You are on page 1of 5

PK3 Phase B

Project Engineer: Engg. Arshad


Project No.: 59-2016/2017
Company Name: AVIC INTL & HOT
Customer Name: DGCA

Date: 10.02.2018
Operator:
PK3 Phase B
10.02.2018

Operator
Telephone
Fax
e-Mail

Glamox C10-S300 T8 236 DL - 2x36W T8 36 W / Luminaire Data Sheet

Luminous emittance 1:

Luminaire classification according to CIE: 100 Luminous emittance 1:


CIE flux code: 64 98 100 100 64
Light source
1 x T8 36, 58W
2 x T8 18, 36, 58W.
Can be supplied with or without light source.

Ballast
Electronic ballast (HF), analogue dimming (HFDa), digital dimming (HFDd)
or DALI.

Body material & colour


Steel body in pre-painted white.

Optics
Double parabolic basic optic type DL or without optic. 4 different farmes can
then be ordered seperately. FR1=Double prismatic acrylic plastic, FR2=
Opal acrylic plastic,
FR3 = Opal multi-cell plastic, FR4 = Specular multi-cell plastic.

Emergency system
Integrated emergency light type standard (S), Selftest (ST) and addressable
DALI (DALI) for 1 or 3 hour duration.

DIALux 4.13 by DIAL GmbH Page 2


PK3 Phase B
10.02.2018

Operator
Telephone
Fax
e-Mail

FM-200 Room / Summary

Height of Room: 5.000 m, Mounting Height: 5.000 m, Maintenance factor: Values in Lux, Scale 1:15
0.70

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 98 96 99 0.983
Floor 20 67 65 70 0.959
Ceiling 70 182 128 235 0.703
Walls (4) 50 198 19 1372 /

Workplane:
Height: 0.750 m
Grid: 8 x 2 Points
Boundary Zone: 0.250 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 2.343, Ceiling / Working Plane: 1.868.
Proportion of points with less than 400 lx (for IEQ-7): 100.00%.
Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
Glamox C10-S300 T8 236 DL - 2x36W T8 36
1 1 4319 6700 88.0
W (1.000)
Total: 4319 Total: 6700 88.0

Specific connected load: 51.76 W/m² = 53.08 W/m²/100 lx (Ground area: 1.70 m²)

DIALux 4.13 by DIAL GmbH Page 3


PK3 Phase B
10.02.2018

Operator
Telephone
Fax
e-Mail

FM-200 Room / Input Protocol

Height of working plane: 0.750 m


Boundary Zone: 0.250 m

Maintenance factor: 0.70

Height of Room: 5.000 m


Ground area: 1.70 m²

Surface Rho [%] from ( [m] | [m] ) towards ( [m] | [m] ) Length [m]
Floor 20 / / /
Ceiling 70 / / /
Wall 1 50 ( 0.000 | 0.000 ) ( 2.000 | 0.000 ) 2.000
Wall 2 50 ( 2.000 | 0.000 ) ( 2.000 | 0.850 ) 0.850
Wall 3 50 ( 2.000 | 0.850 ) ( 0.000 | 0.850 ) 2.000
Wall 4 50 ( 0.000 | 0.850 ) ( 0.000 | 0.000 ) 0.850

DIALux 4.13 by DIAL GmbH Page 4


PK3 Phase B
10.02.2018

Operator
Telephone
Fax
e-Mail

FM-200 Room / Luminaires (coordinates list)

Glamox C10-S300 T8 236 DL - 2x36W T8 36 W


4319 lm, 88.0 W, 1 x 2 x T8 36 W (Correction Factor 1.000).

No. Position [m] Rotation [°]


X Y Z X Y Z
1 1.000 0.420 5.000 0.0 0.0 90.0

DIALux 4.13 by DIAL GmbH Page 5