Luminous emittance 1:
Page 1
Project 1
14.06.2022
Operator
Telephone
Fax
e-Mail
Room 1 / Summary
Height of Room: 9.000 m, Mounting Height: 8.400 m, Light loss factor: Values in Lux, Scale 1:67
0.80
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.795, Ceiling / Working Plane: 0.346.
No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
PHILIPS BY120P G3 1xLED105S/840 WB
1 4 10500 10500 85.0
(1.000)
Total: 42000 Total: 42000 340.0
Specific connected load: 9.91 W/m² = 3.19 W/m²/100 lx (Ground area: 34.32 m²)
Page 2
Project 1
14.06.2022
Operator
Telephone
Fax
e-Mail
Page 3
Project 1
14.06.2022
Operator
Telephone
Fax
e-Mail
Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 202 108 311 / /
Calculation Surface 1 202 108 311 / /
Floor 171 101 272 20 17
Ceiling 0.01 108 108 80 27
Wall 1 134 107 241 50 38
Wall 2 127 107 234 50 37
Wall 3 134 107 241 50 38
Wall 4 127 107 234 50 37
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.795, Ceiling / Working Plane: 0.346.
Specific connected load: 9.91 W/m² = 3.19 W/m²/100 lx (Ground area: 34.32 m²)
Page 4
Project 1
14.06.2022
Operator
Telephone
Fax
e-Mail
Room 2 / Summary
Height of Room: 9.000 m, Mounting Height: 8.400 m, Light loss factor: Values in Lux, Scale 1:67
0.80
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.784, Ceiling / Working Plane: 0.341.
No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
PHILIPS BY120P G3 1xLED105S/840 WB
1 4 10500 10500 85.0
(1.000)
Total: 42000 Total: 42000 340.0
Specific connected load: 9.62 W/m² = 3.13 W/m²/100 lx (Ground area: 35.36 m²)
Page 5
Project 1
14.06.2022
Operator
Telephone
Fax
e-Mail
Page 6
Project 1
14.06.2022
Operator
Telephone
Fax
e-Mail
Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 201 106 308 / /
Calculation Surface 1 201 106 308 / /
Floor 170 100 270 20 17
Ceiling 0.01 105 105 80 27
Wall 1 131 105 236 50 38
Wall 2 123 104 228 50 36
Wall 3 131 105 236 50 38
Wall 4 123 105 229 50 36
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.784, Ceiling / Working Plane: 0.341.
Specific connected load: 9.62 W/m² = 3.13 W/m²/100 lx (Ground area: 35.36 m²)
Page 7
Project 1
14.06.2022
Operator
Telephone
Fax
e-Mail
Room 3 / Summary
Height of Room: 9.000 m, Mounting Height: 8.400 m, Light loss factor: Values in Lux, Scale 1:67
0.80
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.878, Ceiling / Working Plane: 0.383.
No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
PHILIPS BY120P G3 1xLED105S/840 WB
1 5 10500 10500 85.0
(1.000)
Total: 52500 Total: 52500 425.0
Specific connected load: 15.72 W/m² = 3.74 W/m²/100 lx (Ground area: 27.04 m²)
Page 8
Project 1
14.06.2022
Operator
Telephone
Fax
e-Mail
Page 9
Project 1
14.06.2022
Operator
Telephone
Fax
e-Mail
Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 262 158 420 / /
Calculation Surface 1 262 158 420 / /
Floor 219 145 364 20 23
Ceiling 0.01 161 161 80 41
Wall 1 193 160 353 50 56
Wall 2 193 160 353 50 56
Wall 3 193 160 353 50 56
Wall 4 193 160 353 50 56
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.878, Ceiling / Working Plane: 0.383.
Specific connected load: 15.72 W/m² = 3.74 W/m²/100 lx (Ground area: 27.04 m²)
Page 10
Project 1
14.06.2022
Operator
Telephone
Fax
e-Mail
Room 4 / Summary
Height of Room: 9.000 m, Mounting Height: 8.400 m, Light loss factor: Values in Lux, Scale 1:67
0.80
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.797, Ceiling / Working Plane: 0.356.
No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
PHILIPS BY120P G3 1xLED105S/840 WB
1 12 10500 10500 85.0
(1.000)
Total: 126000 Total: 126000 1020.0
Specific connected load: 29.28 W/m² = 3.18 W/m²/100 lx (Ground area: 34.84 m²)
Page 11
Project 1
14.06.2022
Operator
Telephone
Fax
e-Mail
Page 12
Project 1
14.06.2022
Operator
Telephone
Fax
e-Mail
Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 600 319 920 / /
Calculation Surface 1 600 319 920 / /
Floor 508 299 807 20 51
Ceiling 0.02 327 327 80 83
Wall 1 387 318 705 50 112
Wall 2 389 316 705 50 112
Wall 3 387 319 705 50 112
Wall 4 389 316 705 50 112
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.797, Ceiling / Working Plane: 0.356.
Specific connected load: 29.28 W/m² = 3.18 W/m²/100 lx (Ground area: 34.84 m²)
Page 13
Project 1
14.06.2022
Operator
Telephone
Fax
e-Mail
Room 5 / Summary
Height of Room: 9.000 m, Mounting Height: 8.400 m, Light loss factor: Values in Lux, Scale 1:67
0.80
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.797, Ceiling / Working Plane: 0.356.
No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
PHILIPS BY120P G3 1xLED105S/840 WB
1 6 10500 10500 85.0
(1.000)
Total: 63000 Total: 63000 510.0
Specific connected load: 14.64 W/m² = 3.18 W/m²/100 lx (Ground area: 34.84 m²)
Page 14
Project 1
14.06.2022
Operator
Telephone
Fax
e-Mail
Page 15
Project 1
14.06.2022
Operator
Telephone
Fax
e-Mail
Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 300 160 460 / /
Calculation Surface 1 300 160 460 / /
Floor 254 149 404 20 26
Ceiling 0.01 164 164 80 42
Wall 1 193 159 353 50 56
Wall 2 195 158 353 50 56
Wall 3 193 159 353 50 56
Wall 4 195 158 353 50 56
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.797, Ceiling / Working Plane: 0.356.
Specific connected load: 14.64 W/m² = 3.18 W/m²/100 lx (Ground area: 34.84 m²)
Page 16
Project 1
14.06.2022
Operator
Telephone
Fax
e-Mail
Room 6 / Summary
Height of Room: 9.000 m, Mounting Height: 8.400 m, Light loss factor: Values in Lux, Scale 1:67
0.80
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.797, Ceiling / Working Plane: 0.358.
No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
PHILIPS BY120P G3 1xLED105S/840 WB
1 6 10500 10500 85.0
(1.000)
Total: 63000 Total: 63000 510.0
Specific connected load: 14.64 W/m² = 3.18 W/m²/100 lx (Ground area: 34.84 m²)
Page 17
Project 1
14.06.2022
Operator
Telephone
Fax
e-Mail
Page 18
Project 1
14.06.2022
Operator
Telephone
Fax
e-Mail
Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 300 160 460 / /
Calculation Surface 1 300 160 460 / /
Floor 254 150 404 20 26
Ceiling 0.01 165 165 80 42
Wall 1 193 159 353 50 56
Wall 2 195 158 353 50 56
Wall 3 193 160 353 50 56
Wall 4 195 158 353 50 56
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.797, Ceiling / Working Plane: 0.358.
Specific connected load: 14.64 W/m² = 3.18 W/m²/100 lx (Ground area: 34.84 m²)
Page 19
Project 1
14.06.2022
Operator
Telephone
Fax
e-Mail
Room 7 / Summary
Height of Room: 9.000 m, Mounting Height: 8.400 m, Light loss factor: Values in Lux, Scale 1:67
0.80
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.803, Ceiling / Working Plane: 0.359.
No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
PHILIPS BY120P G3 1xLED105S/840 WB
1 6 10500 10500 85.0
(1.000)
Total: 63000 Total: 63000 510.0
Specific connected load: 14.86 W/m² = 3.21 W/m²/100 lx (Ground area: 34.32 m²)
Page 20
Project 1
14.06.2022
Operator
Telephone
Fax
e-Mail
Page 21
Project 1
14.06.2022
Operator
Telephone
Fax
e-Mail
Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 301 161 463 / /
Calculation Surface 4 301 161 463 / /
Floor 255 151 405 20 26
Ceiling 0.01 166 166 80 42
Wall 1 195 161 356 50 57
Wall 2 197 160 357 50 57
Wall 3 195 161 356 50 57
Wall 4 197 160 357 50 57
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.803, Ceiling / Working Plane: 0.359.
Specific connected load: 14.86 W/m² = 3.21 W/m²/100 lx (Ground area: 34.32 m²)
Page 22
Project 1
14.06.2022
Operator
Telephone
Fax
e-Mail
Room 8 / Summary
Height of Room: 9.000 m, Mounting Height: 8.400 m, Light loss factor: Values in Lux, Scale 1:207
0.80
Workplane:
Height: 0.760 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.435, Ceiling / Working Plane: 0.202.
No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
PHILIPS BY120P G3 1xLED105S/840 WB
1 21 10500 10500 85.0
(1.000)
Total: 220500 Total: 220500 1785.0
Specific connected load: 6.15 W/m² = 1.32 W/m²/100 lx (Ground area: 290.24 m²)
Page 23
Project 1
14.06.2022
Operator
Telephone
Fax
e-Mail
Page 24
Project 1
14.06.2022
Operator
Telephone
Fax
e-Mail
Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 373 93 466 / /
Floor 352 94 446 20 28
Ceiling 0.01 94 94 80 24
Wall 1 128 91 219 50 35
Wall 2 107 88 195 50 31
Wall 3 85 89 175 50 28
Wall 4 73 88 161 50 26
Wall 5 115 90 205 50 33
Wall 6 123 91 214 50 34
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.435, Ceiling / Working Plane: 0.202.
Specific connected load: 6.15 W/m² = 1.32 W/m²/100 lx (Ground area: 290.24 m²)
Page 25
Project 1
14.06.2022
Operator
Telephone
Fax
e-Mail
Room 14 / Summary
Height of Room: 9.000 m, Mounting Height: 8.400 m, Light loss factor: Values in Lux, Scale 1:997
0.80
Workplane:
Height: 0.760 m
Grid: 128 x 128 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.366, Ceiling / Working Plane: 0.196.
No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
PHILIPS BY120P G3 1xLED105S/840 WB
1 336 10500 10500 85.0
(1.000)
Total: 3528000 Total: 3528000 28560.0
Specific connected load: 3.89 W/m² = 0.94 W/m²/100 lx (Ground area: 7340.10 m²)
Page 26
Project 1
14.06.2022
Operator
Telephone
Fax
e-Mail
Page 27
Project 1
14.06.2022
Operator
Telephone
Fax
e-Mail
Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 346 68 414 / /
Calculation Surface 1 386 69 455 / /
Floor 342 68 411 20 26
Ceiling 0.01 81 81 80 21
Wall 1 87 69 156 50 25
Wall 2 85 71 155 50 25
Wall 3 106 73 179 50 29
Wall 4 39 52 91 50 15
Wall 5 50 53 103 50 16
Wall 6 42 52 93 50 15
Wall 7 104 74 178 50 28
Wall 8 51 66 116 50 19
Wall 9 70 73 143 50 23
Wall 10 133 73 205 50 33
Wall 11 84 70 154 50 25
Wall 12 84 71 155 50 25
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.366, Ceiling / Working Plane: 0.196.
Specific connected load: 3.89 W/m² = 0.94 W/m²/100 lx (Ground area: 7340.10 m²)
Page 28