Design and simulation
of a grid-connected PV
system for
self-consumption
A Master’s Thesis by
Irene Arranz i López
Supervisor
Univ.-Prof. DDipl.-Ing. Dr.techn. Robert Schürhuber
Dipl.-Ing. Mike Alexander Lagler
September 2020
Design and simulation of a grid-connected PV system for self-consumption
Head of Institute
Univ.-Prof. DDipl.-Ing. Dr.techn. Robert Schürhuber
Supervisor
Univ.-Prof. DDipl.-Ing. Dr.techn. Robert Schürhuber
Dipl.-Ing. Mike Alexander Lagler
A Master’s Thesis by
Irene Arranz i López
September 2020
II
Design and simulation of a grid-connected PV system for self-consumption
Statutory Declaration
I declare that I have authored this thesis independently, that I have not used other than the declared
sources / resources, and that I have explicitly marked all material which has been quoted either literally
or by content from the used sources.
Graz, 15-08-2020
III
Design and simulation of a grid-connected PV system for self-consumption
Acknowledgements
This thesis is the end to a Master’s Degree, and it is as well a representation of a whole experience
abroad. Foremost, I would like to pay my special regards to my thesis tutor at TU Graz, Mike Lagler. I
would like to express my sincere gratitude to him for his feedback, help and support during the
development of the project in the extraordinary circumstances of a global health emergency.
I would like to thank everybody who participated in either a direct or indirect way in my work, making it
easier and more enjoyable with their encouragement. I am truly grateful to all the people I have met in
Graz and with whom I have created the most marvellous memories. I must give special thanks to Javi,
for his unconditional care and for always having my back. To Ada, for motivating me to leave Barcelona
and embarking on such a journey. To Silvia, for showing me the right way to do things, and to Kimchi,
for his inspiration.
At last, but not least, I would like to thank my family for their commitment to my education, and their
continuous assistance and guidance, even from the distance, as this would not have been possible
without them.
IV
Design and simulation of a grid-connected PV system for self-consumption
Abstract
Although Spain is one of the countries with the highest incidence of solar irradiance in Europe, in many
areas of the country PV technology is not fully deployed. This thesis is focused on designing and
assessing through a simulation software the performance of a grid-connected PV system for self-
consumption installed on a building’s rooftop in a location with a high solar potential unused.
An in-depth search on photovoltaic literature was made in order to gain information on the field, as well
as on the grid code requirements in both Europe and Spain. Then, a prospection to find the proper
location for the installation was done. Afterwards, a load profile was created to know the building’s
energy demand, and finally the technology to implement was chosen and sized. With these premises, a
CAD 3D model of the building and surrounding elements was implemented into a simulation software
(PVsyst). This allowed to create the PV layout, to find the most accurate values for the parameters to
optimize the performance of the system (tilt angle, azimuth, and row spacing), and to develop a shading
and loss analysis. The first scenarios were further refined with an additional simulation which took into
account a storage system, providing a final scenario. Finally, an economic study was performed.
The system renders an annual energy production of 20,38 MWh/year, an annual specific yield of 1.742
kWh/kWp with a performance ratio of 79,3%, which cover the household’s demand with an estimate
saving of 2.635,8 €/a and 3409 tCO2/a emitted to the atmosphere. The study showed the system to be
effective and economically viable and profitable, and also provides a design guide for grid-connected
PV systems for self-consumption.
V
Design and simulation of a grid-connected PV system for self-consumption
List of Symbols
α Elevation angle
β Tilt angle
δ Declination angle
η Efficiency
θ Azimuth angle
µ Imbalance degree
ϕ Zenith angle
List of Abbreviations
AC Alternating Current
AM Air Mass
DC Direct Current
VI
Design and simulation of a grid-connected PV system for self-consumption
FF Fill Factor
Gb Direct radiation
Gd / D h Diffuse radiation
Gr Reflected radiation
PR Performance Ratio
PV Photovoltaic
RD Royal Decree
VII
Design and simulation of a grid-connected PV system for self-consumption
UV Ultraviolet
Wp Watt Peak
VIII
Design and simulation of a grid-connected PV system for self-consumption
Table of Contents
Introduction...................................................................................... 1
Objectives ........................................................................................ 3
IX
Design and simulation of a grid-connected PV system for self-consumption
X
Design and simulation of a grid-connected PV system for self-consumption
Results ........................................................................................... 75
Conclusions ................................................................................... 94
Bibliography................................................................................... 97
XI
Design and simulation of a grid-connected PV system for self-consumption
XII
Design and simulation of a grid-connected PV system for self-consumption
List of figures
Figure 1. Representation of air mass spectrum in the Earth’s atmosphere [9] ....................................... 6
Figure 5. Comparison of the I-V curves depending on the electrical configuration of the modules [19]11
Figure 7. Current-voltage curve and Power-voltage curve of a solar cell [14] ...................................... 12
Figure 9. Diodes configuration in panels connected in series and parallel [22] .................................... 15
Figure 11. Percentage of global PV production regarding thin-film technologies (2016) [23] ............... 18
Figure 12. Microstructure of a CIGS solar cell: Coloured image of cleaved CIGS sample (left), Schematic
Figure 13. Inverter typologies: a) Central inverter, b) String inverter, c) Microinverter, d) Multistring
Figure 14. Active power frequency response capability of power-generating modules in LFSM-O [41]
............................................................................................................................................................... 26
Figure 15. Maximum power capability reduction with falling frequency [41] ......................................... 27
Figure 19. CTE map of Spain with classified zones regarding the incident irradiance [47] .................. 37
Figure 22. Maximum and minimum daily temperatures for Linyola [49]................................................ 39
Figure 24. Monthly solar irradiation estimates for Linyola (2016) [50] .................................................. 40
Figure 25. Area of the terrain where building studied is located [51] .................................................... 42
Figure 26. Available and unavailable areas on the building for the placement of PV modules [51] ..... 42
XIII
Design and simulation of a grid-connected PV system for self-consumption
Figure 27. Load profiles of the cars for weekdays and weekends [52] ................................................. 44
Figure 28. Time distribution for daily activities for each member [52] ................................................... 45
Figure 30. Duration curves for the devices on the household [52] ........................................................ 46
Figure 31. Load profile of the household for weekdays and weekends [52] ......................................... 47
Figure 32. Sum profile of the household during the simulated year [52] ............................................... 47
Figure 33. Effect of temperature on ISC, VOC and PMAX [56] ................................................................... 52
Figure 34. Relation between GCR and tilt angle of the PV modules [59] ............................................. 57
Figure 36. Technology and devices data introduced on PVsyst [60] .................................................... 60
Figure 37. Tilt angle and module orientation introduced on PVsyst for a fixed tilted plane [60] ........... 61
Figure 38. Production graph of different modes of tilting modules [61] ................................................. 62
Figure 39. Tilt angle and module orientation introduced on PVsyst for a seasonally tilt-adjusted plane
[60] ......................................................................................................................................................... 63
Figure 42. Axonometric projection of the CAD model of the building and surrounding elements [60] .. 66
Figure 43. Overhead projection of the CAD model of the building and surrounding elements [60] ...... 66
Figure 44. Available zones on the building’s rooftop for the installation of the PV system [60] ............ 67
Figure 45. Electrical configuration of a PV module in landscape (left) and portrait (right) position [69] 68
Figure 46. Side projection of the module layout on the rooftop [60]...................................................... 69
Figure 47. Axonometric projection of the module layout on the rooftop [60] ......................................... 69
Figure 49. Consumption data of the household introduced on PVsyst [60] .......................................... 71
Figure 50. Specified monthly energy need of the household [60] ......................................................... 72
Figure 55. Module layout on scenarios G (left) and H (right) [60] ......................................................... 79
XIV
Design and simulation of a grid-connected PV system for self-consumption
Figure 57. Graph of monthly production and losses for scenario D [60] ............................................... 80
Figure 61. Simplified scheme for direct mode with sufficient irradiance and full charge [60] ............... 84
Figure 62. Simplified scheme for direct mode with insufficient irradiance and no charge [60] ............. 84
Figure 64. Graph of battery’s charging and discharging energy for the month of June [60] ................. 86
Figure 65. Graph of battery’s charging and discharging energy for the month of December [60] ........ 86
Figure 66. Comparison graph between battery discharging energy, energy injected or purchased from
the grid, and energy supplied to the user for the month of June [60] .................................................... 87
Figure 67. Comparison graph between battery discharging energy, energy injected or purchased from
the grid, and energy supplied to the user for the month of December [60] ........................................... 88
Figure 69. Saved carbon dioxide emissions of the PV system on scenario SS [60] ............................. 93
XV
Design and simulation of a grid-connected PV system for self-consumption
List of tables
Table 1. Limits for thresholds for type B,C and D power-generating modules ...................................... 24
Table 2. Minimum time periods for which a power-generating module has to be capable of operating on
different frequencies, deviating from a nominal value, without disconnecting from the network. ......... 25
Table 3. Parameters for fault ride-through capability of synchronous power-generating modules ....... 28
Table 4. Limits on harmonic voltage for each node of the network ....................................................... 33
Table 11. Definition parameters and simulation results for scenarios A, B and C ................................ 75
Table 13. Definition parameters and simulation results for scenarios D, E and F ................................ 78
Table 14. Definition parameters and simulation results for scenarios G and H .................................... 79
Table 15. Definition parameters and simulation results for scenario SS............................................... 85
Table 16. CAPEX and OPEX amounts for the PV system .................................................................... 90
Table 18. Prices of charging the electric cars in a public charging station ........................................... 92
XVI
Design and simulation of a grid-connected PV system for self-consumption
Introduction
Energy is a fundamental pillar of human progress. For over two centuries, fossil fuels (coal, and more
recently natural gas and oil derivatives) have been the main sources of energy, but as societies and
industries develop, the need for energy resources increases. The world’s population is expected to
increase to more than 11,2 billion by the end of the century and recently, a mathematical model that
combined world population, wealth and oil consumption, estimated that to support the natural global
growth of gross domestic product, world energy consumption should increase by approximately 1,7
billion tons of oil equivalent per year by 2025. This means that maintaining an oil energy share of around
33% (2015 levels) would require increasing current oil production by more than 11 million barrels per
day [1].
However, fossil resources are not only exhaustible, but also generate emissions of greenhouse gases
responsible for climate change that can have devastating and irreversible consequences on the
environment. Therefore, the foreseeable increase in energy demand and the depletion of fossil fuels
forces humanity to accelerate the transition to a low carbon economy, which requires the search for
clean and renewable alternative energies. These include hydropower, wind, biomass, geothermal, and
solar energy. All of them are renewable energies, which means that they are naturally replenished and,
therefore, inexhaustible. Nonetheless, the amount of energy they produce is limited per unit of time and,
on the other hand, not all of these sources are sustainable.
Solar energy is the cleanest and most abundant source of energy of our planet and is also inexhaustible.
According to NASA calculations, the Sun still has 6500 million years of life left and, every hour, it throws
onto Earth more of the energy necessary to supply the global demand of a whole year. The Earth’s
surface receives 120,000 terawatts of solar irradiation, which is 20000 times more power than the entire
planet needs [2] and it is calculated that in just 18 days of solar irradiation, the Earth receives an amount
of energy equivalent to that accumulated for all the world’s reserves of coal, oil and natural gas [3].
As said, due to its extraordinary potential, solar energy has been the subject of intense research and
has undergone spectacular development, especially in recent years, mainly applied to the conversion
of solar energy into electrical energy or heat or to production of fuels through an artificial photosynthesis
process. Among renewable energies, photovoltaic energy offers some unique advantages that other
technologies do not provide:
It is 100% renewable: solar energy will radiate the earth for millions of years.
It is sustainable: it does not emit greenhouse gases or any type of pollutant.
It has a global availability: it can be used anywhere in the world, reaching places where the
power line does not reach.
It is sizeable from large plants to domestic installations.
Since the photovoltaic panels have no moving parts their maintenance is cheap and simple and
does not produce noise pollution.
1
Design and simulation of a grid-connected PV system for self-consumption
Despite these drawbacks, the photovoltaic solar energy has not stopped evolving, managing to reduce
panel prices until they are competitive with conventional sources of electricity generation in some
countries, and this way it is foreseeable that in a few years it will become a substantial part of a globally
sustainable energy system.
2
Design and simulation of a grid-connected PV system for self-consumption
Objectives
The main aim of this project is to design and simulate a grid-connected PV system installed on a rooftop
in Spain that can cover the energy demand of a house through self-consumption, and that can
additionally cover the charging of two electric cars. Moreover, other specific goals are set for this study,
such as:
With an average of almost 3,000 hours of sunshine per year, Spain is one of the countries in Europe
with the highest number of insolation hours, and is positioned as one of the leading countries in the
production of solar energy. The Royal Decree of April 2019, which favours self-consumption abolishing
the “Sun tax”, demonstrates the current solid commitment to the use of photovoltaic energy. In fact, the
National Integrated Energy and Climate Plan (PNIEC) foresees a total installed capacity of 37 GW of
photovoltaic solar energy in 2030 and sets the goal of a 100% renewable electricity sector in 2050.
3
Design and simulation of a grid-connected PV system for self-consumption
The design of the domestic PV plant is divided into different steps. The first one must be taken before
starting any design or calculations: it is necessary create a solid theoretical basis of concepts and
literature, among which the design can be done. The review of legislation, regulations and grid codes is
also an essential point whenever any grid-connected electrical system wants to be brought into reality.
Secondly, the development phase takes place. Details and data are analysed in order to find the best
location for the building that can make the most out of the solar potential of the region. The rooftop area
of the chosen building is measured, and a usual load profile for the household is drawn out taking into
account all the activities carried out by the users and the house devices consuming energy during each
hour of the day.
Afterwards, the technology used needs to be chosen, considering new types of modules, prices and
quality. By means of the calculation of different parameters, the electrical configuration of the PV
modules is defined: voltage sizing, minimum and maximum number of panels per string, number of
modules and inverters and a gross estimation of the energy yield produced.
Once an estimated pre-design is done, it can be modelled into the specialized software that will help to
simulate the electrical behaviour and performance of the PV system installed at the house. Different
scenarios need to be created, with diverse orientations and tilts, as the final design is eventually defined
after an iterative process of comparing, discarding and changing parameters on the simulations. Losses
due to shadings and electrical connections are also contemplated on this step, which leads finally to the
analysis of the best layout, and to the application of a storage system to it, that can optimize the use of
the produced energy. This final scenario is then simulated, and from the drawn results, an economic
study and a discussion can be made.
However, this project encounters certain limitations that cannot be solved without making simplifications
and assumptions. The PV system has been only implemented on a rooftop, without considering facades
or other zones that could have a great solar potential. Moreover, aesthetic and architectural details have
not been reviewed. Therefore, this study is totally based on efficiency and performance.
It has to be considered as well that the software used is a simplified tool to simulate PV systems, and
so there is a minimum error that must be assumed, as losses and other multiple factors are
approximations and average values extracted from papers and literature. A PV system by itself is a
complex element to study, as it is subject to many open variables (such as cloud movement) which are
impossible to define in an absolute realistic way. Additionally, updated meteorological data for 2020
were not available, so older values have been used for the simulations.
4
Design and simulation of a grid-connected PV system for self-consumption
Theoretical background
As described elsewhere [4] , the Sun is an element behaving as a blackbody at a temperature of 5778
K. It is an ideal absorber and emitter of a reasonably constant amount of radiation from its surface by
means of fusion reactions.
The solar constant, understood as the intensity of sun radiation flux interacting with a unity of surface,
whilst being measured outside the terrestrial atmosphere in a perpendicular plane to the sun beams, is
considered to have a value of GSC =1367 W/m2 [5]. It includes all wavelengths of the solar radiation, not
only the visible light range. However, this value varies widely when it reaches the atmosphere due to
phenomena and interactions that will be further explained in the following sections.
Upon reaching the atmosphere, solar radiation is affected by different major factors that reduce its power
and split it. These are radiation absorption (by dust and air molecules), scattering and reflection [6].
As a consequence, solar radiation is divided into three components: direct, diffuse and reflected
radiation [7]. Direct radiation (Gb), the most important one in terms of photovoltaic applications, reaches
the Earth’s surface without having changed its direction through the atmosphere, so it does not scatter.
Second, diffuse (or scattered) radiation (Gd) undergoes some previous directional changes on its way
to the Earth’s surface. The sum of these two types constitutes the global solar radiation (G). Lastly, the
reflected radiation (Gr) onto the soil or other elements can also be reabsorbed by other objects.
Air mass (Fig. 1) is defined as the ratio of the distance solar radiation travels through Earth’s atmosphere
(pathlength) and the distance it would travel if the sun’s beams were directly overhead (shortest
pathlength) [5]. This is usually understood as the mass of air solar radiation must travel through to
encounter the Earth’s surface. It can be calculated using the formula below (Eq. 1) [8], being ϕ the Sun’s
vertical angle or zenith angle:
1 1
𝐴𝑖𝑟 𝑀𝑎𝑠𝑠 = −1,6364
≃ (1)
cos(𝜙) + 0.50572 · (96.07995 − 𝜙) cos(𝜙)
Therefore, air mass reflects the reduction in the power of light because of its absorption by dust and air
as it passes through the atmosphere.
5
Design and simulation of a grid-connected PV system for self-consumption
The spectral distribution of the sun outside the atmosphere is considered to be air mass zero, or AM0,
and its power density is the solar constant explained above. Inside the atmosphere, however, when the
vertical angle (zenith angle) of the sun is θ = 0, this spectrum coming directly overhead is called AM1.
Therefore, the standard value for photovoltaic work has been fixed at AM1.5, which refers to a zenith
angle of 48,2 º from overhead, and which gives a power density approximate to 1000 W/m 2 including
direct and diffuse radiation [10].
The Sun’s position varies constantly depending on the season of the year and the hour of the day, and
therefore so does its radiation. The declination angle is the angle measured between a straight line
linking the centre of the Earth with the centre of the Sun, and the Earth’s axis. Hence, due to the Earth’s
rotation and orbit, the declination angle changes depending on those factors mentioned above ranging
from +23,45º on the summer solstice to -23,45º on the winter solstice, whilst this value reaches 0º on
the equinoxes [11]. This variation must be taken into account when sizing PV installations.
6
Design and simulation of a grid-connected PV system for self-consumption
Additionally, two more angles (Fig. 2) are essential for PV applications: the elevation angle and the
azimuth angle. The elevation angle (α) can be measured between the Sun and the horizontal, so being
0º at sunsets and sunrises. The azimuth angle (θ) is the compass direction from where the beams are
coming relating to the exact south.
7
Design and simulation of a grid-connected PV system for self-consumption
Photovoltaics fundamentals
The aim of photovoltaic energy is to achieve the conversion of light into direct current electricity, through
the photoelectric effect shown by some materials show. These kind of materials (usually silicon), used
in solar cells, are classified as semiconductors. Hence, a solar cell is a wafer of a semiconductor material
composed of an upper layer of n-type silicon, whose crystal lattice has a higher number of free electrons
than a layer of pure silicon, and a lower layer of p-type doped silicon that has less amount of free
electrons than a pure silicon layer as well, and therefore, positively charged holes in it. This is known as
a p-n junction [12].
When a p-n junction is produced, a diffusion flow is then pushed between the n-type layer, which
contains a high concentration of free electrons, and the p-type layer, the one with a high amount of
holes. Thus, free electrons migrate from one part to fill the holes to the other, and this results in a positive
charge along the junction in the n-region (where electrons are missing) and a negative charge along the
junction in the p region (where the holes have been filled). As a consequence, a depletion layer is
created in the middle of them. This layer does not contain any electrons or holes, meaning that at its
sides a driving force appears, that is, an electric field (Fig. 3).
8
Design and simulation of a grid-connected PV system for self-consumption
So, when solar radiation in the adequate wavelength strikes the n-layer of the cell, the absorbed photons
pass through the material breaking silicon bonds and tearing off free electrons, thereby creating holes
in the excited atoms. Both free electrons and holes pair up in the depletion region. However, the driving
force of this layer ousts electrons and holes out of it. Hence, free electrons and holes under the effect
of the electric field take opposite directions. This develops into a high concentration of electrons in the
n-region and holes in the p-region, and thus creating a clear potential difference between the layers.
Whenever a load is connected between these two sides, an electric flow will pass through it, travelling
from the n-part to the p-part and eventually recombining with the holes in this one. In this way, solar
cells continuously give direct current. Normally, solar cells use a thin and highly electron-doped n-layer,
and a thick and lightly doped p-layer, so that the depletion region is wider and the cell’s performance
increases [12].
A PV module is formed when multiple solar cells are organized and encapsulated by means of bus bar
connectors in order to maximize their output power. Similarly, if modules are put together in series they
create PV panels, which likewise are put into solar strings or arrays when interconnected.
Most PV modules are stable units with a front surface of a non-reflective material, so that they can
absorb the greatest amount of radiation. This material, usually a tempered, low-iron content glass,
prevents the cells from coming into contact with water, dust, gases and other elements, so they are not
corroded or damaged [14]. Furthermore, as the cells are thin and delicate, the front cover also provides
mechanical resistance and rigidity, as well as a safety barrier that prevents the user from suffering an
electrical shock. Therefore, they must have low thermal resistivity, high resistance to impact and water
good impact and water resistance and a high stability under prolonged exposure to UV rays.
The second component of the modules would be the encapsulation layers. The encapsulant is
responsible for providing adhesion between the strings of solar cells and the front and rear surfaces of
the module. Ethyl vinyl acetate (EVA) is the most commonly used material [15]. When heated up to 150
ºC, it polymerizes and bonds together with the cells and the coatings. It should be transparent, with low
thermal resistance and stable.
Then, a rear surface is needed in order to protect the back part of the module and to provide support to
the aforementioned elements and the wiring. Typically, it is made out of a polymer material [14]. Finally,
an aluminium frame is added to the edge of this series of elements, to attach them and to avoid lateral
lodgement of dirt or water, thus increasing the lifetime of the module.
The power that reaches a PV module depends not only on the power of the sunbeams, but also on the
tilt angle between the panel and the Sun. Power density will reach a maximum peak whenever the panel
is totally perpendicular to the sunlight. Theoretically, if there were no losses, the power density of the
9
Design and simulation of a grid-connected PV system for self-consumption
absorbing surface would equal the one from the sunlight. Nonetheless, due to the Sun’s constantly
changing position, and to various types of losses, this power density is always less than the incident
one.
Finding the optimal tilt angle for panels is essential to obtain the maximum output power from it [16].
There are basically two main kinds of mounting structures for solar systems: fixed systems and tracking
systems. When a panel is fixed, the best tilt angle is equal to the location’s latitude. When increasing
the tilt angle, energy production is optimized during the winter season. Otherwise, decreasing it is
advisable for energy production during the summer. Nevertheless, they are not capable of modifying
neither their orientation nor their tilt angle.
Given these conditions, it is possible to maximize the PV system output power by installing solar tracking
panels [17]. These structures follow the Sun during the day, capturing its direct perpendicular component
of light during the maximum amount of time possible. The most common types of tracking systems have
one or two rotation axis, and thus they differ in the degrees of freedom they have.
One-axis tracking systems are usually aligned with the north-south meridian so they can pursue the
Sun’s path from east to west. On the other hand, two-axis tracking systems have a first axis on the north-
south meridian (tilt, β), and a second axis on the east-west line (azimuth, θ), so they are able to track
the Sun in whichever position in the sky, as well as changing the tilt angle with seasonal height variations
of the Sun. These kind of systems is, of course, much more expensive than fixed ones, and require
more installing and maintenance processes, but energy harnessing is notoriously enhanced.
A single normal solar cell is meant to give an amount of power of about 1 Wp in Standard Test Conditions
(STC; AM1.5, T=25 ºC, 1000 W/m2). When arranged in series on a module, normally 60 to 72 cells are
used [14].
If modules are connected in series, a solar panel or string is created. Otherwise, when several strings
are connected in parallel they form a solar array (Fig.4).
10
Design and simulation of a grid-connected PV system for self-consumption
Under uniform operating conditions, that is, with identical cells and subject to the same irradiance and
temperature values so that there are no mismatch effects, differences between these two types of
arrangement can be spotted [14]. When stringing in series each individual module works with the same
current as the others, but adds to the total voltage of the string. However, the main drawback would be
that when a module is shadowed, the entire string’s current is reduced to that of the module with the
lowest current.
Nonetheless, when creating arrays by connecting panels in parallel, the voltage for each panel remains
the same, while the amperage increases with each additional panel. When a panel is shadowed, the
rest of the array continues with the normal operation without reductions (Fig. 5). This will be further
explained in the following sections.
Figure 5. Comparison of the I-V curves depending on the electrical configuration of the modules [19]
The open-circuit voltage, VOC, is the maximum amount of voltage that can be obtained from a solar cell
when the net current is null [14]. In an ideal photovoltaic cell model, it can be simplified on a theoretical
equivalent circuit as the one shown below (Fig. 6):
11
Design and simulation of a grid-connected PV system for self-consumption
𝐼 𝐾·𝑇cell
𝑉OC = 𝜂 · 𝑉T · ln (𝐼 f + 1) ; 𝑉T =
0 𝑞 (2)
The VOC depends mainly on the saturation current of the solar cell and the light-generated current. The
saturation current, I0, is a function of the recombination effect on the p-n junction (Eq. 2). Thus, VOC is
the measure of the recombination on the solar cell.
This is the current (ISC) flowing through the device when the voltage is zero. It is the one that would flow
through the equivalent circuit when short-circuited [14]. It is the largest current that could be drawn from
the PV cell. It depends on a number of factors such as the area of the cell, the number of photons or the
light intensity arriving to it, the light spectrum (usually standardized as AM1.5), the optical properties of
absorption and reflection that it may have, as well as on other properties (Eq. 3).
𝑞·𝑉
𝐾 · 𝑇cell
𝐼(𝑉) = 𝐼f − 𝐼D = 𝐼f − 𝐼0· (𝑒 𝑛·𝐾·𝑇𝑐𝑒𝑙𝑙 − 1) ; 𝑖𝑓 𝑉 = 0 → 𝐼SC = 𝐼f = (3)
𝑞
The characteristic IV curve of a solar cell represents the different working points of it [14]. It is the fourth-
quadrant curve of a diode inverted as the cell delivers light-generated power. It presents a single
Maximum Power Point (MPP) that gives the peak power value of the cell. In addition, parameters such
as VOC or ISC can be quantified on it (Fig. 7).
12
Design and simulation of a grid-connected PV system for self-consumption
The fill factor, commonly abbreviated as FF, is a measure of the quality of the PV cell. . It is defined as
the ratio of the maximum power from the PV cell to the product of VOC by ISC, as seen below (Eq. 4).
Open-circuit voltage and short-circuit current are maximum parameters of a solar cell. Nevertheless,
when working at these operating points, the output power equals zero. Therefore, the FF, along with
VOC and ISC determines the performance, i.e. the maximum available power, from a solar cell [14].
𝑉mp · 𝐼mp
𝐹𝐹 = <1 (4)
𝑉OC · 𝐼SC
Graphically, when looking at the IV curve, the FF is an indication of its “squareness” that is, of the area
of the largest rectangle that could fit inside the curve, so the closer to 1 is its value the better.
The efficiency of the cell often gives a reliable idea of their performance, and allows the user to compare
it to another type of cell. The efficiency depends on the spectrum and intensity of the light that arrives
to the cell, and is usually measured under STC [14]. Generally, standard solar cells have an efficiency
under 20%. This is determined as the ratio of the electric output energy to the incident solar energy,
which is calculated as the product of irradiance and surface (Eq. 5):
𝑉mp · 𝐼mp
𝜂= (5)
𝑃solar incident
Characteristic curves are measured under STC, but the truth is that under different conditions and
depending on environmental changes, the curves may vary notoriously [14].
As solar irradiance impacting a PV cell increases, so does proportionally its short-circuit current, whilst
the open-circuit voltage rises as well following a logarithmic function, as seen in its formula. Thus, total
power and the maximum power point obviously increase.
On the other side, a detrimental effect to the performance of a solar cell has been shown when it is
heated. With the rise of temperature the band gap energy of the p-n junction is reduced, so bonding is
weaker and more photons are able to create pairs. While it is true that short circuit current may remain
approximately the same, or even increase its value, the open circuit voltage decreases dramatically,
and therefore so does the total power.
13
Design and simulation of a grid-connected PV system for self-consumption
Sometimes in a structure of interconnected modules it happens to appear losses and malfunctions due
to cells or modules behaving differently from one another under different conditions. For example, the
cells or modules can be shadowed by trees, clouds, dust, etc… Whenever the electrical parameters of
a cell or module are altered in relation to those of other cells or modules, mismatch losses appear. These
mismatch effects cause, in the majority of cases, the module or panel to work with the lowest output in
the series, as explained before. Additionally, this can lead to highly localized energy dissipation, resulting
in local heating that may cause irreversible damage to the devices [14].
The impact the effects may have depend on the type of device (hence their parameters), the electrical
configuration and their operating point. Short-circuit current or open-circuit voltage, commonly causes
the most usual mismatches, although others can happen.
5.1.5.1 Hotspots
Hotspot heating appears as a result of the generation of low current by a single solar cell (maybe due
to shading) in a series connection (Fig. 8). When this occurs, the operating current of the entire string
starts lowering down to the short-circuit current of the shaded cell, and then the overall current suffers
a limitation [14]. Despite that, the extra current produced by the normal operating cells follows a forward
bias through them, but when the string is short circuited, this forward bias can cause a reverse bias due
to a higher voltage production of the properly working cells on the shaded one. Therefore, the whole
capacity of power generation the string has dissipates on that bad cell. This huge dissipation in a local
spot heats the cell, leading to great and destructive damage, such as glass cracking, circuit paths
soldering, cell degradation or melting, and reduction of the cell’s lifetime.
5.1.5.2 Shading
The output power production of a cell is proportional to the irradiance they receive. When shading of a
cell occurs, this output declines proportionally to the amount of shading. As explained before, hotspots
and other defects can appear due to shading [14], when a cell starts acting as a resistive load.
14
Design and simulation of a grid-connected PV system for self-consumption
Thus, it is important to protect the system from these kind of destructive effects by placing diodes in the
circuit that block the current flowing through the shaded devices. When modules are connected in series,
by-pass diodes are installed in parallel, so in case one of the modules is shaded and working as a
resistive load, the current can pass through the diode and not through the module.
If the modules are put in a parallel configuration, like arrays, and one of them is shaded, the Kirchhoff
Laws are contradicted, as all the modules should have the same voltage. In this case, the shaded
module works as a resistive load at a voltage imposed by the other units in an unstable configuration.
In this situation, blocking diodes installed in series with the devices are needed, so they can isolate the
shaded branches (Fig. 9).
Photovoltaic technology has been improving exceptionally in the last decades. Nowadays, scientists
and institutes are putting their minds to the research of new systems, materials, devices and designs
that can enhance the performance of the current technology, whilst reducing its economic impact.
15
Design and simulation of a grid-connected PV system for self-consumption
The different technologies used nowadays are reviewed in the section below, but it is worthy of attention
the fact that still in 2020, Silicon-based solar cells have the largest market share [24] among
semiconductor materials. Nonetheless, other designs are starting to rise up in the market.
It is the first generation of PV technology, yet the most used type in solar panels. Although not obsolete
yet, further refinements have been made on it and the range of technology types existing is nowadays
really wide.
However, Silicon is the most abundant solid element on Earth [25], and about 28% of the Earth’s
composition corresponds to this material. This, added to the fact that its processing and manufacturing
technology is now very mature and widely developed after more than 30 years of use, and considering
its relatively high efficiency and low risk of failure, less than 1%, makes Silicon-based solar cells still the
most attractive, with a market share, of about 87% of PV technologies in 2019.
The main kinds of Silicon-based cells are monocrystalline, polycrystalline and back-contact cells:
● Monocrystalline Silicon: This technology was first used in the earliest generation of
photovoltaics, both in on-grid applications and in stand-alone systems, being the most
commonly used one.
Monocrystalline panels are based on Silicon crystal with a high purity. The Silicon material
presents an ordered and periodic arrangement of the atoms, so that it has a single crystalline
orientation. Thus, all the atoms are placed symmetrically. Through the Czochralski process [26],
single crystals are grown by melting the semiconductor-grade material under a strictly controlled
16
Design and simulation of a grid-connected PV system for self-consumption
temperature gradient, and adding dopants such as phosphorus or boron for converting the
silicon into p-type or n-type as desired, depending on the electronic properties needed.
A Silicon ingot has a cylindrical shape with a diameter of 13 to 21 cm, and can reach up to 200
cm in length. It has a deep blue colour and a distinctive metallic luster. Although some
experiments have shown higher values, their efficiency is considered to be of approximately
17% [27].
The crystalline structure that constitutes these solar cells has different shapes and directions.
Polycrystalline silicon ingots are obtained by melting and casting the material, then allowing it
to solidify in a parallelepiped-shaped cast. Therefore, the thin wafers obtained have a square
section. These types of cells can be easily recognized by their superficial appearance, as their
glass grains and metal flakes are highly visible, due to its heterogeneous structure.
Although laboratory experiments with these cells have shown a maximum efficiency of 22%,
their actual efficiency is in between 12% and 14%, a slightly lower value than that of
monocrystalline cells, yet their cost is as well lower [28].
It is worth mentioning that both mono and polycrystalline cells lately have been converted into
Passive Emitter Rear Contact cells, which means that they have a back surface that reflects
photons back into the cell for a second absorption attempt, enhancing their performance.
● Back contact solar cells: Rear contact solar cells provide a new cell design concept
in which all the front contact grids are moved to the back of the cell, eliminating shading
losses this way, and reducing their contact resistance [29]. Therefore, the cells can be
interconnected easily and placed with no space between them in the panels. This
design increases efficiency and it its mainly used in solar concentrators and industrial
processes. There are three main types of back-contact cells: metal wrap-through
(MWT), emitter wrap-through (EWT), and back-junction (BJ).
This is known as the second generation of PV technology. Thin-film technology came about by trying to
make devices lighter and cheaper in order to cut costs, along with greener and more ecological
processes. By reducing the thickness of a solar cell, its open-circuit voltage rises up as a consequence
of a decrease in the saturation current [30].
17
Design and simulation of a grid-connected PV system for self-consumption
These cells are created by adding one or more thin layers of light-absorbing material to a metal, plastic
or glass backing support. The thickness of the cell is much less than that of conventional cells
(conventional cells can use wafers of 200 µm, while thin-film cells can be of only 1 µm [31]), thus thin-
film cells become flexible and lighter. On the other hand, the manufacturing process and materials used
are cheaper, and the lifetime of the cells is practically identical to the standard Silicon ones.
However, they show less efficiency. Indeed, the smaller thickness results in a decrease in capacity,
which although generally compensated by the use of different materials, does not equal the efficiency
of the common Silicon cells. Despite the fact that laboratory tests have shown quite good maximum
efficiencies, the market share of this technology has followed a slight downward trend in recent years
after a big growth. Additionally, tests and physical evidence have shown that the degradation of these
modules is greater and faster, so additional barriers and protectors are needed to prevent damage
caused by heating, oxidation and moisture.
Figure 11. Percentage of global PV production regarding thin-film technologies (2016) [23]
For its making, the silicon is laid on a transparent support forming a fine layer that work as a cell
presenting a brown and dark ash colour. When exposed to the sunlight, the cells suffer a
degradation caused by the Staebler-Wronski effect [32], lowering their efficiency. In order to
optimize this efficiency, other elements can be added to create variations, such as carbon or
germanium.
18
Design and simulation of a grid-connected PV system for self-consumption
Amorphous silicon cells seem to have a promising future prospect, as this technology enables
cells of such small thickness to be created, combined with easy and cheap manufacturing.
Nonetheless, they have a reduced efficiency, between 6 and 8% in commercially available cells,
although the maximum achieved in a laboratory is around 10% [33].
● Cadmium Telluride (CdTe): These cells are one of the solar technologies with the highest
potential. Since its band gap is almost the ideal (1,5 eV), it has a soaring absorption coefficient,
catching about 90% of the incident photons [34].
CdTe's main advantage lies in its manufacturing process, which is lower in costs than silicon-
based cells, and it is suitable for large-scale applications. Its conductivity can be changed to p-
type or n-type, as it can be doped with impurities. An excess of Cd results in n-type, and an
excess of Te in p-type.
Nevertheless, Cadmium is a toxic element with long-term effects on the environment, and the
dearth of telluride might have a repercussion on the selling cost of the technology. Hence,
measures must be adopted in order to make an appropriate use of it. In terms of efficiency,
laboratory testing has shown values of around 21%, but the maximum efficiency in commercially
available cells is in between 9 and 11% [33].
● Copper Indium Selenide/diSelenide (CIS/CuInSe2): These cells are part of the newest
technology being developed and implemented in the most recent PV panels. In these, the silicon
in standard solar cells is replaced by special alloys, such as copper, indium and selenide. There
also exist CIGS (Copper, Indium, Gallium and Selenide) and CIGSS (Copper, Indium, Gallium,
Selenide and Sulfur) cells [34].
The structure of these cells (Fig. 12) is reminiscent of that of silicon cells, since they are
essentially junctions of two semiconductors. Just as the emitter and the receiver in silicon cells
are made out of this material, the emitter in CIS and CIGS is made out of the union of other
semiconductors. In these cells, that possess outstanding electrical properties due to is ideal
band gap energy, which can be increased by adding Gallium, semiconductor elements with a
high optical absorption coefficient are used. Furthermore, the cells can have very small
thicknesses, of around 2-3 µm, in contrast to the 200 µm of common silicon ones, which results
in a cheaper manufacturing process.
19
Design and simulation of a grid-connected PV system for self-consumption
Figure 12. Microstructure of a CIGS solar cell: Coloured image of cleaved CIGS sample (left),
Schematic of the standard structure of a CIGS solar cell (right) [35]
The constituent chemical elements of them are extremely rare, in particular Se and In. In
addition, some have very high toxicities, which compromises the recycling processes of panels
at the end of their useful life. Moreover, Indium presents a shortage problem that rises up the
price of the cells. CIS and CIGS cells can achieve an efficiency of 15% in their commercial form,
with a maximum laboratory efficiency value of almost 20% [33].
● Dye-sensitized solar cell: This is one of the so-called third generation photovoltaics. Also called
Grätzel solar cells [36], their behaviour is based on a non-galvanic chemical process in which
the chemicals are constantly regenerated. The cells are thin, flexible and transparent. They are
formed by a photosensitive anode, a semiconductor and an electrolyte that regenerates the dye.
This electrolyte can freeze at low temperatures and stop the current generation; That is why
alternative solutions are being researched. By means of using a sensitizer dye composed by
Titanium dioxide nanoparticles, the cells generate electrical current, as this layer of dye absorbs
a wide range of wavelengths. When a photon is absorbed, an electron is injected into the
conduction band of the semiconductor, and there appears a diffusion effect of the particles
creating a forward bias current.
Although the technology is still under development, it has shown efficiencies from 11 to 16%,
while having an easy and inexpensive manufacturing process that makes the Grätzel cells a
strong competitor in mass-production.
● Organic cells: Despite the advances in the field of the solar industry, the cost of PV cell
manufacturing continues to be very high for many applications, especially large-scale ones. The
complicated cell manufacturing process, which requires a hot vacuum environment limits the
production to batches that cut their economic profitability. Organic Photovoltaic cells (OPV) are
a rapidly emerging third generation technology that can be produced in large surfaces at a
20
Design and simulation of a grid-connected PV system for self-consumption
relatively low temperature, both by vacuum or sublimation methods, and also by film-forming
polymers [37]. Plenty of organic materials (molecular or polymeric) can be synthesized for the
absorber and the electron acceptor.
In addition, solar panels composed of OPVs are cheaper, lighter and easier to install. In order
to compete with existing silicon technology and to find new applications, organic solar cells have
had to meet a number of requirements in terms of stability, efficiency and cost Although their
lifespan is generally less than that of the inorganic cells, OPVs improve efficiency, being it
currently around 13% but still have long-term reliability as a significant barrier.
The so-called multijunction cells, or usually tandem cells, are those that combine two different types of
semiconductor materials. This superposition of p-n junctions increases the sensitivity of different
wavelengths and improves performance, since each type of material uses only a part of the
electromagnetic spectrum of solar radiation. Multijunction devices use a high-bandgap top cell that
absorbs the photons with the highest energy, while letting the lower-energy ones make their way to the
next material with a slightly lower bandgap to be absorbed there. By combining two or three types of
materials it is possible to profit of a greater part of the sunlight. With this type of cells, efficiencies of 35%
have been achieved. According to some studies, theoretically, unions of three materials could reach
efficiencies of almost 50% [38].
● Gallium Arsenide (GaAs): The GaAs technology [39] has its production limited by the high
budget of its manufacture and the shortage of material. These kind of cells are mainly used for
space applications, taking profit out of their small thickness and unvarying thermal properties.
Additionally, from the point of view of efficiency, it is the most interesting technology, since it is
among values of 25 to 30%.
5.2 Inverters
Inverters are essential to change the type of output current according to its end use. In the case of
photovoltaic plants or installations, these produce a direct current. Within the installations, distribution is
carried out using DC as well, but when delivered to the grid, it must be in the AC form, so that to transform
it into the alternating current compatible and synchronized with the electrical grid, it is necessary to use
an inverter. In addition, they are equipped with a Maximum Power Point Tracker (MPPT), which
searches for the point at which the output power is maximum, selecting the best pair of voltage and
current (MPP) that is constantly varying due to irradiance and cell temperature. There exist multiple
types of solar inverters [40]:
21
Design and simulation of a grid-connected PV system for self-consumption
Central inverters: Working within a range of 100-1200 kW, they are inverters that merge
several strings together connecting them in parallel and boosting their current and voltage.
These are classified as single-stage inverters, as only a single converter is in charge of the
maximum power point tracking (MPPT), the grid current control and the voltage amplification.
They are used in the system when all the modules perform under the same conditions, and
generally in large PV plants.
String inverters: This is the most used and common type of inverter. As a string is a group of
modules connected in series, each of these strings in a PV installation is assigned a single solar
inverter. As explained, if a module is shadowed, the output of the string is reduced to that
generated by that module, so string inverters are not a good solution whenever the modules are
oriented in different directions, as for instance, on the two sides of a rooftop. They can bear a
power range of 0,4-2 kW and they are the most affordable type of inverter. Their maintenance
tasks are simple, as there is only one section of the circuit to watch over. Batteries can be
charged if connected before the inverter, so they can feed from the direct current supply before
it converts to alternating current.
Microinverters: This kind of inverters is used in the opposite way as string ones. In this case,
a whole string is connected to an inverter, but each of the of the array's PV modules is also
connected to a microinverter, and all these microinverters are connected in parallel creating an
alternating current circuit. In this way, each single PV panel works independently, and thus, if
one of them fails, the rest of the array can proceed with normal operation conditions without
being affected. Shading or different orientations, therefore, won’t be a problem in these
installations. They work within a range of 50 to 400 kW in small PV installations.
Additionally, each microinverter can perform monitoring functions for each individual panel,
detecting problems and solving them. Although grounding is fairly easy as it can be integrated
in the general circuit, this kind of system is much more expensive than the others, and its
maintenance is as well complex, because each inverter is under the panels. Whenever panels
are installed in a way that their racking is not easily accessible, maintenance becomes a
complicated task. Moreover, as the direct current output of the panels is directly converted into
alternating current, there is no option for charging a battery tank.
Multistring inverters: This system is similar to the string inverter configuration. However, each
string is first connected to a DC/DC converter for the MPP tracking and the voltage amplification.
Then, several strings are connected to a usual DC/AC converter or inverter that controls the
grid current. This dual-phase inverter topology is used in small ground PV plants or in medium-
large rooftop panels with strings from 1,5 to 6 kW.
22
Design and simulation of a grid-connected PV system for self-consumption
Figure 13. Inverter typologies: a) Central inverter, b) String inverter, c) Microinverter, d) Multistring inverter [85]
As long as the voltage of an array exceeds the maximum limit of the inverter, the production will be
interrupted by the inverter’s output and, in addition, as the inverter is working outside its nominal range,
its lifetime can be substantially reduced. On the other hand, if the array voltage is under the chosen
inverter’s minimum limit, the inverter will not work until the starting voltage has been reached. Therefore,
the entire PV system will be underproducing.
23
Design and simulation of a grid-connected PV system for self-consumption
The European Union established some standard requirements for the member countries in regard to
electrical grid in the document Commission Regulation (EU) 2016/631: Establishing a network code on
requirements for grid connection of generators [41]. As stated in the Article 1 of the document, it is “a
network code which lays down the requirements for grid connection of power-generating facilities,
namely synchronous power-generating modules, power park modules and offshore power park
modules, to the interconnected system. It, therefore, helps to ensure fair conditions of competition in the
internal electricity market, to ensure system security and the integration of renewable electricity sources,
and to facilitate Union-wide trade in electricity” [41, p. 4].
According to that same document, a generating installation with a capacity within a range of 1 MW and
50 MW is considered a type B installation in Continental Europe (Tab. 1).
Table 1. Limits for thresholds for type B,C and D power-generating modules [41]
For this project, as it will be seen in the next sections, the installation capacity will be in between these
values. In articles 13 and 14 [41, pp. 14-18] there appear stated the general requirements for type B
installations.
The installation has to work within the frequency range specified in the document, and ensure a stability
in its operation.
24
Design and simulation of a grid-connected PV system for self-consumption
Table 2. Minimum time periods for which a power-generating module has to be capable of operating
on different frequencies, deviating from a nominal value, without disconnecting from the network [41]
To avoid complications on inhabited areas, in the aforementioned document some regulations can be
found [41, pp. 15-16]:
The installation shall activate the provision of active power frequency response at a specified
frequency threshold and droop settings, decided by the TSO
The delay at the beginning of the power frequency response must be as short as possible. If
the delay lasts longer than two seconds, technical evidence must be provided
If minimum regulating level is ever reached, the installation module should either:
o Keep operating at that level
o Diminish the active power output
The installation should operate with stability during LFSM-O operation. Whenever LFSM-O is
active, its setpoint will prevail over any other active one.
25
Design and simulation of a grid-connected PV system for self-consumption
Figure 14. Active power frequency response capability of power-generating modules in LFSM-O [41]
In the figure above (Fig. 14), extracted from the same document [41, p. 16], ΔΡ is the representation of
the change in the active power produced by the installation. On the other hand, fn equals the network’s
nominal frequency (50 Hz), and Δf its deviation. Whenever in an overfrequency Δf is above Δf1, the
power-generating module needs to create a negative active power output variation, defined by S2.
Active power output shall remain constant despite of variations in frequency. However, there is a value
range within for this output, specified by the TSO, regarding an admissible active power reduction from
maximum output with falling frequency:
The reduction must specify the ambient conditions applicable, as well as take account of the technical
capabilities of power-generating modules.
26
Design and simulation of a grid-connected PV system for self-consumption
Figure 15. Maximum power capability reduction with falling frequency [41]
Cessation of the active power output shall be done within five seconds after receiving instruction at the
input port, which the module shall be equipped with. The TSO has the right to put requirements for the
equipment in order to make a remote operation possible.
The operator of the system is able to define the potential of an installation to produce reactive
power, whenever it has a synchronous operation [41, p. 32].
The installation must have an excitation control system that creates a stable voltage for the
alternator terminal [41, p. 32].
The European Comission [41, p. 17] notes that “automatic connection is allowed unless it is specified
by the system operator”. The requirements set by the TSO for an installation to be able to connect on
its own to the grid contemplate:
The frequency range limits amongst which the system can automatically connect
27
Design and simulation of a grid-connected PV system for self-consumption
In concern of the fault-ride-through capability of the installation, according to Article 14 in the European
Comission document [41, p. 18]:
The TSO should define a profile of voltage and time for fault situations, in which it can be shown
how the installation can stay connected and operating with stability after there has been a power
fault in the transmission system.
This profile expresses a minimum limit that shall not be underpassed by the phase-to-phase
voltages, whenever a symmetrical fault occurs. It is plotted related to time, and it is defined by
the TSO according to the parameters and ranges specified in the table below (Tab. 3).
Table 3. Parameters for fault ride-through capability of synchronous power-generating modules [41]
It is a duty of the TSO to define pre and post-fault requirements for ride-through capability
regarding:
o Minimum short-circuit capacity calculations
o Operating points for active and reactive power before faults
28
Design and simulation of a grid-connected PV system for self-consumption
In the document [41, p. 19] it can be noted that in the diagram (Fig. 16) shown:
“the minimum value of voltage is plotted against time as a percentage of its actual value 1 p.u. value
before, during and after a fault. Being Uret the retained voltage at the connection point during a fault,
and tclear the instant when the fault has been cleared. Urec1, Urec2, trec1, trec2 and trec3 specify certain
points of lower limits of voltage recovery after fault clearance”.
The installation must be able to keep connected and continuously and stably operating when
the actual course of the phase-to-phase voltages during a symmetrical fault remains over the
lower limit specified before, except if disconnection from the network is needed by the protection
scheme. Protection schemes and settings for internal electrical faults must not jeopardise fault-
ridethrough performance.
Protection against undervoltage situations must be installed by the facility, taking into account
the technical capability of the installation. It the system operator needs other settings, they
should be proven and justified by the owner.
The installations must comply with the following according to the restoration capability of the system:
29
Design and simulation of a grid-connected PV system for self-consumption
The TSO has to specify the conditions under which the installation can connect again to the
network after an incidental disconnection.
Installation of automatic systems for the reconnection must be authorised by the relevant system
operator.
Any setting or operation essential for the protection of the grid must be defined by the system
operator. These measures taken to fix internal electrical faults must not threaten the generating
performance of the installation.
System security, mitigating damages on the installation, as well as the health and safety of staff
and public must be considered, so electrical protection takes precedence over operational
controls.
Changes made on the schemes and protections must always be discussed and acknowledged
by the system operator and the facility owner before they are implemented.
30
Design and simulation of a grid-connected PV system for self-consumption
In Spain, the only Transmission System Operator (TSO) is Red Eléctrica de España (REE), and its
publications specify the requirements for the operation of electrical systems in relation to power
generating installations. The Spanish legislature on photovoltaic installations is extensive, detailed and
complex. Naturally, depending on the type of installation, the existing regulations in force impose some
different rights and obligations for each type. As this thesis is solely considering a self-consumption PV
system, the grid code and other regulations shown do not apply to off-grid PV system. Generally, the
main goal of on-grid PV systems is to inject into the grid the maximum surplus of electrical energy they
can produce from sunlight, so they are dimensioned with respect to economic profitability.
Although the so-called “Sun tax” has been recently abolished in the country, numerous rules apply to
on-grid photovoltaic systems, in terms of design, production, distribution, supply and other technical
aspects. The main decrees and laws concerning administrative and economic requirements are the
following (for further details, the reader is referred to Boletín Oficial del Estado [42]):
● RD 1047/2013: Provides calculation methodology for the economic retribution for the
transportation of electric energy.
● RD 15/2018: Provides urgent measures for energetic transition to more sustainable systems
and for consumer safety.
● Law 24/2013: The Electrical System Law (LSE) ensures a supply guarantee, self-consumption,
electrical planification, energy exchange, tariffs and others.
However, the technical details on the design, installation, parameter limits and integration of all the new
installations wanting to access and to connect to the main grid, as well as modifying the existing power
systems are collected in the new version of the document Procedimientos de Operación [43] (operating
procedures) in the articles 12.1 (“Solicitudes de acceso para la conexión de nuevas instalaciones a la
red de transporte”), 12.2 (“Instalaciones conectadas a la red de transporte peninsular: requisitos
mínimos de diseño y equipamiento”) and 1.4 (“Condiciones de entrega de la energía en los puntos
frontera de la red gestionada por el operador del sistema”).
31
Design and simulation of a grid-connected PV system for self-consumption
This concept refers to the characteristic parameters of the voltage wave. The most significant ones that
may influence the product quality are [43, pp. 5-9]:
Faults and ride-throughs: It sets the sudden voltage drop the system may experience, at a
value in between 90% and 1% of the nominal voltage value. This fault by definition might last
10 ms to 1 minute, followed by a ride-through and restoration and recovery of voltage. Its depth
is equal to the difference between the effective voltage during the fault and the nominal value.
Power installations must be able to withstand these failures without being damaged or
disconnected.
Voltage imbalance: It corresponds to a state in which the effective voltage values of each
phase or the phase angles between consecutive phases in a three-phase system are not the
same.
Harmonics: Defined as the sinusoidal voltage whose oscillating frequency is an integral multiple
of the supply voltage (fundamental).
Flicker: Voltage fluctuations cause variations in the luminance of the lights. This results in a
visual effect called flicker, which is a natural effect associated to a visual sensation of instability
due to a luminous stimulus whose luminosity changes through time.
The power exchanged between the transportation grid and the installations shall never exceed the
nominal power indicated by the TSO in the established access documentation [43, p. 9]. The power
value will be limited by means of physical devices or special procedures so as not to surpass the contract
values. In the event that these devices may potentially interfere with the safety of the system, the TSO
has the ability to notify of the programmed disconnection of the installation.
Limits for electromagnetic disturbances emitted by all the devices, systems and components of an
installation connected to the same node of the transmission network have been collected in the design
requirements [43, pp. 7-8]. Emission limits are established for points with a voltage higher than 220 kV
and all generation installations connected to the grid.
Voltage imbalance: Emitters of these kind of perturbations shall never exceed the following
total limits for voltage imbalance on each node of the transmission network:
32
Design and simulation of a grid-connected PV system for self-consumption
Harmonics: In order not to surpass the planification levels of the TSO, the harmonic voltage
shall comply with the following limits on each node of the transmission network (Tab. 4):
Table 4. Limits on harmonic voltage for each node of the network [43]
Odd harmonics
Even harmonics
Non-multiple of 3 Multiple of 3
Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic
order (n) tension (%) order (n) tension (%) order (n) tension (%)
5 1,8 3 1,8 2 1
7 1,8 9 0,9 4 0,7
11 1,3 15 0,3 6 0,3
13 1,3 21 0,2 8 0,3
17 10
17 ≤ n ≤ 49 1,1 · 21 ≤ n ≤ 45 0,2 10 ≤ n ≤ 50 0,17 · + 0,14
𝑛 𝑛
TOTAL HARMONIC DISTORTION RATE (THD) 3,00%
Flicker: The following flicker emission limits for each node of the transmission network, taking
into account the transfer coefficient from HV to LV, so they ought to be compared with the HV
flicker:
They correspond to the maximum level of the electromagnetic disturbances for which the grid has been
designed. The planification levels are a measure of quality that ensures the electromagnetic
compatibility of the system [43, pp. 5-6].
o Voltage imbalance: The imbalance degree (μ) has some planification levels in form of
percentage ratio. Dividing the reverse sequence component (vector magnitude) by the
direct sequence component (vector magnitude) of the voltage, values are obtained. These
are a function of the duration of the voltage imbalance.
33
Design and simulation of a grid-connected PV system for self-consumption
Odd harmonics
Even harmonics
Non-multiple of 3 Multiple of 3
Harmonic Harmonic Harmonic Harmonic Harmonic Harmonic
order (n) tension (%) order (n) tension (%) order (n) tension (%)
5 2 3 2 2 1
7 2 9 1 4 0,8
11 1,5 15 0,3 6 0,4
13 1,5 21 0,2 8 0,4
17 10
17 ≤ n ≤ 49 1,2 · 21 ≤ n ≤ 45 0,2 10 ≤ n ≤ 50 0,19 · + 0,16
𝑛 𝑛
TOTAL HARMONIC DISTORTION RATE (THD) 3,00%
o Flicker: According to the IEC in “Assessment of emission limits for the connection of
fluctuating installations to MV, HV and EHV power systems” the following levels have been
defined for the transmission grid, taking into account the transfer coefficient from HV to LV,
so they ought to be compared with the HV flicker:
All generation units must support in permanent operation a 5% reverse bias component of the nominal
current.
The nominal frequency of the Spanish electric system at which the electricity is exchanged is 50 Hz.
Any variations between 49,85 Hz and 50,15 Hz are considered as normal.
There should always exist a double safety system on every device and component of the installation,
regardless of its type (L, T1, T2, or combinations). The protection system must follow the requirements
specified in the REE document “Criterios Generales de Protección de los Sistemas Eléctricos Insulares
y Extrapeninsulares” [44].
34
Design and simulation of a grid-connected PV system for self-consumption
According to the REE documents [45, pp. 12-15], the connection between a power system and the grid
can be done in different ways:
The following figures represent these basic configurations with their parts, borders and components.
35
Design and simulation of a grid-connected PV system for self-consumption
As stated in the objectives of this study, the designed PV system would be located in Spain, as it is one
of the countries in Europe with the greatest solar potential, due to its geographical situation. However,
in order to define the exact location of the power installation, it would be interesting to know the number
of PV power plants that are currently active in the country and their location (Fig. 18), to see if there is
a region with a high solar potential being currently unused.
Additionally, taking into account the average solar irradiance map shown in the Código Técnico de
Edificación (CTE) [47], a regulating document that is an equivalent to a technical building code, the
different zones in Spain would be classified in the following way (Fig. 19):
36
Design and simulation of a grid-connected PV system for self-consumption
Figure 19. CTE map of Spain with classified zones regarding the incident irradiance [47]
When comparing and studying both maps simultaneously, it can be seen that southern Spain, and
mainly the autonomous community of Andalucía, is fully equipped with photovoltaic power plants, due
to its high levels of irradiation. There is also a huge amount of active PV plants in Murcia and
Extremadura, such as the power plant of Mula, with an installed power capacity of 493,74 MW. However,
the situation in Catalonia is striking, since its southwest region is classified as type IV, yet there is only
one PV plant in Flix, Tarragona, with an installed capacity of 11 MW approximately. Therefore, Catalonia
would be a compelling place for the new PV power installation designed in this thesis, despite it will be
a self-consumption one.
The next step in finding the geographical location of the plant is considering a more detailed map of the
solar irradiation (Fig. 20), where it is possible to analyse Catalonia in further detailed. Hence, it can be
observed that the territory around the province of Lleida receives a daily global irradiance of 4,9 kWh/m2
[48].
37
Design and simulation of a grid-connected PV system for self-consumption
In this specific province region, it is seen that the town of Linyola has no photovoltaic power plant in the
nearest surroundings that could supply its energy demand, only a thermosolar plant, although the
surrounding terrain is wide, flat and without populated areas that could interfere with the construction of
a power plant, as Lleida is one of the less populated provinces in Catalonia. Nonetheless, the aim of the
project is to install PV modules on a building, preferably on its rooftop, located on the suburban area.
Linyola is placed at latitude 41°42′44″N and longitude 0°54′20″E (Fig. 21) and at 248 metres above sea
level. These details make the location a substantial candidate for the project.
38
Design and simulation of a grid-connected PV system for self-consumption
Still, it is necessary to know the monthly evolution of the irradiance data, as well as the hours of sunlight
in the region. Irradiance and other meteorological data are obtained for Linyola, as it may be
representative for all the terrain of the nearby surroundings. The data shown below is the most recent
found in Meteonorm 7.3, a meteorological database containing worldwide weather data (1991-2010),
and from the Photovoltaic Geographical Information System, a tool developed by the European
Comission (2016).
Figure 22. Maximum and minimum daily temperatures for Linyola [49]
39
Design and simulation of a grid-connected PV system for self-consumption
Figure 24. Monthly solar irradiation estimates for Linyola (2016) [50]
January 54 28 72 9,2 3
February 87 30 132 10,4 3,4
March 139 44 181 13 3,5
April 172 62 182 15,2 3,5
May 207 76 202 18,8 3,1
Where:
Gh: Global Horizontal Irradiation (GHI) [kWh/m2]
Dh: Diffuse Radiation [kWh/m 2]
Bn: Direct Normal Radiation [kWh/m2]
40
Design and simulation of a grid-connected PV system for self-consumption
related to the installation cost. As said, the ideal terrain in the study location should be flat or with a slight
south-facing slope, with no urbanistic constructions or with the presence of big mountains around that
could create undesired shading. The selected area is considered to meet these requirements.
The soil in Linyola is assumed suitable for the study, regarding its dryness, resistivity, ability to bear big
loads, chemical properties and presence of obstructions, as generally the ground layer in the region is
really thick and steady. Information about other aspects such as wind speed, average temperature,
snow risk, rainfalls, flooding risk, etc… need to be collected too so it can be analysed whether they are
influential to the performance of the plant or not. Extreme temperatures can drastically decrease the
efficiency of the cells. High wind speeds could damage the technology and the components used.
Rainwater, snow and dust could lower seasonally the energy production of the installation, and also
cause damages to the structures, increasing the maintenance cost. However, the chosen location is not
under extreme weather conditions, so every parameter is assumed to not affect the performance of the
plant.
The building of study for this project is a residential household placed in Linyola. The exact location of
the house is.
The terrain, as seen in the picture below (Fig. 25), is placed in a corner formed by the crossing of streets.
The measured area of the whole parcel, including the garden space, consists of 488,5 m 2. The front
facade of the building is oriented almost towards the northern direction, with an angle of 2,2º with respect
to it (87,8º from the eastern direction).
41
Design and simulation of a grid-connected PV system for self-consumption
Figure 25. Area of the terrain where building studied is located [51]
The house has two floors and two balconies, which represent a useless space in terms of installing a
PV system for the energetic supply of the building. Nonetheless, the rooftop of the building is a flat and
wide space that is totally suitable for the installation of PV modules. This open-air surface is shown,
marked in green, in the image below (Fig. 26). It provides 161,66 m2 of available space for the PV
infrastructure.
Figure 26. Available and unavailable areas on the building for the placement of PV modules [51]
42
Design and simulation of a grid-connected PV system for self-consumption
Therefore, this area will be studied, and some module layouts displayed and simulated in order to find
the optimal that can cover the demand of the household.
Load profiles represent the measurement of the electrical demand throughout time. When designing a
self-consumption system, it is important to know the load profiles of the user in order to size it and
calculate some parameters, such as the efficiency or the degree of autonomy of the installation.
Additionally, these profiles give information about the peaks and valleys of the load.
The load profile will always depend on the type of user, the season, the local holidays, etc… Thus,
defining the load profile data is crucial for calculating and making an evaluation of equipment needs,
maintenance and upgrades, as well as knowing when the system can supply the user or when it is
unable to do so.
For the chosen building, a first load profile is going to be created. The household is considered to shelter
a family with two children in school age, and in which both of the adult parents have a normal day job.
This means that this house will most likely present peaks in the morning and afternoon, whilst during
the working hours nobody will be at home, and only standby consumption is going to be reflected on the
profile.
The vacation period is considered to be of 27 days between the 1 st and the 28th of August for all the
family members, being this period one with the family being absent from the house and with all the
electrical devices turned off. Nonetheless, an assumption is made: some devices are still turned on and
in standby mode because the family does not unplug them all. Hence, some energy use is still present
on the load profile.
The rest of holidays, like Christmas or Easter (plus taking into account all the holidays of the Spanish
calendar), are spent at home with the energy consumption peaks this fact represents.
Moreover, a usual route has been added to define a way between the house and the workplace. Two
means of transport have been decided for the transportation of the adults: one car usually running at an
average speed of 50 km/h (which travels a 5 km route to the workplace in an urban area) and a fast car
running at an average speed of 70 km/h (making a 30 km route to the second workplace). Both of them,
assumed electric cars, can be charged at a maximum power of 22 kW. However, the charging station
installed at the household is only able to give an output charging power of 3,7 kW. This domestic
charging station is considered to have a dynamic control of the power load, this meaning that if the
household’s consumption rises, the power demanded by the electric car charging at that moment
diminishes in order not to surpass the contracted power.
Given that the cars are used during the day, the charge is going to be made either after the working time
or at night. The load profile for the charging cars performing as loads can be seen in Figure 27:
43
Design and simulation of a grid-connected PV system for self-consumption
Weekday [W]
2000
1000
0
2000
Saturday [W]
1000
0
2000
Sunday [W]
1000
0
00:00 06:00 12:00 18:00 00:00
Figure 27. Load profiles of the cars for weekdays and weekends [52]
On the other hand, a list of activities, devices used, personal needs and illness periods is defined for
each family member, so individual and collective consumption can be calculated separately, although
the total data values are the ones to be used for an accurate recording of the load profile for the
household. The amount of time spent for each action by the members is also specified, as in Figure 28:
44
Design and simulation of a grid-connected PV system for self-consumption
100
115701 min
111021 min
Media use
Time in percent [%]
Media use
(22,0%)
(21,1%)
202600 min
60
(38,4%)
Sleep
173636 min
171570 min
(32,9%)
(32,6%)
Sleep
Sleep
20
Figure 28. Time distribution for daily activities for each member [52]
The activities reviewed include basic domestic chores, like washing, cooking, drying, cooling or using
the lights or the bathroom, as well as other spare time actions, such as watching TV, playing instruments
or using a computer. An example of device profiles used for each chore is shown in Figure 29 for a
normal weekday.
Then, specific device models are introduced in the load profile so a power value can be registered and
the duration curves can be drawn, so an overview of power consumption can be given, as seen in Figure
30.
The computation of the load profile is made in time steps of 15 minutes throughout a whole year, from
January 1st to December 31st. The load profile data created is then going to be introduced into the
simulation software in CSV format to calculate the PV supply to the home. The key graph is shown in
Figure 31, where an average daily curve is shown for different seasons and split by weekdays, Saturdays
and Sundays.
45
Design and simulation of a grid-connected PV system for self-consumption
5
Electricity [kW]
0
00:00 06:00 12:00 18:00 00:00
12
10
Electricity [kW]
0
0 50 100 150 200 250 300 350 400 450 500
Time step (·103)
Figure 30. Duration curves for the devices on the household [52]
46
Design and simulation of a grid-connected PV system for self-consumption
Weekday [W]
2000
1000
0
2000
Saturday [W]
1000
0
2000
Sunday [W]
1000
0
00:00 06:00 12:00 18:00 00:00
Figure 31. Load profile of the household for weekdays and weekends [52]
It can be noticed that the biggest peak for all four seasons graphed is located in the range time between
18 p.m. and 1 a.m. A summed up profile of the energy consumption during the whole year can also be
observed in Figure 32:
12
10
Electricity [kW]
0
0 50 100 150 200 250 300 350 400 450 500
47
Design and simulation of a grid-connected PV system for self-consumption
After running the simulations for the PV system, this load profile will be analysed using the optimal
technology configuration and module layout previously found. The study of the suitability of the PV
system for supplying the installation of the electric car charger in the household will be carried out too.
Before starting any calculations for the sizing of the PV system it is essential to choose which kind of
devices are going to be implemented on it. Making a wise choice in terms of technology is going to be
an essential factor in order to reduce costs and ensure the lifetime of the building plant.
8.4.1 PV modules
When choosing solar modules, it is important to take into account some guidelines and criteria in order
to make the most out of their performance. The most important parameters for the choice are [53]:
Solar module type: As explained in former sections, the materials used for the cells have an
essential role in the behaviour of the module’s performance. Each way of production and
working principle change completely the output of each kind of panel.
Efficiency of the module: It is representative of the amount of solar energy that a module can
transform into usable electricity. Therefore, it is one of the most important parameters to bear
in mind.
Wiring and busing: Heat losses may happen excessively depending on how the mounting of
wires and buses is done.
Power rating: This is the amount of direct current the module can produce under Standard Test
Conditions.
Temperature coefficient: Measures how the power output, the open-circuit voltage and the
short-circuit current values change with any variations in the temperature of the solar cell. The
temperature coefficient is a percentage of that change expressed in (%/ºC). All three variables
of a module are inversely proportional to the temperature. The less sensitive the temperature
coefficient, the longer the module will last.
Power tolerance: Measures a range (with an upper limit as positive tolerance and a lower limit
as negative tolerance) within the electrical power output can have a value, higher or lower than
its nominal rating.
48
Design and simulation of a grid-connected PV system for self-consumption
Module warranty: It gives an idea of the quality of the module. If a sudden drawback takes
place after the installation of the module the manufacturing company shall take care of it and
provide the necessary service.
Durability: A module’s durability is a measure of the resistance of the module to the damage
that time may cause. It is important to check the encapsulating material, the seals, and the
connectors and back sheets. The International Electrotechnical Commission sets the standard
in the IEC 61215, testing the modules under stress conditions that simulate the outdoor
circumstances that they will face during their lifetime.
Quality: The quality check is done when the standard ISO 9000 is met, meaning that a certified
manufacturer has developed the product.
One model of PV module has been chosen for this study. It is a CdTe panel (FS-6450) made by
FirstSolar, one of the biggest module manufacturers in the US. It is built with up to 264 thin-film cells,
with a rated power of approximately 400 Wp at Normal Module Operating Temperature (NMOT), and
450 Wp at STC, and it presents an efficiency of 18,2%. The product has a lifetime warranty of 25 years
with a power output of 86%. More information can be found in the table below (Tab. 7) and in the
attached datasheets in the Appendix 15.1.1.
Ratings at NOCT (Cell temp of 45ºC, 800 W/m2, 20ºC air temp, AM1.5, 1 m/s wind speed)
Nominal power PMAX (W) 339,9
Voltage at PMAX VMAX (V) 175,2
Current at PMAX IMAX (A) 1,94
Open Circuit Voltage VOC (V) 208,8
Short Circuit Current ISC (A) 2,07
49
Design and simulation of a grid-connected PV system for self-consumption
The inverter selected for the project is one manufactured by the Chinese company SofarSolar. The
model, a central inverter compliant with the Spanish grid regulations, is the SOFAR 12KTL-X, which has
two independent MPPT. With an efficiency of 98,3% and a total harmonic distortion of less than 3%, it
can provide a rated power output of 12 kW. More data than the shown below (Tab. 8) can be checked
in the Appendix 15.1.2.
Output (AC)
THDi < 3%
Power factor 1 (Adjustable ± 0,8)
50
Design and simulation of a grid-connected PV system for self-consumption
Depending on the environment conditions, being the air temperature a crucial factor on it, the nominal
AC active power generated, in this case 12 kVA, may vary. Regarding the standard conditions, as well
as the power factor (𝑐𝑜𝑠𝜑) and the apparent nominal output power of this model of inverter, the active
power produced can be easily calculated with the formula below (Eq. 6):
𝑃 = 𝑆 · cos 𝜑 (6)
In which:
P = AC active power
S = Apparent power of the inverter
𝑐𝑜𝑠𝜑 = Power factor
𝑃 = 12 𝑘𝑉𝐴 · 1 = 12 𝑘𝑊
On the other hand, the DC power injected into the inverter in order to provide the expected AC output is
depending on the efficiency of the device (Eq. 7). Therefore:
𝑃AC
𝑃DC = (7)
𝜂
In which:
PDC: DC input power of inverter
PAC: AC active power
𝜂: Inverter efficiency
As the maximum efficiency, according to the inverter’s datasheet, has a value of 98,3%:
51
Design and simulation of a grid-connected PV system for self-consumption
As the open-circuit voltage diminishes with the increase of the solar cell temperature, it is interesting to
consider the lowest temperature in the selected location, in order to calculate the maximum open circuit
voltage that can be reached by the module at that temperature value (Eq. 8).
Where:
VOC: Maximum open-circuit voltage
VOC, STC: Open-circuit voltage under STC
λ: Temperature coefficient for VOC
TCell: Cell temperature, corresponding to the minimum temperature in the location
The coldest temperature registered in the place of study is -1,98 ºC in the last 20 years of record [57].
Hence, for the selected PV modules:
CdTe (FS-6450):
52
Design and simulation of a grid-connected PV system for self-consumption
On the opposite, the minimum voltage on the PV module is calculated taking into account the highest
temperature value on the location. Analogously, the calculations should be made with 34,6ºC, being that
the temperature peak in the last 20 years [57]. However, the datasheet considers the module operating
range to be between -40 ºC and 85 ºC for the model. Therefore, the formulas (Eq. 9) will apply the 85 ºC
value:
Where:
VMPP: Minimum MPP module voltage
VMPP, STC: Module’s voltage at the maximum power point
λ: Temperature coefficient for VSC
TCell: Cell temperature, corresponding to the maximum operating temperature of the module
CdTe (FS-6450):
The current in a PV module is also dependant on temperature, although not as much as voltage. It
slightly rises when the temperature of the module does so. In consequence, in order to know the
maximum current, it should be considered the maximum temperature value of the site. Nonetheless,
following the prior methodology, the maximum operating temperature will be used (Eq. 10).
Where:
ISC: Maximum short-circuit current
ISC, STC: Short-circuit current under STC
σ: Temperature coefficient for Isc
TCell: Cell temperature, corresponding to the maximum temperature in the location
53
Design and simulation of a grid-connected PV system for self-consumption
CdTe (FS-6450):
In this case, the inverter maximum input voltage limits the amount of modules that can be connected in
series on a string. The formula below (Eq. 11) shows the calculation of the number of panels:
𝑉𝑖𝑛𝑝𝑢𝑡
𝑛MAX ≤ (11)
𝑉max 𝑚𝑜𝑑
Where:
nMAX: Maximum number of modules on a string.
Vinput: Maximum input voltage of the inverter
Vmax mod: Maximum module voltage
CdTe (FS-6450):
960 𝑉
𝑛MAX ≤ ≤ 4,04 ~ 4 𝑚𝑜𝑑𝑢𝑙𝑒𝑠
237,8 𝑉
The other way around, it is important to know the lower limit of modules that can be connected to the
string (Eq. 12), in order to achieve the minimum input voltage of the inverter and minimize the losses.
Where:
nMIN: Minimum number of modules on a string.
Vmin MPP input: Minimum mpp voltage of the inverter
Vmin mod: Minimum module voltage
54
Design and simulation of a grid-connected PV system for self-consumption
CdTe (FS-6450):
160 𝑉
𝑛MIN ≤ ≤ 1,03 ~1 𝑚𝑜𝑑𝑢𝑙𝑒
155, 41 𝑉
The chosen number of modules per string is the maximum allowed at first instance in order to calculate
the maximum and minimum string voltages. Later on, the exact number of modules needed will be
decided, but for now the use of the maximum amount of PV modules per string is considered in order
to have an idea of the voltage threshold. However, the maximum and minimum voltage values must be
in between the inverter’s voltage range. They are calculated by the following method (Eq. 13, Eq. 14):
Where:
Vmax: Maximum voltage per string
Vmin: Minimum voltage per string
n: Number of modules per string
Vmax mod: Maximum PV module Voltage
Vmin mod: Minimum PV module Voltage
CdTe (FS-6450):
𝑉𝑚𝑎𝑥 𝑠𝑡𝑟 = 4 · 237,8 𝑉 = 951,2 𝑉
𝑉𝑚𝑖𝑛 𝑠𝑡𝑟 = 4 · 155,41 = 621,64 𝑉
These values are comprised in between the MPP voltage range of the inverter, from 160 V to 960 V
(Appendix 15.1.2). This would allow in reality a minimum of two modules per string, which would result
in a maximum voltage of 475,6 V and a minimum voltage of 310,82 V for each one.
The exact number of PV modules will be decided during the modelling process regarding the area
available on the rooftop, as the maximum amount of panels will be installed. Other factors such as row
spacing and shading will be taken into account.
55
Design and simulation of a grid-connected PV system for self-consumption
It is possible to make a rough estimation of the energy output that could be obtained out of the PV
system installed on the building rooftop [58]. Later on, however, this value is going to be compared and
substituted with the highly accurate one from the simulation software, but at first instance it allows to
foresee an idea of the performance of the setup. The calculation is done using the formula below (Eq.
15):
In which:
The Ground Coverage Ratio (Eq. 16), or GCR, is the ratio between the area covered by the PV modules
and the total ground area where the modules are placed [59].
𝑃𝑉 𝑚𝑜𝑑𝑢𝑙𝑒𝑠 𝑎𝑟𝑒𝑎
𝐺𝐶𝑅 = (16)
𝐺𝑟𝑜𝑢𝑛𝑑 𝑎𝑟𝑒𝑎 𝑜𝑓 𝑡ℎ𝑒 𝑎𝑟𝑟𝑎𝑦
In a fixed structure module system (as the one usually installed on a rooftop), if the tilt angle is increased,
less area is covering the ground in an overhead projected view, so the GCR decreases (Fig. 34).
Additionally, inter-row shading rises proportionally to the tilt angle, so if the modules are more tilted,
more space between rows needs to be implemented to avoid it.
56
Design and simulation of a grid-connected PV system for self-consumption
Figure 34. Relation between GCR and tilt angle of the PV modules [59]
This ratio is always below 1, and it usually takes values around 30 and 70%. In this approximate
calculation case, a 0.3 coefficient is going to be used, along with an efficiency of 20% for the whole
system. The estimation of the energy is then made with the yearly irradiation mean value to the area.
The sun radiation on the modules shown is also an estimation calculated from the GCR, and considering
these panels are ideal (Tab. 10).
Irradiation Available roof area PV area Sun radiation on modules Energy output
Month
[kWh/m2] [m2] [m2] [MWh] [MWh]
57
Design and simulation of a grid-connected PV system for self-consumption
9.1 Software
In order to model, simulate and analyse the system and its performance, the software PVsyst [60] is
going to be used in this project. This software allows to define and size a PV installation (regardless of
it being a stand-alone system, an on-grid one or a DC-grid system), whilst calculating and analysing its
behavioural data. It enables tools such as 3D shading simulation, meteorological and irradiation models,
a wide database of the technology available with their parameters, ageing simulation or, for instance,
design and optimization of storage systems. For a detailed study, it is necessary to know some data for
the design:
Geographical information
Irradiation and meteorological data
Technology selection of PV modules and inverters
Available roof area or output power of the system
User’s needs or load profiles
3D model of the building and surrounding elements
Orientation and tilt angle of the PV modules
System’s losses
Various simulations will be run so they can be compared, hence the system design can sequentially be
optimized. Results on the total energy output and losses will be provided by the software, as well as an
economic assessment with prices, energy costs and profitability.
The design process and implementation of the system into PVsyst requires entering data and defining
plenty of parameters in order to create a precise, valid and detailed grid-connected system. The idea of
installing solar panels on a household is to be able to cover its demand whenever it is possible, but
without the use of storage systems, so the excess of energy can be directly injected and sold into the
grid, or otherwise, the lack of it can be extracted from it. Hereunder are stated and explained the various
steps followed for the whole definition of the installation, right before the simulations can be run.
As stated before, meteorological data is key to an accurate simulation of the PV system. As the location
of the building is not on the software’s database, a Meteo file for Linyola (Fig. 35) is created using the
58
Design and simulation of a grid-connected PV system for self-consumption
latitude and longitude of the place, and irradiance and temperature data are imported from Meteonorm
7.2.
As explained in sections above (Ch. 8.4), the used modules are the First Solar FS-6450 with a peak
power of 450 Wp, and an inverter made by the manufacturer SofarSolar, the SOFAR 12000TL-X. This
inverter has an operating voltage of 160-960 V and a global power of 12kW, which allows the system to
connect in series up to 4 modules. At first instance, 8 strings are going to be implemented, as the
maximum space on the rooftop grants the installation of 31 panels, which represent an active area of
78,7 m2.
Later on, should be modified this layout on other scenarios, it will be noted. However, the technology
used is going to be implemented in all the simulation scenarios, as the aim this project is not based on
comparing technology, but to compare layouts, whilst trying a new module technology apart from the
usual Silicon-based panels.
59
Design and simulation of a grid-connected PV system for self-consumption
The orientation and tilt angle of the PV modules must be set in order to get the maximum energy output.
In the study case, fixed modules are used due to economic reasons and an ease on maintenance duties.
Moreover, as it is a domestic rooftop PV system, the installation of tracking systems would not be
amortized in a short period of time.
Therefore, given a fixed structure for the panels, their tilt angle and azimuth orientation shall be defined.
For that aim, and according to the PVGIS tools of the European Commission, the optimal angles for the
chosen location should be 37º for a fixed tilt angle β throughout the whole year, and 1º for the azimuth
angle.
Other approaches [61] propose different means of calculation, as for example the formula shown below
(Eq. 17):
60
Design and simulation of a grid-connected PV system for self-consumption
Figure 37. Tilt angle and module orientation introduced on PVsyst for a fixed tilted plane [60]
Despite this value, adjusting the tilt angle twice a year is also considered as a possibility that is going to
be evaluated on the performed simulations. Seasonal adjustment usually provides a better performance
(Fig. 38). To calculate the values for the summer and winter angles, a rough method [62] is considered
at first instance, consisting on adding and subtracting 10º from the site’s latitude (Eq. 18). Then:
Despite this, another calculation model [61] suggests the following procedure (Eq. 19, Eq. 20) when
adjusting the tilt angle twice a year:
61
Design and simulation of a grid-connected PV system for self-consumption
However, many models are used in several studies and scientific papers that differ so much from each
other. Hence, in this situation, a 35º tilt angle is going to be used as a first simulation value for a fixed
tilt throughout the year, and 18º and 55º values will be implemented for the adjusting tilt simulation. In
regard to the azimuth orientation, the modules will be facing South direction, this meaning an azimuth
angle of 0º to create the first layout.
62
Design and simulation of a grid-connected PV system for self-consumption
Figure 39. Tilt angle and module orientation introduced on PVsyst for a seasonally tilt-adjusted plane
[60]
These angles will be optimized by means of running simulations on PVsyst for an iterative design
process that will eventually lead to the optimal position of the modules.
For an optimal layout of the PV modules, the right minimum inter-row distance has to be implemented
so there are no undesired shadows between them (Fig. 40).
63
Design and simulation of a grid-connected PV system for self-consumption
To have a first approach to this distance value, the Sun path chart [64] below is going to be used for the
location of study:
This chart (Fig. 41) plots data between solstices, from December through June, so the worst case
scenario can be studied. Considering solar hours from 9am to 3pm for the winter solstice, a solar
elevation of 13º and an Azimuth correction of 41º are obtained.
Using the optimal tilt angle of 35º, a rough estimation of the row spacing distance between panels can
be calculated. There are different methodologies to get this distance value. One of the most common,
yet basic methods [65] is to use an inter-row distance of three times the height of the panel (Eq. 21):
However, this calculation can be more exact when using other and most complex formulas [66] (Eq. 22).
Therefore:
Where:
64
Design and simulation of a grid-connected PV system for self-consumption
L: Module length
β: Desired Tilt Angle
α: Elevation Angle on December 21st at 9:00am
Adding a final product to this formula (Eq. 23), using the azimuth angle, the minimum row-spacing
distance can be obtained:
Where:
Azc: Azimuth correction angle, or difference between the azimuth angle on December 21st at 9:00am
and the southern direction.
In conclusion, from this approximate value, the first module layout is going to be done, and the different
scenarios for the performed simulations are going to be decided.
9.2.5 3D Modelling
The 3D scene can be created by use of the PVsyst design tools, or otherwise importing a building or
scene CAD model from other design software compatible with PVsyst, such as Autocad. In this case,
the building is modelled, placed and oriented towards the appropriate direction, following the coordinates
on the map. On this scene no surrounding buildings are created, as it is assumed that they have no
influence on shadowing the panels. However, four trees are integrated on the scene, introducing their
diameter and height, so the near shadings can be analyzed. The model can be seen in the figures below
(Fig. 42, Fig. 43).
65
Design and simulation of a grid-connected PV system for self-consumption
Figure 42. Axonometric projection of the CAD model of the building and surrounding elements [60]
Figure 43. Overhead projection of the CAD model of the building and surrounding elements [60]
66
Design and simulation of a grid-connected PV system for self-consumption
With the 3D model of the scene, the available rooftop area to lay the modules shall be selected using a
polygonal shape. Afterwards, the layout of the modules will be created, depending on parameters such
as pitch distance, tilt angle, the model of the panels and the inverter used, or the lateral spacing. In the
picture below (Fig. 44), three zones are created, although Zone #2 and Zone #3 are very likely to be
unused.
Figure 44. Available zones on the building’s rooftop for the installation of the PV system [60]
After having implemented into the software the 3D model of the building, the surrounding elements must
be analysed in terms of shading to see if they interfere with the full performance of the PV system.
Although the building has an inclination of 2,2º with respect to the vertical line that defines the northern
direction, to create the layout this fact has been disregarded, as it does not make any difference to the
layout of the modules (which will be oriented at azimuth 0º), and it becomes easier to design it on the
program.
67
Design and simulation of a grid-connected PV system for self-consumption
In this project, the shadings taken into account for the simulations are considered linear shadings, which
measure the lack of irradiance without considering the electrical effect, which will be assumed as a loss
percentage on other sections of the modelling, as in practice the linear shading factor is not so far from
the real effect with electrical losses.
For the layout, it is precise to define the position of the modules, as in landscape or portrait form [67]. In
a horizontal or landscape position, the shading losses are minimized, due to the electrical
interconnection of the cells. The bypass diodes (usually three in each panel) are placed in such way that
when a row of cells is shaded, the rest of the cells can continue working at their fullest output power
value. However, when in portrait position, or vertically placed, the bypass diodes induce the whole
module to stop its energy production whenever the lower row of cells is shaded, or covered by snow or
dust [68].
Figure 45. Electrical configuration of a PV module in landscape (left) and portrait (right) position [69]
On the figure above (Fig. 45), it is shown how for the landscape position on the left, if row S1 is shaded,
the other ⅔ of the module can still produce energy by bypassing S1, while on the other hand for the
portrait position on the right, if the lower row of cells is shaded, S1, S2 and S3 would be bypassed with
a null energy output resulting from it. For this reason, in order to optimize the losses, the landscape
position is the one to be used for this study.
On the 161,65 m2 of free rooftop area, the layout of modules must be drawn, using the pitch distance,
tilt angle and azimuth corresponding to each simulation scenario. The lateral spacing between panels
is fixed to be 0,2 m as it does not affect the system’s behaviour (Fig. 46, Fig. 47).
68
Design and simulation of a grid-connected PV system for self-consumption
Figure 46. Side projection of the module layout on the rooftop [60]
The near shadings simulation will be run defining the winter solstice as the day of study, in steps of 15
minutes, and the main objective is to detect the shadows caused by the near trees also modelled in the
3D scene, by the building shapes and by the panels themselves, as there are no higher surrounding
buildings that could induce shadings on the PV system.
Figure 47. Axonometric projection of the module layout on the rooftop [60]
69
Design and simulation of a grid-connected PV system for self-consumption
Regarding the losses, the thermal ones are set to be the ones corresponding to free outdoor mounted
modules with air circulation, and not modified respecting to the default value the software suggests. The
wind loss factor in this study is considered not relevant.
Ohmic losses on the DC circuit are set to a loss fraction at STC of 1,5%, while the voltage drop across
the diodes and the losses on the AC circuit after the inverter are not considered. Light induced
degradation (LID) is not taken into account given that crystalline silicon modules are not being used, so
the loss factor for LID is 0%. The mismatch losses are fixed at the default value of a power loss at MPP
of 0,8%.
In terms of unavailability of the system, a constant loss of 2% is assumed, this corresponding to 7,3
unavailable days a year, while the soiling loss factor (losses caused by dust, dirt or debris on the module
surface) is set to 3%. Spectral correction, ageing of the technology and Incidence Angle Modifier (IAM)
are neither considered in the simulations, although an initial degradation for the modules is said to be
of 5% due to the Staebler-Wronski effect [32], as this causes the module to work at a higher voltage
during the first two or three operating months. The losses can be seen graphed in Figure 48:
70
Design and simulation of a grid-connected PV system for self-consumption
9.2.8 Self-consumption
The energy demand files have to be introduced into the software as well in order to calculate the amount
of energy produced that is dedicated to self-consumption, and to know consequently which part of it is
injected into the grid. In the worst case scenario, it is to be calculated too if the energy produced by the
PV system is not enough to supply the household’s demand.
To do so, a table with the energy consumption data of the household is imported into the program (Fig.
49). This document contains sub hourly data of the demand in time steps of 15 minutes during the 365
days of the year, despite PVsyst simulates in time steps of 1h, by making an average of the consumption
every 15 minutes.
The software will analyse the CSV file and calculate the average and maximum load needs for the
household, which will be later shown on graphs in an hourly, daily or monthly scale. According to these
values, the simulations will be run to see if the demand can be covered. The load profile defined in
section 8.3 draws an annual need of 7.211 kWh/year (Fig. 50), which represents a daily average demand
of 19,76 kWh/day.
71
Design and simulation of a grid-connected PV system for self-consumption
9.2.9 Horizon
The horizon is by definition a broken line superimposed on the sun path diagram, which can hold any
number of height or azimuth points. It is used for the setting and analysis of far shadings on the PV field.
However, after having defined the near shadings parameters, the horizon study is only useful for
shadings caused by objects placed sufficiently far, as at a distance typically higher than ten times the
PV field size.
In the case of study, it has been assumed that there are no objects or buildings in the surroundings of
the PV system that could act directly on it by shading the modules. The objects around, besides from
the trees planted on the selected terrain, are not higher than the studied building, so the sunlight
shouldn’t encounter any obstacles on its way to the rooftop.
Hence, as explained, the default values of the horizon profile for Linyola are not going to be modified in
any simulation as the effect of far shadings is not considered to affect the scene in a direct way. Given
this, only diffuse and albedo factors are taken into account.
Once the steps stated in the sections above are completed, and all the details established and fixed,
the grid-connected system that has been created looks in a simplified schema like in Figure 51:
72
Design and simulation of a grid-connected PV system for self-consumption
In the PV installation, whenever there is an excess of energy production not used for the self-
consumption needs of the household, that energy surplus will be injected into the grid. Otherwise, when
there is not enough energy to cover the demand of the user, such as during night time, the energy
consumed by the load will be extracted from the grid as back-up energy. For now, no storage system is
going to be implemented in the first simulations.
Thus, with all this explained, several simulation scenarios can be defined. To start, the inter-row spacing
or pitch distance is going to be compared in different layouts to minimize the shadings. From the
minimum distance calculated in section 9.2.4, with a value of 2,31 m (rounded to 2,3 m), a first scenario
(Scenario A) will be built with the 35º tilt and a 0º azimuth orientation. That layout will allow the installation
of 30 panels in the building rooftop (in a configuration of up to 4 panels per string and 8 strings).
Then, the pitch distance will be increased to 3 m and to 3,3 m (Scenarios B and C), without modifying
the tilt nor azimuth angles. The loss percentage is going to be evaluated at this point. Nonetheless, the
number of PV modules is subsequently going to decrease as the pitch distance rises, so a whole
assessment is required to find a balance point between losses and energy production.
Once the best pitch distance is chosen, regarding as well the number of PV modules that fit into the
rooftop, a change in tilt will be performed in the next simulation (Scenario D), in order to gauge the
beneficial or detrimental effect of seasonal tilt adjustment. The PV modules in this scenario will remain
oriented to the southern direction.
Afterwards, having already determined the optimal pitch distance, the number of panels, and whether
the tilt should be fixed of adjustable, different tilt angles will be studied, by means of trying the initial tilt
and adding and subtracting 10º from that value (Scenarios E and F).
73
Design and simulation of a grid-connected PV system for self-consumption
Moreover, two simulation scenarios (Scenarios G and H) with a different azimuth orientation for the
modules are going to be compared as well. The modules in these scenes will be oriented south west
and south east and aligned with the building orientation, maintaining the best tilt found in the previous
scenarios.
Trying other layouts apart from these explained above might be interesting if the results issued by the
software show any tendencies or if any findings are made. Afterwards, the best scenario found is going
to be optimized with the installation of a storage system that will be defined later on.
In summary, all the simulation scenarios are collected in the Table below (Tab. 10):
A 35 2,3 31
B 35 3 26
C 35 3,3 26
Chosen Corresponding to chosen
D 18/55
from A/B/C pitch distance
0
Chosen from A/D Chosen Corresponding to chosen
E
+10º from A/B/C pitch distance
74
Design and simulation of a grid-connected PV system for self-consumption
Results
The results obtained from the simulations are going to be shown in this section, along with the process
used to find the best solution for the PV system. Details can be further seen in the Appendix 15.2.
Initially, scenarios A, B and C were implemented on the 3D scene and in the software data, and each
simulation was run according to the parameters stated in Table 11. For these first three cases, an
azimuth angle of 0º was used with a tilt angle of 35º. The inter-row distances vary from 2,3 to 3 to 3,3 m
in each corresponding scenario. As said in sections above, other parameters such as losses or
technology configuration are kept the same for every situation. Scenario A presents an active module
area of 79,2 m2, whilst both scenarios B and C have an active module area of 64,4 m 2.
The main results for scenarios A, B and C are shown below in Table 11:
Table 12. Definition parameters and simulation results for scenarios A, B and C
In this table (Tab. 11), the energy production represents the effective energy value at the inverter output,
without considering the unavailability of the system, which will be counted in later on for the calculations
of the grid-injected energy.
Specific production is the yield or energy produced for installed kWp of module capacity over a year
[70]. It can also be understood as the amount of hours that the PV system would need to work at its
nominal power to produce the same energy value as the actual system under the current conditions:
𝐸total
𝑌𝑖𝑒𝑙𝑑specific = (24)
𝑃plant,nom
Where:
Etotal: Total energy output
Pplant,nom: Installed capacity of the plant
The performance ratio (PR) is an indicator calculated by the ratio of the effectively produced energy that
is injected into the grid with respect to the energy that would be produced by an ideal system working
continuously under STC conditions [70]. The PR, although it is not directly dependant on meteorological
75
Design and simulation of a grid-connected PV system for self-consumption
conditions nor module orientation, includes optical (IAM, soiling, shadings) and array losses. It is a useful
indicator for comparison of the system quality between different locations and layouts. It is calculated
as:
𝐸total
𝑃𝑅(%) = · 100 (25)
𝑃plant,nom · 𝐺𝑡 · 10−6
Where:
Shading losses show the percentage of linear losses caused by the shadows of surrounding objects
and the own installation elements.
Finally, the system efficiency is the ratio of the produced energy with respect to the incident solar energy.
Then, according to the values on the Table 11, it is seen that Scenario A, although having a higher
installed capacity (due to a different module disposition that allows more panels on the rooftop) and
consequently a higher energy production, it shows lower specific yield, performance ratio and global
system efficiency values. Moreover, the shading losses are much higher than the ones in Scenarios B
and C. This comparison can be observed in Figures 51, 52 and 53, in the iso-shadings diagrams for
each situation:
76
Design and simulation of a grid-connected PV system for self-consumption
77
Design and simulation of a grid-connected PV system for self-consumption
Regarding these last detrimental results, scenario A is discarded, and the pitch distance chosen
between 3 m and 3,3 m has to be decided from studying scenarios B and C. Nonetheless, parameters
in scenarios B and C are almost identical, despite the simulations are showing a tendency to better
values on scenario C. Because of this slightly higher yield and performance results, pitch distance on
scenario C is the one used for the next simulation scenarios (D, E and F).
The next step of the simulation process is performed on scenarios D, E and F. The aim of this part of
the simulations is to assess the implementation of a seasonal tilt adjustment on the PV modules. The
parameters used in these three simulations are the ones stated in Table 12:
The results obtained for scenarios D, E and F are shown in the table below (Tab. 13):
Table 13. Definition parameters and simulation results for scenarios D, E and F
In regard of these results, it can be seen that scenario D is the one that shows the best performance in
terms of specific yield. Its efficiency is fairly higher than the one from scenarios E and F as well. Although
the performance ratio and the shading losses in this studied situation are not the optimal ones, the
values are considered acceptable and scenario D is the one chosen in between these three.
The numbers for scenarios C and D are subsequently compared to obtain the best tilt configuration for
the panels choosing in between a fixed tilt angle of 35º or a seasonal adjustment of 18º for the summer
and 55º for the winter. When doing so, it is seen that the specific production is significantly higher for
scenario D, despite it has a lower performance ratio due to a larger percentage of shading losses.
Nonetheless, it is a meaningless difference, so it is assumed that the best tilt to continue the study is
the seasonally adjusted one, as the production seems to be the optimal.
For scenarios G and H, the layout configuration of the modules can be observed in Figure 55:
78
Design and simulation of a grid-connected PV system for self-consumption
As explained before, these two configurations are tried, aligning the panels to the building orientation to
create the most logical layouts, (and facing the southern direction in both scenes), and in order to try
new azimuths that could help improve the performance. An azimuth of 2,2º SW is implemented for
scenario G, and 87,7º SE is the orientation for scenario H. The results for the simulations are shown in
Table 14:
Table 14. Definition parameters and simulation results for scenarios G and H
As it was to be expected, scenario H draws results below the average values that have been appearing
on the other scenarios, because of an orientation that is almost facing east. Plus, its global efficiency is
around a 23% less than the one in scenario D. For these reasons, this scene is discarded against the
others. Otherwise, divergences between scenarios D and G are absolutely insignificant, as 2,2º of
azimuth angle is almost a southern orientation. Hence, as the values don’t change significantly, scenario
D is going to be maintained, because the southern direction is usually considered the optimal one.
In this situation, scenario D is considered the one with the most optimized parameters for its integration
on the rooftop. To sum up, this configuration delivers an energy flow at the inverter’s output of 20,38
MWh/year. The near shadings losses represent a 3,71% of the available irradiance (Fig. 56), and thus
the performance ratio of the system is of 82,95%.
79
Design and simulation of a grid-connected PV system for self-consumption
This scenario has an specific production of 1.742 kWh/kWp/year, with an installed capacity of 11,7 kWp
out of 26 PV modules oriented south and with a seasonal tilt adjustment of 18º for summer and 55º for
winter season. However, the array itself presents losses of 0,81 kWh/kWp/day, whilst the system formed
by the inverter and wiring loses 0,16 kWh/kWp/day (Fig. 57).
Figure 57. Graph of monthly production and losses for scenario D [60]
80
Design and simulation of a grid-connected PV system for self-consumption
In view of the results obtained after the simulations, the best layout has been defined: 26 PV modules
south oriented with a tilt angle that varies in between the summer and winter season, with 18º and 55º
respectively. Overall, the installation shows a good performance: it produces around 20,4 MWh/year,
with pretty low electrical and shading losses.
However, this apparently good operation leaves behind the objective of covering the household’s
electrical demand. If the installation was to inject all the energy output into the grid, it would be suitable.
But when coming to analyse the load profiles of the household, as observed in Section 8.3, the users
have a need for energy in the morning hours before leaving the house for other tasks. During midday
and early afternoon hours, the demand of the place stabilises in only the stand-by consumption of the
electrical devices that are plugged in, such as the fridge. When the users come back home, they start
demanding energy again. Therefore, the consumption peak of the building takes place in the afternoon
and evening, when the charge of the two electric cars needs to be done, as well as cooking and other
chores.
In the way the installation is intended to operate, it is necessary either to inject the produced energy
from the PV modules directly to the grid, or to consume it instantly. During the sun hours, when the
demand is at its lowest level, and the irradiance of the panels is the highest, the necessity is fully covered
and a great surplus is sold to the grid. Nonetheless, the users encounter the opposite situation in the
evening, having no other choice than consuming energy from the grid, as they are unable to use the PV
system when there is any sunlight.
Prior to having any PV system, the house consumed 7.211 kWh/year from the grid. On the other hand,
in scenario D, and as it can be observed in Figure 58, now the demand from the network is 4.017
kWh/year. Despite having a solar system that produces 20,4 MWh/year, only 3194 kWh/year are used
by the family, and the rest of it, 16912 kWh/year, are directly sold to the grid as they are being produced
during the hours the family are not at home.
In this situation, one could think that as long as the energy surplus is sold, there is no need to do a self-
consumption strategy to cover the demand. Although this excess of output energy is indeed sold, the
selling retributions in Spain for self-consumption installations are considerably lower than the price of
electricity purchased from the grid. In fact, they are in average about 3 times lower, and as the purchase
tariffs are usually time-dependant, consuming at night would require paying the highest tariff. This being
stated, there is no point in not using as much energy as it is produced by the household’s own system,
and to avoid as long as it is possible to purchase energy.
81
Design and simulation of a grid-connected PV system for self-consumption
In order to solve these problems and to serve accurately the demand, a storage system is going to be
implemented along with the PV modules. This self-consumption strategy with storage allows as said to
consume the energy produced by the rooftop installation and to optimize the cost of electricity.
The energy produced by the PV system is stored in the battery pack when the PV production surpasses
the needs of the individuals at the house, and from that point, when the demand cannot be covered by
the solar irradiation, it is satisfied from the battery until it discharges. The rest of the moments when the
battery is empty and the PV production is null, back-up energy is purchased from the grid. However, the
82
Design and simulation of a grid-connected PV system for self-consumption
battery may never inject energy to the grid, as the household’s consumption and the grid share the same
circuit, and so the battery’s inverter and control devices shall modulate the power and feed properly the
user.
There are five main operating modes for the storage system:
Charging mode
The PV system feeds the battery when it is empty to charge it, as well as feeding the user’s
needs as a priority. If the battery pack charges completely and the user’s demand is covered,
the surplus energy is injected into the grid (direct mode).
Once the battery is fully charged, the PV system covers the user’s demand until it is unable to
do so (e.g. lack of sunlight), and so the storage system discharges energy to the household.
However, if the battery reaches the full discharge level, energy is purchased from the grid.
Direct mode during the day with sufficient irradiance and full charge
Whenever there is enough solar irradiance to cover the user’s demand and the battery is fully
charged, direct mode supplies electricity to the user and injects the surplus to the grid.
83
Design and simulation of a grid-connected PV system for self-consumption
Figure 61. Simplified scheme for direct mode with sufficient irradiance and full charge [60]
Direct mode during the day with insufficient irradiance and empty battery
As user’s needs are a priority, if the storage system is fully discharged and there is not enough
irradiance to cover the demand, direct mode will only supply the user, who will also have a need
to extract back-up energy from the grid, while the battery will remain discharged until surplus
energy is available.
Figure 62. Simplified scheme for direct mode with insufficient irradiance and no charge [60]
Night mode
In the night hours, when no sunlight is available, the battery pack and the grid are the
responsible sources to feed the user’s consumption, as long as the battery is still charged.
84
Design and simulation of a grid-connected PV system for self-consumption
According to this functioning system, a Lithium-ion battery pack from the manufacturer LG Chem is
chosen. The model is RESU13, which has a usable energy of 12,4 kWh and a capacity of 252 Ah.It has
a nominal voltage of 51,8 V, and two modules of this battery are connected in parallel, so it can store
21,3 kWh at 80% DOD. The thresholds set to the SOC of the pack are 95% for maximum charging and
20% for maximum discharging, so it can operate with efficiencies in between 95% and 97%.
The maximum charging power the storage system can handle is 11,5 kW, as the installed capacity of
the panels is 11,7 kW and with a clear sky the maximum output power obtained from them is 11,29 kW
AC. Regarding the maximum discharging power, it is of 9 kW, as the maximum user’s power is 8,91 kW,
and the average power is 0,82 kW. The capacity and charge and discharge power values of the battery
pack allow a charging time during full sun conditions on 1,8h. Its discharge under an average load can
take up to 25,9h and under maximum load conditions about 2,4h (for more details, see Appendix 15.1.3).
Once this battery is implemented along with the parameters defined on Scenario D, a new simulation
scenario is completed: Scenario SS. The results drawn from it are the following (Tab. 15):
Obviously, these results are almost identical to the ones in Scenario D, assuming the internal variations
of the simulation software. However, a new variant of losses is added, the losses from the battery pack,
which reach a value of around 3%. The performance ratio in this case is slightly diminished from the
previous one, down to 79,3%. Taking two representative months of each summer and winter seasons,
such as June and December respectively, some graphs can be plotted to easily see the magnitude and
management of the energy handled by the system, as in the figures below (Fig. 64, Fig. 65, Fig. 66, Fig.
67):
85
Design and simulation of a grid-connected PV system for self-consumption
Power [kWh/day]
Figure 64. Graph of battery’s charging and discharging energy for the month of June [60]
Power [kWh/day]
Figure 65. Graph of battery’s charging and discharging energy for the month of December [60]
86
Design and simulation of a grid-connected PV system for self-consumption
Figures 63 and 64 show the battery’s charging and discharging energy through a whole month according
to average daily values extracted from the hourly ones. The left axis represents power in kWh/day. There
are no significant differences between June and December, as both average values resemble and the
charts tendency seems logical, although these variables need to be compared with other ones that
consider consumption.
In the following charts (Fig. 66, Fig. 67), there are therefore compared the values of the battery’s
discharge (only to the user, as it does not re-inject to the grid), the energy purchased from the grid, the
energy injected into the grid (the surplus), and an amount of energy supplied to the user in general,
either from solar energy in a direct mode, as from the storage system or the grid.
In this case, there is a huge difference between the two representative months, as the amount of
irradiance in winter is much under the one in summer. That turns into a higher consumption of grid
energy in December, along with quite less grid injection, as in general terms all the available solar energy
goes to the battery pack or to the user directly.
Power [kWh/day]
Figure 66. Comparison graph between battery discharging energy, energy injected or purchased from
the grid, and energy supplied to the user for the month of June [60]
87
Design and simulation of a grid-connected PV system for self-consumption
Power [kWh/day]
Figure 67. Comparison graph between battery discharging energy, energy injected or purchased from
the grid, and energy supplied to the user for the month of December [60]
Considering it all in general, from the 20,38 MWh generated at the inverter’s output, a 22,7% is stored,
which mean 4,626 MWh/year that are specifically used to supply the family’s demand. The remaining
77,3% of it is used in direct mode. Eventually, the PV system provides the user with 6,84 MWh every
year, whilst 12,38 MWh are injected into the grid. Knowing that 4,626 MWh/year come from the battery
pack, it is deduced that 2,214 MWh/year come from direct mode (Fig. 68).
Only a 7,6% of the time the user needs to purchase back-up energy from the grid, which represents a
value of 370 kWh/year, barely a 5% of the initial consumption value. This brings up the notorious
optimization of the energy use, having now little dependence on the grid itself, as the majority of the
household’s demand is satisfied by the own system.
88
Design and simulation of a grid-connected PV system for self-consumption
89
Design and simulation of a grid-connected PV system for self-consumption
Economic analysis
Once the design is simulated and considered viable, it is necessary to study the economic feasibility of
the installation of the PV rooftop system. Usually, the technology used in these kind of installations is
available on the market at high prices, but when installed in a region with a high solar potential, and
given their long-lasting life expectancy, the purchase can be amortized quite easily.
For this economic analysis, the calculation model used includes OPEX, CAPEX, taxes and energy
production, along with its PPA (Power Purchase Agreement).
CAPEX is defined as Capital Expenditures [71], which represent all installation and material goods costs
in €/Wp, or in other words, all the elements purchased by the user. In the table below (Tab. 16), the
devices used in the PV system are summarized, to show the elements that are going to be taken into
account when calculating the CAPEX budget of the project. Moreover, the rest of components, such as
wires and the installation of the technology have been valued in 1000 €.
On the other hand, OPEX is understood as Operational Expenditures [71], which comprises the
permanent cost of maintaining and improving the assets. OPEX may include operations and
maintenance (O&M), security, monitoring, insurances or land rentals. In this case, no bank charges,
land rents or insurances are going to be taken into account, only a permanent cost due to maintenance,
which will be considered as a 2% of the initial investment represented by the CAPEX (Tab. 16). However,
this is a simplification, as maintenance would be null the first years of operation, and would increase
non-proportionally towards the end of the life cycle of the system. The amortization of the technology is
calculated along 25 years of life expectancy with a linear degradation of the item. Therefore, the project
lifetime is set to be of 25 years and the calculations are related to annual values.
OPEX item
Maintenance - - 300
90
Design and simulation of a grid-connected PV system for self-consumption
However, a vast investment of money would be useless in financial terms without earnings associated
to it that could make the investment profitable in a relatively short time scope. For the PV system
analysed, income in terms of selling the energy surplus that is not being used or stored produces a
certain amount of money each year. The selling price is given by the Power Purchase Agreement (PPA)
of Red Eléctrica de España, and valued in 53,28 €/MWh (Precio de la energía excedentaria del
autoconsumo para el mecanismo de compensación simplificada [75]). Otherwise, the electricity that had
been usually purchased from the grid at the normal Spanish price for kWh (an average of 0,116 €/kWh
[76]) is now transformed into saved money as well. This can be observed in Table 17:
Additionally, a notorious amount of money is saved when charging two electric cars at home using solar
energy only (Tab. 18). As said in section 8.3 of the project, the household owners use two electric cars
to make a usual route to work. One of them makes a 30 km path to the workplace, which sums 60 km
of travel a day. The second one, sums 10 km of travel a day, considering the 5 km path to the workplace.
Regardless of the average speed they travel at, to make an estimation of their consumption, two models
of electric car for a working class household have been chosen to make the calculations: Opel Corsa-e
for the long path and Peugeot e-208 for the short one. The first one of them has an average consumption
of 17 kWh/100 km [77], and the second one of 15,1 kWh/100 km [78] in an urban driving environment.
In view of this data, the Opel Corsa-e shows a daily consumption of 10,2 kWh. The Peugeot e-208, for
its part, presents an energy consumption of 1,51 kWh.
Considering that the battery of the cars is charged at home, the saving in money comes from not having
an expenditure in public charging stations. The price per kWh considered in this study is the one offered
in the charging stations of Endesa X, the biggest company in Spain for electric charging, and the owner
enterprise of the majority of charging stations. The price for the fast-charge is of 0,54 €/kWh [79]. The
total consumption of the cars during 260 working days in a year constitutes 3044,6 kWh, and a total
amount of money saved in charging stations of 1644,08 €.
91
Design and simulation of a grid-connected PV system for self-consumption
Table 18. Prices of charging the electric cars in a public charging station
Average Daily
Charging price Total price
consumption consumption
[€/kWh] [€]
[kWh/100 km] [kWh]
It must be said too that there are governmental grants conferred to users who decide to install a self-
consumption system in Spain, in order to propitiate the use of renewable energy in the country. This
financial help is intended to defray the technology used, in order to reduce the initial investment made
out of own funds. Specifically, in Catalonia these subventions provide around 5000 € (ICAEN: Sistemes
d’emmagatzematge d’energia elèctrica amb bateries associats a instal·lacions fotovoltaiques
d’autoconsum [80]) to the citizens that implement PV systems for self-consumption at their own homes.
With these data, a financial study is developed with a 25 year horizon and a discount rate of 10%, which
draws the results summed up in Table 19. The details can be further seen in the Appendix 15.3.
NPV 1668,02 €
IRR 9%
Payback period 6,4 years
According to the results of the simulation of Scenario SS, the amount of CO 2 saved with the use of the
PV system is of 85231 tons in a 25 year period (Fig. 69), which means 3409 tCO2/year considering an
annual degradation of 1%. This is also a value of 0,291 tCO 2/kWp/year, and shows that each tCO2 is
worth 5,85€ of inversion, which seems very reasonable in ecological terms.
92
Design and simulation of a grid-connected PV system for self-consumption
Figure 69. Saved carbon dioxide emissions of the PV system on scenario SS [60]
When wanting to know at what cost the energy is generated at the plant during its lifetime, the Levelized
Cost Of Energy (LCOE) is used. The LCOE is also very useful to compare different power-generating
technologies [81]. Its formula (Eq. 26) is the following:
𝑛 𝐼𝑡 +𝑀𝑡 +𝐹𝑡
𝑆𝑢𝑚 𝑜𝑓 𝑐𝑜𝑠𝑡𝑠 𝑜𝑣𝑒𝑟 𝑙𝑖𝑓𝑒𝑡𝑖𝑚𝑒 ∑𝑡=1
(1+𝑟)𝑡
𝐿𝐶𝑂𝐸 = = 𝐸𝑡 (26)
𝑆𝑢𝑚 𝑜𝑓 𝑒𝑙𝑒𝑐𝑡𝑟𝑖𝑐𝑎𝑙 𝑒𝑛𝑒𝑟𝑔𝑦 𝑝𝑟𝑜𝑑𝑢𝑐𝑒𝑑 𝑜𝑣𝑒𝑟 𝑙𝑖𝑓𝑒𝑡𝑖𝑚𝑒 ∑𝑛 𝑡=1 (1+𝑟)𝑡
Where:
It: Investment expenditures in year t
Mt: O&M expenditures in year t
Ft: Fuel expenditures in year t, null in this case
Et: Electrical energy generated in year t
r: Discount rate
n: Expected lifetime of the system
The system produces 20376 kWh/year, and the initial investment made on it plus the maintenance cost
for the 25 year lifetime sums an amount of 27424 €. The LCOE then is 0,1224 €/kWh , that compared
to the average LCOE for PV systems with batteries in Spain [82] (between 0,118 and 0,205 €/kWh) is
pretty accurate to the range.
93
Design and simulation of a grid-connected PV system for self-consumption
Conclusions
Being Spain one of the countries with the highest incidence of solar irradiance in Europe, it could seem
logical to think that photovoltaic energy is quite exploited around the territory. However, this is not the
case, among other factors, because of the “Sun tax” that was abolished only a year ago. This means
that it is far from common that individual users possess a PV installation to supply the energy demand
of their own homes. Hence, this thesis had as a main goal to design and assess through a simulation
software the performance of a grid-connected PV system for self-consumption installed on a building’s
rooftop in a location with a high solar potential unused. With this purpose, the choice of a suitable site
for the installation and of the technology to be used, sizing calculations, the creation of a load profile,
the modelling of the building and its simulation were made. The following are the major findings that can
be drawn from the study:
The study shows that an iterative design leads to an optimization of the first approach made for the
system. For instance, it can be seen that an adjustable tilt angle for summer and winter seasons
boosts the annual energy production, discarding the fixed tilt angle calculated at first. Conversely,
the azimuth orientation was already the optimal one, as the rear facade of the house is facing the
southern direction, so the sunlight reaches the surface of the PV modules most of the daytime.
The shading analysis shows that the surrounding elements of the building do not interfere with the
performance of the plant, although the main shading loss is caused by the own modules, as when
they are put in winter position (55º), during some hours of the day the inter-row distance is scarce.
Broadening the inter-row distance could have avoided the shading losses, but then the limited area
of the rooftop would have required to remove some panels. This detrimental action to the energy
production would not have been justified by a shading loss of less than 4%.
Once the simulations were completed, a proper functioning scenario was found presenting an
annual energy production of 20,38 MWh/year and a specific yield of 1742 kWh/kWp·year. The
performance ratio of the plant was of almost 83% and its global efficiency of 18,7%. Although the
production was acceptable, it was seen that the PV system mainly injected energy into the grid
instead of supplying the user. This would be satisfactory if the retribution obtained from the injected
electricity was higher than the price of the energy purchased from the network. Unfortunately, the
current situation in Spain stands the opposite way, meaning that systems operating in those
circumstances would leave the household’s demand to be supplied by the grid, as the way it was
before any PV installations were made. Therefore, such a design was considered not suitable, and
a PV system with a storage system was considered more appropriate instead.
The load profiles generated for the house presented a peak in the evening hours, which forced to
implement a storage system that could save the energy generated during the sun hours, and that
could release it during the consumption peak to fit the curve. Thus, new results were obtained,
maximizing in this way the energy used by the people in the house that came from their own PV
94
Design and simulation of a grid-connected PV system for self-consumption
system. In the new scenario with storage system, the user receives 6,84 MWh/year, more than
doubling the value of 3,19 MWh/year that they received without the battery pack. The energy
purchased from the grid is reduced almost a 95% from the initial demand value, and constitutes the
7,6% of the consumption time, proving that a storage system implies a great improvement to the
prior scenario without modifying its global efficiency.
In terms of economic profitability, the system designed can supply the demand of a whole family,
including the charge of electric vehicles. The total cost of the PV system for the end user, once
discounted the governmental subvention, is of 14924 €, which represents an annual saving of
2635,8 €. The system also produces environmental benefits, saving approximately the emission of
3409 tCO2/year, with a reasonable cost of 5,85€/saved tCO2.
These findings illustrate how new photovoltaic technologies for solar cells, such as thin-film
technologies, can meet the standards set by the normal Silicon crystalline (which was a secondary aim
of study) with less cost and less pollutant manufacturing processes. Nevertheless, the study has some
limitations:
As they were not accessible, meteorological data used to implement in the simulations were not
fully updated. Nevertheless, most likely this fact would not have affected the results, as the
values used were quite recent.
Calculations were made taking into account current costs of electricity without considering future
variations. Also, eventual future changes in user’s needs were not considered, as they are
unpredictable.
Small costs attributable to different concepts exist, such as reparations, grid connection costs
or transport. As these are almost impossible to calculate, they were included in wider concepts
that were imputed an approximate value. Low amounts were assumed for them, so it was
considered that this would not have influenced the study significantly.
Also, in regard to the losses of the PV installation, very difficult to calculate accurately, default
values were assigned.
Finally, the study could be further completed by means of providing calculations for properly sizing AC
and DC wires and other components, studying other possible load profiles to check the versatility of the
PV system and even considering installing sun-tracking systems or other technologies for PV panels
that for this thesis have been discarded due to their high economic investment.
To summarize, it can be said that the objectives of the project have been fulfilled, as a PV system design
has been implemented, evaluated and found effective and economically viable and profitable, while it
feeds the energetic demand of a household and it is able to supply the charge of two electric cars.
Additionally, this thesis provides a design guide for grid-connected PV systems for self-consumption
that can be further optimized in more complex scenarios. Nonetheless, as technical and economic
95
Design and simulation of a grid-connected PV system for self-consumption
barriers are breaking down, the use of photovoltaic energy is becoming an unavoidable step to reduce
the use of fossil fuels towards the future. Thus, more research needs to be implemented in the field,
especially in the regions of Spain with a high solar potential, where these kind of systems can be installed
in houses and buildings reducing the need to consume energy that come from non-renewable sources.
96
Design and simulation of a grid-connected PV system for self-consumption
Bibliography
[2] Energías Renovables Info, “Energías Renovables Info,” 2017. [Online]. Available:
http://www.energiasrenovablesinfo.com/. [Accessed July 2020].
[3] Union of Concerned Scientists, “Union of Concerned Scientists,” 2017. [Online]. Available:
https://www.ucsusa.org/. [Accessed July 2020].
[5] K. Sukhatme and S. P. Sukhatme, Solar Energy: Principles of Thermal Collection and Storage,
Tata McGraw-Hill Education, 1984.
[6] S. Harrouni, Modeling Solar Radiation at the Earth's Surface: Recent Advances, V. Badescu,
Ed., Springer, 2008.
[7] College of Engineering and Applied Science of Cincinnati, “Sunlight,” [Online]. Available:
http://www.eng.uc.edu/~beaucag/Classes/SolarPowerForAfrica/BookPartsPVTechnical
/Sunlight_01.pdf. [Accessed February 2020].
[8] F. Kasten and A. T. Young, Revised optical air mass tables and approximation formula Applied
Optics, 1989.
[10] C. S. Solanki, Solar Photovoltaics: Fundamentals, Technologies And Applications, PHI Eastern
Economy Edition, 2015.
[11] R. Sizmann, Solar Power Plants: Fundamentals, Technology, Systems, Economics, Springer-
Verlag, 1991.
[12] T. R. Kuphaldt, “Lessons in Electric Circuits: The P-N Junction,” vol. 3, no. Chapter 2:
Semiconductors, 2011.
[13] D. B. Needleman, Optical design guidelines for spectral splitting photovoltaic systems : a
sensitivity analysis approach, 2014.
[15] Cornelia Peike, Ingrid Hädrich, Karl-Anders Weiß, Ines Dürr, Overview of PV module
encapsulation materials, Fraunhofer ISE, 2013.
[16] Ekadewi A.Handoyo, Djatmiko Ichsani, Prabowo, “The Optimal Tilt Angle of a Solar Collector,”
Energy Procedia, vol. 32, pp. 166-175, 2013.
[17] M. Rycroft, Solar PV tracking systems can increase output, EE Publishers, 2016.
97
Design and simulation of a grid-connected PV system for self-consumption
[18] Vivek Kumar, Namrata Patil, Bhavesh Zope, “Solar Panel Selection for 5KW System,”
International Journal of Engineering and Advanced Technology (IJEAT), 2017.
[21] Mohammadreza Maghami, Hashim Hizam, Chandima Gomes, Shahrooz Hajighorbani, Nima
Rezaei, Evaluation of the 2013 Southeast Asian Haze on Solar Generation Performance,
2015.
[23] Fraunhofer-Institut für Solare Energiesysteme ISE, “Daten zu Erneuerbaren Energien,” 2009.
[Online]. Available: https://www.ise.fraunhofer.de/de/daten-zu-erneuerbaren-
energien.html. [Accessed April 2020].
[24] Grand View Research, “Solar Cell Market Analysis By Product (Silicon Wafer, Monocrystalline,
Multicrystalline, Cadmium Telluride, Copper Indium Galium Selenide, Amorphous silica),
And Segment Forecasts To 2022,” 2016.
[25] N. S. Lewis, “Research opportunities to advance solar energy utilization,” Science Magazine,
vol. 351, 2016.
[28] Parida, B.; Iniyan, S;, Goic, R., “A review of solar photovoltaic technologies,” Renewable and
Sustainable Energy Reviews, vol. 15, pp. 1625-1636, 2011.
[29] V. Benda, “Crystalline Silicon Solar Cell and Module Technology,” in A Comprehensive Guide to
Solar Energy Systems, 2018.
[30] A. U. Taesoo D.Lee, “A review of thin film solar cell technologies and challenges,” Renewable
and Sustainable Energy Reviews, vol. 70, pp. 1286-1297, 2017.
[31] A. Shah, “Thin-Film Silicon Solar Cells,” McEvoy's Handbook of Photovoltaics, 2018.
[32] M. Raja, Thin Film Techniques and Applications, Allied Publishers PVT. Limited, 2004.
[33] Martin A. Green, Ewan D. Dunlop, Jochen Hohl‐Ebinger, Masahiro Yoshita, Nikos Kopidakis,
Xiaojing Hao, “Solar cell efficiency tables,” Progress in photovoltaics, vol. 25, pp. 668-
676, 2020.
[34] K. Chopra, P. Paulson and V. Dutta, “Thin-film solar cells: an overview,” Progress in
photovoltaics: research and applications, vol. 12, 2004.
[35] Powalla, M., “Manufacture of CIGS thin-film solar cells,” 2020. [Online]. Available:
https://www.zsw-bw.de/en/research/photovoltaics/topics/thin-film-solar-cells-and-
modules.html#c460.
98
Design and simulation of a grid-connected PV system for self-consumption
[36] Khushboo Sharma, Vinay Sharma, S. S. Sharma, “Dye-Sensitized Solar Cells: Fundamentals
and Current Status,” Nanoscale Research Letters, 2018.
[37] A. A.-G. Carlos Amador-Bedolla, “Organic Solar Cells,” Handbook of Organic Materials for
Optical and (Opto)electronic Devices, 2013.
[38] Simon P.Philipps, FrankDimroth, Andreas W.Bett, “High-Efficiency III–V Multijunction Solar
Cells,” McEvoy's Handbook of Photovoltaics, pp. 439-472, 2018.
[39] Andreev, Vyacheslav M., “GaAs and High-Efficiency Space Cells,” McEvoy's Handbook of
Photovoltaics, pp. 421-438, 2018.
[40] Teodorescu, R.; Liserre, M.; Rodríguez, P., Grid converters for photovoltaic and wind power,
Wiley, 2011.
[41] European Comission, “Comission Regulation (EU) 2016/631: establishing a network code on
requirements for grid connection of generators,” in Official Journal of the European
Union, 2016.
[42] Gobierno de España, “Boletín Oficial del Estado (BOE),” Agencia Estatal, [Online]. Available:
https://www.boe.es/. [Accessed March 2020].
[43] Red Eléctrica de España, “Operación del sistema eléctrico. Procedimientos de Operación,”
[Online]. [Accessed 18 March 2020].
[44] Red Eléctrica de España, Criterios Generales de Protección de los Sistemas Eléctricos Insulares
y Extrapeninsulares”, 2005.
[45] Red Eléctrica de España, “Instalaciones conectadas a la red de transporte peninsular: requisitos
mínimos de diseño y equipamiento,” 2018.
[46] Red Eléctrica de España, “Mapa de instalaciones fotovoltaicas nacionales,” [Online]. Available:
esios.ree.es/es/mapas-de-interes/mapa-instalaciones-fotovoltaicas. [Accessed April
2020].
[50] European Comission, “Photovoltaic Geographical Information System (PVGIS),” 2016. [Online].
Available: https://ec.europa.eu/jrc/en/pvgis. [Accessed May 2020].
99
Design and simulation of a grid-connected PV system for self-consumption
[54] First Solar, “Technical Documents. Series 6 Datasheets,” 2020. [Online]. Available:
http://www.firstsolar.com/en-Emea/-/media/First-Solar/Technical-Documents/Series-6-
Datasheets/Series-6-Datasheet.ashx. [Accessed April 2020].
[57] NASA, “NASA Data Access Viewer,” 2020. [Online]. Available: https://power.larc.nasa.gov/data-
access-viewer/. [Accessed April 2020].
[59] J. B. Matthew Culligan, “Impact of tilt angle on system economics for area constrained rooftops,”
2011.
[62] Qiu, G.; Riffat, S. B., “Optimum tilt angle of solar collectors and its impact on performance,”
International Journal of Ambient Energy, 2011.
[63] Saint-Drenan, Y. M.; Barbier, T., Data-analysis and modelling of the effect of inter-row shading
on the power production of photovoltaic plants, 2019.
[64] University of Oregon, “Solar Radiation Monitoring Laboratory,” 2007. [Online]. Available:
http://solardat.uoregon.edu/SunChartProgram.html. [Accessed June 2020].
[67] Solar Island Energy, “Solar modules: Why do tilt and orientation matter?,” 2019. [Online].
Available: https://solarisland.energy/2019/04/solar-modules-why-do-tilt-and-orientation-
matter/. [Accessed May 2020].
[68] Barreiro C.; Jansson, P.; Thompson, A.; Schmalzel, J., “PV by-pass diode performance in
landscape and portrait modalities,” Conference Record of the IEEE Photovoltaic
Specialists Conference, 2011.
[69] Jason A Galtieri, Philip T. Krein, “Designing solar arrays to account for reduced performance
from self-shading,” IEEE Power and Energy Conference at Illinois (PECI), 2015.
100
Design and simulation of a grid-connected PV system for self-consumption
[70] Jamil, M.; Rizwan, M,; Kothari, D. P., Grid Integration of Solar Photovoltaic Systems, CRC Press,
2017.
[71] M. Gentle, The CRM Project Management Handbook: Building Realistic Expectations and
Managing Risk, Kogan Page Publishers, 2002.
[73] LG, “LG Chem,” [Online]. Available: https://www.lgchem.com/. [Accessed July 2020].
[81] DOE Office of Indian Energy, “Levelized Cost of Energy (LCOE),” 2015. [Online]. Available:
https://www.energy.gov/sites/prod/files/2015/08/f25/LCOE.pdf. [Accessed July 2020].
[83] Albarqouni, S.; Hussein, M. T. , Enhanced Model Of One Axis-Two Positions Manual Tracking
Photovoltaic Panels For Lighting Projects In Palestine, 2010.
101
Design and simulation of a grid-connected PV system for self-consumption
15 Appendix
15.1 Datasheets
102
Design and simulation of a grid-connected PV system for self-consumption
15.1.1 FS-6450
103
Design and simulation of a grid-connected PV system for self-consumption
104
Design and simulation of a grid-connected PV system for self-consumption
105
Design and simulation of a grid-connected PV system for self-consumption
106
Design and simulation of a grid-connected PV system for self-consumption
15.2.1 Scenario A
107
Design and simulation of a grid-connected PV system for self-consumption
108
Design and simulation of a grid-connected PV system for self-consumption
109
Design and simulation of a grid-connected PV system for self-consumption
110
Design and simulation of a grid-connected PV system for self-consumption
111
Design and simulation of a grid-connected PV system for self-consumption
112
Design and simulation of a grid-connected PV system for self-consumption
15.2.2 Scenario B
113
Design and simulation of a grid-connected PV system for self-consumption
114
Design and simulation of a grid-connected PV system for self-consumption
115
Design and simulation of a grid-connected PV system for self-consumption
116
Design and simulation of a grid-connected PV system for self-consumption
117
Design and simulation of a grid-connected PV system for self-consumption
118
Design and simulation of a grid-connected PV system for self-consumption
15.2.3 Scenario C
119
Design and simulation of a grid-connected PV system for self-consumption
120
Design and simulation of a grid-connected PV system for self-consumption
121
Design and simulation of a grid-connected PV system for self-consumption
122
Design and simulation of a grid-connected PV system for self-consumption
123
Design and simulation of a grid-connected PV system for self-consumption
124
Design and simulation of a grid-connected PV system for self-consumption
15.2.4 Scenario D
125
Design and simulation of a grid-connected PV system for self-consumption
126
Design and simulation of a grid-connected PV system for self-consumption
127
Design and simulation of a grid-connected PV system for self-consumption
128
Design and simulation of a grid-connected PV system for self-consumption
129
Design and simulation of a grid-connected PV system for self-consumption
130
Design and simulation of a grid-connected PV system for self-consumption
15.2.5 Scenario E
131
Design and simulation of a grid-connected PV system for self-consumption
132
Design and simulation of a grid-connected PV system for self-consumption
133
Design and simulation of a grid-connected PV system for self-consumption
134
Design and simulation of a grid-connected PV system for self-consumption
135
Design and simulation of a grid-connected PV system for self-consumption
136
Design and simulation of a grid-connected PV system for self-consumption
15.2.6 Scenario F
137
Design and simulation of a grid-connected PV system for self-consumption
138
Design and simulation of a grid-connected PV system for self-consumption
139
Design and simulation of a grid-connected PV system for self-consumption
140
Design and simulation of a grid-connected PV system for self-consumption
141
Design and simulation of a grid-connected PV system for self-consumption
142
Design and simulation of a grid-connected PV system for self-consumption
15.2.7 Scenario G
143
Design and simulation of a grid-connected PV system for self-consumption
144
Design and simulation of a grid-connected PV system for self-consumption
145
Design and simulation of a grid-connected PV system for self-consumption
146
Design and simulation of a grid-connected PV system for self-consumption
147
Design and simulation of a grid-connected PV system for self-consumption
148
Design and simulation of a grid-connected PV system for self-consumption
15.2.8 Scenario H
149
Design and simulation of a grid-connected PV system for self-consumption
150
Design and simulation of a grid-connected PV system for self-consumption
151
Design and simulation of a grid-connected PV system for self-consumption
152
Design and simulation of a grid-connected PV system for self-consumption
153
Design and simulation of a grid-connected PV system for self-consumption
154
Design and simulation of a grid-connected PV system for self-consumption
15.2.9 Scenario SS
155
Design and simulation of a grid-connected PV system for self-consumption
156
Design and simulation of a grid-connected PV system for self-consumption
157
Design and simulation of a grid-connected PV system for self-consumption
158
Design and simulation of a grid-connected PV system for self-consumption
159
Design and simulation of a grid-connected PV system for self-consumption
160
YEAR 0 1 2 3 4 5 6 7 8 9 10 11 12
Expenses 14924 300 300 300 300 300 300 300 300 300 300 300 300
CAPEX 19924
Subvention -5000
OPEX 300 300 300 300 300 300 300 300 300 300 300 300
Benefit 0 2.635,80 € 2.635,80 € 2.635,80 € 2.635,80 € 2.635,80 € 2.635,80 € 2.635,80 € 2.635,80 € 2.635,80 € 2.635,80 € 2.635,80 € 2.635,80 €
Electricity injection 0 659,6064 659,6064 659,6064 659,6064 659,6064 659,6064 659,6064 659,6064 659,6064 659,6064 659,6064 659,6064
Electricity saved 820,92 820,92 820,92 820,92 820,92 820,92 820,92 820,92 820,92 820,92 820,92 820,92
Car electricity saved 1644,08 1644,08 1644,08 1644,08 1644,08 1644,08 1644,08 1644,08 1644,08 1644,08 1644,08 1644,08
Amortization 796,96 796,96 796,96 796,96 796,96 796,96 796,96 796,96 796,96 796,96 796,96 796,96
BBT -14.924,00 € 2.327,65 € 2.327,65 € 2.327,65 € 2.327,65 € 2.327,65 € 2.327,65 € 2.327,65 € 2.327,65 € 2.327,65 € 2.327,65 € 2.327,65 € 2.327,65 €
TAX (21%) 488,81 € 488,81 € 488,81 € 488,81 € 488,81 € 488,81 € 488,81 € 488,81 € 488,81 € 488,81 € 488,81 € 488,81 €
BAT 1.838,84 € 1.838,84 € 1.838,84 € 1.838,84 € 1.838,84 € 1.838,84 € 1.838,84 € 1.838,84 € 1.838,84 € 1.838,84 € 1.838,84 € 1.838,84 €
Economic analysis
Amortization 796,96 796,96 796,96 796,96 796,96 796,96 796,96 796,96 796,96 796,96 796,96 796,96
Cashflow -14924 2.335,80 € 2.335,80 € 2.335,80 € 2.335,80 € 2.335,80 € 2.335,80 € 2.335,80 € 2.335,80 € 2.335,80 € 2.335,80 € 2.335,80 € 2.335,80 €
Cumulative cashflow -14.924,00 € -12.588,20 € -10.252,40 € -7.916,60 € -5.580,80 € -3.245,00 € -909,20 € 1.426,60 € 3.762,41 € 6.098,21 € 8.434,01 € 10.769,81 € 13.105,61 €
Updated cashflow 2.123,46 € 1.930,41 € 1.754,92 € 1.595,38 € 1.450,35 € 1.318,50 € 1.198,64 € 1.089,67 € 990,61 € 900,55 € 818,68 € 744,26 €
Annual NPV 272,73 € 247,93 € 225,39 € 204,90 € 186,28 € 169,342179 153,9474355 139,9522141 127,2292855 115,6629868 105,1481698 95,58924531
NPV -12.800,54 € -12.800,54 € -12.800,54 € -12.800,54 € -12.800,54 € -12.800,54 € -12.800,54 € -12.800,54 € -12.800,54 € -12.800,54 € -12.800,54 € -12.800,54 €
IRR 1.668,02 €
PAYBACK 9%
PAYBACK 6,4
13 14 15 16 17 18 19 20 21 22 23 24 25
300 300 300 300 300 300 300 300 300 300 300 300 300
300 300 300 300 300 300 300 300 300 300 300 300 300
Design and simulation of a grid-connected PV system for self-consumption
2.635,80 € 2.635,80 € 2.635,80 € 2.635,80 € 2.635,80 € 2.635,80 € 2.635,80 € 2.635,80 € 2.635,80 € 2.635,80 € 2.635,80 € 2.635,80 € 2.635,80 €
659,6064 659,6064 659,6064 659,6064 659,6064 659,6064 659,6064 659,6064 659,6064 659,6064 659,6064 659,6064 659,6064
820,92 820,92 820,92 820,92 820,92 820,92 820,92 820,92 820,92 820,92 820,92 820,92 820,92
1644,08 1644,08 1644,08 1644,08 1644,08 1644,08 1644,08 1644,08 1644,08 1644,08 1644,08 1644,08 1644,08
796,96 796,96 796,96 796,96 796,96 796,96 796,96 796,96 796,96 796,96 796,96 796,96 796,96
2.327,65 € 2.327,65 € 2.327,65 € 2.327,65 € 2.327,65 € 2.327,65 € 2.327,65 € 2.327,65 € 2.327,65 € 2.327,65 € 2.327,65 € 2.327,65 € 2.327,65 €
488,81 € 488,81 € 488,81 € 488,81 € 488,81 € 488,81 € 488,81 € 488,81 € 488,81 € 488,81 € 488,81 € 488,81 € 488,81 €
1.838,84 € 1.838,84 € 1.838,84 € 1.838,84 € 1.838,84 € 1.838,84 € 1.838,84 € 1.838,84 € 1.838,84 € 1.838,84 € 1.838,84 € 1.838,84 € 1.838,84 €
796,96 796,96 796,96 796,96 796,96 796,96 796,96 796,96 796,96 796,96 796,96 796,96 796,96
2.335,80 € 2.335,80 € 2.335,80 € 2.335,80 € 2.335,80 € 2.335,80 € 2.335,80 € 2.335,80 € 2.335,80 € 2.335,80 € 2.335,80 € 2.335,80 € 2.335,80 €
15.441,41 € 17.777,21 € 20.113,01 € 22.448,81 € 24.784,61 € 27.120,41 € 29.456,21 € 31.792,01 € 34.127,81 € 36.463,61 € 38.799,42 € 41.135,22 € 43.471,02 €
676,60 € 615,09 € 559,17 € 508,34 € 462,13 € 420,11 € 381,92 € 347,20 € 40,53917128 286,94 € 260,86 € 237,14 € 215,59 €
86,89931392 78,99937629 71,81761481 65,28874074 59,35340067 53,95763697 49,05239725 44,59308841 40,53917128 36,85379207 33,50344734 30,4576794 27,68879945
-12.800,54 € -12.800,54 € -12.800,54 € -12.800,54 € -12.800,54 € -12.800,54 € -12.800,54 € -12.800,54 € -12.800,54 € -12.800,54 € -12.800,54 € -12.800,54 € -12.800,54 €
161