AREA (Light scene 1)


Summary

Ground area 19.30 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

10
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 03 PASSAGE AREA (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 142 lx

Uo (g1 ) 0.68

Energy estimation(2) Consumption 149 kWh/a

Room Lighting power density 3.11 W/m²

2.18 W/m²/100 lx

(1) Based on a rectangular space of 9.650 m x 2.000 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

4 Regent Blaire – 15.0 W 1501 lm 100.1 lm/W

11
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 03 PASSAGE AREA (Light scene 1)


Calculation objects

12
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 03 PASSAGE AREA (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (03 PASSAGE AREA) 142 lx 96.0 lx 171 lx 0.68 0.56 WP3
Perpendicular illuminance (adaptive)
Height: 0.000 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 9.650 m x 2.000 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

13
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 04 STAFF RM (Light scene 1)


Summary

Ground area 82.39 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

14
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 04 STAFF RM (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 477 lx

Uo (g1 ) 0.45

Energy estimation(2) Consumption 1238 kWh/a

Room Lighting power density 6.07 W/m²

1.27 W/m²/100 lx

(1) Based on a rectangular space of 10.700 m x 7.700 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

20 Regent ZEN22 – 25.0 W 2500 lm 100.0 lm/W

15
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 04 STAFF RM (Light scene 1)


Calculation objects

16
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 04 STAFF RM (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (04 STAFF RM) 477 lx 214 lx 645 lx 0.45 0.33 WP4
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 10.700 m x 7.700 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

17
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 05 CROCKERY STORE (Light scene 1)


Summary

Ground area 22.62 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

18
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 05 CROCKERY STORE (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 432 lx

Uo (g1 ) 0.33

Energy estimation(2) Consumption 371 kWh/a

Room Lighting power density 6.63 W/m²

1.53 W/m²/100 lx

(1) Based on a rectangular space of 4.350 m x 5.200 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

6 Regent ZEN22 – 25.0 W 2500 lm 100.0 lm/W

19
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 05 CROCKERY STORE (Light scene 1)


Calculation objects

20
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 05 CROCKERY STORE (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (05 CROCKERY STORE) 432 lx 143 lx 592 lx 0.33 0.24 WP5
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 4.350 m x 5.200 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

21
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 06 CUTLERY STORE (Light scene 1)


Summary

Ground area 10.87 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

22
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 06 CUTLERY STORE (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 255 lx

Uo (g1 ) 0.33

Energy estimation(2) Consumption 124 kWh/a

Room Lighting power density 4.60 W/m²

1.81 W/m²/100 lx

(1) Based on a rectangular space of 4.350 m x 2.500 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

2 Regent ZEN22 – 25.0 W 2500 lm 100.0 lm/W

23
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 06 CUTLERY STORE (Light scene 1)


Calculation objects

24
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 06 CUTLERY STORE (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (06 CUTLERY STORE) 255 lx 83.7 lx 425 lx 0.33 0.20 WP6
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 4.350 m x 2.500 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

25
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 07 EQUIPMENT STORE (Light scene 1)


Summary

Ground area 11.28 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

26
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 07 EQUIPMENT STORE (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 263 lx

Uo (g1 ) 0.36

Energy estimation(2) Consumption 124 kWh/a

Room Lighting power density 4.43 W/m²

1.68 W/m²/100 lx

(1) Based on a rectangular space of 4.350 m x 2.600 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

2 Regent ZEN22 – 25.0 W 2500 lm 100.0 lm/W

27
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 07 EQUIPMENT STORE (Light scene 1)


Calculation objects

28
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 07 EQUIPMENT STORE (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (07 EQUIPMENT STORE) 263 lx 95.9 lx 411 lx 0.36 0.23 WP7
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 4.350 m x 2.600 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

29
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 08 KITCHEN STORE (Light scene 1)


Summary

Ground area 31.57 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

30
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 08 KITCHEN STORE (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 555 lx

Uo (g1 ) 0.27

Glare valuation(1) RUG, max 18

Energy estimation(2) Consumption 619 kWh/a

Room Lighting power density 7.92 W/m²

1.43 W/m²/100 lx

(1) Based on a rectangular space of 2.950 m x 10.700 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

10 Regent LED 0799 Kosher Eco 17 25.0 W 2500 lm 100.0 lm/W

31
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 08 KITCHEN STORE (Light scene 1)


Calculation objects

32
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 08 KITCHEN STORE (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (08 KITCHEN STORE) 555 lx 152 lx 798 lx 0.27 0.19 WP8
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 2.950 m x 10.700 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

33
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 09 CBS RM (Light scene 1)


Summary

Ground area 16.01 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

34
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 09 CBS RM (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 334 lx

Uo (g1 ) 0.55

Glare valuation(1) RUG, max 28

Energy estimation(2) Consumption 198 kWh/a

Room Lighting power density 5.00 W/m²

1.50 W/m²/100 lx

(1) Based on a rectangular space of 3.000 m x 5.350 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

2 Regent Stark 27 40.0 W 4800 lm 120.0 lm/W

35
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 09 CBS RM (Light scene 1)


Calculation objects

36
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 09 CBS RM (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (09 CBS RM) 334 lx 184 lx 488 lx 0.55 0.38 WP9
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 3.000 m x 5.350 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

37
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 10 SECURITY CONTROL RM (Light scene 1)


Summary

Ground area 26.67 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

38
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 10 SECURITY CONTROL RM (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 385 lx

Uo (g1 ) 0.44

Energy estimation(2) Consumption 371 kWh/a

Room Lighting power density 5.62 W/m²

1.46 W/m²/100 lx

(1) Based on a rectangular space of 4.200 m x 6.350 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

6 Regent ZEN22 – 25.0 W 2500 lm 100.0 lm/W

39
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 10 SECURITY CONTROL RM (Light scene 1)


Calculation objects

40
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 10 SECURITY CONTROL RM (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (10 SECURITY CONTROL RM) 385 lx 169 lx 534 lx 0.44 0.32 WP10
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 4.200 m x 6.350 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

41
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 11 FEMALE PRAYER RM (Light scene 1)


Summary

Ground area 30.83 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

42
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 11 FEMALE PRAYER RM (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 238 lx

Uo (g1 ) 0.33

Energy estimation(2) Consumption 260 kWh/a

Room Lighting power density 3.41 W/m²

1.43 W/m²/100 lx

(1) Based on a rectangular space of 5.800 m x 5.350 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

7 Regent Blaire – 15.0 W 1501 lm 100.1 lm/W

43
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 11 FEMALE PRAYER RM (Light scene 1)


Calculation objects

44
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 11 FEMALE PRAYER RM (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (11 FEMALE PRAYER RM) 238 lx 79.0 lx 369 lx 0.33 0.21 WP11
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 5.800 m x 5.350 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

45
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 12 TOILET RM D3/E (Light scene 1)


Summary

Ground area 1.63 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

46
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 12 TOILET RM D3/E (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 216 lx

Uo (g1 ) 0.47

Energy estimation(2) Consumption 32.9 kWh/a

Room Lighting power density 8.15 W/m²

3.77 W/m²/100 lx

(1) Based on a rectangular space of 1.500 m x 1.088 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

1 Not yet a LD1082- Shallow Recessed Low Glare Fixed LED – 13.3 W 905 lm 68.0 lm/W
DIALux 700-LW30- Downlight
member WB

47
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 12 TOILET RM D3/E (Light scene 1)


Calculation objects

48
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 12 TOILET RM D3/E (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (12 TOILET RM D3/E) 216 lx 101 lx 297 lx 0.47 0.34 WP12
Perpendicular illuminance (adaptive)
Height: 0.000 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 1.500 m x 1.088 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

49
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 14 FEMALE WASHROOM (Light scene 1)


Summary

Ground area 51.89 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

50
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 14 FEMALE WASHROOM (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 244 lx

Uo (g1 ) 0.12

Energy estimation(2) Consumption 625 kWh/a

Room Lighting power density 4.87 W/m²

1.99 W/m²/100 lx

(1) Based on a rectangular space of 5.800 m x 13.925 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

19 Not yet a LD1082- Shallow Recessed Low Glare Fixed LED – 13.3 W 905 lm 68.0 lm/W
DIALux 700-LW30- Downlight
member WB

51
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 14 FEMALE WASHROOM (Light scene 1)


Calculation objects

52
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 14 FEMALE WASHROOM (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (14 FEMALE WASHROOM) 244 lx 28.9 lx 581 lx 0.12 0.050 WP13
Perpendicular illuminance (adaptive)
Height: 0.000 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 5.800 m x 13.925 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

53
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 15 MALE WASHROOM (Light scene 1)


Summary

Ground area 52.25 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

54
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 15 MALE WASHROOM (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 230 lx

Uo (g1 ) 0.15

Energy estimation(2) Consumption 560 kWh/a

Room Lighting power density 4.33 W/m²

1.88 W/m²/100 lx

(1) Based on a rectangular space of 5.800 m x 14.125 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

17 Not yet a LD1082- Shallow Recessed Low Glare Fixed LED – 13.3 W 905 lm 68.0 lm/W
DIALux 700-LW30- Downlight
member WB

55
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 15 MALE WASHROOM (Light scene 1)


Calculation objects

56
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 15 MALE WASHROOM (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (15 MALE WASHROOM) 230 lx 35.3 lx 406 lx 0.15 0.087 WP14
Perpendicular illuminance (adaptive)
Height: 0.000 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 5.800 m x 14.125 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

57
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 16 CHANGING RM (Light scene 1)


Summary

Ground area 5.18 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

58
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 16 CHANGING RM (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 251 lx

Uo (g1 ) 0.088

Energy estimation(2) Consumption 65.8 kWh/a

Room Lighting power density 5.14 W/m²

2.05 W/m²/100 lx

(1) Based on a rectangular space of 3.700 m x 1.400 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

2 Not yet a LD1082- Shallow Recessed Low Glare Fixed LED – 13.3 W 905 lm 68.0 lm/W
DIALux 700-LW30- Downlight
member WB

59
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 16 CHANGING RM (Light scene 1)


Calculation objects

60
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 16 CHANGING RM (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (16 CHANGING RM) 251 lx 22.2 lx 606 lx 0.088 0.037 WP15
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 3.700 m x 1.400 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

61
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 17 MALE PRAYER RM (Light scene 1)


Summary

Ground area 28.22 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

62
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 17 MALE PRAYER RM (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 338 lx

Uo (g1 ) 0.43

Energy estimation(2) Consumption 334 kWh/a

Room Lighting power density 4.78 W/m²

1.42 W/m²/100 lx

(1) Based on a rectangular space of 5.800 m x 4.900 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

9 Regent Blaire – 15.0 W 1501 lm 100.1 lm/W

63
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 17 MALE PRAYER RM (Light scene 1)


Calculation objects

64
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 17 MALE PRAYER RM (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (17 MALE PRAYER RM) 338 lx 146 lx 485 lx 0.43 0.30 WP16
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 5.800 m x 4.900 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

65
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 18 ROOM (Light scene 1)


Summary

Ground area 197.99 m² Clearance height 3.000 m

Reflection factors Ceiling: 30.0 %, Mounting height 3.000 m


Walls: 50.0 %,
Floor: 10.0 % Height Working plane 0.000 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

66
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 18 ROOM (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 172 lx

Uo (g1 ) 0.39

Glare valuation(1) RUG, max 33

Energy estimation(2) Consumption 1188 kWh/a

Room Lighting power density 2.42 W/m²

1.41 W/m²/100 lx

(1) Based on a rectangular space of 7.400 m x 27.350 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

12 Regent Stark 32 40.0 W 4800 lm 120.0 lm/W

67
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 18 ROOM (Light scene 1)


Calculation objects

68
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 18 ROOM (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (18 ROOM) 172 lx 67.1 lx 224 lx 0.39 0.30 WP17
Perpendicular illuminance (adaptive)
Height: 0.000 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 7.400 m x 27.350 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

69
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 19 SECURITY RM (Light scene 1)


Summary

Ground area 14.60 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

70
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 19 SECURITY RM (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 425 lx

Uo (g1 ) 0.096

Energy estimation(2) Consumption 248 kWh/a

Room Lighting power density 6.85 W/m²

1.61 W/m²/100 lx

(1) Based on a rectangular space of 3.645 m x 4.050 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

4 Regent ZEN22 – 25.0 W 2500 lm 100.0 lm/W

71
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 19 SECURITY RM (Light scene 1)


Calculation objects

72
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 19 SECURITY RM (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (19 SECURITY RM) 425 lx 41.0 lx 645 lx 0.096 0.064 WP18
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 3.645 m x 4.050 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

73
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 20 STAIRCASE (Light scene 1)


Summary

Ground area 10.16 m² Clearance height 3.000 m

Reflection factors Ceiling: 70.0 %, Mounting height 3.000 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

74
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 20 STAIRCASE (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 205 lx

Uo (g1 ) 0.64

Energy estimation(2) Consumption 178 kWh/a

Room Lighting power density 7.09 W/m²

3.45 W/m²/100 lx

(1) Based on a rectangular space of 6.200 m x 2.050 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

4 Regent Zing – 18.0 W 1801 lm 100.1 lm/W

75
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 20 STAIRCASE (Light scene 1)


Calculation objects

76
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 20 STAIRCASE (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (20 STAIRCASE) 205 lx 131 lx 249 lx 0.64 0.53 WP19
Perpendicular illuminance (adaptive)
Height: 0.000 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 6.200 m x 2.050 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

77
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 21 LIFT PLATFORM (Light scene 1)


Summary

Ground area 4.32 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

78
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 21 LIFT PLATFORM (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 198 lx

Uo (g1 ) 0.66

Energy estimation(2) Consumption 74.3 kWh/a

Room Lighting power density 6.94 W/m²

3.51 W/m²/100 lx

(1) Based on a rectangular space of 2.400 m x 1.800 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

2 Regent Blaire – 15.0 W 1501 lm 100.1 lm/W

79
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 21 LIFT PLATFORM (Light scene 1)


Calculation objects

80
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 21 LIFT PLATFORM (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (21 LIFT PLATFORM) 198 lx 131 lx 242 lx 0.66 0.54 WP20
Perpendicular illuminance (adaptive)
Height: 0.000 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 2.400 m x 1.800 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

81
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 22 CORRIDOR (Light scene 1)


Summary

Ground area 203.91 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

82
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 22 CORRIDOR (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 212 lx

Uo (g1 ) 0.41

Energy estimation(2) Consumption 1819 kWh/a

Room Lighting power density 3.60 W/m²

1.70 W/m²/100 lx

(1) Based on a rectangular space of 47.268 m x 24.300 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

49 Regent Blaire – 15.0 W 1501 lm 100.1 lm/W

83
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 22 CORRIDOR (Light scene 1)


Calculation objects

84
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 22 CORRIDOR (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (22 CORRIDOR) 212 lx 86.5 lx 326 lx 0.41 0.27 WP21
Perpendicular illuminance (adaptive)
Height: 0.000 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 47.268 m x 24.300 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

85
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 23 LINEN (Light scene 1)


Summary

Ground area 54.61 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

86
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 23 LINEN (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 405 lx

Uo (g1 ) 0.32

Energy estimation(2) Consumption 743 kWh/a

Room Lighting power density 5.49 W/m²

1.36 W/m²/100 lx

(1) Based on a rectangular space of 11.100 m x 4.950 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

12 Regent ZEN22 – 25.0 W 2500 lm 100.0 lm/W

87
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 23 LINEN (Light scene 1)


Calculation objects

88
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 23 LINEN (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (23 LINEN) 405 lx 131 lx 541 lx 0.32 0.24 WP22
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 11.100 m x 4.950 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

89
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 24 GENERATOR RM (Light scene 1)


Summary

Ground area 34.81 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

90
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 24 GENERATOR RM (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 362 lx

Uo (g1 ) 0.55

Glare valuation(1) RUG, max 30

Energy estimation(2) Consumption 396 kWh/a

Room Lighting power density 4.60 W/m²

1.27 W/m²/100 lx

(1) Based on a rectangular space of 7.010 m x 5.000 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

4 Regent Stark 30 40.0 W 4800 lm 120.0 lm/W

91
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 24 GENERATOR RM (Light scene 1)


Calculation objects

92
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 24 GENERATOR RM (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (24 GENERATOR RM) 362 lx 199 lx 523 lx 0.55 0.38 WP23
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 7.010 m x 5.000 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

93
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 25 L.V. RM (Light scene 1)


Summary

Ground area 74.84 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

94
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 25 L.V. RM (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 361 lx

Uo (g1 ) 0.52

Glare valuation(1) RUG, max 32

Energy estimation(2) Consumption 792 kWh/a

Room Lighting power density 4.28 W/m²

1.18 W/m²/100 lx

(1) Based on a rectangular space of 15.040 m x 5.000 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

8 Regent Stark 32 40.0 W 4800 lm 120.0 lm/W

95
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 25 L.V. RM (Light scene 1)


Calculation objects

96
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 25 L.V. RM (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (25 L.V. RM) 361 lx 187 lx 532 lx 0.52 0.35 WP24
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 15.040 m x 5.000 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

97
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 26 SUBSTATION (Light scene 1)


Summary

Ground area 110.62 m² Clearance height 2.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.500 m – 3.000 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

98
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 26 SUBSTATION (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 278 lx

Uo (g1 ) 0.43

Glare valuation(1) RUG, max 32

Energy estimation(2) Consumption 1188 kWh/a

Room Lighting power density 4.34 W/m²

1.56 W/m²/100 lx

(1) Based on a rectangular space of 18.500 m x 6.000 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

12 Regent Stark 32 40.0 W 4800 lm 120.0 lm/W

99
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 26 SUBSTATION (Light scene 1)


Calculation objects

100
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 26 SUBSTATION (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (26 SUBSTATION) 278 lx 120 lx 552 lx 0.43 0.22 WP25
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 18.500 m x 6.000 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

101
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 27 PARKING FOR TOWER (Light scene 1)


Summary

Ground area 3380.53 m² Clearance height 3.000 m

Reflection factors Ceiling: 30.0 %, Mounting height 3.000 m


Walls: 50.0 %,
Floor: 10.0 % Height Working plane 0.000 m

Maintenance factor 0.85 (fixed) Wall zone Working plane 0.000 m

102
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 27 PARKING FOR TOWER (Light scene 1)


Summary

Results

Symbol Calculated

Working plane Ēperpendicular 111 lx

Uo (g1 ) 0.22

Glare valuation(1) RUG, max 33

Energy estimation(2) Consumption 10791 kWh/a

Room Lighting power density 1.29 W/m²

1.16 W/m²/100 lx

(1) Based on a rectangular space of 58.388 m x 63.025 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

109 Regent Stark 32 40.0 W 4800 lm 120.0 lm/W

103
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 27 PARKING FOR TOWER (Light scene 1)


Calculation objects

104
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024

Building 1 · Storey 1 · 27 PARKING FOR TOWER (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index

Working plane (27 PARKING FOR TOWER) 111 lx 24.5 lx 198 lx 0.22 0.12 WP26
Perpendicular illuminance (adaptive)
Height: 0.000 m, Wall zone: 0.000 m

(1) Based on a rectangular space of 58.388 m x 63.025 m and SHR of 0.25.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

105