Professional Documents
Culture Documents
06.03.2022
Operator
Telephone
Fax
e-Mail
Luminous emittance 1:
Page 1
B93 BATH
06.03.2022
Operator
Telephone
Fax
e-Mail
Room 2 / Summary
Height of Room: 3.000 m, Mounting Height: 3.000 m, Maintenance factor: Values in Lux, Scale 1:24
0.80
Workplane:
Height: 0.700 m
Grid: 32 x 32 Points
Boundary Zone: 0.200 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.609, Ceiling / Working Plane: 0.269.
Luminaire Parts List
No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
1 1 DN145B PSD D166 LED10S/840 NO (1.000) 1100 1100 13.0
Total: 1100 Total: 1100 13.0
Specific connected load: 3.36 W/m² = 3.39 W/m²/100 lx (Ground area: 3.87 m²)
Page 2
B93 BATH
06.03.2022
Operator
Telephone
Fax
e-Mail
Page 3
B93 BATH
06.03.2022
Operator
Telephone
Fax
e-Mail
Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 70 29 99 / /
Floor 42 23 65 20 4.11
Ceiling 0.00 27 27 70 5.95
Wall 1 32 24 56 50 8.88
Wall 2 29 24 53 50 8.42
Wall 3 32 24 56 50 8.89
Wall 4 29 24 53 50 8.42
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.609, Ceiling / Working Plane: 0.269.
Specific connected load: 3.36 W/m² = 3.39 W/m²/100 lx (Ground area: 3.87 m²)
Page 4
B93 BATH
06.03.2022
Operator
Telephone
Fax
e-Mail
Room 3 / Summary
Height of Room: 3.000 m, Mounting Height: 3.000 m, Maintenance factor: Values in Lux, Scale 1:31
0.80
No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
1 2 DN145B PSD D166 LED10S/840 NO (1.000) 1100 1100 13.0
Total: 2200 Total: 2200 26.0
Specific connected load: 3.36 W/m² = 2.78 W/m²/100 lx (Ground area: 7.74 m²)
Page 5
B93 BATH
06.03.2022
Operator
Telephone
Fax
e-Mail
Page 6
B93 BATH
06.03.2022
Operator
Telephone
Fax
e-Mail
Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 89 32 121 / /
Floor 59 27 87 20 5.52
Ceiling 0.00 30 30 70 6.60
Wall 1 33 27 60 50 9.52
Wall 2 37 27 64 50 10
Wall 3 33 27 60 50 9.48
Wall 4 37 28 64 50 10
Specific connected load: 3.36 W/m² = 2.78 W/m²/100 lx (Ground area: 7.74 m²)
Page 7
B93 BATH
06.03.2022
Operator
Telephone
Fax
e-Mail
Room 4 / Summary
Height of Room: 3.000 m, Mounting Height: 3.000 m, Maintenance factor: Values in Lux, Scale 1:107
0.80
Workplane:
Height: 0.700 m
Grid: 128 x 128 Points
Boundary Zone: 0.200 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.558, Ceiling / Working Plane: 0.245.
Luminaire Parts List
No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
1 7 DN145B PSD D166 LED10S/840 NO (1.000) 1100 1100 13.0
Total: 7701 Total: 7700 91.0
Specific connected load: 3.40 W/m² = 2.46 W/m²/100 lx (Ground area: 26.80 m²)
Page 8
B93 BATH
06.03.2022
Operator
Telephone
Fax
e-Mail
Page 9
B93 BATH
06.03.2022
Operator
Telephone
Fax
e-Mail
Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 104 34 138 / /
Floor 76 31 107 20 6.83
Ceiling 0.00 34 34 70 7.53
Wall 1 28 27 55 50 8.82
Wall 2 38 29 67 50 11
Wall 3 15 28 43 50 6.91
Wall 4 31 32 64 50 10
Wall 5 40 32 72 50 12
Wall 6 25 26 51 50 8.16
Wall 7 46 32 77 50 12
Wall 8 47 31 78 50 12
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.558, Ceiling / Working Plane: 0.245.
Specific connected load: 3.40 W/m² = 2.46 W/m²/100 lx (Ground area: 26.80 m²)
Page 10