You are on page 1of 5

MainCamp 22

Partner for Contact:


Order No.:
Company:
Customer No.:

Date: 21.09.2021
Operator:
MainCamp 22
21.09.2021

Operator
Telephone
Fax
e-Mail

PHILIPS TBS318 C 2x18W M2 TL-D HFE 2xTL-D18W/840/840 / Luminaire Data Sheet

Luminous emittance 1:

See our luminaire catalog for an image of the


luminaire.

Luminaire classification according to CIE: 100 Luminous emittance 1:


CIE flux code: 57 91 99 100 64

Page 2
MainCamp 22
21.09.2021

Operator
Telephone
Fax
e-Mail

CAMP OFFICE_Meeting Room / Summary

Height of Room: 2.800 m, Mounting Height: 2.800 m, Light loss factor: Values in Lux, Scale 1:52
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 400 248 521 0.621
Floor 20 340 231 423 0.678
Ceiling 80 84 66 91 0.784
Walls (4) 50 194 73 401 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.700 m Left Wall 16 18
Grid: 32 x 32 Points Lower Wall 16 19
Boundary Zone: 0.000 m (CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.497, Ceiling / Working Plane: 0.210.
Proportion of points with less than 400 lx (for IEQ-7): 49.61%.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
PHILIPS TBS318 C 2x18W M2 TL-D HFE
1 9 1728 2700 0.0
2xTL-D18W/840/840 (1.000)
Total: 15552 Total: 24300 0.0

Specific connected load: 0.00 W/m² = 0.00 W/m²/ lx (Ground area: 24.00 m²)

Page 3
MainCamp 22
21.09.2021

Operator
Telephone
Fax
e-Mail

CAMP OFFICE_Meeting Room / Input Protocol

Height of working plane: 0.700 m


Boundary Zone: 0.000 m

Light loss factor: 0.80

Height of Room: 2.800 m


Ground area: 24.00 m²

Surface Rho [%] from ( [m] | [m] ) towards ( [m] | [m] ) Length [m]
Floor 20 / / /
Ceiling 80 / / /
Wall 1 50 ( 0.000 | 0.000 ) ( 6.000 | 0.000 ) 6.000
Wall 2 50 ( 6.000 | 0.000 ) ( 6.000 | 4.000 ) 4.000
Wall 3 50 ( 6.000 | 4.000 ) ( 0.000 | 4.000 ) 6.000
Wall 4 50 ( 0.000 | 4.000 ) ( 0.000 | 0.000 ) 4.000

Page 4
MainCamp 22
21.09.2021

Operator
Telephone
Fax
e-Mail

CAMP OFFICE_Meeting Room / Luminaires (coordinates list)

PHILIPS TBS318 C 2x18W M2 TL-D HFE 2xTL-D18W/840/840


1728 lm, 0.0 W, 1 x 2 x TL-D18W/840 (Correction Factor 1.000).

No. Position [m] Rotation [°]


X Y Z X Y Z
1 1.000 0.670 2.800 0.0 0.0 90.0
2 1.000 2.000 2.800 0.0 0.0 90.0
3 1.000 3.330 2.800 0.0 0.0 90.0
4 3.000 0.670 2.800 0.0 0.0 90.0
5 3.000 2.000 2.800 0.0 0.0 90.0
6 3.000 3.330 2.800 0.0 0.0 90.0
7 5.000 0.670 2.800 0.0 0.0 90.0
8 5.000 2.000 2.800 0.0 0.0 90.0
9 5.000 3.330 2.800 0.0 0.0 90.0

Page 5