Professional Documents
Culture Documents
Project Information:
Location
Building Owner
Program User ACADEMIC
Company
Comments
System Information:
Calculation Method Equal Friction
Friction Rate 0.10
Correct For Leakage? NO
Correct For Thermal Losses/Gains? NO
Auto-Balance? NO
Resize Non-Critical Paths? NO
Air Conditions:
Elevation 0.00 ft
Dry-Bulb Temperature 55.00 °F
Air Density 0.077 lb/cu ft
Fan Information:
Total VAV Box/Diffuser Airflow (As Entered) 16,022 cfm
Peak Fan Airflow (Including Leakage and Thermal Changes) 16,022 cfm
Block Fan Airflow (Including Leakage and Thermal Changes) 16,022 cfm
Diversity Factor 1.00
Fan Outlet Shape Rectangular
Fan Outlet Dimensions
Width 20.00 in.
Height 16.00 in.
Discharge Velocity 7,209.90 fpm
Fan Static Pressure (At Sea Level) 2.80 in. wg
Fan Static Pressure (At Altitude) 2.80 in. wg
Static Pressure Through Equipment and Return (At Sea Level) 0.20 in. wg
Static Pressure Through Equipment and Return (At Altitude) 0.20 in. wg
Leakage Airflow 0.00 cfm
Thermal Losses/Gains Airflow 0.00 cfm