110 · VACON® arfiff03 Grid Converter

2.6.1.5 Short Circuit Fault Voltage Level ID 1518


The BiPhase fault is detected by monitoring the supply voltage. Set this value lower than
the supply voltage would be in normal operation.
This limit can be activated also for three phase faults if need by setting Control Options 2
B07 TRUE, Residual Voltage Limit

Short Circuit detection


Two phase
Fault: F91 Short Circuit

P Supply Voltage

P ShortCircuitTime
P BiPhsFaultVLevel

M Supply Voltage

Figure 32.

2.6.1.6 Output Active Current Limit ID 1290


This parameter sets the active current limit for the generator side operation of the
regenerative unit. 100.0% is equal to nominal power, defined by System Rated Current.

2.6.1.7 Input Active Current Limit ID 1289


This parameter sets the active current limit for the motoring side operation of the
regenerative unit. 100.0% is equal to nominal power, defined by System Rated Current.

2.6.1.8 Software Over Current fault level ID1094


Software level Over Current Protection. This is instantaneous value, related to P2.1.3
System Rated Current. (𝑃2.1.3 ∗ √2). Drive stops to F1 Over Current Sub Code S4

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/


6 Classified as Public