MOUNTING HEIGHTS

FIRE ALARAM (NFPA 72)


FACP/FSCP PANEL
ISOLATOR
CEILING PULL CORD
RESET BUTTON
MANUAL CALL POINT
BEACONS/SOUNDER/FLASHER (OR) STROBES

SMOKE/HEAT DETECTOR CEILING MOUNT

MAGNETIC DOOR HOLDER


EXIT SIGN
FIRE PHONE JACK
SMALL POWER & LIGHTING

POWER SOCKET

INDUSTRIAL SOCKET
HAND DRYER
FUSED SPUR/RESET SWITCH/ ALARM CALLS
LIGHTING SWITCH/THERMOSTART/ TEMP SENSOR
FLOOR BOX
DB
WALL MOUNTED LIGHTING FIXTURE
NIGHT LIGHTS
CLOCK OUTLETS
BED LIGHTS
Energy METERS
WALL MOUNTED LIGHTING FIXTURE SWITCH BOX
CONTAINMENT
TRUNKING
CABLE TRAY

TELECOM & SECURITY


DATA/ VOICE/ TV SOCKETS/ TELECOM
CCTV PORTS
BELL PUSH/ ENTRY PHONE
WALL INTERCOM STATIONS
MOUNTING HEIGHTS

FIRE ALARAM (NFPA 72)


1800 F/A
1250 F/B
100 LOWER Δle & 800 -1000 UPPER Δle
1200
1200 - 1400, 125 FROM SIDE OF DOOR
2000-2500 F/B (OR) 150 BELOW CEILING
500 FROM SIDE OF BEAM(ANY OBSTRUCTION)
250 FROM SIDE OF LIGHT
900 FROM SIDE OF DIFFUSER
150 BELOW THE TOP OF DOOR
150 ABOVE THE TOP OF DOOR
1200 F/B
SMALL POWER & LIGHTING
450 F/B (NOT MORE THAN1000 & 250 FROM WORKTOP
50 GAP SIDE TO SIDE,
No sockets above gas or electric hobs
No sockets within 300 range from sink
1000 F/B
1100 F/B
750 - 1200
1250 F/B & 150 FROM SIDE OF THE DOOR
FLOOR MOUNTED
1800 - 2200 F/A
2000 F/B
450
2500 (OR) 150 BELOW CEILING
1800
1200-1400
2050
CONTAINMENT
MIN 100 SIDE TO SIDE
MIN 150 SIDE TO SIDE, critical areas take 30 deg bend
150 CLEARENCE AROUND CT, 45deg or 90 deg bends only
NEVER RUN PARALLEL TO WET SERVICE
SUPPORTS 1500 DISTANCE HAVE TO MAINTAIN
TELECOM & SECURITY
450 F/B
NEAR CAM & ATTACH TO CEILING
1200 MAX
1200