The nominal values shown in the calculation report are the result of
precision calculations, based upon precisely positioned luminaires in
a fixed relationship to each other and to the area under examination.
In practice the values may vary due to tolerances on luminaires,
luminaire position, reflection properties of room walls, ceilings, floor,
furniture texture and finishes, road surface variances, declared
lumen output and intensity of luminaire are nominal values which are
subject to +/- 10% variation as per BIS guidelines. There could be
further tolerance of +/- 7% due to various reasons like tolerance in
Supply voltage (as per BIS norms), ambient temperature, dirt
accumulation in luminaire surfaces. Lighting calculations are usually
done for open area without any obstructions. Any obstructions like
trees, buildings or furniture, racks, general building elements will
impact lighting levels and shadow patterns. Such inputs are generally
not considered during design estimation.
1
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
2
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.56
1.49 W/m²/100 lx
Luminaire list
3
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
4
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Working planes
Working plane (01 GARBAGE RM) 318 lx 179 lx 426 lx 0.56 0.42 WP1
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m
5
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
6
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.62
1.65 W/m²/100 lx
Luminaire list
7
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
8
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Working planes
Working plane (02 MAIN TEL. RM) 448 lx 279 lx 594 lx 0.62 0.47 WP2
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m
9
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
10
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.68
2.18 W/m²/100 lx
Luminaire list
11
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
12
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Working planes
Working plane (03 PASSAGE AREA) 142 lx 96.0 lx 171 lx 0.68 0.56 WP3
Perpendicular illuminance (adaptive)
Height: 0.000 m, Wall zone: 0.000 m
13
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
14
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.45
1.27 W/m²/100 lx
Luminaire list
15
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
16
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Working planes
Working plane (04 STAFF RM) 477 lx 214 lx 645 lx 0.45 0.33 WP4
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m
17
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
18
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.33
1.53 W/m²/100 lx
Luminaire list
19
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
20
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Working planes
Working plane (05 CROCKERY STORE) 432 lx 143 lx 592 lx 0.33 0.24 WP5
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m
21
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
22
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.33
1.81 W/m²/100 lx
Luminaire list
23
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
24
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Working planes
Working plane (06 CUTLERY STORE) 255 lx 83.7 lx 425 lx 0.33 0.20 WP6
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m
25
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
26
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.36
1.68 W/m²/100 lx
Luminaire list
27
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
28
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Working planes
Working plane (07 EQUIPMENT STORE) 263 lx 95.9 lx 411 lx 0.36 0.23 WP7
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m
29
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
30
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.27
1.43 W/m²/100 lx
Luminaire list
31
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
32
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Working planes
Working plane (08 KITCHEN STORE) 555 lx 152 lx 798 lx 0.27 0.19 WP8
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m
33
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
34
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.55
1.50 W/m²/100 lx
Luminaire list
35
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
36
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Working planes
Working plane (09 CBS RM) 334 lx 184 lx 488 lx 0.55 0.38 WP9
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m
37
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
38
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.44
1.46 W/m²/100 lx
Luminaire list
39
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
40
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Working planes
Working plane (10 SECURITY CONTROL RM) 385 lx 169 lx 534 lx 0.44 0.32 WP10
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m
41
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
42
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.33
1.43 W/m²/100 lx
Luminaire list
43
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
44
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Working planes
Working plane (11 FEMALE PRAYER RM) 238 lx 79.0 lx 369 lx 0.33 0.21 WP11
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m
45
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
46
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.47
3.77 W/m²/100 lx
Luminaire list
1 Not yet a LD1082- Shallow Recessed Low Glare Fixed LED – 13.3 W 905 lm 68.0 lm/W
DIALux 700-LW30- Downlight
member WB
47
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
48
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Working planes
Working plane (12 TOILET RM D3/E) 216 lx 101 lx 297 lx 0.47 0.34 WP12
Perpendicular illuminance (adaptive)
Height: 0.000 m, Wall zone: 0.000 m
49
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
50
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.12
1.99 W/m²/100 lx
Luminaire list
19 Not yet a LD1082- Shallow Recessed Low Glare Fixed LED – 13.3 W 905 lm 68.0 lm/W
DIALux 700-LW30- Downlight
member WB
51
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
52
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Working planes
Working plane (14 FEMALE WASHROOM) 244 lx 28.9 lx 581 lx 0.12 0.050 WP13
Perpendicular illuminance (adaptive)
Height: 0.000 m, Wall zone: 0.000 m
53
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
54
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.15
1.88 W/m²/100 lx
Luminaire list
17 Not yet a LD1082- Shallow Recessed Low Glare Fixed LED – 13.3 W 905 lm 68.0 lm/W
DIALux 700-LW30- Downlight
member WB
55
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
56
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Working planes
Working plane (15 MALE WASHROOM) 230 lx 35.3 lx 406 lx 0.15 0.087 WP14
Perpendicular illuminance (adaptive)
Height: 0.000 m, Wall zone: 0.000 m
57
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
58
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.088
2.05 W/m²/100 lx
Luminaire list
2 Not yet a LD1082- Shallow Recessed Low Glare Fixed LED – 13.3 W 905 lm 68.0 lm/W
DIALux 700-LW30- Downlight
member WB
59
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
60
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Working planes
Working plane (16 CHANGING RM) 251 lx 22.2 lx 606 lx 0.088 0.037 WP15
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m
61
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
62
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.43
1.42 W/m²/100 lx
Luminaire list
63
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
64
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Working planes
Working plane (17 MALE PRAYER RM) 338 lx 146 lx 485 lx 0.43 0.30 WP16
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m
65
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
66
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.39
1.41 W/m²/100 lx
Luminaire list
67
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
68
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Working planes
Working plane (18 ROOM) 172 lx 67.1 lx 224 lx 0.39 0.30 WP17
Perpendicular illuminance (adaptive)
Height: 0.000 m, Wall zone: 0.000 m
69
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
70
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.096
1.61 W/m²/100 lx
Luminaire list
71
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
72
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Working planes
Working plane (19 SECURITY RM) 425 lx 41.0 lx 645 lx 0.096 0.064 WP18
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m
73
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
74
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.64
3.45 W/m²/100 lx
Luminaire list
75
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
76
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Working planes
Working plane (20 STAIRCASE) 205 lx 131 lx 249 lx 0.64 0.53 WP19
Perpendicular illuminance (adaptive)
Height: 0.000 m, Wall zone: 0.000 m
77
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
78
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.66
3.51 W/m²/100 lx
Luminaire list
79
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
80
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Working planes
Working plane (21 LIFT PLATFORM) 198 lx 131 lx 242 lx 0.66 0.54 WP20
Perpendicular illuminance (adaptive)
Height: 0.000 m, Wall zone: 0.000 m
81
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
82
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.41
1.70 W/m²/100 lx
Luminaire list
83
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
84
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Working planes
Working plane (22 CORRIDOR) 212 lx 86.5 lx 326 lx 0.41 0.27 WP21
Perpendicular illuminance (adaptive)
Height: 0.000 m, Wall zone: 0.000 m
85
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
86
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.32
1.36 W/m²/100 lx
Luminaire list
87
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
88
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Working planes
Working plane (23 LINEN) 405 lx 131 lx 541 lx 0.32 0.24 WP22
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m
89
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
90
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.55
1.27 W/m²/100 lx
Luminaire list
91
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
92
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Working planes
Working plane (24 GENERATOR RM) 362 lx 199 lx 523 lx 0.55 0.38 WP23
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m
93
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
94
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.52
1.18 W/m²/100 lx
Luminaire list
95
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
96
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Working planes
Working plane (25 L.V. RM) 361 lx 187 lx 532 lx 0.52 0.35 WP24
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m
97
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
98
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.43
1.56 W/m²/100 lx
Luminaire list
99
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
100
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Working planes
Working plane (26 SUBSTATION) 278 lx 120 lx 552 lx 0.43 0.22 WP25
Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m
101
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
102
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Results
Symbol Calculated
Uo (g1 ) 0.22
1.16 W/m²/100 lx
Luminaire list
103
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
104
RLA_HOTEL PROJECT_GROUND FLOOR_24.01.2024
Working planes
Working plane (27 PARKING FOR TOWER) 111 lx 24.5 lx 198 lx 0.22 0.12 WP26
Perpendicular illuminance (adaptive)
Height: 0.000 m, Wall zone: 0.000 m
105