USER INTERFACE You can now scroll through the contents key to move to the next parameter.
of each folder, modify it or use its func- PLEASE NOTE: It is strongly recommended
The user has a display and four keys for
tions. If you do not use the keyboard for to switch off and switch on again the con-
controlling status and programming of the
over 15 seconds (time-out) or if you press troller anytime parameters have been
instrument.
the “fnc” key once, the last value shown changed to prevent malfunctioning on
KEYS AND MENUS on the display is confirmed and you return configuration and/or ongoing timings.
to the previous screen mask.
UP key Scrolls through the menu PASSWORD
items
Increases the values
MACHINE STATUS MENU The password “PA1” allows access to level
(See Machine Status Menu Diagram) 1 parameters. In the standard configura-
DOWN key Scrolls through the menu items To access the “Machine Status” menu tion passwords is not present.
Decreases the values
Press and quickly release the “set” key. To enable it (value 0) and assign the
The label “SP1” appears. desired value, access the “Programming”
fnc key
fnc ESC function (exit) By using the “UP” and “DOWN” keys you menu, within the folder with the “diS”
can scroll through the other folders in the label. If passwords is enabled, you will see
set key Accesses the setpoint menu: it at the entrance of the “Programming”
set Accesses the menus -SP1: Setpoint 1 setting folder. menu.
Confirms the commands -SP2: Setpoint 2 setting folder.
Setpoint 1 (Setpoint 2) Setting COPY CARD
Access the “Machine Status” menu by The Copy Card is an accessory connected
out 2 out 1 pressing and quickly releasing the “set” to the TTL serial port which allows pro-
f nc key. The label of the “SP1” folder appears. gramming quickly the instrument parame-
(To set Setpoint 2 use the “UP” and ters (upload and download parameter’s
“DOWN” keys until iy is shown “SP2”. map). The operation is performed as fol-
set
To display the Setpoint 1 (2) value press lows:
IC915 the “set” key again. Format
The value appears on the display. This command allows copy card formatting,
At start-up the instrument performs a To change the Setpoint 1 (2) value, use an operation necessary in case of first use
Lamp Test; for few seconds the display and the “UP” and “DOWN” keys within 15 sec- or to copy maps with different models.
the leds blink, in order to verify their onds. Warning: if the copy card has been pro-
integrity and correct operation. The instru- If the parameter is LOC = y the Setpoint grammed, using the “Fr” the data entered
ment has two main menus: the “Machine cannot be changed. are erased. This operation cannot be can-
Status” and “Programming” menu. celled.
PROGRAMMING MENU Upload
ACCESSING AND USING MENUS (See Programming Menu Diagram) This operation loads the programming
Resources are arranged in a menu, which To enter the “Programming” menu, press parameters from the instrument.
can be accessed by pressing and quickly the “set” key for more than 5 seconds. Download
releasing the “set” key (“Machine Status” If specified, the access PASSWORD will be This operation downloads to the instru-
menu) or by holding down the “set” key requested, (parameter “PA1”), and the ment the programming parameters.
for more than 5 seconds (“Programming” label of the first folder will follow. The operations are performed accessing
menu). To scroll through the other folders, use the folder identified by the “FPr” label and
To access the contents of each folder, indi- the “UP” and “DOWN” keys; selecting, according to the case, “UL”, “dL”
cated by the relevant label, just press the To enter the folder, press “set”. The label or “Fr” commands; the operation is con-
“set” key once. of the first visible parameter appears. To firmed by pressing the “set” key. If the
scroll through the other parameters, use operation is successful an “y” is displayed,
the “UP” and “DOWN” keys; to change the on the contrary, if it fails a “n” will be dis-
parameter, press and release “set”, then played.
set the desired value using the “UP” and NOTE:
“DOWN” keys, and confirm with the “set” • UPLOAD: instrument --> Copy Card
• DOWNLOAD: Copy Card --> instru-
LED ment.
Download “from reset (instrumennt
Position Related Function Status OFF”
OUT1 relay 1 (OUT1) ON when the regulator is started up; blinking in case of delay, Connect the copy card with the instru-
protection or blocked enabling
ment OFF (not under voltage).
OUT2 relay 2 (OUT2) ON when the regulator is started up; blinking in case of delay, When the instrument is switched on the
protection or blocked enabling programming parameters will be down-
loaded into the instrument; after the
Alarm ON when the alarm is enabled; blinking when the alarm is silenced
lamp-test the diplay will show for about 5
seconds:
• label dLY if copy operation successful ELECTRICAL LIABILITY AND RESIDUAL
• label DLn if not WIRING RISKS
PLEASE NOTE:
• after the download operation the instru- Attention! Never work on electrical Invensys Controls Italy S.r.L. shall not be
ment will immediately work with the new connections when the machine is liable for any damages deriving from:
parameters map setting switched on. - installation/use other than that pre-
The instrument is equipped with screw ter- scribed and, in particular, that which does
KEYBOARD LOCKING minal boards for connection of electrical not comply with safety standards anticipat-
The instrument includes a facility for dis- cables with a diameter of 2.5 mm2 (one ed by regulations and/or those given here-
abling the keyboard, by programming the conductor only per terminal for power in;
“LOC” parameter (see folder with “diS” connections). - use on boards which do not guarantee
label). If the keyboard is locked, you can For the capacity of the terminals, see the adequate protection against electric shock,
still access the programming menu by label on the instrument. water or dust under the conditions of
pressing the “set” key. The relay contacts are voltage free. Do not assembly applied;
The Setpoint can also be viewed. exceed the maximum current allowed; in - use on boards which allow access to dan-
case of higher loads, use an appropriate gerous parts without the use of tools;
DIAGNOSTICS contactor. Make sure the power supply - tampering with and/or alteration of the
voltage complies with the one required by products;
The alarm condition is always signalled by the instrument.
the buzzer (if present) and by the led of In 12V versions the power supply must be TECHNICAL DATA
the alarm icon provided by a security transformer with
Frontal panel protection: IP65.
the protection of a delayed 250 mA fuse.
Casing: plastic body in resin type
The alarm signal produced by a faulty reg- Probes have no connection polarity and
PC+ABS UL94 V-0, inspection window in
ulator probe (referred to probe 1) can be extended using a regular bipolar
polycarbonate, buttons in thermoplastic
cable (note that the extension of the
resin.
Error table probes affects the EMC electromagnetic
Dimensions: frontal panel 74x32 mm,
compatibility of the instrument: pay depth 59 mm (without wirings).
DISPLAY ERROR extreme attention to wiring). Installation: on panel, with drilling tem-
E1 regulator probe fault Probe cables, power supply cables and the plate 71x29 mm (+0.2/–0.1 mm).
TTL serial cables should be distant from Use temperature: –5…55 °C.
is shown as E1 on the instrument display power cables. Storage temperature.: –30…85 °C.
When the sensor detects an error condi- CONDITIONS OF USE Use environment humidity: 10…90 % RH
tion: (not condensing).
• the code E1 is displayed PERMITTED USE Storage environment humidity: 10…90% RH
• the regulator is activated as indicated by For safety reasons the instrument must be (not condensing).
the "On1 (On2)" and "OF1 (OF2)" parame- installed and used according to the Viewing range:
ters if programmed for the duty cycle or: instruction provided and in particular, • NTC: –50…110°C (–58…230°F);
under normal conditions, parts bearing • PTC: –50…140°C (–58…302°F)
On1 (On2) OF1 (OF2) regulator output dangerous voltage levels must not be without decimal point (selectable through
0 0 OFF accessible. parameter on 3 digit & 1/2 + mark display.
0 >0 OFF The device must be adequately protected
>0 0 ON Serial: TTL for connection to Copy Card.
>0 >0 dc from water and dust as per the application Analog input: one PTC or NTC input
and must also only be accessible via the (programmable by parameter).
use of tools (with the exception of the Digital outputs: 1 SPDT output on 8(3)A
frontlet). 1/2 hp, 1 SPST output on 8(3)A 1/2 hp
INSTALLATION The device is ideally suited for use on configurables. (for relay capabilities see
household appliances and/or similar refrig- label on the instrument)
The instrument is designed for panel eration equipment and has been tested Measuring range: from –50 to 140 °C.
mounting. Make a hole of 29x71 mm, with regard to the aspects concerning Accuracy: 0.5% better than end scale + 1
insert the instrument and fix it using the European reference standards on safety. It digit.
brackets provided. Do not mount the is classified as follows: Resolution: 0,1°C (0,1°F within +199,9°F,
instrument in humid and/or dirty places; it • according to its manufacture: as an auto- 1°F over).
is suitable for use in ordinary polluted matic electronic control device to be Consumption
places. Ventilate the place in proximity to incorporated by independent mounting; • model 230V: 3 VA max.
the instrument colling slits. • according to its automatic operating fea- • model 12V: 1,5 VA max.
,,
tures: as a 1 B-type operated control type; Power supply: 12 Va/c ±10% or 230Va
• as a Class A device in relation to the cat- ±10% 50/60 Hz.
egory and structure of the software
Warning: check the power supply specified
UNPERMITTED USE on the instrument label; for relay and
,,
Any other use other than that permitted is power supply capacities, contact the Sales
de facto prohibited. It should be noted Office).
that the relay contacts provided are of a
practical type and therefore subject to
fault. Any protection devices required by
,
product standards or dictated by common
sense due to obvious safety reasons should
be applied externally.
scroll
rE2 set level 1 par
parameters
change
par value
diS set level 1 par
* DEFAULT column: for parameters HC1/2, HS1/2, LS1/2, DF1/2, H00/01/10 the default depends don the model.
* VALUE column: to be filled manually, with customized settings (if different from the default value).
(!) WARNING!
• If one or more of these parameters highlighted with (!) are modified, teh controller must be switched off and switched on again to ensure correct operation.
• It is strongly recommended, anyway to switch off and switch on again the controller anytime parameters have been changed to prevent malfunctioning on configuration
and/or ongoing timings
HC1=H HC2=C
ON-OFF Regulation Diagram ON-OFF regulation diagram
independent. On
Off Off On
The outputs regulate as they as
H01=in
completely independent dF1 dF2
OUTPUT 2 OUTPUT 1
ON-OFF regulation diagram
Neutral Zone. On
Off On
NOTE: if dF1 and dF2 are both
=0 outputs will open when they dF2 dF1
Wiring diagram
A
1 - 2 N.C. regulator 1 relay output (OUT1) IC 915 NTC-PTC - 12 V
1 - 3 N.O. regulator 1 relay output (OUT1) OUT1 OUT2
4 - 5 N.O. regulator 2 relay output (OUT2)
6 - 7 Power supply 1,5 VA max. (12V version)
Pb1
Power supply 3 VA max. (230V version)
8 - 10 Probe 1 input (regulator) Pb1 1 2 3 4 5 6 7 8 9 10
A TTL input for Copy Card
Pb1
1 2 3 4 5 6 7 8 9 10
5/2003 eng
cod. 9IS22086