You are on page 1of 4

Mona_interior

26.09.2014

Operator
Telephone
Fax
e-Mail

PHILIPS TBS162 4xTL5-14W HF C6-60 / Luminaire Data Sheet

Luminous emittance 1:

See our luminaire catalog for an image of the


luminaire.

Luminaire classification according to CIE: 100 Luminous emittance 1:


CIE flux code: 73 100 100 100 71

Page 1
Mona_interior
26.09.2014

Operator
Telephone
Fax
e-Mail

Sala_1 / Summary

Height of Room: 3.200 m, Mounting Height: 3.280 m, Light loss factor: Values in Lux, Scale 1:80
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 653 314 915 0.481
Floor 20 527 240 858 0.455
Ceiling 70 88 56 105 0.637
Walls (6) 50 174 55 435 /

Workplane:
Height: 0.750 m
Grid: 32 x 32 Points
Boundary Zone: 0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.222, Ceiling / Working Plane: 0.135.
Proportion of points with less than 400 lx (for IEQ-7): 7.03%.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
PHILIPS TBS162 4xTL5-14W HF C6-60
1 11 3600 5000 63.0
(1.000)
Total: 39600 Total: 55000 693.0

Specific connected load: 14.34 W/m² = 2.20 W/m²/100 lx (Ground area: 48.32 m²)

Page 2
Mona_interior
26.09.2014

Operator
Telephone
Fax
e-Mail

Sala_1 / Luminaire parts list

11 Pieces PHILIPS TBS162 4xTL5-14W HF C6-60 See our luminaire


Article No.: catalog for an image of
Luminous flux (Luminaire): 3600 lm the luminaire.
Luminous flux (Lamps): 5000 lm
Luminaire Wattage: 63.0 W
Luminaire classification according to CIE: 100
CIE flux code: 73 100 100 100 71
Fitting: 4 x TL5-14W/840 (Correction Factor
1.000).

Page 3
Mona_interior
26.09.2014

Operator
Telephone
Fax
e-Mail

Sala_1 / Photometric Results

Total Luminous Flux: 39600 lm


Total Load: 693.0 W
Light loss factor: 0.80
Boundary Zone: 0.500 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 587 65 653 / /
Floor 451 77 527 20 34
Ceiling 0.00 88 88 70 20
Wall 1 126 83 209 50 33
Wall 2 89 75 165 50 26
Wall 3 82 76 158 50 25
Wall 4 42 75 116 50 19
Wall 5 101 74 176 50 28
Wall 6 84 79 163 50 26

Uniformity on the working plane


u0: 0.481 (1:2)
Emin / Emax: 0.343 (1:3)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.222, Ceiling / Working Plane: 0.135.
Proportion of points with less than 400 lx (for IEQ-7): 7.03%.

Specific connected load: 14.34 W/m² = 2.20 W/m²/100 lx (Ground area: 48.32 m²)