You are on page 1of 5

PK3-Phase B

Project Engineer: Engg. Arshad


Project No.: 59-2016/2017
Company Name: AVIC INTL & HOT
Customer Name: DGCA

Date: 10.02.2018
Operator:
PK3-Phase B
10.02.2018

Operator
Telephone
Fax
e-Mail

Glamox C10-S300 T8 236 DL - 2x36W T8 36 W / Luminaire Data Sheet

Luminous emittance 1:

Luminaire classification according to CIE: 100 Luminous emittance 1:


CIE flux code: 64 98 100 100 64
Light source
1 x T8 36, 58W
2 x T8 18, 36, 58W.
Can be supplied with or without light source.

Ballast
Electronic ballast (HF), analogue dimming (HFDa), digital dimming (HFDd)
or DALI.

Body material & colour


Steel body in pre-painted white.

Optics
Double parabolic basic optic type DL or without optic. 4 different farmes can
then be ordered seperately. FR1=Double prismatic acrylic plastic, FR2=
Opal acrylic plastic,
FR3 = Opal multi-cell plastic, FR4 = Specular multi-cell plastic.

Emergency system
Integrated emergency light type standard (S), Selftest (ST) and addressable
DALI (DALI) for 1 or 3 hour duration.

DIALux 4.13 by DIAL GmbH Page 2


PK3-Phase B
10.02.2018

Operator
Telephone
Fax
e-Mail

Generator Room / Summary

Height of Room: 5.000 m, Mounting Height: 5.000 m, Maintenance factor: Values in Lux, Scale 1:152
0.70

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 209 141 252 0.674
Floor 20 180 123 214 0.687
Ceiling 70 47 33 55 0.694
Walls (4) 50 110 34 289 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.750 m Left Wall 14 10
Grid: 32 x 64 Points Lower Wall 14 10
Boundary Zone: 0.250 m (CIE, SHR = 1.00.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.532, Ceiling / Working Plane: 0.225.
Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
Glamox C10-S300 T8 236 DL - 2x36W T8 36
1 6 4319 6700 88.0
W (1.000)
Total: 25917 Total: 40200 528.0

Specific connected load: 9.32 W/m² = 4.46 W/m²/100 lx (Ground area: 56.64 m²)

DIALux 4.13 by DIAL GmbH Page 3


PK3-Phase B
10.02.2018

Operator
Telephone
Fax
e-Mail

Generator Room / Input Protocol

Height of working plane: 0.750 m


Boundary Zone: 0.250 m

Maintenance factor: 0.70

Height of Room: 5.000 m


Ground area: 56.64 m²

Surface Rho [%] from ( [m] | [m] ) towards ( [m] | [m] ) Length [m]
Floor 20 / / /
Ceiling 70 / / /
Wall 1 50 ( 0.000 | 0.000 ) ( 4.800 | 0.000 ) 4.800
Wall 2 50 ( 4.800 | 0.000 ) ( 4.800 | 11.800 ) 11.800
Wall 3 50 ( 4.800 | 11.800 ) ( 0.000 | 11.800 ) 4.800
Wall 4 50 ( 0.000 | 11.800 ) ( 0.000 | 0.000 ) 11.800

DIALux 4.13 by DIAL GmbH Page 4


PK3-Phase B
10.02.2018

Operator
Telephone
Fax
e-Mail

Generator Room / Luminaires (coordinates list)

Glamox C10-S300 T8 236 DL - 2x36W T8 36 W


4319 lm, 88.0 W, 1 x 2 x T8 36 W (Correction Factor 1.000).

No. Position [m] Rotation [°]


X Y Z X Y Z
1 1.200 1.970 5.000 0.0 0.0 0.0
2 1.200 5.900 5.000 0.0 0.0 0.0
3 1.200 9.830 5.000 0.0 0.0 0.0
4 3.600 1.970 5.000 0.0 0.0 0.0
5 3.600 5.900 5.000 0.0 0.0 0.0
6 3.600 9.830 5.000 0.0 0.0 0.0

DIALux 4.13 by DIAL GmbH Page 5