For CSA-A23.3-14:
Sv ≤ 3t Clause 14.1.8.4
≤ Clause 14.1.8.4
500mm
For CSA-A23.3-04:
Sv ≤ 3t Clause 14.1.8.4
≤ Clause 14.1.8.4
500mm
≤ Clause.21.6.5.1
450mm for Rd > 2, non-
plastic region
≤ Clause.21.6.5.1
300mm for Rd > 2,
plastic hinge
region
mk:@MSITStore:C:\Program%20Files%20(x86)\S-FRAME%20Software\S-FRAME%2... 2018-03-28
Wall Detailing Requirements – CSA-A23.3-04 & 14 Page 2 of 5
According to Clause 21.6.4.4 of CSA-A23.3-04, ductile walls shall not have horizontal and vertical bar
diameters bigger than one-tenth of the thickness of the wall at the bar location. In CSA-A23.3-14,
similar requirement is postulated in Clause 14.1.8.2 that applies for all walls.
According to Clause 14.1.8.3, when two curtains of reinforcing is specified, clear cover to the
reinforcing bars should not be more than 1/3 of the thickness of the wall.
According to Clause 14.1.8.7, for ρv ≥ 0.005 or db > 19.5 mm (20M), vertical distributed reinforcing
may require lateral ties that satisfy Clause 7.6.5. S-CONCRETE interprets these clauses as a limit of
maximum bar diameter size because the panel distributed reinforcements are not tied.
Clause 21.5.5.4 of CSA-A23.3-14 has a similar requirement, except that this applies only for ductile and
moderately ductile walls in plastic hinge regions; and the tie should satisfy the buckling prevention ties
requirements of Clause 21.2.8.1.
Clause 21.6.5.1 and 21.7.3.3.1 of CSA-A23.3-04 are now Clause 21.5.5.1 of CSA-A23.3-14.
Panel Reinforcing – Horizontal Bars
See Shear Reinforcing for Walls.
Clear spacing between vertical bars must meet minimum requirements. This translates to a maximum number of
bars permitted for a given tie configuration and splice type. Splice type also affects the maximum number of bars
permitted.
mk:@MSITStore:C:\Program%20Files%20(x86)\S-FRAME%20Software\S-FRAME%2... 2018-03-28
Wall Detailing Requirements – CSA-A23.3-04 & 14 Page 3 of 5
Note that in CSA-A23.3-14, the requirements from Clause 21.6.5.1 of CSA-A23.3-04 no longer exist.
Let As = Area of
Concentrated
(or Zone)
Reinforcement
Azone = Gross Area of
Zone
Clauses 21.6.6.3 & 21.6.6.4 of A23.3-04 or Clauses 21.5.6.1 & 21.5.6.2 of A23.3-14 for Rd > 2:
As ≥ 0.0010 t Lw for
non-plastic regions
As ≥ 0.0015 t Lw for
plastic hinge
regions
As ≥ 0.0005 t Lw for
non-plastic regions
As ≥ 0.00075 t Lw for
mk:@MSITStore:C:\Program%20Files%20(x86)\S-FRAME%20Software\S-FRAME%2... 2018-03-28
Wall Detailing Requirements – CSA-A23.3-04 & 14 Page 4 of 5
plastic hinge
regions
Clause 21.6.6.5 of A23.3-04 or Clauses 21.5.6.3 of A23.3-14 for Rd > 2: additional requirements for
flanged walls.
According to Clause 21.6.6.1 of A23.3-04 or 21.5.6.1 of A23.3-14 for Rd > 2, a minimum of 4 bars (in 2
layers) shall be placed in all corners, ends of panels, and at intersections of panels. For A23.3-14 only,
this requirement also applies to plastic regions of R = 1.5 walls according to Clause 21.6.3.7.4.
d
According to Clause 12.14.2.1, lap splices shall not be permitted for vertical bars greater than 35.7mm
in diameter (35M). Furthermore, if the section is subjected to tensile loads, bearing splices should not be
used. Lap or mechanical splices are recommended instead under these circumstances.
According to Clause 21.6.4.4 of A23.3-04 for Rd > 2 or Clause 14.1.8.2 of A23.3-14 for all Rd:
db ≤ 0.1t for horizontal & vertical bars
According to Clause 6.6.5.2 of A23.1-04 & 14, tie spacing should be greater than or equal to:
mk:@MSITStore:C:\Program%20Files%20(x86)\S-FRAME%20Software\S-FRAME%2... 2018-03-28
Wall Detailing Requirements – CSA-A23.3-04 & 14 Page 5 of 5
According to Clause 7.6.5.1, the diameter of the tie must be greater than or equal to:
According to Clause 14.1.8.7, for As ≥ 0.005Azone or db > 19.5 mm (20M), vertical distributed
reinforcing may require lateral ties that satisfy Clause 7.6.5. Same requirement is postulated in Clause
21.5.5.4, except that this applies only for ductile and moderately ductile walls in plastic hinge regions,
and the tie should satisfy the buckling prevention ties requirements of Clause 21.2.8.1.