Instrumentation Submittal
المقاول
مصنع حلوان للصناعات المتطورة
Table of contents:
1- Instrument List
2- Open channel flowmeter (Radar flowmeter)
- GWF
- Nivus
3- Dissolved oxygen & PH transmitters & sensors
- E+H
- HACH
4- Level meter
- Siemens
- Vega
5- Float switch
- Flygt
6- Pressure transmitter
- E+H
- WIKA
7- Ultrasonic flowmeter
- Siemens
- E+H
8- Pressure gauge
- WIKA
9- Level meter (with two elements & relay)
- E+H
• Controller
• Sensor
- Siemens
• Controller
• Sensor
10- Pressure Switch
- WIKA
11- Magnetic Flowmeter
- E+H
- Siemens
1-Instrument List
TAG NO. Description Location Mounting Device purpose Vendor Model 1 Model 2 Range Power supply
LSH 1501 FLOAT SWITCH HEAD WORKS FIELD MOUNTED USED TO DETECT HIGH THE WATER LEVEL IN RELAXATION CHAMBER (UCM-10-001) FLYGT ENM-10 0-1 m X
FLOW METER
GWF (GWF) (NIVUS)
FIT 1501 A (Open channel) HEAD WORKS FIELD MOUNTED USED TO MEASURE , DETECT AD TRANSMIT TO PLC THE TOTAL AMOUNT OF WATER FEEDING THE PLANT 0-3000 m3/h 220 VAC 50/60 Hz SELF POWERED
NIVUS Q-Eye radar Nivu flow 550/7550
(With Optional Enclosure)
(HACH) (E+H)
PH/Temp METER HEAD WORKS HACH-
AIT 1501 FIELD MOUNTED USED TO MEASURE , DETECT AD TRANSMIT TO PLC THE TOTAL AMOUNT OF PH IN RELAXATION CHAMBER (UCM-10-001) Transmitter :SC 4500 Transmitter :CM 442 1_12 220 VAC 50/60 Hz SELF POWERED
(With Relays) (UCM-10-001) E+H
Sensor: DPD1P1 Sensor: CPS11D
SIEMENS- (Siemens) (Vega)
LT 1501 LEVEL METER HEAD WORKS FIELD MOUNTED USED TO MEASURE, INDICATE AND TRANSMIT TO PLC THE WATER LEVEL IN RELAXATION CHAMBER (UCM-10-001) 0-10 m 220 VAC 50/60 Hz SELF POWERED
VEGA Probe LU 240 VEGAPLUS 31
(Siemens) (E+H)
LEVEL METER SIEMENS-
LT 001 HEAD WORKS FIELD MOUNTED USED TO MEASURE, INDICATE AND TRANSMIT TO PLC THE WATER LEVEL BEFORE AND AFTER SCREEN MS-10-001 Transmitter :MultiRanger 100/200 Transmitter :Prosonic FMU90 0-1.5 m 220 VAC 50/60 Hz SELF POWERED
(WITH TWO ELEMENTS AND RELAY) E+H
Sensor: XPS10/15F Sensor: Prosonic S FDU90
(Siemens) (E+H)
LEVEL METER SIEMENS-
LT 002 HEAD WORKS FIELD MOUNTED USED TO MEASURE, INDICATE AND TRANSMIT TO PLC THE WATER LEVEL BEFORE AND AFTER SCREEN MS-10-002 Transmitter :MultiRanger 100/200 Transmitter :Prosonic FMU90 0-1.5 m 220 VAC 50/60 Hz SELF POWERED
(WITH TWO ELEMENTS AND RELAY) E+H
Sensor: XPS10/15F Sensor: Prosonic S FDU90
(Siemens) (E+H)
LEVEL METER SIEMENS-
LT 003 HEAD WORKS FIELD MOUNTED USED TO MEASURE, INDICATE AND TRANSMIT TO PLC THE WATER LEVEL BEFORE AND AFTER SCREEN MS-10-002 Transmitter :MultiRanger 100/200 Transmitter :Prosonic FMU90 0-1.5 m 220 VAC 50/60 Hz SELF POWERED
(WITH TWO ELEMENTS AND RELAY) E+H
Sensor: XPS10/15F Sensor: Prosonic S FDU90
PISL-001 PRESSURE SWITCH HEAD WORKS FIELD MOUNTED USED TO DETECT LOW PRESSURE IN SERVICE WATER LINE OF SCREENS WIKA PGS 23.100 0-1 bar X
(HACH) (E+H)
DISSOLVED OXYGEN METER USED TO MEASURE, INDICATE AND TRANSMIT TO PLC T THE AMOUNT OF THE DISSOLVED OXYGEN IN THE BIOLOGICAL HACH-
AIT 201A AERATION SYSTEM FIELD MOUNTED Transmitter :SC 4500 Transmitter :CM 442 0-20 mg/l 220 VAC 50/60HZ SELF POWERED
(WITH RELAYS) REACTOR#A (UTK-20-001) E+H
Sensor: LDO 2 Sc Sensor: Oxymax COS61D
(HACH) (E+H)
DISSOLVED OXYGEN METER USED TO MEASURE, INDICATE AND TRANSMIT TO PLC T THE AMOUNT OF THE DISSOLVED OXYGEN IN THE BIOLOGICAL HACH-
AIT 201B AERATION SYSTEM FIELD MOUNTED Transmitter :SC 4500 Transmitter :CM 442 0-20 mg/l 220 VAC 50/60HZ SELF POWERED
(WITH RELAYS) REACTOR#B (UTK-20-002) E+H
Sensor: LDO 2 Sc Sensor: Oxymax COS61D
(HACH) (E+H)
DISSOLVED OXYGEN METER USED TO MEASURE, INDICATE AND TRANSMIT TO PLC T THE AMOUNT OF THE DISSOLVED OXYGEN IN THE BIOLOGICAL HACH-
AIT 201C AERATION SYSTEM FIELD MOUNTED Transmitter :SC 4500 Transmitter :CM 442 0-20 mg/l 220 VAC 50/60HZ SELF POWERED
(WITH RELAYS) REACTOR#C (UTK-20-003) E+H
Sensor: LDO 2 Sc Sensor: Oxymax COS61D
(HACH) (E+H)
DISSOLVED OXYGEN METER USED TO MEASURE, INDICATE AND TRANSMIT TO PLC T THE AMOUNT OF THE DISSOLVED OXYGEN IN THE BIOLOGICAL HACH-
AIT 201D AERATION SYSTEM FIELD MOUNTED Transmitter :SC 4500 Transmitter :CM 442 0-20 mg/l 220 VAC 50/60HZ SELF POWERED
(WITH RELAYS) REACTOR#D (UTK-20-004) E+H
Sensor: LDO 2 Sc Sensor: Oxymax COS61D
USED TO MEASURE, INDICATE AND TRANSMIT TO PLC THE WATER LEVEL IN SLUDGE CHAMBER VEGA- (Siemens) (Vega)
LT 3501 LEVEL METER SLUDGE CHAMBER FIELD MOUNTED 0-10 m 12.5 - 42 VDC LOOP POWERED
(UTK-35-001) SIEMENS Probe LU 240 VEGAPLUS 31
USED TO DETECT LOW LEVEL IN RAS & WAS SUMP
LSL 3501 FLOAT SWITCH RAS & WAS SUMP FIELD MOUNTED FLYGT ENM-10 0-13 m X
(UTK-35-001)
FLOW METER USED TO MEASURE , DETECT AD TRANSMIT TO PLC THE TOTAL AMOUNT OF SIEMENS- (Siemens) (E+H)
FIT 1501 C WAS PUMPS OUTLET FIELD MOUNTED 0-3000 m3/h 220 VAC 50/60 Hz SELF POWERED
(Magnetic) DISCHARGE OF WAS PUMPS OUT LINE DN 150 E+H Sitrans MAG 5100 W Promag W400
FLOW METER USED TO MEASURE , DETECT AD TRANSMIT TO PLC THE TOTAL AMOUNT OF WATER OF OUTLET SIEMENS- (Siemens) (E+H)
FIT 1501 D OUTLET OF STATION FIELD MOUNTED 0-3000 m3/h 220 VAC 50/60 Hz SELF POWERED
(UltraSonic) DISCHARGE CHAMBER E+H Sitrans FS220 Prosonic Flow 91W
LSHH 6501 FLOAT SWITCH SUPERNATANT SUMP FIELD MOUNTED USED TO DETECT HIGH HIGH LEVEL IN SUPERNATANT SUMP (UTK-65-001) FLYGT ENM-10 0-10 m X
LSH 6501 FLOAT SWITCH SUPERNATANT SUMP FIELD MOUNTED USED TO DETECT HIGH LEVEL IN SUPERNATANT SUMP (UTK-65-001) FLYGT ENM-10 0-10 m X
LSL 6501 FLOAT SWITCH SUPERNATANT SUMP FIELD MOUNTED USED TO DETECT LOW LEVEL IN SUPERNATANT SUMP (UTK-65-001 FLYGT ENM-10 0-10 m X
LSLL 6501 FLOAT SWITCH SUPERNATANT SUMP FIELD MOUNTED USED TO DETECT LOW LOW LEVEL IN SUPERNATANT SUMP (UTK-65-001 FLYGT ENM-10 0-10 m X
PISH 001 PRESSURE SWITCH HEAD WORKS FIELD MOUNTED USED TO DETECT HIGH PRESSURE OF DISCHARGE OF GRIT PUMP MSP-10-001 WIKA PGS 23.100 0-1 bar X
PISH 002 PRESSURE SWITCH HEAD WORKS FIELD MOUNTED USED TO DETECT HIGH PRESSURE OF DISCHARGE OF GRIT PUMP MSP-10-002 WIKA PGS 23.100 0-1 bar X
PISH 003 PRESSURE SWITCH HEAD WORKS FIELD MOUNTED USED TO DETECT HIGH PRESSURE OF DISCHARGE OF GRIT PUMP MSP-10-003 WIKA PGS 23.100 0-1 bar X
PISH 301 PRESSURE SWITCH BLOWERS FIELD MOUNTED USED TO DETECT HIGH PRESSURE OF DISCHARGE OF AIR BLOWER MBL-25-001 WIKA PGS 23.100 0-1 bar X
I N T E C H
INTERNATIONAL ENVIRONMENTAL TECHNOLOGIES Co.
TAG NO. Description Location Mounting Device purpose Vendor Model 1 Model 2 Range Power supply
PISH 302 PRESSURE SWITCH BLOWERS FIELD MOUNTED USED TO DETECT HIGH PRESSURE OF DISCHARGE OF AIR BLOWER MBL-25-002 WIKA PGS 23.100 0-1 bar X
PISH 303 PRESSURE SWITCH BLOWERS FIELD MOUNTED USED TO DETECT HIGH PRESSURE OF DISCHARGE OF AIR BLOWER MBL-25-003 WIKA PGS 23.100 0-1 bar X
PISH 304 PRESSURE SWITCH BLOWERS FIELD MOUNTED USED TO DETECT HIGH PRESSURE OF DISCHARGE OF AIR BLOWER MBL-25-004 WIKA PGS 23.100 0-1 bar X
PISH 305 PRESSURE SWITCH BLOWERS FIELD MOUNTED USED TO DETECT HIGH PRESSURE OF DISCHARGE OF AIR BLOWER MBL-25-005 WIKA PGS 23.100 0-1 bar X
PISH 306 PRESSURE SWITCH BLOWERS FIELD MOUNTED USED TO INDICATE AND DETECT HIGH PRESSURE OF DISCHARGE OF AIR BLOWER MBL-25-006 WIKA PGS 23.100 0-1 bar X
PISH 3501 PRESSURE SWITCH RAS PUMPS FIELD MOUNTED USED TO INDICATE AND DETECT HIGH PRESSURE OF DISCHAGE OF RETURN SLUDGE PUMP MVP-35-001 WIKA PGS 23.100 0-4 bar X
PISH 3503 PRESSURE SWITCH RAS PUMPS FIELD MOUNTED USED TO INDICATE AND DETECT HIGH PRESSURE OF DISCHAGE OF RETURN SLUDGE PUMP MVP-35-003 WIKA PGS 23.100 0-4 bar X
PISH 3505 PRESSURE SWITCH RAS PUMPS FIELD MOUNTED USED TO INDICATE AND DETECT HIGH PRESSURE OF DISCHAGE OF RETURN SLUDGE PUMP MVP-35-005 WIKA PGS 23.100 0-4 bar X
PISH 6001 PRESSURE SWITCH WAS PUMPS FIELD MOUNTED USED TO INDICATE AND DETECT HIGH PRESSURE OF DISCHAGE OF EXCESS SLUDGE PUMP MSP-60-001 WIKA PGS 23.100 0-4 bar X
PISH 6002 PRESSURE SWITCH WAS PUMPS FIELD MOUNTED USED TO INDICATE AND DETECT HIGH PRESSURE OF DISCHAGE OF EXCESS SLUDGE PUMP MSP-60-002 WIKA PGS 23.100 0-4 bar X
PISH 3511 PRESSURE SWITCH DEWATERING PUMPS FIELD MOUNTED USED TO INDICATE AND DETECT HIGH PRESSURE OF DISCHAGE OF DEWATERING PUMP MSP-35-001 WIKA PGS 23.100 0-2 bar X
PISH 3512 PRESSURE SWITCH DEWATERING PUMPS FIELD MOUNTED USED TO INDICATE AND DETECT HIGH PRESSURE OF DISCHAGE OF DEWATERING PUMP MSP-35-002 WIKA PGS 23.100 0-2 bar X
PISH 6501 PRESSURE SWITCH SUPERNATANT PUMPS FIELD MOUNTED USED TO INDICATE AND DETECT HIGH PRESSURE OF DISCHAGE OF SUPERNATANT PUMP MSP-65-001 WIKA PGS 23.100 0-4 bar X
PISH 6502 PRESSURE SWITCH SUPERNATANT PUMPS FIELD MOUNTED USED TO INDICATE AND DETECT HIGH PRESSURE OF DISCHAGE OF SUPERNATANT PUMP MSP-65-002 WIKA PGS 23.100 0-4 bar X
PRESSURE SWITCH
PISH 6003 THICKENED SLUDGE PUMPS FIELD MOUNTED USED TO INDICATE AND DETECT HIGH PRESSURE OF DISCHAGE OF THICKENED SLUDGE PUMP MPP-60-001 X
(Included in Pump Vendor Package)
PRESSURE SWITCH
PISH 6004 THICKENED SLUDGE PUMPS FIELD MOUNTED USED TO INDICATE AND DETECT HIGH PRESSURE OF DISCHAGE OF THICKENED SLUDGE PUMP MPP-60-002 X
(Included in Pump Vendor Package)
USED TO INDICATE DISCHARGE PRESSURE OF WATER DISCHAGE FROM THICKENED SLUDGE PUMPS MPP-60-001,MPP-60-
PI 6005 PRESSURE GAUGE THICKENED SLUDGE PUMPS FIELD MOUNTED WIKA PG 233.50 0-6 bar X
002
Note:We use PIT-101 pressure transmitter instead of pressure switches as there is no place to put pressure switches
before blowers outlet valves so we put atransmitter after blowers discharge valves to get reading of pressure and stop
blowers in case of blower operation and no reading on it (valve closed)
BANI GHALEB WASTEWATER TREATMENT PLANT
- GWF
Radar Flowmeter
Manufacturer: GWF
Type: Stationary non-contact flow meter for open channels and partially filled pipes
Description: The Q-Eye Radar flow meter is designed for stationary flow monitoring of
slightly to heavily polluted media in open channels or partially filled pipes. Q-Eye Radar is
an exceptionally versatile flow measurement system designed for continuous operation
and suitable for application in wastewater and storm water sewers as well as open
channels and rivers. Compact construction combined with the non-contact measurement
principle enables an easy installation and use. Additionally, the Q-Eye Radar measures bi-
directional flow over the entire measurement range and near zero flow velocities down to
0.02 m/s.
Features
Range: ± 15 m/s
Measurement of low velocities down to 0.02 m/s Bi-directional measurement over the entire
flow range.
Analog inputs for external sensors (2-wire loop-powered) Multiple analog and digital
outputs, user programmable
Output: 4 – 20 mA
Q-Eye Radar
Stationary non-contact flow meter for open
channels and partially filled pipes
■ Platform-independent web interface for ■ Measurement of low velocities down to 0.02 m/s
configuration, operation and maintenance:
■ Bi-directional measurement over the entire flow range
Easy and fast setup with multi-language
graphical user interface. Parametrization ■ Uncertainty velocity:
with any mobile device, no software needed ■ RV11: ± 0.5 % of reading ± 0.01 m/s
■ RV24: ± 1 % of reading
■ Integrated Wi-Fi access point and LAN
interface, optional mobile connection: ■ Uncertainty flow: Typically < 5 % of reading
Efficient system integration, real-time ■ Integrated Wi-Fi access point
remote access anytime and anywhere
■ Graphical user interface in multiple languages
■ Adaptable to surcharge conditions:
Combine radar measurement with ■ All units for display and data storage can be customized by the user
submersible pressure transducer ■ Preselection of typical cross sections or user-definable irregular shapes
The Q-Eye Radar flow meter is designed for stationary flow monitoring of
slightly to heavily polluted media in open channels or partially filled pipes.
The level sensor is used to measure the height of the water at the exact
point where the surface velocity was determined. Q-Eye Radar calculates
the area and total discharge based on the user-definable channel profile.
The Q-Eye Radar system is composed of a wall-mounted transmitter, a radar velocity sensor and any level sensor (ultrasonic,
radar or pressure). For surcharge conditions, submersible level sensors are available.
Transmitter
The Q-Eye Radar transmitter incorporates all the required algorithms and
software to ensure measurement accuracy and repeatability. The IP66
(NEMA 4X) compact housing features a 4 x 20 alphanumeric LCD display
and a 4 button keypad.
All configuration data as well as measured and calculated data are stored
inside a 16 GB Micro-SD card. The transmitter controls the measurements,
calculates the flow rate and provides freely programmable current outputs,
Wall-mounted transmitter
status alarms, frequency outputs and totalizer readings.
The Q-Eye Radar is designed to accept any depth sensor (ultrasonic, radar
and pressure) with an analog input (4-20 mA). Our Q-Eye Radar transmitter
offers the best in wastewater measurement.
The radar velocity sensors are operating at the free 24 GHz band frequency
RV11 radar RV24 radar and make use of the Doppler effect to gain information about the speed of the
velocity sensor velocity sensor
moving surface. The sensor does this by beaming a microwave signal to the
flow surface at a defined angle and analyzing the signal reflection from particles
and disturbances moving with the flow. The frequency of this returning signal
has been shifted by an amount directly proportional to the spot velocity.
Alternatively, the system can be equipped with an additional radar water level
sensor, which is independent of ambient air temperature.
For some applications, flow conditions change from open channel flow to
surcharged conditions (e.g. in sewers). Down-looking level sensors cannot
provide information when submerged. Consequently, Q-Eye Radar can be
equipped with an optional depth sensor (pressure transducer) which provides
Pressure level continuous measurement in surcharge events.
sensor
256
Technical data
Keyboard 4 keys
4x
6,4
1x M16x1.5 (IP68)
1x M20x1.5 (IP68) 3x M16x1.5 (IP68)
Approval IP66 (NEMA 4)
Enclosure Aluminum
Operating temperature - 20 °C to + 60 °C
Storage temperature - 20 °C to + 70 °C
30 30 30 30 30
Q-Eye Radar is available with a variety of ultrasonic and radar down-looking level sensors as well as a submersible pressure level
sensor. Please consult the separate brochure for further details on the depth sensors.
Headquarter Sales
GWF MessSysteme AG GWF Technologies GmbH T +49 8341-959990
Obergrundstrasse 119 T +41 41 319 50 50 Gewerbestraße 46f info@gwf-technologies.de
6005 Lucerne, Switzerland info@gwf.ch, www.gwf.ch 87600 Kaufbeuren, Germany www.gwf-technologies.de
- Nivus
Radar Flowmeter
Manufacturer: nivus
Type: Fix installation flow meter for slightly to heavily polluted media in part filled and full
pipes, channels and flumes.
Transmitter:
Up to 0/4–20 mA with
Outputs: 0/4–20 mA
Sensor
Protection: IP 68
Operating Temp: 30 to 70 °C
Modular System
Our Radar flow measurement system is modular. Therefore we can offer the Your Advantages
suitable solution for each application. + Ideal level measurement on the correct
location
+ Choose the optimum level
measurement method for the
application
Radar flow sensor fastening variants Radar flow compact module
+ Optional ultrasonic measurement for
reliable flow measurement in
surcharge conditions
+ Enhanced accuracy by redundant
ultrasonic flow measurement
Modular radar flow measurement installation with separate Compact radar flow measurement with ultrasonic or radar
ultrasonic level measurement level measurement in single housing
Normal conditions: Radar flow measurement with combined Surcharge conditions: Ultrasonic flow measurement detects
ultrasonic or radar level measurement in operation. The flow profile with combined hydrostatic level measurement. An
surcharge sensor is not active at low level flow. additional ultrasonic level measurement detects sediments on
ground level.
Your Advantages
24
40
60
ø6.5
80 ø10.4
130 M16
45°
17
90°
3
Side view
12
237
63,5
320 Dimensions in mm
Dimensions in mm
Surcharge Flow-Level Sensor (optional)
113.5
Flow Measurement
Measurement method ultrasonic profile scanner (cross correlation)
OFR Radar Sensor Measurement range - 6 m/s up to + 6 m/s
Measurement method Radar - 24 GHz - ISM band Protection IP 68
Measurement range 0.15 m/s - 10 m/s Measurement uncertainty 0,5% of measurement value (v: 0,05 - 0,5 m/s);
Temperature range -30 °C to 70 °C 1% of measurement value (v > 0,5 m/s)
-20 °C to 50 °C in ATEX Zone 1 Level Measurement
Measurement distance 0.3 m - 10 m Measurement method hydrostatic for surcharge detection
Protection IP 68 - completely encapsulated Measurement range 0 - 10 m
Enclosure material high-performance composite Sediment Detection
Interface RS485 for connection to NivuFlow or Measurement method ultrasound
OCM Pro CF transmitters Measurement range 0-5m
Measurement uncertainty ± 0.5 % of measurement value; Ex Approval II 2 G EEx ib IIB T4 Gb; TÜV 03 ATEX 2262;
± 0,01 m/s IECEx TUN 15.0014
Ex Approval II 2 G Ex ib IIB T4 Gb; TÜV 16 ATEX 185271X;
IECEx 16.0034X
Transmitter, Type NivuFlow
140
52
135
134 (5.3")
195 74
88
1" NPT
Power supply 10 - 28 V DC
Outputs HART® – loop powered (2-wire)
4 - 20 mA (3.8 - 22 mA)
Functions level, distance, empty space, volume
and linearisation using 16 breakpoints
Operating temperature -40 to 80 °C 354,8 ca. 130
Radar flow measurement and level measurement NivuFlow 7550 Connection plug with cage clamp terminals
+ surcharge measurement with ultrasonic Inputs up to 7 x 4 - 20 mA, up to 4 x RS 485
cross correlation sensor Outputs up to 4 x 0/4 – 20 mA, up to 5 x relays (SPDT)
Hybrid flow measurement with radar and NivuFlow 7550 Data memory 2.0 GB internal memory, flexibly expandable,
ultrasonic cross correlation sensors readout on faceplate via USB stick
+ level measurement (radar, ultrasonic, hydrostatic) Communication Modbus, HART®
Measurement uncertainty flow (Q): ± 5% typical;
± 2% under reference conditions
- E+H
• PH Sensor:
Model: Digital pH sensor Memosens CPS11D/E
Description: Memosens 2.0 pH electrode for standard applications in
process and water
& wastewater industries
Specs at a glance:
Measurement range Application A • pH: 1 to 12
Process temperature Application A: –15 to 80 °C (5 to 176 °F)
1-/2-channel transmitter
Liquiline CM442
Expandable multiparameter field device for all
industries
F L E X Benefits:
• Clever simplicity:
One controller for all parameters and applications, intuitive user
interface, automatic sensor recognition, hot plug & play with pre-
calibrated Memosens sensors.
• High flexibility:
Universal modules for all parameters minimize spare part stock and
allow for easy extension to up to 8 channels at any time.
• Seamless system integration:
Unique portfolio of communication standards suits every distributed
control system (DCS).
• Simple and safe commissioning:
Saving configuration on SD card enables fast set-up on duplicate
installations.
• Process control from a distance:
Integrated web server that allows the operator to remotely view
diagnostic data, perform configurations, or access device parameters in
any web browser - even via Smartphone.
• Higher availability, lower costs:
Heartbeat Technology enables status-oriented maintenance and easy
verification of the entire measuring point and helps to carry out
optimization measures.
Specs at a glance
• Input 1 to 2x Memosens digital input
• Output / communication 2 to 4x 0/4...20 mA current outputs
Alarmrelay, 2x relay
• Ingres protection IP67
Liquiline CM442
Application
Modular 4 wire controller
Multichannel: 1/2 digital channels for Memosens protocol
Multiparameter: pH, redox, ISFET, conductivity inductive and conductive,
dissolved oxygen, nitrate and turbidity
Two sensors connectable in any combination
Functionality modular extendable at any time
Plug and play for modules and sensors
Characteristic
Robust plastic housing
All non-ex applications
Design
2x Memosens input, 2 to 4x current output, Alarmrelay
2x relay, SD card for software update and copy & paste of setup
Material
Housing base: PC-FR
Housing seal: EPDM
Dimension
237 x 194 x 162 mm
9.33 x 7.64 x 7.38 inch
2 Endress+Hauser
Liquiline CM442
Ingres protection
IP67
Input
1 to 2x Memosens digital input
Output / communication
2 to 4x 0/4...20 mA current outputs
Alarmrelay, 2x relay
Additional certifications
EAC, cCSAus, MCERTS
pH Measuring principle
Potentiometric
Application
Modular 4 wire controller
Multichannel: 1/2 digital channels for Memosens protocol
Multiparameter: pH, redox, ISFET, conductivity inductive and conductive,
dissolved oxygen, nitrate and turbidity
Two sensors connectable in any combination
Functionality modular extendable at any time
Plug and play for modules and sensors
Characteristic
Robust plastic housing
All non-ex applications
Design
2x Memosens input, 2 to 4x current output, Alarmrelay,
2x relay, SD card for software update and copy & paste of setup
3 Endress+Hauser
Liquiline CM442
pH Material
Housing base: PC-FR
Housing seal: EPDM
Dimension
237 x 194 x 162 mm
9.33 x 7.64 x 7.38 inch
Process temperature
-20 to 60 °C (0 to 140 °F)
Ingres protection
IP66 / IP67
Input
1 to 2x Memosens digital input
2x 0/4 to 20mA input optional
2x Digital input optional
Output / communication
2 to 8x 0/4 to 20 mA current outputs
Alarmrelay, 2x relay, ProfibusDP, Modbus RS485, Modbus TCP, Ethernet
Additional certifications
EAC, cCSAus, MCERTS
Application
Modular 4 wire controller
Multichannel: 1/2 digital channels for Memosens protocol
Multiparameter: pH, redox, ISFET, conductivity inductive and conductive,
dissolved oxygen, nitrate and turbidity
Two sensors connectable in any combination
Functionality modular extendable at any time
Plug and play for modules and sensors
4 Endress+Hauser
Liquiline CM442
Design
2x Memosens input, 2 to 4x current output, Alarmrelay
2x relay, SD card for software update and copy & paste of setup
Material
Housing base: PC-FR
Housing seal: EPDM
Dimension
237 x 194 x 162 mm
9.33 x 7.64 x 7.38 inch
Process temperature
-20 to 60 °C (0 to 140 °F)
Ingres protection
IP66 / IP67
Input
1 to 2x Memosens digital input
2x 0/4 to 20mA input optional
2x Digital input optional
Output / communication
2 to 8x 0/4 to 20 mA current outputs
Alarmrelay, 2x relay, ProfibusDP, Modbus RS485, Modbus TCP, Ethernet
Additional certifications
EAC, cCSAus, MCERTS
5 Endress+Hauser
Liquiline CM442
Disinfection Application
Modular 4 wire controller
Multichannel: 1/2 digital channels for Memosens protocol
Multiparameter: pH, redox, ISFET, conductivity inductive and conductive,
dissolved oxygen, nitrate and turbidity
Two sensors connectable in any combination
Functionality modular extendable at any time
Plug and play for modules and sensors
Characteristic
Robust plastic housing
All non-ex applications
Design
2x Memosens input, 2 to 4x current output, Alarmrelay
2x relay, SD card for software update and copy & paste of setup
Material
Housing base: PC-FR
Housing seal: EPDM
Dimension
237 x 194 x 162 mm
9.33 x 7.64 x 7.38 inch
Process temperature
-20 to 60 °C (0 to 140 °F)
Input
1 to 2x Memosens digital input
Output / communication
2 to 4x 0/4 to 20 mA current outputs
Alarmrelay, 2x relay
Additional certifications
EAC, cCSAus, MCERTS
6 Endress+Hauser
Liquiline CM442
Characteristic
Robust plastic housing
All non-ex applications
Design
2x Memosens input, 2 to 4x current output, Alarmrelay
2x relay, SD card for software update and copy & paste of setup
Process temperature
-20 to 60 °C (0 to 140 °F)
Application
Modular 4 wire controller
Multichannel: 1/2 digital channels for Memosens protocol
Multiparameter: pH, redox, ISFET, conductivity inductive and conductive,
dissolved oxygen, nitrate and turbidity
Two sensors connectable in any combination
Functionality modular extendable at any time
Plug and play for modules and sensors
Output / communication
2 to 8x 0/4 to 20 mA current outputs
Alarmrelay, 2x relay
Input
1 to 2x Memosens digital input
7 Endress+Hauser
Liquiline CM442
Conductivity Application
Modular 4 wire controller
Multichannel: 1/2 digital channels for Memosens protocol
Multiparameter: pH, redox, ISFET, conductivity inductive and conductive,
dissolved oxygen, nitrate and turbidity
Two sensors connectable in any combination
Functionality modular extendable at any time
Plug and play for modules and sensors
Characteristic
Robust plastic housing
All non-ex applications
Design
2x Memosens input, 2 to 4x current output, Alarmrelay
2x relay, SD card for software update and copy & paste of setup
Material
Housing base: PC-FR
Housing seal: EPDM
Dimension
237 x 194 x 162 mm
9.33 x 7.64 x 7.38 inch
Process temperature
-20 to 60 °C (0 to 140 °F)
Ingres protection
IP66 / IP67
Input
1 to 2x Memosens digital input
Output / communication
2 to 8x 0/4 to 20 mA current outputs
Alarmrelay, 2x relay
8 Endress+Hauser
Liquiline CM442
Application
Modular 4 wire controller
Multichannel: 1/2 digital channels for Memosens protocol
Multiparameter: pH, redox, ISFET, conductivity inductive and conductive,
dissolved oxygen, nitrate and turbidity
Two sensors connectable in any combination
Functionality modular extendable at any time
Plug and play for modules and sensors
Characteristic
Robust plastic housing
All non-ex applications
Design
2x Memosens input, 2 to 4x current output, Alarmrelay,
2x relay, SD card for software update and copy & paste of setup
Material
Housing base: PC-FR
Housing seal: EPDM
Dimension
237 x 194 x 162 mm
9.33 x 7.64 x 7.38 inch
Process temperature
-20 to 60 °C (0 to 140 °F)
Ingres protection
IP66 / IP67
9 Endress+Hauser
Liquiline CM442
Turbidity Input
1 to 2x Memosens digital input
2x 0/4 to 20mA input optional
2x Digital input optional
Output / communication
2 to 4x 0/4 to 20 mA current outputs,
Alarmrelay, 2x relay
Additional certifications
EAC, cCSAus, MCERTS
Application
Modular 4 wire controller
Multichannel: 1/2 digital channels for Memosens protocol
Multiparameter: pH, redox, ISFET, conductivity inductive and conductive,
dissolved oxygen, nitrate and turbidity
Two sensors connectable in any combination
Functionality modular extendable at any time
Plug and play for modules and sensors
Characteristic
Robust plastic housing
All non-ex applications
Design
2x Memosens input, 2 to 4x current output, Alarmrelay,
2x relay, SD card for software update and copy & paste of setup
Material
Housing base: PC-FR
Housing seal: EPDM
10 Endress+Hauser
Liquiline CM442
Process temperature
-20 to 60 °C (0 to 140 °F)
Ingres protection
IP66 / IP67
Input
1 to 2x Memosens digital input
Output / communication
2 to 8x 0/4 to 20 mA current outputs
Alarmrelay, 2x relay
Additional certifications
EAC, cCSAus, MCERTS
Endress+Hauser AG addresses.endress.com
Switzerland info@endress.com
TI00387C/07/EN/15.21 Products Solutions Services
71517960
2021-02-02
Technical Information
Oxymax COS61D/COS61
Optical sensor for measuring dissolved oxygen
Application
• Wastewater treatment plants
• Oxygen measurement and regulation in the activated sludge basin for a highly
efficient biological cleaning process
• Monitoring the oxygen content in the wastewater treatment plant outlet
• Water monitoring
Oxygen measurement in rivers, lakes or seas as an indicator of the water quality
• Water treatment
Oxygen measurement for status monitoring, e.g. of drinking water (oxygen
enrichment, corrosion protection etc.)
• Fish farming
Oxygen measurement and regulation for optimum living and growth conditions
Your benefits
• Optical technology:
• Minimum maintenance
• Maximum availability
• Sensor with digital signal processing:
• Calibration data saved in sensor
• High degree of EMC protection thanks to digital communication with the
transmitter
• Extended maintenance intervals and a high degree of longterm stability
• Intelligent self-monitoring guarantees reliable measured values
• No flow needed - measurement possible in still water
• COS61D - the Liquiline sensor
• Plug&Play: Safe communication based on Memosens protocol
• Optionally with M12 plug for fast connection to the transmitter
• COS61 - the Liquisys sensor
• Compatible with tried-and-tested COS31 with COM2x3W: Easy measuring point
changeover to optical technology
• Compatible with COS41 with COM2x3D with conversion kit
Oxymax COS61D/COS61
Measurement result
‣ The sensor returns a signal that depends on the concentration of oxygen in the medium.
The air pressure can be either set statically or entered via an additional sensor. The medium
temperature is automatically recorded in the sensor. Both values are taken into consideration in the
calculation of the oxygen concentration.
The sensor provides measured values for temperature and partial pressure as well as a raw measured
value. This value corresponds to the fluorescence decay time and is approx. 20 μs in air and
approx. 60 μs in oxygen-free media.
2 Endress+Hauser
Oxymax COS61D/COS61
1 2
6 3
5 4
A0042837
Endress+Hauser 3
Oxymax COS61D/COS61
COS61
A complete measuring system comprises:
• Oxymax COS61 oxygen sensor
• Transmitter, e.g. Liquisys COM2x3-W
• Sensor cable
• Assembly, e.g. flow assembly COA250, immersion assembly CYA112 or
retractable assembly COA451
Optionally:
• Flexdip CYH112 assembly holder for immersion operation
• VS junction box (for cable extension)
• Cleaning system
1 2
6 3
5 4
A0012885
Input
Measured variables Dissolved oxygen [mg/l, µg/l, ppm, ppb or %SAT or hPa]
Measuring ranges Measuring ranges apply for 20 °C (68 °F) and 1013 hPa (15 psi)
With Liquiline CM44x, CM44xR, CM44P or with Liquisys COM2x3-W:
• 0 to 20 mg/l
• 0 to 400 hPa
• 0 to 200 % SAT
4 Endress+Hauser
Oxymax COS61D/COS61
Power supply
Electrical connection COS61D
Connection data
Sensor cable connected directly to the terminal connector of the basic module of the transmitter
PK U+
GY U–
GN COM A
YE COM B
Optional: sensor cable plug connected to the M12 sensor socket of the transmitter
With this type of connection, the transmitter is already wired at the factory.
Connection to field device
The sensor is directly connected to the transmitter via the special measuring cable with the SXP plug.
4 SXP connector
Terminal Sensor with fixed cable (OMK) Sensor with TOP68 plug connection (CYK71)
COM223
Core Assignment Core Assignment
87 YE +UB YE +UB
0 GN 0V WH 0V
Performance characteristics
Response time From air to nitrogen at reference operating conditions:
t90 : 60 s
Endress+Hauser 5
Oxymax COS61D/COS61
COS61
Measuring range Maximum measured error
< 12 mg/l 0.02 mg/l or ±1 % of reading
12 mg/l to 20 mg/l ±2% of reading
Operating life of sensor cap >2 years (under reference operating conditions, protect against direct sunlight)
Installation
Installation examples
Immersion operation Universal holder and chain assembly
1 2 1 2
7 3
6 3
4
4
6
5
5
A0042857 A0042858
6 Endress+Hauser
Oxymax COS61D/COS61
1 2
6 3
5
4
A0042859
1 2
5
3
4
A0042860
Endress+Hauser 7
Oxymax COS61D/COS61
Float
The CYA112 float is for use in the case of large fluctuations in water level, for example in rivers or
lakes.
4
Ø200 (7.87)
500 (19.69)
G1
5
6
7
A0032159
9 Dimensions in mm (inch)
8 3 2
7 6 5 4
A0013319 A0030570
Environment
Ambient temperature –20 to 60 °C (–4 to 140 °F)
at 95% relative air humidity, non-condensing
8 Endress+Hauser
Oxymax COS61D/COS61
Electromagnetic COS61D
compatibility Interference emission and interference immunity as per EN 61326: 2005, Namur NE 21:2007
COS61
Interference emission and interference immunity as per EN 61326: 1997 / A1: 1998
Process
Process temperature –5 to +60 ˚C (20 to 140 ˚F)
Mechanical construction
Design, dimensions COS61D
21 (0.83)
15 (0.59)
46.5 (1.83)
NPT ¾"
G1
12 (0.47)
11 (0.43)
232.5 (9.15)
243.5 (9.59)
186 (7.32)
197 (7.76)
77 (3.04) / 66 (2.59)*
Ø40 (1.57)
A0042896 A0042897
Endress+Hauser 9
Oxymax COS61D/COS61
G1
G1
220 (8.66)
220 (8.66)
186 (7.32)
186 (7.32)
Ø40 (1.57)
Ø40 (1.57)
A0027092 A0027093
77 (3.04)
50 (1.97)
11 (0.43)
19 (0.75)
Ø40 (1.57)
°
24
28.5 (1.12)
B
61 (2.40)
A0043286
16 Dimensions in mm (inch)
A Compressed air cleaning COS61/61D OD 6/8 mm (additional information → 14
B Compressed air cleaning COS61/61D OD 6.35 mm (¼") (additional information → 14
10 Endress+Hauser
Oxymax COS61D/COS61
Maximum cable length max. 100 m (330 ft), incl. Cable extension
Endress+Hauser 11
Oxymax COS61D/COS61
Interface COS61D
Memosens protocol
COS61
RS 485
EAC (COS61D-GR) The product has been certified according to guidelines TP TC 004/2011 and TP TC 020/2011 which
apply in the European Economic Area (EEA). The EAC conformity mark is affixed to the product.
CSA GP (COS61D-CA) Dieses Gerät hat eine CSA GP Zulassung und erfüllt die folgenden Anforderungen:
• Versorgung durch eine Klasse 2 oder begrenzte Energiequelle gemäß CSA 61010-1-12.
• Überspannungskategorie I.
• Umgebungsbedingungen: max. Höhenlage 2 000 m (6 560 ft)
2)
CSAus NI Cl 1, Div 2 Explosionsgefährdete Bereiche nach CSAus CL 1, DIV 2
(COS61D-CJ)
• Das Gerät muss in einem Gehäuse oder (Montage-)Schrank installiert werden, der nur mit einem
Werkzeug oder Schlüssel zugänglich ist.
• Beachten Sie die Control Drawing und die angegebenen Einsatzbedingungen im Anhang der
Betriebsanleitung sowie die dortigen Hinweise.
Ex-Zulassungen
Class 1, Division 2, Groups A, B, C und D T6; IP67/IP68 2)
Dieses Produkt erfüllt die Anforderungen der folgenden Normen:
• ANSI/UL 61010-1, 3. Ed.
• ANSI/UL 121201-2017
• ANSI/IEC 60529, Edition 2.2. 2013-08 Degrees of protection provided by enclosures (IP Code)
Installation und Betrieb in explosionsgefährdeten Bereichen CL 1, DIV 2
Dieses nicht-funkende Gerät hat folgende spezifizierte Explosionsschutz-Daten:
• CSAus CL 1, DIV 2
• Groups A, B, C, and D
• Temperaturklasse T6, –20 °C (–4 °F) ≤ Ta ≤ 60 °C (140 °F)
• IP-Schutzart: IP67/IP68
• Control drawing: 211050778
Ordering information
Product page www.endress.com/cos61
www.endress.com/cos61d
Product Configurator On the product page there is a Configure button to the right of the product image.
1. Click this button.
The Configurator opens in a separate window.
12 Endress+Hauser
Oxymax COS61D/COS61
2. Select all the options to configure the device in line with your requirements.
In this way, you receive a valid and complete order code for the device.
3. Export the order code as a PDF or Excel file. To do so, click the appropriate button on the right
above the selection window.
For many products you also have the option of downloading CAD or 2D drawings of the
selected product version. Click the CAD tab for this and select the desired file type using
picklists.
Accessories
The following are the most important accessories available at the time this documentation was
issued.
‣ For accessories not listed here, please contact your Service or Sales Center.
Flowfit COA250
• Flow assembly for oxygen measurement
• Product Configurator on the product page: www.endress.com/coa250
Technical Information TI00111C
Cleanfit COA451
• Manual retractable assembly made of stainless steel with ball valve shutoff
• For oxygen sensors
• Product Configurator on the product page: www.endress.com/coa451
Technical Information TI00368C
Endress+Hauser 13
Oxymax COS61D/COS61
14 Endress+Hauser
TI01493C/07/EN/01.20 Products Solutions Services
71486977
2020-06-29
Technical Information
Memosens CPS11E
pH sensor for standard applications in process
technology and environmental engineering
Application
• Long-term monitoring and limit control in processes with stable process conditions
• Chemical industry: strong acids/bases, plastic, pulp and paper industry
• Power plants (e. g. flue gas cleaning), oil and gas
• Incinerator plants
• Water and wastewater treatment
• Boiler feedwater and cooling water
• Well water and drinking water
• All industrial and municipal treatment plants
With ATEX, IECEx, CSA C/US, NEPSI, Japan and INMETRO approvals for use in
hazardous areas Zone 0, Zone 1 and Zone 2.
Your benefits
• Low-maintenance and robust thanks to large PTFE ring junction
• Can be used at pressures up to 17 bar (246.5 psi) (absolute)
• Process glass for standard applications (application A)
• Process glass also for highly alkaline applications (application B)
• Process glass for applications in media containing hydrofluoric acid (application F)
• Integrated NTC 30K temperature sensor for effective temperature compensation
• Optional: for media with low conductivity (reference system AS with salt storage)
• Optional: Poison-resistant reference with improved ion trap (reference system TA)
Other advantages provided by Memosens technology
• Maximum process safety thanks to non-contact, inductive signal transmission
• Data security thanks to digital data transmission
• Very easy to use as sensor data are saved in the sensor
• Predictive maintenance can be performed with the Memobase Plus CYZ71D by
recording sensor load data in the sensor
Memosens CPS11E
Measuring system A complete measuring system consists of the following components at least:
• pH sensor CPS11E
• Transmitter, e. g. Liquiline CM42, CM44x
• Memosens data cable CYK10 or CYK20
• Assembly
• Immersion assembly, e. g. Dipfit CPA111
• Flow assembly, e. g. Flowfit CPA250
• Retractable assembly, e. g. Cleanfit CPA871
• Permanent installation assembly, e. g. Unifit CPA842
Additional options are available depending on the application:
Automatic cleaning and calibration system, e. g. Liquiline Control CDC90
A0025757
2 Endress+Hauser
Memosens CPS11E
Dependability Reliability
Easy handling
Sensors with Memosens technology have integrated electronics that store calibration data and other
information (e. g. total hours of operation or operating hours under extreme measuring conditions).
Once the sensor has been connected, the sensor data are transferred automatically to the transmitter
and used to calculate the current measured value. As the calibration data are stored in the sensor,
the sensor can be calibrated and adjusted independently of the measuring point. The result:
• Easy calibration in the measuring lab under optimum external conditions increases the quality of
the calibration.
• Pre-calibrated sensors can be replaced quickly and easily, resulting in a dramatic increase in the
availability of the measuring point.
• Thanks to the availability of the sensor data, maintenance intervals can be accurately defined and
predictive maintenance is possible.
• The sensor history can be documented on external data carriers and in evaluation programs, e. g.
Memobase Plus CYZ71D.
• The saved application data of the sensor can be used to determine the continued use of the sensor
in a targeted manner.
Interference immunity
Data security thanks to digital data transmission
Memosens technology digitizes the measured values in the sensor and transmits the data to the
transmitter via a non-contact connection that is free from potential interference. The result:
• If the sensor fails or there is an interruption in the connection between the sensor and transmitter,
this is reliably detected and reported.
• The availability of the measuring point is reliably detected and reported.
Endress+Hauser 3
Memosens CPS11E
Safety
Maximum process safety
With inductive transmission of the measured value using a non-contact connection, Memosens
guarantees maximum process safety and offers the following benefits:
• All problems caused by moisture are eliminated:
• No corrosion at the connection
• Measured values cannot be distorted by moisture
• The transmitter is galvanically decoupled from the medium. Issues concerning "symmetrical high-
impedance" or "asymmetry" or the type of impedance converter are a thing of the past.
• Electromagnetic compatibility (EMC) is guaranteed by screening measures for the digital
transmission of measured values.
• Intrinsically safe electronics mean operation in hazardous areas is not a problem. Complete
flexibility thanks to individual Ex approvals for all components, such as sensors, cables and
transmitters.
Input
Measured variable pH value
Temperature
Power supply
Electrical connection
GY GND EY/NG
YE Com B
GN Com A
WH –
BN +
A0024019
Performance characteristics
Reference system Ag/AgCl reference lead, bridge electrolyte: gel KCl, 3M, AgCl-free (reference system TA)
4 Endress+Hauser
Memosens CPS11E
Installation
Orientation • Do not install the sensors upside-down.
• The installation angle from the horizontal must be at least 15°.
An installation angle < 15° is not permitted, as otherwise an air bubble will form. Contact between
the membrane glass and the reference lead will then no longer be guaranteed.
A
15° 15°
A0028039
Installation instructions • Before screwing in the sensor, make sure the assembly thread, the O-rings and the sealing surface
are clean and undamaged and that the thread runs smoothly.
• Pay attention to the installation instructions provided in the Operating Instructions of the
assembly used.
‣ Screw in the sensor and tighten by hand with a torque of 3 Nm (2.21 lbf ft) (specifications only
apply if installing in Endress+Hauser assemblies).
Environment
Ambient temperature range NOTICE
Risk of damage from frost!
‣ Do not use the sensor at temperatures below –15 °C (5 °F) .
Degree of protection IP 68 (10 m (33 ft) water column, 25 °C (77 °F), 45 days, 1 M KCl)
Process
Process temperature range Application A: –15 to 80 °C (5 to 176 °F)
Application B: 0 to 135 °C (32 to 275 °F)
Application F: 0 to 70 °C (32 to 158 °F)
Process pressure range Applications A and B: 0.8 to 17 bar (11.6 to 246.5 psi) absolute
Application F: 0.8 to 7 bar (11.6 to 101.5 psi) absolute
Endress+Hauser 5
Memosens CPS11E
LCAUTION
Pressurization of sensor due to prolonged use under increased process pressure
Possibility of sudden rupture and injury from glass splinters!
‣ Avoid fast heating of these pressurized sensors if they are used under reduced process pressure
or under atmospheric pressure.
‣ When handling these sensors, always wear protective goggles and appropriate protective gloves.
Conductivity Reference system AA, TA: minimum 50 μS/cm (minimized flow; pressure and temperature
must be stable)
Reference system AS: minimum 0.1 μS/cm (stainless steel flow assembly with grounding;
stable and minimized flow; pressure and temperature must be
stable)
Pressure-temperature
[psi] p [bar]
ratings
261 18
232 16
203 14
174 12
145 10
116 8 A
87 6
58 4
29 2 x
0 0 [°C]
-15 0 20 40 60 80 100 120 T
[°F]
5 32 68 104 140 176 212 248
A0039323-EN
4 Pressure-temperature ratings
A Application A
x Atmospheric pressure
[psi] p [bar]
261 18
232 16
203 14
174 12 B
145 10
116 8
87 6
58 4 F
29 2 x
0 0 [°C]
-15 0 20 40 60 80 100 120 140 T
[°F]
5 32 68 104 140 176 212 248 284
A0039326-EN
5 Pressure-temperature ratings
B Application B
F Application F
x Atmospheric pressure
6 Endress+Hauser
Memosens CPS11E
Mechanical construction
Design, dimensions
50(1.97)
50(1.97)
1 1
2 2
3
4 3
6 6
7 7
8 8
Ø 12 (0.47) Ø 12 (0.47)
A0042535 A0042536
6 CPS11E with salt storage. Engineering unit: 7 CPS11E with ion trap. Engineering unit: mm (in)
mm (in)
1 Memosens plug-in head with process connection
1 Memosens plug-in head with process connection 2 O-ring with thrust collar
2 O-ring with thrust collar 3 Reference lead
3 Reference lead 4 pH reference lead
4 pH reference lead 5 Ion trap
5 Salt storage 6 Junction
6 Junction 7 Temperature sensor
7 Temperature sensor 8 pH glass membrane
8 pH glass membrane
Weight Installed length 120 mm (4.72 in) 225 mm (8.86 in) 360 mm (14.17 in) 425 mm (16.73 in)
Weight 40 g (1.4 oz) 60 g (2.1 oz) 90 g (3.2 oz) 100 g (3.5 oz)
Plug-in head Memosens plug-in head for digital, non-contact data transmission, pressure resistance
16 bar (232 psi)(relative)
Endress+Hauser 7
Memosens CPS11E
Ex approval ATEX
II 1G Ex ia IIC T3/T4/T6 Ga
IECEx
Ex ia IIC T3/T4/T6 Ga
NEPSI
Ex ia IIC T3/T4/T6 Ga
CSA C/US
• IS Cl. I Div 1, GP A-D Ex ia IIC T3/T4/T6
• IS Cl. I Zone 0, AEx ia IIC T3/T4/T6
Japan Ex
Ex ia IIC T3/T4/T6 Ga
INMETRO
Ex ia IIC T3/T4/T6 Ga
Ex versions of digital sensors with Memosens technology are identified by an orange-red ring
on the plug-in head.
Pay attention to the instructions for Memosens data cable CYK10 and transmitter CM82.
TÜV certificate for Pressure resistance 16 bar (232 psi) relative, minimum three times the safety pressure
Memosens plug-in head
EAC The product has been certified according to guidelines TP TC 004/2011 and TP TC 020/2011 which
apply in the European Economic Area (EEA). The EAC conformity mark is affixed to the product.
Ordering information
Product page www.endress.com/cps11e
Product Configurator On the product page there is a Configure button to the right of the product image.
1. Click this button.
The Configurator opens in a separate window.
2. Select all the options to configure the device in line with your requirements.
In this way, you receive a valid and complete order code for the device.
3. Export the order code as a PDF or Excel file. To do so, click the appropriate button on the right
above the selection window.
For many products you also have the option of downloading CAD or 2D drawings of the
selected product version. Click the CAD tab for this and select the desired file type using
picklists.
8 Endress+Hauser
Memosens CPS11E
Accessories
The following are the most important accessories available at the time this documentation was
issued.
‣ For accessories not listed here, please contact your Service or Sales Center.
Cleanfit CPA875
• Retractable process assembly for sterile and hygienic applications
• For in-line measurement with standard sensors with 12 mm diameter, e.g. for pH, ORP, oxygen
• Product Configurator on the product page: www.endress.com/cpa875
Technical Information TI01168C
Dipfit CPA140
• pH/ORP immersion assembly with flange connection for very demanding processes
• Product Configurator on the product page: www.endress.com/cpa140
Technical Information TI00178C
Cleanfit CPA871
• Flexible process retractable assembly for water, wastewater and the chemical industry
• For applications with standard sensors with 12 mm diameter
• Product Configurator on the product page: www.endress.com/cpa871
Technical Information TI01191C
Cleanfit CPA473
• Stainless steel process retractable assembly with ball valve shutoff for particularly reliable
separation of the medium from the environment
• Product Configurator on the product page: www.endress.com/cpa473
Technical Information TI00344C
Cleanfit CPA474
• Plastic process retractable assembly with ball valve shutoff for particularly reliable separation of
the medium from the environment
• Product Configurator on the product page: www.endress.com/cpa474
Technical Information TI00345C
Dipfit CPA111
• Immersion and installation assembly made of plastic for open and closed vessels
• Product Configurator on the product page: www.endress.com/cpa111
Technical Information TI00112C
Flowfit CPA240
• pH/ORP flow assembly for processes with stringent requirements
• Product Configurator on the product page: www.endress.com/cpa240
Technical Information TI00179C
Flowfit CPA250
• Flow assembly for pH/ORP measurement
• Product Configurator on the product page: www.endress.com/cpa250
Technical Information TI00041C
Endress+Hauser 9
BLANSORA WASTE WATER TREATMENT PLANT
- HACH
Manufacturer: HACH
• Transmitter:
Description: One controller for 40+ sensors and 14 parameters The digital 1-channel SC
4500 Controller is compatible with our complete range of digital and analogue sensors.
There are 40+ sensors to choose – from Ammonium to Turbidity as well as special
parameters such as Oil in Water. The one-stop-shop controller and its family of sensors
monitor processes for all applications in wastewater, drinking and process water.
Output: 4-20 MA
IP: 65 / NEM 4X
• DO Sensor:
Enclosure rating: IP 68
• PH Sensor:
Model: HACH
glass electrodes perform well in this range. Some industrial applications require accurate
Measuring Range: 0 to 14 pH
Technical Data*
www.hach.com
Digital Controller SC4500 3
Compatible Instruments
Nutrients (Ammonium, Phosphate, Nitrate): Amtax sc, AN-ISE sc, A-ISE sc, N-ISE sc, Nitratax sc, Nitratax clear sc, Nitratax eco sc,
Nitratax plus sc, Nitratax 60 sc, Phosphax sc, Phosphax sc LR/MR/HR
Turbidity & Suspended Solids: TSS sc, Solitax sc, TU5300sc, TU5400sc, SS7 sc (in Bypass), Ultraturb seawater sc, 1720E,
Sonatax sc (Sludge Level)
Disinfection (Chlorine, Ozone, Chlorine dioxide): CL17sc, CL10sc, 9184sc, 9185sc, 9187sc
Organics: Uvas plus sc, Uvas eco sc (China only)
Dissolved Oxygen: LDO 2 sc
Conductivty & Concentration: 3798sc, 3700sc, 3422sc, Analog 3400 + Contacting Cond. Digital Gateway 6120700
pH/ORP: pHD sc, pHD-S sc, pHD analog + Digital Gateway 6120500, RC and PC analog sensor + Digital Gateway for conventional
analog pH and ORP sensors 6120600, 8362sc
Other: mA Input Module
Dimensions
Panel mounting dimensions
www.hach.com
4 Digital Controller SC4500
Order Information
Controller
LXV525.99A11551 SC4500 Controller, Prognosys, 5x mA Output, 2 digital Sensors, without plug
LXV525.99E11551 SC4500 Controller, Prognosys, 5x mA Output, 2 digital Sensors, US plug
LXV525.99A11541 SC4500 Controller, Prognosys, 5x mA Output, 1 digital Sensor, 1 mA Input, without plug
LXV525.99E11541 SC4500 Controller, Prognosys, 5x mA Output, 1 digital Sensor, 1 mA Input, US plug
LXV525.99AA1551 SC4500 Controller, Claros-enabled, 5x mA Output, 2 digital Sensors, without plug
LXV525.99EA1551 SC4500 Controller, Claros-enabled, 5x mA Output, 2 digital Sensors, US plug
LXV525.99AA1541 SC4500 Controller, Claros-enabled, 5x mA Output, 1 digital Sensor, 1 mA Input, without plug
LXV525.99EA1541 SC4500 Controller, Claros-enabled, 5x mA Output, 1 digital Sensor, 1 mA Input, US plug
Additional configurations are available. Please contact Hach Technical Support or your Hach representative.
Accessories
LXZ525.99.D0001 SC4500 mA Input Module
LXZ525.99.D0002 SC4x00 mA Output Module (5 Outputs)
LXZ525.99.C0002 SC4500 Ethernet IP Upgrade Kit
LXZ525.99.C0003 SC4500 Modbus TCP/IP Upgrade Kit
LXZ525.99.C0004 SC4500 Prognosys Upgrade Kit
LXZ525.99.00026 SC4500 Ethernet Cable M12 to M12 / C1D2, 10 m
LXZ525.99.00017 SC4500 USB Stick
LXZ524.99.00004 SC4x00 UV Protection Screen
LXZ524.99.00005 SC4x00 UV protection screen with sunroof
LXZ524.99.00033 SC4x00 Sunroof Visor
LXZ524.99.00036 SC4x00 Mounting Hardware Sunroof with Visor
LXZ524.99.00037 SC4x00 Sunroof with Visor
This instrument connects to Claros, Hach’s innovative Water With Hach Service, you have a global partner who
Intelligence System. Claros allows you to seamlessly connect understands your needs and cares about delivering timely,
and manage instruments, data, and process – anywhere, high-quality service you can trust. Our Service Team brings
anytime. The result is greater confidence in your data and unique expertise to help you maximize instrument uptime,
improved efficiencies in your operations. To unlock the full ensure data integrity, maintain operational stability, and reduce
potential of Claros, insist on Claros Enabled instruments. compliance risk.
DOC053.53.35316.Nov20
The new LDO generation - even simpler, even more reliable and even more cost-effective
Immersion or flow-through probe with optical luminescence measuring method. Calibration-free & drift-free.
No electrolyte or membrane changes due to the optical measurement method. The new LDO probe ensures there is only a minimal amount of
maintenance. The luminescence method means the measurement is unaffected by any type of interference.
Years of practical experience have shown that this method completely overcomes the disadvantages of traditional electrochemical O2
measurement methods.
Prognosys is a predictive diagnostic system that allows you to be proactive in your maintenance, by alerting you to upcoming instrument
issues. Know with confidence whether changes in your measurements are due to changes in your instrument or your water.
This instrument connects to Claros, Hach’s innovative Water Intelligence System, enabling you to seamlessly connect and manage instruments,
data, and process – anywhere, anytime. The result is greater confidence in your data and improved efficiency in your operations. To unlock the
full potential of Claros, insist on Claros Enabled instruments.
The optimised temperature sensor and the new 3D factory calibration make O2 measurement even more accurate
Remote functions for simple and convenient data transfer via Internet and SMS
Specifications
Accuracy: ±0.1 mg/L @ DO < 5 mg/L
Cable length: 10 m
Calibration method: All probes are factory calibrated and ready to use
The smart choice for accurate and reliable online process pH measurement
General Purpose Online Process pH Sensor with Integrated Digital Electronics for "Plug and Play" with Hach Digital SC Controllers - pHD
Technology, Glass pH Electrode, PEEK Housing, Convertible Mount, 10 m Cable
This instrument connects to Claros, Hach’s innovative Water Intelligence System, enabling you to seamlessly connect and manage instruments,
data, and process – anywhere, anytime. The result is greater confidence in your data and improved efficiency in your operations. To unlock the
full potential of Claros, insist on Claros Enabled instruments.
Exceptional Process pH Sensor Performance with the Differential Electrode pHD Measurement Technique
This field-proven technique uses three electrodes instead of the two normally used in conventional pH sensors. Process and reference
electrodes measure the pH differentially with respect to a third ground electrode. The end result is unsurpassed measurement accuracy, reduced
reference junction potential, and elimination of sensor ground loops. These process pH sensors provide greater reliability, resulting in less
downtime and maintenance.
Innovative Technology
The former GLI, now a Hach Company brand, invented the Differential Electrode Technique for pH measurement in 1970. The pHD™ sensor
series (U.S. Patent Number 6395158B1, dated May 28, 2002) takes this field-proven technology to a new level.
Specifications
Accuracy: ± 0.02 pH
Cable connection: Digital
Calibration method: Two point automatic, one point automatic, two point manual, one point manual.
Communication: Modbus
Drift: 0.03 pH per 24 hours, non-cumulative
Electrode type: General Purpose
Flow rate: 3 m (10 ft.) per second, maximum
Housing material: PEEK
Length: 271.3 mm
Measuring range: -2.0 - 14.0 pH
Mounting: Convertible
Operating temperature range: Digital Sensor: -5 - 70 °C
pH Range: 0 - 14 pH
Pressure range: Maximum 10.7 bar . 6.9 bar for Digital Sensor at 70°C, and 6.9 bar for Analog Sensor at 105°C.
Region: EU
Repeatability: ± 0.05 pH
Sensitivity: ± 0.01 pH
Sensor cable: 10 m (33 ft.) polyurethane, 4-conductor cable with one shield, rated to 105°C (221°F)
Sensor thread: 1" NPT
Storage conditions: 4 - 70 °C, 0-95% relative humidity (non-condensing)
Temperature accuracy: ± 0.5 °C
Temperature compensation: Automatic with NTC 300 Ω thermistor, or manually fixed at a user-entered temperature,
Required Accessories
• SC1000 Probe Module, 4 Sensors, 4x 4-20mA Out, 4x Relays, 110-240V AC, EU Cord (Item LXV400.99.2R121)
• SC1000 Display Module with Touchscreen (Item LXV402.99.00001)
BANI GHALEB WASTEWATER TREATMENT PLANT
4-Level meter
- Siemens
Level Transmitter
Manufacturer: Siemens
It works with liquids, slurries and bulk materials up to 12m (40 ft).
Communications: 4 to 20 mA
Enclosure type of protection: Non-Ex (ordinary locations) cCSAus, CE, RCM, EAC
Electrical connections/ cable entries: 2 x M20 x 1.5 (one general purpose polyamide
cable gland and one polyamide blocking plug provided).
Level Measurement
Continuous level measurement
Ultrasonic transmitters
SITRANS Probe LU240
■ Overview ■ Configuration
4
SITRANS Probe LU240 ultrasonic level transmitter, ideal for
level, volume, and volume flow measurements. It works with
liquids, slurries, and bulk materials up to 12 m (40 ft).
■ Benefits
• Continuous level measurement up to 12 m (40 ft) range
• Easy installation and simple startup
• Programming using 4-button HMI or SIMATIC PDM Pipe
• Communication using HART
• ETFE or PVDF transducers for chemical compatibility
Rungs
• Process Intelligence signal processing
• Auto False Echo Suppression for fixed obstruction avoidance
• Low power and current startup
• Optional Bluetooth configuration and monitoring via Seams
SITRANS mobile IQ
■ Application
SITRANS Probe LU240 is ideal for level monitoring in the water
and wastewater industry, chemical storage vessels, and small
bulk hoppers. SITRANS Probe LU240 mounting
Level Measurement
Continuous level measurement
Ultrasonic transmitters
SITRANS Probe LU240
■ Technical specifications
Mode of operation Process connection
Measuring principle Ultrasonic level measurement Threaded connection 2" NPT [(Taper), ASME B1.20.1]
Typical application Level measurement in storage R 2" [(BSPT), EN 10226]
vessels and simple process vessels or
Inputs G 2" [(BSPP), EN ISO 228-1]
Measuring range Flange connection 3 inch (80 mm) universal flange
• 3 m (10 ft) 0.2 ... 3 m (8 inch ... 10 ft) Other connection FMS 200 mounting bracket
• 6 m (20 ft) model 0.2 ... 6 m (8 inch ... 20 ft) (see page 4/186) or customer
• 12 m (40 ft) model 0.2 ... 12 m (8 inch ... 40 ft) supplied mount
Frequency 54 kHz Display and Controls
Outputs Interface Local: LCD display
mA/HART Remote: Available via HART or
Bluetooth
• Range 4 ... 20 mA
• Accuracy ± 0.0096 mA Configuration 4-button HMI
4 • HART version
• Startup current
7
3.6 mA
Memory Non-volatile EEPROM, no battery
required
• Fail-safe Programmable as high, low, or hold Power supply
(loss of echo) per NAMUR NE43
4 ... 20 mA/HART 10.5 ... 30 V DC
Performance
Certificates and Approvals
Resolution 3 mm (0.12 inch)
General FM, CCSAUS, CE, RCM, EAC, KC,
Accuracy
VLAREM
3 m (10 ft) version 10 mm (0.39 inch) Hazardous
6 m (20 ft), 12 m (40 ft) version • ± the greater of 0.15 % of range or • Intrinsically Safe
6 mm (0.25 inch) [valid from 0.25 m
(0.82 ft)] - Europe ATEX II 1G Ex ia IIC T4 Ga
• ± 2 mm (0.08 inch) on ranges 4 m - International IECEx SIR 18.0013X Ex ia IIC T4 Ga
(13 ft) or less - USA/Canada FM/CCSAUS Class I, Div. 1,
Groups A, B, C, D, Class II, Div. 1,
Non-repeatability 3 mm (0.12 inch)
Groups E, F, G, Class III T4
Blanking distance 0.2 m (0.66 ft) - Brazil INMETRO Ex ia IIC T4 Ga
Update time 4s - China NEPSI Ex ia IIC T4 Ga
- South Africa SABS Ex ia IIC Tx Ga
Temperature compensation Built-in to compensate over
- Russia EAC Ex 1G Ex ia IIC T4 Ga
temperature range
- Korea KOSHA KSs Ex ia IIC T4
Beam angle 10° • Non-incendive
Rated operating conditions - USA FM, Class I, Div. 2, Groups A, B, C, D
Ambient conditions Tx
• Location Indoor/outdoor Marine Lloyd’s Register,
• Ambient temperature • Storage: -40 ... +85 °C American Bureau of Shipping (ABS),
(-40 ... +185 °F) DNV GL, Bureau Veritas, CCS
• Operating: -40 ... +80 °C
Metrological MCERTS, CPA,
(-40 ... +176 °F)
Kazakhstan pattern approval
• Relative humidity/ingress protection Suitable for outdoor
• Installation category I Radio (Bluetooth) USA, Canada, EU, China
• Pollution degree 4
Medium conditions
• Temperature at flange or threads -40 ... +85 °C (-40 ... +185 °F)
• Pressure (vessel) 0.5 bar g (7.25 psi g)
Display -20 … +80 °C (-4 … +176 °F)
Design
Material (enclosure) PBT (Polybutylene Terephthalate)
Degree of protection Type 4X, Type 6, IP66, IP68
Weight 0.93 kg (2.1 lb)
Cable inlet 2 x M20 x 1.5 cable gland or
1 x ½" NPT thread
Material (transducer) ETFE (Ethylene Tetrafluoroethylene)
or PVDF (Polyvinylidene Fluoride)
Buna-N seal
Level Measurement
Continuous level measurement
Ultrasonic transmitters
SITRANS Probe LU240
Level Measurement
Continuous level measurement
Ultrasonic transmitters
SITRANS Probe LU240
Accessories Article No.
Tag, stainless steel, 12 x 45 mm, one text line 7ML1930-1AC
(max. 16 characters)
Stainless steel FMS200 universal box bracket mounting 7ML1830-1BK
kit
3" ASME/DIN Universal mounting adapter, 2" NPT, ETFE 7ML1830-1BT
3" ASME/DIN Universal mounting adapter, 2" BSP, ETFE 7ML1830-1BU
2" NPT nylon plastic locknut 7ML1830-1DT
2" BSP nylon plastic locknut 7ML1830-1DQ
Cable Gland Polyamide - General Purpose A5E34457564
(-20 ... +60 °C)
Bluetooth kit A5E50514198
SITRANS LT500, a versatile, single and multi-vessel 7ML60..-.....-....
level monitor/controller for virtually any application in a
wide range of industries.
Spare Parts
Level Measurement
Continuous level measurement
Ultrasonic transmitters
SITRANS Probe LU240
■ Options
7ML1830-1BK
4
SITRANS Probe LU240 with optional FMS 200 universal box bracket
190
(7.48)
24
(0.94)
Level Measurement
Continuous level measurement
Ultrasonic transmitters
SITRANS Probe LU240
■ Dimensional drawings
113.4
(4.46)
4
51 Ø108
(2.0) (4.25)
Threaded coupling
1/2" NPT
(optional)
Bluetooth adapter
(optional)
64
(2.52)
231.4
(9.11)
Transducer housing
21
PVDF or ETFE (0.83)
107.4
(4.22)
Thread type 2" NPT, 79.4
(3.12)
2" BSP,
or PF2/G
Ø 51
(2.0)
Level Measurement
Continuous level measurement
Ultrasonic transmitters
SITRANS Probe LU240
■ Circuit diagrams
Female
end of
display
cable
Male end 4
of display
cable
- Vega
Level Transmitter
Manufacturer: VEGA
Model: - VEGAPULS 31
Deviation: ≤ 2 mm
Beam angle: 8°
Operating voltage: 12 … 35 V DC
VEGAPULS 31
Two-wire 4 … 20 mA/HART
Radar sensor for continuous level measurement
Technical data
Measuring range up to 15 m (49.21 ft)
Deviation ≤ 2 mm
Beam angle 8°
Measuring frequency W-band (80 GHz technology)
Output signal 4 … 20 mA/HART
Process fitting Thread G1½, 1½ NPT, R1½
Process pressure -1 … +3 bar (-100 … +200 kPa/-
14.5 … +43.51 psig)
Process temperature -40 … +80 °C (-40 … +176 °F)
Bluetooth standard Bluetooth 5.0 (downward compatible to
Bluetooth 4.0 LE)
Max. effective range 25 m (82 ft)
Operating voltage 12 … 35 V DC
Protection rating IP66/IP67 acc. to IEC 60529, Type 4X acc.
to UL 50
Materials
The wetted parts of the instrument are made of PVDF. The process seal
Application area is made of FKM.
The VEGAPULS 31 is the ideal radar sensor for non-contact level You will find a complete overview of the available materials and seals in
measurement in standard applications in all industrial plants. the "Configurator" at www.vega.com and "Products".
It is particularly suitable for level measurement and measured value
visualisation in water treatment, storage tanks with acids and lyes, addi-
Housing versions
tives in all industrial areas or for measuring levels through a plastic tank
or IBC container. The housing is made of PBT plastic and is available in protection rating
The sensor is suitable both for measuring liquids and for use on small IP66/IP67.
bulk solids silos or bulk solids containers.
Electronics versions
Your benefit
The instrument is available in the 4 … 20 mA/HART electronics version.
• Maintenance-free operation due to non-contact 80 GHz radar tech-
nology
Approvals
• Exact measurement results independent of medium properties and
process conditions Worldwide approvals are available for VEGA instruments, e.g. for use in
• Local display for easy checking of the level. Maintenance-free opera- hazardous areas, on ships or in hygienic applications.
tion due to non-contact measuring principle The technical data in the respective safety instructions are valid for ap-
proved instruments (e.g. with Ex approval). In some cases, these data
can differ from the data listed herein.
Function
You can find detailed information on the existing approvals with the ap-
The sensor emits a continuous radar signal through the antenna. The propriate product on our homepage.
emitted signal is reflected by the medium and received as an echo by
the antenna.
The frequency difference between the emitted and received signal
is proportional to the distance and depends on the filling height. The
determined filling height is converted into a respective output signal and
output as measured value.
VEGA Grieshaber KG, Am Hohenstein 113, 77761 Schiltach/Germany, www.vega.com VEGAPULS 31 - 58364-EN-200305
Adjustment Dimensions
Adjustment on site
On-site adjustment of the device is carried out via the integrated display
VEGAPULS 31
and adjustment unit.
Adjustment via the signal cable
The adjustment of the instrument is carried out via the interface adapter
VEGACONNECT and a PC with the adjustment software PACTware
ø 77,5 mm
(3.05")
156 mm
smartphones/tablets (iOS/Android) or Windows PCs.
(6.14")
122 mm
(4.80")
SW 50
G1½
1½ - 14 NPT R 1½
50 mm
(1.97")
25 mm
(0.98")
ø 58 mm
(2.28")
1 2 3
Dimensions VEGAPULS 31
1 Thread G1½
2 Thread 1½ NPT
3 Thread R1½
Wireless connection to standard operating devices
Operation is via a free app from the "Apple App Store", the "Goog-
le Play Store" or the "Baidu Store". Alternatively, adjustment can also be Mounting accessories
carried out via PACTware/DTM and a Windows PC.
For the VEGAPULS 31 the suitable mounting accessories for ceiling or
wall mounting is available.
Electrical connection Mounting strap with adjustable sensor holder for sensors with lateral cable outlet -
Wall mounting (example)
You can find further information on the mounting accessory on our
homepage.
Information
(+)1 2(-)
You can find further information on the VEGA product line on our home-
2 page.
In the download section on our homepage you'll find operating
instructions, product information, brochures, approval documents,
instrument drawings and much, much more.
1
Software accessories such as the current device software and the ap-
propriate operating software are also available there.
Connection compartment VEGAPULS 31
1 Voltage supply, signal output
2 Plug connector for the display and adjustment module or interface adapter Instrument selection
You can find details on electrical connection in the instrument operating On our homepage under "Products" you can select the suitable meas-
instructions at www.vega.com/downloads. uring principle and instrument for your application.
You can find detailed information on the instrument versions at www.
vega.com and "Products".
VEGA Grieshaber KG, Am Hohenstein 113, 77761 Schiltach/Germany, www.vega.com VEGAPULS 31 - 58364-EN-200305
BANI GHALEB WASTEWATER TREATMENT PLANT
5-Float switch
- Flygt
Level Switch
Manufacturer: Flygt
Model: ENM-10
Liquid temp: 0 – 60oC
Liquid density: 0.65 – 1.52 cm3
IP: 68, 13m
Capacity of micro switch:
Resistive 250 VAC, 10A
Inductive: 250 VAC, 3A cos ɸ = 0.5
30 VDC, 5A
Country of origin: Sweden
Environmentally friendly
The Flygt ENM-10 level regulator contains no harmful or toxic
materials such as lead or mercury and does not require the use of
any adhesives. All plastic components are welded and screwed
together.
111
Operating principle
222 333 444
1. Media to be pumped 2. The pumping process drains 3. The pumping process stops 4. The media level begins to
reaches the pre-set level the media. when the lower regulator re- rise, starting the process
and tilts the upper regulator, turns to the vertical position again.
which signals the start of the and signals a stop.
pumping process.
2
With a variety of installations in mind
The Flygt liquid level regulator comes in two main versions, standard and Ex-
approved. Depending upon the media and type of installation, the Flygt ENM-10
is available for a broad range of liquid densities and with many cable lengths from
which to choose.
Features
Watertight cable Bending relief (protective sleeve)
Encases and protects power supply Enables watertight, oil-resistant cable
to the microswitch. entry.
Technical data
Standard version Ex-approved version
Cable lengths 6, 13, 20, 30 or 50 m* 6, 13, or 20 m
(20, 42, 65,100 or 167 ft.) (20, 42 or 65 ft.)
Liquid density Between 0.95 and 1.10 g/cm³* Between 0.95 and 1.10 g/cm³
Materials Body: Polypropylene Body: Conductive polypropylene/carbon
Bending relief: EPDM rubber black
Cable: Special compound PVC & NBR/PVC Bending relief: NBR/PVC rubber
Cable: NBR/PVC
Liquid temperature Min. 0°C (32°F) Min. 0°C (32°F)
Max. 60°C (140°F) Max. 60°C (140°F)
Ingress protection IP 68 IP 68
Electrical range Interrupting capacity: Interrupting capacity:
(microswitch) AC: 250 V/10 A resistive load AC: 250 V/10 A resistive load
AC: 250 V/3 A inductive load at cosφ = 0.5 AC: 250 V/3 A inductive load at cosφ = 0.5
DC: 24 V/ 10mA min., 6 A max. DC: 24 V/ 10mA min., 6 A max.
Note that local regulations may limit the Note that local regulations may limit the
voltage. voltage.
Approvals CE, CSA, SEMKO, NEMKO, DEMKO CE, SEMKO, NEMKO, DEMKO, ATEX/IECEX
*Other cable lengths and liquid densities available upon request.
The Flygt ENM-10 is a part of the Level Sensor product range from Xylem, covering most level measuring needs.
3
1319 . Flygt ENM 10 . 1 . Master . 1 . 20120103
1) The tissue in plants that brings water upward from the roots
2) A leading global water technology company
6-Pressure transmitter
- E+H
Description: - pressure switch with oil-free ceramic sensor for measurement in gases or liquids
Sensor range: 1 bar / 100 kPa / 15 psi abs, overload: 10 bar / 1 MPA/ 150 psi
Seal: FKM
Specs at a glance
F L E X Benefits:
• Integrated switching electronics for decentral and economic process
monitoring and control
• Easy function check and information on site thanks to LEDs and digital
display
• Dry capacitance ceramic sensor (Ceraphire) and minimum span of up
to 0 to 20mbar provide reliable insight to the process
• High process availability for vacuum applications and applications with
abrasive media
• IO-Link reduces costs and complexity due to easy configuration and
flexible integration in all fieldbus systems.
Specs at a glance
• Measuring cell +100 mbar....+40 bar (+1.5 psi....600 psi)
Pressure Characteristic
Intelligent pressure switch with capacitive sensor, long term stable and
abrasion resistant
Supply voltage
10...30 VDC
Reference Accuracy
0.5 %,
Platinum: 0.3 %
Process temperature
-25 °C....+100 °C
Ambient temperature
-20 °C...+70 °C
Measuring cell
+100 mbar....+40 bar
2 Endress+Hauser
Ceraphant PTC31B
G1/4, G1/2,
MNPT1/4, MNPT1/2,
DIN13,
JIS R1/2
Communication
1x PNP switch
2x PNP switch
1x PNP switch +
4...20mA analogue
Design approvals
EN 10204-3.1 Final inspection
report
Specialities
Digital display
- WIKA
Manufacturer: WIKA
Model PSD-4
Power supply: 15 … 35 V DC
Output: 4 – 20 mA
Shielding: No
Shield: yes
Flexible length: 5m
Applications
■■ Machine tools
■■ Hydraulics and pneumatics
■■ Pumps and compressors
■■ Special-purpose machine building
Special features
■■ Easily readable, robust digital display
■■ Intuitive and fast setup
■■ Easy and flexible mounting configurations
■■ Flexibly configurable and scalable output signals
Description
Leading in design and functionality High quality
The model PSD-4 pressure switch represents the extensive During development of the WIKA switch family a high value
further development of the PSD-30 pressure switch, itself was placed on a robust design and the selection of appropri-
already awarded with the “iF product design award” for its ate materials suited to machine-building applications. For this
outstanding functionality. A high accuracy of 0.5 %, freely reason the case and the threaded connection of the electrical
configurable output signals (PNP/NPN, 4 ... 20 mA/0 ... 10 connector are made from stainless steel. Overwinding or
V), the 5:1 scalability of the analogue output, in addition to tearing off the connector is therefore virtually impossible.
outstanding self-diagnostics, make the PSD-4 an excellent
automation solution. IO-Link 1.1
With the optional output signal in accordance with the IO-Link
Customised installation communication standard, the PSD-4 allows a fast integration
The installation of the PSD-4 can be flexibly adapted to the into modern automation systems. IO-Link offers simpler and
individual mounting situation. Due to the almost unlimited faster installation, parameterisation and higher functionality
rotation of the digital display and case by more than 300°, the for the PSD-4.
digital display can be adjusted independently of the electrical
connection. The digital display can thus always be aligned to
face the operator, and the M12 x 1 connection positioned to
suit the desired cable routing.
Absolute pressure
bar 0 ... 0.4 1) 0 ... 0.6 1) 0 ... 1 1) 0 ... 1.6 1) 0 ... 2.5 0 ... 4 0 ... 6 0 ... 10
0 ... 16 0 ... 25
psi 0 ... 10 1) 0 ... 15 1) 0 ... 25 1) 0 ... 30 1) 0 ... 50 0 ... 100 0 ... 160 0 ... 200
0 ... 300
The stated measuring ranges are also available in kg/cm² and MPa.
Special measuring ranges between 0 ... 0.4 and 0 ... 1,000 bar (0 ... 10 bis 0 ... 7,500 psi) are available on request.
Special measuring ranges have a reduced long-term stability and increased temperature errors.
Overload safety
The overload safety is based on the sensor element used. Dependent on the selected process connection and the sealing,
restrictions in overload safety can result.
Vacuum-tight
Yes
Digital display
Load
Analogue signal 4 ... 20 mA: ≤ 500 Ω Reference conditions (per IEC 61298-1)
Analogue signal DC 0 ... 10 V: > max. output voltage / 1 mA
Temperature: 15 ... 25 °C (59 ... 77 °F)
Service life Atmospheric pressure: 860 ... 1,060 mbar (12.5 ... 15.4 psi)
100 million switching cycles Humidity: 45 ... 75 % r. h.
Nominal position: Process connection lower mount
Power supply: DC 24 V
Load: see output signals
Process connections
Standard Thread size Overload limit Sealing
DIN 3852-E G¼A 1,000 bar (14,500 psi) NBR (options: Without, FPM/FKM)
G½A 1,000 bar (14,500 psi) NBR (options: Without, FPM/FKM)
EN 837 G⅛B 400 bar (5,800 psi) without (options: Copper, stainless steel)
G ¼ B 1) 1,000 bar (14,500 psi) without (options: Copper, stainless steel)
G ¼ female 1)
1,000 bar (14,500 psi) -
G ½ B 1) 1,000 bar (14,500 psi) without (options: Copper, stainless steel)
ANSI/ASME B1.20.1 ¼ NPT 1) 1,000 bar (14,500 psi) -
½ NPT 1) 1,000 bar (14,500 psi) -
ISO 7 R¼ 1)
1,000 bar (14,500 psi) -
KS PT ¼ 1) 1,000 bar (14,500 psi) -
- G ¼ female (Ermeto compatible) 1,000 bar (14,500 psi) -
G ½ B flush 1,000 bar (14,500 psi) NBR (option: FPM/FKM)
1) suitable for oxygen, oil and grease free.
Restrictor (option)
For applications where pressure spikes can occur, the use
of a restrictor is recommended. The restrictor narrows the
pressure port to 0.3 mm and thus increases the resistance
against pressure spikes.
Connections
■■ Circular connector M12 x 1 (4-pin)
■■ Circular connector M12 x 1 (5-pin) 1)
1) Only for version with two switching outputs and additional analogue signal
Electrical safety
Short-circuit resistance: S+ / SP1 / SP2 vs. U-
Reverse polarity protection: U+ vs. U-
Insulation voltage: DC 500 V
Overvoltage protection: DC 40 V
Connection diagrams
Circular connector M12 x 1 (4-pin)
U+ 1
U- 3
S+ 2
SP1 / C 4
SP2 2
Approvals
Logo Description Country
EU declaration of conformity European Union
■■ EMC directive
■■ Pressure equipment directive
■■ RoHS directive
(∅1.50) (1.16)
(1.42)
(2.83)
(1.02)
(∅1.38)
(1.06)
(0.79)
G L1 G L1 G L1
G ¼ A DIN 3852-E 14 (0.55) G ¼ B EN 837 13 (0.51) ¼ NPT 13 (0.51)
G ½ A DIN 3852-E 17 (0.67) G ½ B EN 837 20 (0.79) ½ NPT 19 (0.75)
R¼ 13 (0.51)
PT ¼ 13 (0.51)
G L1 L2 L3 D1 G L1 L2 L3 D1 G L1 L2 L3 D1
G ¼ 1) 20 15 12 ∅ 25 G¼ 20 13 10 ∅ 25 G½B 2)
23 20.5 10 ∅ 18
(0.79) (0.59) (0.47) (0.98) EN 837 (0.79) (0.51) (0.39) (0.98) (0.91) (0.81) (0.39) (0.71)
1) Ermeto compatible
2) Welding sockets recommended as defined counter-thread (see accessories)
Sealings
Description Order no.
NBR profile sealing G ¼ A DIN 3852-E 1537857
FPM/FKM profile sealing G ¼ A DIN 3852-E 1576534
NBR profile sealing G ½ A DIN 3852-E 1039067
FPM/FKM profile sealing G ½ A DIN 3852-E 1039075
Copper G ¼ B EN 837 11250810
Stainless steel G ¼ B EN 837 11250844
Copper G ½ B EN 837 11250861
Stainless steel G ½ B EN 837 11251042
Max. medium temperature 200 °C (392 °F) at an ambient temperature of max. 30 °C (86 °F) 14109815
Max. operating pressure 600 bar (8,700 psi)
Ordering information
Model / Measuring range / Output signal / Options for specific media / Process connection / Sealing
© 08/2017 WIKA Alexander Wiegand SE & Co. KG, all rights reserved.
The specifications given in this document represent the state of engineering at the time of publishing.
We reserve the right to make modifications to the specifications and materials.
7-Ultrasonic flowmeter
- Siemens
Ultrasonic Flowmeter
Manufacturer: Siemens
Meter power: 90 - 240 V AC (50 / 60 Hz). FSS200 Sensor pair Universal size E2, for any
pipe material.
Output: 4 – 20 mA
Place of installation: - used to measure plant outlet flow installed before the pipe before
chlorine contact tank.
Sensor:
IP: 68
Type: Clamp on
Flow Measurement
SITRANS FS (ultrasonic)
Clamp-on ultrasonic flowmeters
SITRANS FS220 ultrasonic flowmeter
■ Overview ■ Application
The SITRANS FS220 can be used for the following application
conditions:
• Pipe sizes from 10 mm to 10 m
• Pipe materials: ideal for all metals, glass, FRP and most PVC
variants; NOT for concrete pipes and special compound
pipes
• Pipe wall thickness from 1 to 35 mm; specials on request up
to 65 mm
• Media temperatures from -40 to 121 °C; universal high tem-
3 perature sensors for up to 230 °C max.
• Underground/submerged locations, non-ideal environments,
strong pipe vibrations
SITRANS FS220 flowmeters are suitable for most clean liquid ap-
plications, including the following:
• Water and wastewater industry
- Potable water
The SITRANS FS220 is a clamp-on ultrasonic flow system con-
- Water and aqueous solutions
sisting of an FST020 transmitter and FSS200 clamp-on sensors.
- Wastewater, influent & effluent
The transmitter classification FST020 describes a basic clamp- - Processed sewage, sludge
on ultrasonic flowmeter for basic application requirements. • Chemical feed industry
Based on the same digitalized platform as the FST030 this sys- - Sodium hypochlorite
tem provides the same accuracy and similar functions on a - Sodium hydroxide
lower cost level. This system is ideal for water measurement and
any application not requiring temperature or viscosity compen- • HVAC and power industries
sation. - Coolant flow
- Fuel flow
■ Benefits
- Utility district heating, cooling
- Refrigeration liquids
• Easy installation at any time; no production stop, no need to • Process control
cut pipe or stop flow - Chemicals
• Minimal maintenance; external sensors do not require peri- - Pharmaceuticals
odic cleaning - Food products
- Very low flow sensitiity (< 0.1 m/s)
• No moving parts to foul or wear. No contact with media - High temperature liquids > 120 °C (248 °F)
• No pressure drop or energy loss
• Wide turn-down ratio, bidirectional and high stability at zero
flow conditions
• Anomaly compensation tool for correction of non-ideal straight
pipe runs. Automatic compensation during backflow
• Optional WideBeam technology ensures highest performance
and accuracy
• Compatible with all previously installed transit time sensors
Flow Measurement
SITRANS FS (ultrasonic)
Clamp-on ultrasonic flowmeters
SITRANS FS220 ultrasonic flowmeter
■ Application (continued)
Sensor type selection guide
Application condition
Standard sensor supported in MLFB
High precision Universal Notes
3
Note all that apply before making selection
Media
General survey (clean liquids) on non-steel pipes X
General survey (clean liquids) on a limited range of steel X
pipes
Moderately aerated liquid or slurry, up to 121 °C (250 °F) X
Permanent installation on steel pipe (clean liquids) X
Installation in offshore or corrosive environment X With optional stainless steel mounting
Liquid temperature greater than 120 °C (248 °F) O X High temperature metal block sensors
(up to 230 °C (446 °F))
Operation on single pipeline flowing multiple products X O
Pipe material
Steel X
Steel pipe with diameter/wall thickness ratio < 10 O X
Non-steel pipe material (copper, ductile iron, cast iron, etc.) O X High precision sensors can also be used on plastic and
aluminum pipes in special cases
O = not suitable X = preferred choice
Definitions
Sensor chart Description
FSS200 Formerly 1011 clamp-on sensors of the 1010 systems
Standard Standard system sensor, selectable as part of a configured product
Special Sensors available for non-standard applications and pipes. Contact tech support for application use
Corrosions resistant Stainless steel metal parts on all Size C, D and E and all high temperature sensors
Aluminum Aluminum metal parts on all HP and Universal size A and B (Corrosion resistant on request for size B)
Spare Not available as part of a configured product, must be ordered separately
CE Transmitter and sensors certified for sale in the EU
Trackless mount Sensors fixed only by straps, no other mounting (spacer bar as an option) - not recommended
Tracks Permanent installation for universal size A/B, high precision size A/B and all sizes of high temperature. Tracks always come as dual-
part for either direct or reflect mounting, and always with straps.
Frames Three sizes, for permanent installation for universal size C/ D/ E, and for high precision size C/D. For universal and high precision
size B available for pipes > 125 OD (Spare)
T1 Usable from -40 ... +120 °C (-40 ... +248 °F), but best for Ø temperature below 80 °C (< 176 °F); standard
T2 Usable from -40 ... +120 °C (-40 ... +248 °F), but best for Ø temperature above 80 °C (< 176 °F)
Submersible Sensors can be used submerged; adding Denso for supplemental protection is recommended
Flow Measurement
SITRANS FS (ultrasonic)
Clamp-on ultrasonic flowmeters
SITRANS FS220 ultrasonic flowmeter
■ Application (continued)
Sensor Availability Guide
Availability
Submersible
Spare only
Trackless
Standard
Catalog
Frames
Tracks
T1
T2
Sensor models
Universal Sensor -40 … 120 °C housing CE IP68
A1 Universal for pipe OD – 5.8 … 50.8 mm (0.23" … 2") X X X
A2 Universal for pipe OD – 12.7 … 50.8 mm (0.5" … 2") X X X X
B1 Universal for pipe OD – 12.7 … 76 mm (0.5" … 3") X X X X
B2 Universal for pipe OD – 12.7 … 76 mm (0.5" … 3") X X X X
B3 Universal for pipe OD – 19 … 127 mm (0.75" … 5") X X X X X
C1 Universal for pipe OD – 51 … 254 mm (2" … 10") X X X X X
C2 Universal for pipe OD – 51 … 254 mm (2" … 10") X X X X X
C3 Universal for pipe OD – 51 … 305 mm (2" … 12") X X X X X X
D1 Universal for pipe OD – 102 … 508 mm (4" … 20") X X X X X
D2 Universal for pipe OD – 152 … 610 mm (6" … 24") X X X X X
D3 Universal for pipe OD – 203 … 610 mm (8" … 24") X X X X X X
*E1 Universal for pipe OD – 254 … 3048 mm (10" … 120") X X X X X
*E2 Universal for pipe OD – 254 … 6096 mm (10" … 240") X X X X X X
*E3 Universal for pipe OD – 304 … 10007 mm (12" … 394") X X X X X
High Precision Sensor -40 … 120 °C (-40 ... +248 °F) T1 (T2) CE IP68
A1H (High Precision) for pipe WT - 0.64 ... 1.0 mm (0.025" ... 0.04") X X X X X
A2H (High Precision) for pipe WT - 1.0 ... 1.5 mm (0.04" ... 0.06") X X X X X
A3H (High Precision) for pipe WT - 1.5 ... 2.0 mm (0.06" ... 0.08") X X X X X
B1H (High Precision) for pipe WT - 2.0 ... 3.0 mm (0.08" ... 0.12") X X X X X X X
B2H (High Precision) for pipe WT - 3.0 ... 4.1 mm (0.12" ... 0.16") X X X X X X X
B3H (High Precision) for pipe WT - 2.7 ... 3.3 mm (0.106" ... 0.128") X X X X X X X
C1H (High Precision) for pipe WT - 4.1 ... 5.8 mm (0.16" ... 0.23") X X X X X X X X
C2H (High Precision) for pipe WT - 5.8 ... 8.1 mm (0..23" ... 0.32") X X X X X X X X
* D1H (High Precision) for pipe WT - 8.1 ... 11.2 mm (0..32" ... 0.44") X X X X X X X X
* D2H (High Precision) for pipe WT - 11.2 ... 15.7 mm (0.44" ... 0.62") X X X X X X X X
* D3H (High Precision) for pipe WT - 7.4 ... 9.0 mm (0..293" ... 0.354") X X X X X X X X
* D4H (High Precision) for pipe WT - 15.7 ... 31.8 mm (0..62" ... 1.25") X X X X X X X X
High Temperature Universal Sensor -40 ... +230 °C (-40 ... +446 °F)
High Temperature size 1 ... 230 °C (Ø 12.7 ... 100 mm) X X X X1)
High Temperature size 2 ... 230 °C (Ø 30 ... 200 mm ) X X X X X
High Temperature size 3 ... 230 °C (Ø 150 ... 610 mm) X X X X X
High Temperature size 4 ... 230 °C (Ø 400 ... 1200 mm) X X X X X
High Temperature size 2A ... 230 °C (Ø 30 ... 200 mm) X X X X1)
High Temperature size 3A ... 230 °C (Ø 150 ... 610 mm) X X X X1)
High Temperature size 4A ... 230 °C (Ø 400 ... 1200 mm) X X X X1)
Flow Measurement
SITRANS FS (ultrasonic)
Clamp-on ultrasonic flowmeters
SITRANS FS220 ultrasonic flowmeter
■ Application (continued)
Sensor mounting availability guide
Sensor (Dedicated)
Universal High precision High temperature
universal
Mounting
Trackless (straps only) X X
Tracks universal dedicated X
Tracks HP dedicated X
Frames universal dedicated X 3
Frames HP dedicated X
Tracks high temperature universal X
High precision mounting single enclosure for one pair sensors X
High precision mounting dual enclosure for one pair sensors X
SpacerBar X X
Straps X X X
Denso X X
■ Function
Operating principle Once the raw flow velocity is determined, the fluid Reynolds
Number (Re) must be determined to properly correct for fully de-
The SITRANS F S system is a transit-time ultrasonic meter that veloped flow profile. This requires the entry of the fluid’s kine-
provides exceptional performance using a non-intrusive clamp- matic viscosity (visc) as shown in the equations below, where Q
on approach. Ultrasonic sensors transmit and receive acoustic represents the final flow profile compensated volumetric flow
signals directly though the existing pipe wall, where the fluid re- rate.
fraction angle is governed by Snell’s law of refraction.
Re = Di · v / visc Q = K(Re) · ( π / 4 ·Di2 ) · v
v = Flow velocity
A B
visc = μ / ρ = (dynamic viscosity / density)
K(Re) = Reynolds flow profile compensation
In wetted type ultrasonic flowmeters the meter constants are
θ configured prior to leaving the factory. As this is not possible with
Di
v
clamp-on meters, the settings must be made by the customer at
c
the time of installation. These settings include pipe diameter, wall
thickness, liquid viscosity, etc.
SITRANS clamp-on flowmeters that include temperature sensing
can be configured to dynamically infer changes in fluid viscosity
Clamp-on sensor mounted in a reflect configuration for the purpose of computing the most accurate flow profile com-
pensation (KRe).
The beam refraction angle is calculated as follows:
Ultrasonic sensor types
sin θ = c / Vϕ
Two basic types of clamp-on sensors can be selected for use
c = Velocity of sound in fluid with the SITRANS F S flowmeter. The lower cost "universal" sen-
Vϕ = Phase velocity (a constant in the pipe wall) sor is the most common type in the industry and is suitable for
most single liquid applications where the sound velocity does
The flowmeter automatically compensates for any change in not vary much. This sensor type can be used on any sonically
fluid sound velocity (or beam angle) in response to variations in conductive pipe material (including steel) making it well suited
the average transit time between sensors A and B. By subtract- for temporary survey applications. Universal sensors are se-
ing the computed fixed times (within the sensor and pipe wall) lected based on the pipe diameter range alone, so wall thick-
from the measured average transit time, the meter can then infer ness is less important to the selection process..
the required transit time in the fluid (TFluid).
The second sensor type is the patented "WideBeam" sensor
The sound waves traveling in the same direction as the flow (called high precision), which utilizes the pipe wall as a kind of
(TA,B) arrive earlier than sound waves traveling against the direc- waveguide to optimize the signal to noise ratio and provide a
tion of flow (TB,A). This time difference (Δt) is used to compute wider area of vibration. This makes this kind of sensor less sen-
the line integrated flow velocity (v) as shown in the equation be- sitive to any change in the fluid medium.
low:
The WideBeam sensor is designed for steel pipes, but can also
v = Vϕ / 2 · Δt / TFluid be used with aluminum and titanium. It is the preferred sensor for
HPI applications. Note that unlike the universal type, this sensor
selection is dependent only on the pipe’s wall thickness.
Flow Measurement
SITRANS FS (ultrasonic)
Clamp-on ultrasonic flowmeters
SITRANS FS220 ultrasonic flowmeter
Flow Measurement
SITRANS FS (ultrasonic)
Clamp-on ultrasonic flowmeters
SITRANS FS220 ultrasonic flowmeter
0 MC 0 0
3
tracks (including portable) • Frames for universal sensor size D 0 MC 0 1
FSS200 A2 universal LB0 1 • Frames for universal sensor size E 0 MC 0 2
FSS200 B3 universal LC0 1 • Frames for High precision sensor size B CQO:1012FNH-PB
FSS200 C3 universal LD0 0 (for pipes >125 mm (5 inch))
• Frames for High precision sensor size C 0 MD 0 0
FSS200 D3 universal LE 0 0
• Frames for High precision sensor size D 0 MD 0 1
FSS200 E2 universal L F 0 0
Mounting straps for mounting frames
FSS200 A1H (high precision) LG0 1 (slotted stainless steel)
FSS200 A2H (high precision) LH0 1 • Straps for pipes from DN 50 to DN 150 0 SM 0 0
FSS200 A3H (high precision) L J 0 1 • Straps fFor pipes from DN 50 to DN 300 0 SM 1 0
FSS200 B1H (high precision) GK 1 • Straps fFor pipes from DN 300 to DN 600 0 SM 2 0
• Straps for pipes from DN 600 to DN 1200 0 SM 3 0
FSS200 B2H (high precision) GL 1
• Straps for pipes from DN 1200 to DN 1500 0 SM 4 0
FSS200 B3H (high precision) GT 1 • Straps fFor pipes from DN 1500 to DN 2100 0 SM 5 0
FSS200 C1H (high precision) GM 0 • Straps for pipes from DN 2100 to DN 3000 0 SM 6 0
FSS200 C2H (high precision) GN 0 Spacer bars (for indexing sensors on pipe)
FSS200 D1H (high precision) GP 0 • Spacer bar for pipes to 200 mm/8 inch (liquid), 0MS 1 0
FSS200 D2H (high precision) GQ 0 600 mm/24 inch (gas)
• Spacer bar for pipes to 500 mm/20 inch (liquid), 0MS 2 0
FSS200 D3H (high precision) GU 0 DN 1200/48 inch (gas)
FSS200 D4H (high precision) GR 0 • Spacer bar for pipes to 800 mm/32 inch (liquid) 0MS 3 0
High temperature universal liquid sensors • Spacer bar-extension for pipes to 1200 mm/48 inch 0MS 4 0
up to 230 °C (446 °F) (liquid) Only use in conjunction with
7ME3960-0MS30
FSS200 High temp. sensor size 1 for LA1 3
12.7 to 100 mm diam. High precision mounting enclosures. Spacer bar is
FSS200 High temp. sensor size 2 for LA2 3 included; straps should be ordered separately
30 to 200 mm diam. • Stainless steel mounts for high precision size "C" 0WS 5 0
sensor pair, single enclosure (each)
FSS200 High temp. sensor size 3 for LA4 3
• Stainless steel mounts for high precision size "D/E" 0WS 6 0
150 to 600 mm diam.
sensor pair, single enclosure (each)
FSS200 High temp. sensor size 4 for LA7 3 • Stainless steel mounts for high precision size "C" 0 WD 5 0
400 to 1200 mm diam. sensors, dual enclosure (pair)
• Stainless steel mounts for high precision size "D/E" 0 WD 6 0
sensors, dual enclosure (pair)
Stainless steel straps for weld seal enclosure
mounting (2 x required for dual enclosures)
Mounting strap for pipe diameter to 300 mm 0 SM0 1
(13 inch)
Mounting strap for pipe diameter to 600 mm 0 SM1 1
(24 inch)
Mounting strap for pipe diameter to 1200 mm 0 SM2 1
(48 inch)
Mounting strap for pipe diameter to 1500 mm 0 SM3 1
(60 inch)
Mounting strap for pipe diameter to 2130 mm 0 SM4 1
(84 inch)
Mounting strap for pipe diameter to 3050 mm 0 SM5 1
(120 inch)
Flow Measurement
SITRANS FS (ultrasonic)
Clamp-on ultrasonic flowmeters
SITRANS FS220 ultrasonic flowmeter
Flow Measurement
SITRANS FS (ultrasonic)
Clamp-on ultrasonic flowmeters
SITRANS FS220 ultrasonic flowmeter
Flow Measurement
SITRANS FS (ultrasonic)
Clamp-on ultrasonic flowmeters
SITRANS FS220 ultrasonic flowmeter
■ Dimensional drawings
175.6 (6.9) 130.6 (5.1)
227.6 (9.0)
240.2 (9.5)
3
80.4 (3.17)
87.2 (3.43)
(1.61)
Ø26.7
40.9
(1.05)
SITRANS FST020 IP65 (NEMA 4X), wall mount enclosure, dimensions in mm (inch)
Flow Measurement
SITRANS FS (ultrasonic)
Clamp-on ultrasonic flowmeters
SITRANS FST020 ultrasonic flow transmitter, wall mount housing
3
shooting and meter validation
• Configurable upper and lower alarm and warning limits for all
process values
Outputs and control
• Monitoring comprised of 1 individually configurable totalizer
• Single parameter outputs that can be assigned individually to
any of the following parameters:
- Volume flow
The SITRANS FST020 is the basic device for simple and cost-ef- - Flow velocity
fective clamp-on applications. As a single-path device, it is suit- - Sound velocity
able for flow measurement on liquids that do not require tem- - Flow direction
perature or viscosity consideration and where highest Channel 1 is 4 to 20 mA analog output. The current signal can
accuracies are not required. be configured for passive volume flow.
Historically, the FST020 comes from the clamp-on family of ana- Relay output(s) can be user configured to Alarm status or warn-
log FUS1010 transmitters. Since the revision in 2017, the up- ing.
dated transmitter is now part of a digital platform based on the
latest developments within Digital Signal Processing (DSP) tech- Modbus RTU RS 485 comes as standard.
nology - engineered for high measuring performance, fast re-
sponse to step changes in flow, high immunity against process Signal input
noise and simplicity in installation, commissioning and mainte- The signal input can be user-configured for:
nance.
• Totalizer reset functions
The FST020 transmitter delivers standard parameter measure- • Forcing outputs or freezing process values
ments i.e. volume flow, flow speed or sound velocity by analog
outputs and Modbus communication. • Initiating automatic zero point adjustment
Process values Approvals and certificates
• Volume flow The SITRANS FST020 transmitter was designed to comply with
• Flow velocity or exceed the requirements of international standards and regu-
lations.
• Sound velocity
• Totalizer 1 ■ Design
■ Benefits • Field clamp-on (non-intrusive)
• Single path, for only one pair of sensors on one pipe
Flow calculation and measurement • IP65 (NEMA 4X) wall mount housing, constructed of polycar-
• Dedicated volume flow calculation with DSP technology bonate
• 100 Hz update rate for all primary process values • Available AC or DC power, 100 to 240 V AC, 11.5 to 28.5 V DC
• Maximum data age from sensor to output is 20 ms
• Independent low flow cut-off settings for volume flow and ve- ■ Function
locity • 240 x 160 pixel graphical display with 4 key navigation and
• Zero-point adjustment on command from discrete input or backlight
host system • 6 user programmable views for individual process and diag-
Operation and display nostic information
• User-configurable operation display • Modbus RTU communication
- Fully graphical display 240 x 160 pixel display with up to • 100 Hz update rate for all primary process value
6 programmable views • Independent low flow cut-off settings for volume and flow ve-
- Self-explaining alarm handling/log in clear text locity
- Help text for all parameters appears automatically in the con-
figuration menu • Fully compatible with Siemens PDM version 8.2 service pack
1 or higher
• Bidirectional flow operation
• Menus available in English and German
Flow Measurement
SITRANS FS (ultrasonic)
Clamp-on ultrasonic flowmeters
SITRANS FST020 ultrasonic flow transmitter, wall mount housing
■ Technical specifications
Input
Flow range ± 12 m/s (± 40 ft/s), depending on
pipe size higher or lower
Flow direction bi-directional
Flow sensitivity 0.0003 m/s (0.001 ft/s) flow rate inde-
pendent
Digital inputs
Totalizer Hold Optically isolated diode
3
Activated ON: Input voltage:
2 … 10 V DC
Totalizer Reset Opticall isolated diode
Activated ON: Input voltage:
2 … 10 V DC
Output Channel 1
Current 4 ... 20 mA (isolated)
Externally powered 10 … 30 V DC
Relay 30 V DC, 3 VA AC max.
Pulse rate Optically isolated transistor 10 mA,
30 V DC max
Pulse: 41.6 ms ... 5 s pulse duration
Frequency: 0 ... 12.5 kHz (50 % duty
cycle)
Accuracy
Accuracy For velocities above 0.3 m/s (1 ft/s),
±1.0 % of flow
Repeatability ± 0.25 % (according to ISO 11631)
Zero Drift 0.1 % of rate; < ±0.001 m/s
(±0.003 ft/s)
Data refresh rate 100 Hz
Rated operation conditions
Operating temperature -10 … +50 °C (14 … +122 °F)
Storage temperature -20 … +60 °C (-4 … +140 °F)
Degree of protection IP65/NEMA 4X
Design
Weight 1.4 kg (3.0 lbs)
Dimensions (W x H x D) 176 x 240 x 87 mm
(6.9 x 9.5 x 3.4 inch)
Enclosure material Polycarbonate
Power supply 100 ... 240 V AC @ 20 VA or
11.5 ... 28.5 V DC @ 10 W
Certificates and approvals
Unclassified locations
• General safety UL, cUL, CE
Flow Measurement
SITRANS FS (ultrasonic)
Clamp-on ultrasonic flowmeters
SITRANS FST020 ultrasonic flow transmitter, wall mount housing
3
Meter power options
100 ... 240 V AC A
11.5 ... 28.5 V DC B
Sensor FSS2001)
When ordering a flow system, sensors always come automatically with suitable mounting equipment. Smaller sensor sizes A &
B come with mounting tracks, while sensor sizes C, D & E are supplied with frames and spacer bars. Straps provided are for the
indicated maximum OD listed below.Strap kits are available to accommodate larger pipes (refer to spare part list). Refer to
"Sensor Selection Charts" to find the most suitable sensors for specific pipe sizes and wall thicknesses.
No sensor A
For the following Universal sensors, temperature range is -40 ... +121 °C (-40 ... +250 °F), FSS200 Universal: select according
to outer pipe diameter
FSS200 Universal A2 12.7 ... 50 mm (0.5 ... 2") Track mount and straps provided up to 75 mm (3") B
FSS200 Universal B3 19 ... 127 mm (0.75 ... 5") Track mount and straps provided up to 125 mm (5") C
FSS200 Universal C3 51 ... 305 mm (2 ... 12") Mounting frame, straps and spacer bar provided up to D
330 mm (13")
FSS200 Universal D3 203 ... 610 mm (8 ... 24") Mounting frame and straps and spacer bar provded up to E
600 mm (24")
FSS200 Universal E2 304 ... 9144 mm (12 ... 360") Mounting frame and straps and spacer bar provided up to F
1200 mm (48")
For the following High Precision sensors T1, temperature range is -40 ... +120 °C (-40 ... +248 °F), FSS200 High Precision:
select according to pipe wall thickness
FSS200 HP A1H 0.6 ... 1.0 mm (0.025 ... 0.4") Track mount and straps provided up to 75 mm (3") G
FSS200 HP A2H 1.0 ... 1.5 mm (0.04 ... 0.06") Track mount and straps provided up to 75 mm (3") H
FSS200 HP A3H 1.5 ... 2.0 mm (0.06 ... 0.08") Track mount and straps provided up to 75 mm (3") J
FSS200 HP B1H 2.0 ... 3.0 mm (0.08 ... 0.12") Track mount and straps provided up to 125 mm (5") K
FSS200 HP B2H 3.0 ... 4.1 mm (0.12 ... 0.16") Track mount and straps provided up to 125 mm (5") L
FSS200 HP C1H 4.1 ... 5.8 mm (0.16 ... 0.23") Mounting frame, straps and spacer bar up to 600 min (24") M
FSS200 HP C2H 5.8 ... 8.1 mm (0.23 ... 0.32") Mounting frame, straps and spacer bar up to 600 min (24") N
FSS200 HP D1H 8.1 ... 11.2 mm (0.32 ... 0.44") Mounting frame and straps provided up to 1200 mm (48")1) P
FSS200 HP D2H 11.2 ... 15.7 mm (0.44 ... 0.62") Mounting frame and straps provided up to 1200 mm (48")1) Q
FSS200 HP D4H 15.7 ... 31.8 mm (0.62 ... 1.25") Mounting frame and straps provided up to 1200 mm (48")1) R
For the following High Temperature sensors, temperature range is -40 ... +230 °C (-40 ... +446 °F), FSS200 High Temperature:
select according go outer diameter
FSS200 HT Size 2 30 ... 200 mm (1 ... 8") Mounting track and straps provided up to 250 mm (10") Z P1A
FSS200 HT Size 3 150 ... 610 mm (6 ... 24") Mounting track and straps provided up to 650 mm (26") Z P2A
FSS200 HT Size 4 400 ... 1200 mm (16 ... 48") Mounting track and straps provided up to 1250 mm (50") Z P3A
Sensor cable (pair - terminated)
No sensor cable A
Sensor cable, HDPE jacket, submersible, length
• 5 m (16.4 ft) P
• 10 m (32.8 ft) Q
• 20 m (65.6 ft) R
Approvals
UL, ULc, CE 1
1) Supplied spacer bar supports pipes up to 1050 mm (42"). For pipes larger than 1050 mm (42") purchase also, spare part 7ME3960-0MS40 (1012BN-4).
2) Made of stainless steel construction.
Flow Measurement
SITRANS FS (ultrasonic)
Clamp-on ultrasonic flowmeters
SITRANS FST020 ultrasonic flow transmitter, wall mount housing
Further designs
Please add "-Z" to Article No. and specify Order
code(s).
Cable termination kit for customer supplied sen-
sor cable pair
Sensor cable termination for standard and plenum T01
cable
Mass storage
Enable mass storage function or SD-card (not avail- S30
3 able for USA)
Tag and name plates
Tag plate, transmitter and sensor Y19
■ Dimensional drawings
175.6 (6.9) 130.6 (5.1)
227.6 (9.0)
240.2 (9.5)
80.4 (3.17)
87.2 (3.43)
(1.61)
Ø26.7
40.9
(1.05)
SITRANS FST020 IP65 (NEMA 4X), wall mount enclosure, dimensions in mm (inch)
- E+H
Ultrasonic Flowmeter
Description: - Device with automatic frequency scan for max. measuring performance
and cost-effective transmitter
language: English
Specs at a glance
Volume flow:
Measuring range
IP:67
8-Pressure gauge
- WIKA
Pressure Gauge
Manufacturer: WIKA
Model: - Bourdon tube pressure gauge, model 232.50/233.50, NS 100 [4"] stainless steel
Applications
environments
technology
Special features
Applications
■ For gaseous and liquid aggressive media that are
not highly viscous or crystallising, also in aggressive
environments
■ Chemical and petrochemical industries, oil and gas indus-
try, power engineering and also water and wastewater
technology
■ Machine building and general plant construction
Special features
■ Excellent load-cycle stability and shock resistance
■ With case filling (model 233.50) for applications with high
dynamic pressure loads and vibrations
■ Completely from stainless steel
■ Scale ranges from 0 … 0.6 to 0 … 1,600 bar
[0 ... 10 to 0 ... 20,000 psi] Bourdon tube pressure gauge, model 232.50,
NS 100 [4"]
Description
This high-quality Bourdon tube pressure gauge has been WIKA manufactures and qualifies the pressure gauge
designed especially for the process industry. in accordance with the standards EN 837-1 and
ASME B40.100. This instrument has as safety function a
The use of high-quality stainless steel materials and the blow-out device with blow-out plug on the back of the case. In
robust design are geared to applications in the chemical the event of a failure, overpressure can escape there.
and process engineering industries. Thus the instrument is
suitable for liquid and gaseous media, also in aggressive The model 233.50 with liquid-filled case is suitable for high
environments. dynamic pressure loads and vibrations.
Measuring element
Type of measuring element Bourdon tube, C-type or helical type
Material ■ Stainless steel 1.4404 (316L)
■ Monel (models 262.50 and 263.50)
Leak tightness ■ Helium tested, leakage rate: < 5∙10-3 mbar l/s
■ Helium tested, leakage rate: < 1∙10-6 mbar l/s
Accuracy specifications
Accuracy class
NS 63 [2 ½"] ■ EN 837-1 Class 1.6
■ ASME B40.100 ±2 ½ % of measuring span (grade A)
NS 100 [4"], 160 [6"] ■ EN 837-1 Class 1,0
■ ASME B40.100 ±1.0 % of measuring span (grade 1A)
Temperature error On deviation from the reference conditions at the measuring system:
≤ ±0.4 % per 10 °C [≤ ±0.4 % per 18 °F] of full scale value
Reference conditions
Ambient temperature +20 °C [68 °F]
Dial
Scale colour Black
Material Aluminium
Special scale ■ Without
■ With temperature scale for refrigerant, e.g. for NH3: R 717
Other scales or customer-specific dials, e.g. with red mark, circular arcs or circular
sectors, on request
Pointer
Instrument pointer Aluminium, black
Mark pointer/drag pointer ■ Without
■ Red mark pointer on dial, fixed
■ Red mark pointer on window, adjustable
■ Mark pointer on bayonet ring, adjustable
■ Red drag pointer on window, adjustable
Pointer stop pin ■ Without
■ At the zero point (only for NS 63 [2 ½"])
■ At 6 o‘clock (only for NS 100 [4"], 160 [6"])
Process connections
Standard ■ EN 837-1
■ ISO 7
■ ANSI/B1.20.1
Size
EN 837-1 ■ G ⅛ B, male thread
■ G ¼ B, male thread
■ G ½ B, male thread
■ M12 x 1.5, male thread
■ M20 x 1.5, male thread
ISO 7 ■ R ¼, male thread
■ R ½, male thread
Restrictor ■ Without
■ ∅ 0,6 mm [0,024"], stainless steel
■ ∅ 0,3 mm [0,012"], stainless steel
Materials (wetted)
Process connection ■ NS 100 [4"], 160 [6"]: Stainless steel 1.4404 (316L)
■ NS 63 [2 ½"]: Stainless steel 1.4571 (316 Ti)
■ Monel (models 262.50 and 263.50)
Optional approvals
Logo Description Country
EU declaration of conformity European Union
ATEX directive
Hazardous areas
- Ex h Gas II 2G Ex h IIC T6 ... T1 Gb X
Dust II 2D Ex h IIIC T85°C ... T450°C Db X
Certificates (option)
Certificates
Certificates ■ 2.2 test report per EN 10204 (e.g. state-of-the-art manufacturing, indication accuracy)
■ 3.1 inspection certificate per EN 10204 (e.g. material proof for wetted metal parts, indication accuracy)
■ PCA calibration certificate, traceable and accredited in accordance with ISO/IEC 17025
■ Calibration certificate by the national accreditation body, traceable and accredited in accordance with
ISO/IEC 17025 on request
Recommended 1 year (dependent on conditions of use)
recalibration interval
ØD1
ØD2 NS Weight
h
14311051.01
63 [2 ½"] approx. 0.16 kg [0.35 lbs] approx. 0.20 kg [0.44 lbs]
G G
100 [4"] approx. 0.6 kg [1.32 lbs] approx. 0.9 kg [1.98 lbs]
ISO ANSI a 160 [6"] approx. 1.1 kg [2.43 lbs] approx. 2.0 kg [4.41 lbs]
1) Plus 16 mm [0.630 in] with scale range 0 ... 1,600 bar [0 ... 20,000 psi]
i
Øk
ØD1
SW
ØD2
e
ISO
G
NS Weight
Model 232.50 Model 233.50
ANSI
1431111.01
h1 100 [4"] approx. 0.6 kg [1.32 lbs] approx. 0.9 kg [1.98 lbs]
160 [6"] approx. 1.1 kg [2.43 lbs] approx. 2.0 kg [4.41 lbs]
1) Plus 16 mm [0.630 in] with scale range 0 ... 1,600 bar [0 ... 20,000 psi]
2) Plus 16 mm [0.630 in] with scale ranges ≥ 0 ... 100 bar [≥ 0 ... 1,500 psi]
b
≤ 16 bar [≤ 300 psi] with vent valve j
> 16 bar [> 300 psi] without vent valve Øk
i
SW
ISO
ØD1
ØD2
G
ANSI
G
h1
NS Weight
14112247.01
Model 232.50 Model 233.50
63 [2 ½“] approx. 0.16 kg [0.35 lbs] approx. 0.20 kg [0.44 lbs]
Dimensions in mm [in]
Ød2 Ød2
Ød1 Ød1
°
°
120
120
120
120
°
°
Ød3
Ød3
NS Dimensions in mm [in]
Recommended panel cutout d1 d2 d3
63 [2 ½"] ∅ 67 ±0.3 / ∅ 2.6 [∅ 2.64 ±0.01 / ∅ 0.10] 75 [2.95] 85 [3.35] 3.6 [0.14]
100 [4"] ∅ 104 ±0.5 / ∅ 4.1 [∅ 4.04 ±0.02 / ∅ 0.16] 117 [4.61] 132 [5.20] 4.8 [0.19]
160 [6"] ∅ 164 ±0.5 / ∅ 6.5 [∅ 6.46 ±0.02 / ∅ 0.26] 178 [7.01] 196 [7.71] 5.8 [0.23]
NS Dimensions in mm [in]
Recommended panel d4
Ød4
cutout
63 [2 ½"] ∅ 64.5 ±0.5 / ∅ 2.5 ≤ 69 [2.72]
[∅ 2.54 ±0.02 / ∅ 0.01]
NS 100 [4"] ∅ 102 ±1.0 / ∅ 4.0 ≤ 108 [4.25]
[∅ 4.02 ±0.04 / ∅ 0.16]
NS 160 [6"] ∅ 162.6 ±1.0 / ∅ 6.4 ≤ 168 [6.61]
[∅ 6.40 ±0.04 / ∅ 0.25]
Model Description
910.17 Sealings
→ see data sheet AC 09.08
910.15 Syphons
→ see data sheet AC 09.06
Ordering information
Model / Nominal size / Scale range / Process connection / Connection location / Options
© 02/1995 WIKA Alexander Wiegand SE & Co. KG, all rights reserved.
The specifications given in this document represent the state of engineering at the time of publishing.
We reserve the right to make modifications to the specifications and materials.
01/2021 EN
- Siemens
Manufacturer: Siemens
standard
Enclosure.
• Controller
Operating Instructions
Edition 11/2019
The MultiRanger 100 and 200
The MultiRanger is available in two models, MultiRanger 100 and MultiRanger 200, and is
designed for a variety of applications:
• water and wastewater
• storage tanks, for measuring liquids, slurries, and solids
• hoppers, ore bunkers, flotation cells
MultiRanger 100
MultiRanger 100/200
The MultiRanger 100 is a single or dual-point level, one, three, or six relay measurement
device. It is equipped with digital communications and offers the latest in echo
processing technology and diagnostic features.
MultiRanger 200
The MultiRanger 200 is a single or dual-point, three or six relay device that offers both
level and volume measurement. It has Open Channel Monitoring capabilities, a larger
number of advanced pump control algorithms, and is equipped with digital
communications. It offers the latest in echo processing technology and diagnostic
features.
The Manual
Notes:
• This product is intended for use in industrial areas. Operation of this equipment
in a residential area may cause interference to several frequency based
communications.
• Please follow the installation and operating procedures for a quick, trouble-free
installation and to ensure the maximum accuracy and reliability of your
MultiRanger.
The manual provides instruction for both MultiRanger 100 and MultiRanger 200 models.
For your convenience, the manual uses MultiRanger 100 features as its standard content.
Additional MultiRanger 200 features are clearly marked.
The manual is designed to help you get the most out of your MultiRanger, and it provides
information on the following:
Manual Symbols
Please note their use carefully.
Alternating Current
MultiRanger 100/200
Direct Current
Configuration Examples
The configuration examples used in this manual illustrate the versatility of the
MultiRanger. Because there is often a range of ways to approach an application, other
configurations may also apply.
In all examples, substitute your own application details. If the examples do not apply to
your application, check the applicable parameter reference for the available options.
Should you require more information, please contact your Siemens Milltronics
representative. For a complete list of Siemens Milltronics representatives, go to
www.siemens.com/processautomation.
DC version
• 12-30 V DC, 20W1
• fuse: F3: 2 AG, Slow Blow, 2A, 250V
Transmitter fuse
• F1: Belling Lee, L754, 4000A HRC, ceramic type, 100mA, 250V
Mounting
Specifications
Location
• indoor / outdoor
Altitude
• 2000 m max.
Ambient temperature
• -20 to 50 °C (-5 to 122 °F)
Relative humidity
• Wall Mount: suitable for outdoors (Type 4X / Nema 4X, IP65 Enclosure)
• Panel Mount: suitable for outdoors (Type 3 / Nema 3, IP54 Enclosure)
Installation category
• II
Pollution degree
• 4
Accuracy
• 0.25% of maximum range or 6 mm (0.24”), whichever is greater
Resolution
• 0.1% of program range1 or 2 mm (0.08”), whichever is greater
Memory
• 1 MB static RAM with battery backup
• 512 kB flash EPROM
Programming
Primary
• handheld programmer
Secondary
Specifications
Display
• back lit LCD
Temperature Compensation
• Range: -50 to 150 °C (-58 to 302 °F)
Source
• integral transducer sensor
• TS-3 temperature sensor
• programmable fixed temperature
Temperature Error
Sensor
• 0.09 % of range
1.
Program range is defined as the empty distance from the face of the transducer
(P006) plus any range extension (P801).
Outputs
Transducer drive
• 315 V peak
mA Analog
MultiRanger 100/200:
Single or Dual point versions include two mA outputs
• 0-20 mA
• 4-20 mA
• 750 ohm maximum
• Resolution of 0.1%
• Isolated
Relays1)
• One:
• 1 control
• Three:
Specifications
• 2 control
• 1 alarm control
• Six:
• 4 control
• 2 alarm control
• All relays rated:
• 5A at 250 V AC, non-inductive
• 5A at 30 V DC, non-inductive
Control Relays
• 1, 2 or 4 Form A, NO relays (numbers 1, 2, 4, 5)
Alarm Relay
• 0, 1 or 2 Form C, NO, or NC relay (numbers 3, 6)
Communication
• RS-232 running Modbus RTU and ASCII via RJ-11 connector
• RS-485 running Modbus RTU and ASCII via terminal blocks
Optional
• SmartLinx® compatible
1.
All relays are certified only for use with equipment that fails in a state at or
under the rated maximums of the relays.
Discrete (2)
• 10-50 V DC switching level
• logical 0 = < 0.5 V DC
• logical 1 = 10 to 50 V DC
• 3 mA maximum draw
Enclosure
Wall Mount
• 240 mm (9.5") x 175 mm (6.9"). Width dimension includes hinges.
• Type 4X / NEMA 4X / IP 651
• Polycarbonate
Panel Mount
• 278 mm (10.93") x 198 mm (7.8") Width dimension includes flange.
• Type 3 / Nema 3 / IP54
Specifications
• Polycarbonate
Weight
• Wall mount: 1.37 kg (3.02 lb)
• Panel mount: 1.5 kg (3.3 lb)
Approvals
• See product nameplate
Compatible Transducers
• Echomax series and STH series
Transducer Frequency
• 44 kHz
1.
For watertight applications, use only approved, suitable size hubs in the
enclosure’s conduit holes.
Note: The MultiRanger is to be used only in the manner outlined in this instruction
manual or protection provided by the equipment may be impaired.
Specifications
• Sensor
About the…
equipment in a residential area may cause interference to several
frequency based communications.
For the XPS 10 F series transducer, a hazardous seal must be used to suit
hazardous area classification. This seal is not supplied by Siemens.
The XPS 15 F comes equipped with a stainless steel coupling suitable for
use in hazardous locations.
Frequency:
43kHz
Beam Angle:
12°
Specifications
Environmental
location: indoor/outdoor
altitude: 2000m maximum
ambient temperature: -20 to 95°C (-4 to 203°F)
pollution degree: 4
Construction
exposure: Kynar®1
colour: slate gray
mounting: 1” NPT conduit connection
options: factory flange to suit ANSI standard
submergence shield, where flooding can occur
split flange for field mounting to suit ANSI
cable: 2-wire shielded / twisted, 0.5 mm2 (20 AWG) PVC
jacket
Supply Source
Transducer shall only be supplied by a Siemens certified controller.
Weight2
0.8kg (1.8lb)
Separation
365m (1200ft) from transducer
Approvals
FM Class 1 Div 1, Group A, B, C and D
FM Class 2 Div 1, Group E, F, and G
see nameplate or consult Siemens for other current approvals
1
Kynar® is registered trade mark of ELF Atochem.
2
approximate shipping weight of transducer with standard cable length
Frequency:
43kHz
Beam Angle:
6°
Environmental
location: indoor/outdoor
Specifications
altitude: 2000m maximum
ambient temperature: -20 to 95°C (-4 to 203°F)
pollution degree: 4
Construction
exposure: Kynar®3
colour: slate gray
mounting: 1” NPT conduit connection
options: factory flange to suit ANSI standard
submergence shield, where flooding can occur
split flange for field mounting to suit ANSI
cable: 2-wire shielded / twisted, 0.5 mm2 (20 AWG) PVC
jacket
Supply Source
Transducer shall only be supplied by a Siemens certified controller.
Weight4
2.0 kg (4.4lb)
Separation
365m (1200ft) from transducer
Approvals
FM Class 1 Div 1, Group A, B, C and D
FM Class 2 Div 1, Group E, F, and G
see nameplate or consult Siemens for other current approvals
3 ®
Kynar is registered trade mark of ELF Atochem
4
approximate shipping weight of transducer with standard cable length
122mm 122mm
(4.8”) (4.8”)
128mm
(5.0”)
nominal
152mm
(6.0”)
to suit ANSI
standards
124mm
(4.9”)
Note:
For the XPS 10 F series transducer, a hazardous seal must be used to
suit hazardous area classification. This seal is not supplied by Siemens.
For more information, refer to page 20.
304
stainless 185mm
steel (7.3”) 185mm
(7.3”)
120mm radiating
to suit ANSI
(4.7”) face
standards
to suit ANSI
standards
158mm
(6.2”)
Note:
The XPS 15 F comes equipped with a stainless steel coupling suitable for
use in hazardous locations.
Easy Aimer
(typical model)
Mounting
safety chain
transducer
Note:
For the XPS 10 F series transducer, a hazardous seal must be used
to suit hazardous area classification. This seal is not supplied by
Siemens. For more information, refer to page 20.
steel
channel
hazardous seal
(XPS 10 F only)
safety
chain
transducer
rigid metal
conduit
Mounting
submergence
shield
hazardous seal
(XPS 10 F only)
factory flanged
transducer
Mounting
bolt
gasket
customer flanged,
flat face only
nut
Note: Tighten the flange bolts evenly in order to ensure a good seal between
the mating flanges.
Caution: Over-tightening can cause performance degradation.
Note:
Installation should only be performed by qualified personnel and in
accordance with local governing regulations.
Recommendations
When using an XPS 15 F transducer, configure the electronic transceiver for
an XCT-12. These two transducers use the same settings.
Do not route cable openly.
For optimum isolation against electrical noise, run cable separately in a
grounded metal conduit.
Seal all thread connections to prevent ingress of moisture.
Do not run cable near high voltage or current runs, contactors and SCR
control drives.
Note:
In the interconnection examples that follow:
an XPS 10 F Series transducer is shown. An XPS 15 F transducer can
also be used, but no hazardous seal is required.
assume that the transducer is located in a Hazardous location (Class I,
Div. 1, Group A,B,C,D or Class II, Div. 1, Group E,F,G.) and the
transceiver in a Non-Hazardous (Safe) Location.
Note:
When connecting to SITRANS LUT400, SITRANS LUC500,
MultiRanger 100/200, or HydroRanger 200, the white,
black, and shield wires are all connected separately. DO
NOT tie the white and shield wires together.
blk
wht
metal conduit
Note:
When connecting to SITRANS LUT400, SITRANS
LUC500, MultiRanger 100/200, or HydroRanger 200, do
NOT use coaxial cable.
Interconnection
Applications
Notes:
The transducer is to be used only in the manner outlined in this
instruction manual.
Normally, the transducer requires no cleaning or maintenance.
However, if performance changes are observed, immediately shut
down the level measurement system and perform a thorough
inspection, especially on the transducer.
An XPS 10 F Series transducer is shown in these examples. An XPS
15 F transducer can also be used, but no hazardous seal is required.
Liquid Applications
Stilling Well / OCM
blind flange
air vent
TS-3 *
transducer
standpipe
bracing
standpipe inlet
stilling well
primary element
Submergence
In applications where flooding is possible, the transducer can be fitted with a
submergence shield*. The shield acts as a bell to create an air pocket in
front of the transducer face. The associated transceiver* interprets this as a
flooding condition, and reacts accordingly.
Note:
Refer to transceiver manual for programming requirements.
hazardous seal
(XPS 10 F only)
transducer
submergence shield*
(Refer to Siemens
instruction manual
7ML19981EG01 for
assembly details)
air pocket
* on applicable models
Applications
Siemens can provide factory bonded flanged transducers or a split flange kit
that will readily mate to the flanged standpipe. Another option is to hang the
transducer from a blind flange.
The standpipe length should be as short and the diameter as large as
possible. As a rule of thumb, the -3 dB cone of the sound beam should not
intersect the standpipe wall in applications opening into a vessel or larger
area. Otherwise, additional blanking will be required to compensate for the
interference zone created by the opening.
Note: When using a stilling well, make sure there is no build-up, welds,
couplings, or other debris on the inside of the well wall. This can affect
reliability of measurement.
flanged
transducer
no no
intersection vessel
vessel
nipple nipple
welded into welded into
blind flange blind flange
vessel
standpipe reflection at
end cut on a interference
45° angle zone created
typically by opening
span:
beam corresponds to tank
angle manufacturer’s
empty level.
rise
1. Beam should not detect bin bottom. If this occurs, use range extension
parameters (on transceivers where available) to omit false echoes. A 6° beam
angle (XPS 15 F) represents a rise:run of about 20:1 (10:1 for the 12° beam
angle of the XPS 10 F). In most tanks, the transducer should be centered as
much as possible (without interference from inlet) for optimum reading range.
2. Sound beam must be perpendicular to liquid surface. If standpipe is used,
refer to page 13.
3. Echo has missed improperly levelled transducer.
4. When performing an empty or full calibration, the tank must contain its
normal vapour and be at its normal temperature.
5. When used in hazardous areas, the XPS 10 F series transducer (shown)
must use a hazardous seal. This seal is not supplied by Siemens. The XPS
15 F Series transducer comes equipped with a stainless steel coupling
suitable for use in hazardous locations.
Differential Level
Applications
Pump Control
Sewage Lift
- E+H
housing or top hat rail housing for control cabinet instrumentation are
sludge and powdery to coarse bulk solids. Also, the flow measurement in
level and flow in a storm water overflow basin with only 1 sensor. Up to 6
1 or 2 channel version.
• Controller
Ultrasonic measurement
Time-of-Flight
Prosonic FMU90
Transmitter in housing for field or top hat rail
mounting for up to 2 sensors
FDU90/91/92/93/95
F L E X Benefits:
• Simple, menu-guided operation with 6-line plain text display, 15
languages selectable
• Envelope curves on the display for quick and simple diagnosis
• Easy operation, diagnosis and measuring point documentation with
the supplied "FieldCare" operating program
• Time-of-Flight correction via integrated or external temperature
sensors
• Linearisation (up to 32 points, freely configurable) for the most
common flumes and weirs
pre-programmed and selectable
• Online calculation of the flume-/weir-flows via integrated flow curves
• Automatic detection of the sensors FDU9x
Characteristic / Application
Separated version with Field housing or top hat rail housing for control
cabinet instrumentation, up to 6 relays for pump / rake / limit control, 1
or 2 channel version
Specialities
Protection Class IP 66 / NEMA 4x
automatic sensor recognition of FDU9x sensors
option: flow measurement for open channel and weirs or additional
pump control functions
Supply / Communication
90 ... 253 VAC
10.5 ... 32 VDC
up to 2x 4...20mA HART
Profibus DP
Accuracy
+/- 2mm + 0.17% of measured distance
Ambient temperature
-40 °C ... 60 °C
(-40 °F ... 140 °F)
Communication
up to 2x 4 ... 20 mA HART
Profibus DP
Certificates / Approvals
ATEX, CSA
Options
Illuminated display, 6 line graphic display with country specific menu
guidance, on-site diagnosis with envelope curve on display
2 Endress+Hauser
Prosonic S FMU90
Product headline
Separated version with field housing or top hat rail housing for control
cabinet instrumentation, up to 6 relays for tendency alarm, flow pulse
output or backwater / sludge alarm, 1 or 2 channel version
Sensor features
pre-programed flow curves for typical open channel measurement
Degree of protection
IP66 (Fieldhousing)
IP20 (top hat rail housing)
Display/Operation
Illuminated display, 6 line graphic display with country specific menu
guidance, on-site diagnosis with envelope curve on display
Outputs
4...20mA HART
Optional:
second 4...20 mA output (e.g. for 2 times flow measurement
1 relay (standard)
Optional:
3 or 6 relays
Inputs
up to 2 FDU9x sensors
Digital communication
HART, Profibus DP
3 Endress+Hauser
Prosonic S FMU90
Characteristic / Application
Separated version with Field housing or top hat rail housing for control
cabinet instrumentation, up to 6 relays for limit control, 1 or 2 channel
version
Specialities
Protection Class IP 66 / NEMA 4x
automatic sensor recognition of FDU9x sensors
Supply / Communication
90 ... 253 VAC
10.5 ... 32 VDC
up to 2x 4...20mA HART
Profibus DP
Accuracy
+/- 2mm + 0.17% of measured distance
Ambient temperature
-40 °C ... 60 °C
(-4 °F ... 140 °F)
Communication
up to 2x 4 ... 20 mA HART
Profibus DP
Certificates / Approvals
ATEX, CSA
4 Endress+Hauser
Prosonic S FMU90
Components
Sensors FDU9x
Endress+Hauser AG addresses.endress.com
Switzerland info@endress.com
BANI GHALEB WASTEWATER TREATMENT PLANT
• Sensor
Technical Information
Prosonic S FDU90
Ultrasonic measuring technology
Application
• Continuous, non-contact level measurement of liquids and bulk solids in silos, on
conveyor belts, in material stockpiles and in crushers
• Flow measurement in open flumes and measuring weirs
• Maximum measuring range: 3 m (9.8 ft) in liquids; 1.2 m (3.9 ft) in bulk solids
Your benefits
• Integrated temperature sensor for time-of-flight correction, enabling accurate
measurements even if temperatures change
• Hermetically welded PVDF sensor for maximum chemical resistance
• Suitable for harsh ambient conditions thanks to separate transmitter installation
(up to 300 m (984 ft))
• Self-cleaning effect ensures minimum deposit build-up
• Weather resistant and flood-proof (IP68)
• International Dust-Ex and Gas-Ex certificates available
Prosonic S FDU90
BD
2
100%
D
E
F
L 0%
A0034882
1 Prosonic S sensor
2 Prosonic S transmitter
BD Blocking distance
D Distance between reference point (sensor membrane) and surface of medium
E Empty distance
F Span
L Level
The sensor transmits ultrasonic pulses in the direction of the surface of the medium. There, they are
reflected back and received by the sensor. The transmitter measures the time t between the
transmission and reception of a pulse. From this time, and using the sonic velocity c, the transmitter
calculates the distance D between the reference point (sensor membrane) and the surface of the
medium:
D = c ⋅ t/2
The level L is derived from D. With linearization, the volume V or the mass M is derived from L.
Q
Q
A0035219
1 Prosonic S sensor
2 Prosonic S transmitter
D Distance between sensor membrane and surface of liquid
Q Flow
The sensor transmits ultrasonic pulses in the direction of the surface of the liquid. There, they are
reflected back and received by the sensor. The transmitter measures the time t between the
transmission and reception of a pulse. From this time, and using the sonic velocity c, the transmitter
calculates the distance D between the (reference point) sensor membrane and the surface of the
liquid:
D = c x t/2
4 Endress+Hauser
Prosonic S FDU90
The level L is derived from D. With linearization, the flow Q is derived from L.
Input
Blocking distance Signals within the blocking distance (BD) range cannot be measured due to the transient response of
the sensor.
A B
(0.23)
0.07
A0039791
Measuring range Estimation of the effective sensor range depending on the operating conditions
1. Add up all the applicable attenuation values from the following lists.
2. From the total calculated attenuation, use the range chart below to calculate the range of the
sensor.
Endress+Hauser 5
Prosonic S FDU90
[ft] R [m]
33 10
9.8 3
0 0 A [dB]
0 10 20 30 40 50 60 70 80 90 100
A0039796
Power supply
Supply voltage Is provided by the transmitter.
Connection data
• Supply voltage: 24 VDC ± 10 %
• Residual ripple: < 100 mV
• Current consumption: 250 mA per sensor
• Suitable power supply unit: RNB130 from Endress+Hauser
• When the sensor heater is active, the integrated temperature sensor cannot be used. Instead,
use one of the following external temperature sensors:
• Pt100
• Omnigrad S TR61 from Endress+Hauser
• For information on connecting the external temperature sensor, see Technical Information
TI00397F.
NOTICE
A damaged cable shield may cause malfunctions
‣ For pre-terminated cables: connect the black wire (shield) to the "BK" terminal.
‣ For extension cables: twist the shield and connect to the "BK" terminal.
6 Endress+Hauser
Prosonic S FDU90
1
≤30 m
(98 ft)
YE BK RD YE BK RD BN BU
≤300 m 2
(984 ft)
3
+ -
YE BK RD YE BK RD 24 VDC
FMU90 FMU90
A0039801
3 Connection diagram for sensor; YE: yellow, BK: black; RD: red; BU: blue; BN: brown; protective conductor
GNYE: green/yellow
A Without sensor heater
B With sensor heater
1 Shielding of sensor cable
2 Terminal box
3 Shielding of extension cable
max. (1)
30 m
YE BK RD
max. (2)
300 m
(3)
YE BK RD
FMU95
A0039804
4 Connection diagram for sensor; YE: yellow, BK: black; RD: red; BU: blue; BN: brown; protective conductor
GNYE: green/yellow
1 Shielding of sensor cable
2 Terminal box
3 Shielding of extension cable
Endress+Hauser 7
Prosonic S FDU90
• Cross-section
0.75 to 2.5 mm2 (18 to 14 AWG)
• Resistance
Max. 8 Ω per wire
• Capacitance, wire to shield
Max. 60 nF
Suitable extension cables are available from Endress+Hauser.
Shortening the sensor cable The sensor cable can be shortened if necessary (see the Operating Instructions for the FMU90 or
FMU95 transmitter).
Installation
Installation conditions for
level measurement
2 3
6
BD
BD
BD
1/6D 4
1
D L
5 a
A0036746
Emitting angle/beam
• α (typical) = 12 °
• L (max) = 3 m (9.8 ft)
• r (max) = 0.31 m (1.0 ft)
Other conditions
• The lower edge of the sensor should be located inside the vessel
• The maximum level may not enter the blocking distance
Several sensors in one vessel
Sensors that are connected to a common FMU90 or FMU95 transmitter can be used in one vessel.
8 Endress+Hauser
Prosonic S FDU90
B C
BD
E
Hmax V
A
1xb 0
b
0
A0036744
A Khafagi-Venturi flume
b0 Width of Khafagi-Venturi flume
B Upstream side
C Downstream side
BD Blocking distance of the sensor
E Empty calibration (to be entered during commissioning)
Hmax Maximum upstream level
V Flow
BD
E ≥3 H max
H max
A0036745
Endress+Hauser 9
Prosonic S FDU90
Installation options
A B C
(examples)
. -
-
A0036747
6 Installation in systems
A On U-rail or bracket
B With FAU40 alignment unit
C With 1" sleeve welded to a grating
A B C
1 1
A0036748
Nozzle mounting
L L
45° 45°
D
D
A0039838
D Nozzle diameter
L Nozzle length
10 Endress+Hauser
Prosonic S FDU90
A0036695
1 Venting hole
A B C D
41 mm
A0036749
Environment
Degree of protection Tested according to IP68/NEMA6P (24 h at 1.83 m (6 ft) under water)
Thermal shock resistance Based on DIN EN 60068-2-14; test according to min./max. process temperature; 0.5 K/min; 1 000 h
Electromagnetic Electromagnetic compatibility in accordance with all the relevant requirements outlined in the EN
compatibility 61326 series and NAMUR Recommendation EMC (NE 21). For details, refer to the Declaration of
Endress+Hauser 11
Prosonic S FDU90
Conformity. With regard to interference emission, the devices meet the requirements of class A, and
are only designed for use in an "industrial environment".
Process
Process temperature –40 to +80 °C (–40 to +176 °F)
To prevent the build-up of ice on the sensor, the sensors are available in a version with integrated
sensor heating.
Mechanical construction
Dimensions
109 (4.29) A B
26 (1.02)
137 (5.39)
28 (1.1)
a
ø75 (2.95)
A0036335
9 FDU90-*G*** (G1 and G1-1/2 thread); FDU90-*N*** (NPT 1 and NPT 1-1/2 thread). Unit of
measurement mm (in)
A Cable gland
B Pipe adapter
a Front thread; G1-1/2 or NPT1-1/2
b Rear thread; G1 or NPT1
12 Endress+Hauser
Prosonic S FDU90
86 (3.39)
26 (1.02)
58 (2.28)
a ø75 (2.95)
89 (3.5) 8 (0.31)
R2
.5
(0
.1)
B A
A0044086
2 (0.08)
8 (0.31)
2 (0.08)
1 G 1"
41 mm
A0036333
• The counter nut is included in the delivery for the following sensors:
FDU90-*G*** (rear G1 thread)
• The counter nut is not suitable for NPT threads.
Endress+Hauser 13
Prosonic S FDU90
Materials
3 4
5
2
6
1
A0038714
12 Materials
1 Sensor housing: PVDF
2 Counter nut: PA6.6
3 Cable gland: PA
4 Pipe adapter: CuZn nickel-plated
5 O-ring: EPDM
6 Seal: EPDM
RoHS The measuring system complies with the substance restrictions of the Restriction on Hazardous
Substances Directive 2011/65/EU (RoHS 2).
RCM-Tick marking The supplied product or measuring system meets the ACMA (Australian Communications and Media
Authority) requirements for network integrity, interoperability, performance characteristics as well
as health and safety regulations. Here, especially the regulatory arrangements for electromagnetic
compatibility are met. The products are labelled with the RCM- Tick marking on the name plate.
A0029561
14 Endress+Hauser
Prosonic S FDU90
Ordering information
Ordering information Detailed ordering information is available for your nearest sales organization
www.addresses.endress.comor in the Product Configurator under www.endress.com
1. Click Corporate
2. Select the country
3. Click Products
4. Select the product using the filters and search field
5. Open the product page
The Configuration button to the right of the product image opens the Product Configurator.
R
A
100%
E
F
0%
A0019526
Endress+Hauser 15
Prosonic S FDU90
Accessories
Sensor extension cable • Maximum permissible total length (sensor cable + extension cable): 300 m (984 ft)
• The sensor cable and extension cable are the same type of cable.
Sensor without sensor heater
• Cable type: LiYCY 2x(0.75)
• Material: PVC
• Ambient temperature:–40 to +105 °C (–40 to +221 °F)
• Order number: 71027742
Sensor with sensor heater
• Cable type: LiYY 2x(0.75)D+2x0.75
• Material: PVC
• Ambient temperature:–40 to +105 °C (–40 to +221 °F)
• Order number: 71027746
ø98 (3.86)
A0036332
• Material: PVDF
• Order number: 52025686
16 Endress+Hauser
BANI GHALEB WASTEWATER TREATMENT PLANT
- WIKA
PRESSURE SWITCH
MANUFACTURER: - WIKA
MODEL: - PGS23
Ingress protection: IP 65
Permissible medium temperature: -20 ... +100 °C (-4 ... +212 °F)
Applications
■■ Control and regulation of processes
■■ Monitoring of plants and switching of circuits
■■ For gaseous and liquid aggressive media that are
not highly viscous or crystallising, also in aggressive
environments
■■ Chemical industry, petrochemical industry, power plants,
mining, on-/offshore, environmental technology, machine
building and general plant construction
Special features
■■ Up to 4 switch contacts per instrument
■■ Also available with case filling for high dynamic pressure
loads or vibrations
■■ Instruments with inductive contacts for use in hazardous
areas
■■ Instruments with contacts for PLC applications
■■ Instruments optionally available in safety version S3 per Model PGS23.100 with switch contact model 831.1
EN 837
Description
Wherever the process pressure has to be indicated locally Switch contacts consisting of several contacts can also be
and, at the same time, circuits need to be switched, the set to a single set point. Contact actuation is made when the
model PGS23.1x0 switchGAUGE finds its use. actual value pointer travels beyond or below the desired set
point.
Switch contacts (electrical switch contacts) make or break an
electric control circuit dependent upon the pointer position The pressure gauge is manufactured in accordance with
of the indicating measuring instrument. The switch contacts DIN 16085 and fulfils all requirements of the relevant stand-
are adjustable over the full extent of the scale range (see ards (EN 837-1) and regulations for the on-site display of the
DIN 16085), and are mounted predominantly below the dial, working pressure of pressure vessels.
though also partly on top of the dial. The instrument pointer
(actual value pointer) moves freely across the entire scale As switch contacts, magnetic snap-action contacts, reed
range, independent of the setting. switches, inductive contacts and electronic contacts are
The set pointer can be adjusted using a removable adjust- available. Inductive contacts can be used in hazardous
ment key in the window. areas. For triggering programmable logic controllers (PLC),
electronic contacts and reed switches can be used.
Other versions
Measuring span Nominal size Max. number of contacts Switching current range I Switch version 1)
≤ 1.0 bar 100, 160 1 0.02 ... 0.3 A L
> 1.0 bar 100, 160 1 0.02 ... 0.6 A S
≤ 1.6 bar 100, 160 2 0.02 ... 0.3 A L
> 1.6 bar 100, 160 2 0.02 ... 0.6 A S
≤ 4.0 bar 100 3 or 4 0.02 ... 0.3 A L
> 4.0 bar 100 3 or 4 0.02 ... 0.6 A S
≤ 2.5 bar 160 3 or 4 0.02 ... 0.3 A L
> 2.5 bar 160 3 or 4 0.02 ... 0.6 A S
1) Design of the contact coil: Version “L” = light-weight, version “S” = heavy
The recommended setting range of the contacts is 25 ... 75 % of the scale (0 ... 100 % on request).
Contact material (standard): Silver-nickel, gold-plated
Legend:
S1 = Standard version, with blow-out device (per EN 837)
S3 = Safety version, Solidfront (per EN 837)
The recommended setting range of the contacts is 10 ... 90 % of the scale (0 ... 100 % on request).
Legend:
S1 = Standard version, with blow-out device (per EN 837)
S3 = Safety version, Solidfront (per EN 837)
The recommended setting range of the contacts is 10 ... 90 % of the scale (0 ... 100 % on request).
Characteristics
Contact version Normally open, normally closed
Type of output PNP transistor
Operating voltage DC 10 ... 30 V
Residual ripple max. 10 %
No-load current ≤ 10 mA
Switching current ≤ 100 mA
Residual current ≤ 100 µA
Voltage drop (with Imax.) ≤ 0.7 V
Reverse polarity protection Conditional UB (the switched output 3 or 4 must never be set directly to minus)
Anti-inductive protection 1 kV, 0.1 ms, 1 kΩ
Oscillator frequency approx. 1,000 kHz
EMC per EN 60947-5-2
1 1
- -
RL (load)
2. contact 2. contact
RL (2. load)
Legend:
S1 = Standard version, with blow-out device (per EN 837)
S3 = Safety version, Solidfront (per EN 837)
Characteristics
Contact version Change-over contact
Type of contact Bistable
Max. switching voltage AC/DC 250 V
Min. switching voltage Not required
Switching current AC/DC 1 A
Min. switching current Not required
Transport current AC/DC 2 A
cos ϕ 1
Switching power 60 W/ VA
Contact resistance (static) 100 mΩ
Insulation resistance 109 Ω
Breakdown voltage DC 1,000 V
Switching time incl. contact chatter 4.5 ms
Contact material Rhodium
Switch hysteresis 3 ... 5 %
Certificates (option)
■■ 2.2 test report per EN 10204 (e.g. state-of-the-art
manufacturing, indication accuracy)
■■ 3.1 inspection certificate per EN 10204 (e.g. indication
accuracy)
Accessories
■■ Panel mounting flange, polished stainless steel
■■ Surface mounting flange, stainless steel
■■ Sealings (model 910.17, see data sheet AC 09.08)
■■ Valves (models IV20/IV21, see data sheet AC 09.19, and
models IV10/IV11, see data sheet AC 09.22)
■■ Syphons (model 910.15, see data sheet AC 09.06)
■■ Overpressure protector (model 910.13, see data sheet
AC 09.04)
■■ Cooling element (model 910.32, see data sheet AC 09.21)
■■ Diaphragm seal
Contact models: 821 and 851 Contact models: 831 und 830 E
14062234.01
14336089.01
Only use cable with a Only use cable with a
diameter of 5 ... 10 mm diameter of 7 ... 13 mm
49.5
68
M20x1,5
M20x1,5
11417412.01
> 16 bar without vent valve
removable
adjustment key
11417421.02
≤ 16 bar with vent valve
> 16 bar without vent valve
removable
adjustment key
11417005.01
removable adjust-
ment key
11417013.02
removable
adjustment key
1543369.01
≤ 16 bar with vent valve
> 16 bar without vent valve
removable
adjustment key
1584839.01
≤ 16 bar with vent valve
> 16 bar without vent valve
removable
adjustment key
0406090.07
Type of contact Dimensions in mm Process Dimensions in mm
X Y Z connection h ±1 S2 S3 S4 S5 S6
Single or double contact 141 30.5 1) 48 G½B 118 6 20 3 17 17.5
Triple contact 153.5 30.5 1) 60.5 ½ NPT 117 - 19 - - -
M20 x 1.5 118 6 20 3 17 17.5
1) Plus 17 mm with pressure ranges ≤ 0 ... 60 bar
11421955.01
removable
adjustment key
Process Dimensions in mm
connection h ±1 S2 S3 S4 S5 S6
G½B 87 6 20 3 17 17.5
G¼B 80 5 13 2 11 9.5
G⅜B 83 5.5 16 3 14 13
½ NPT 86 - 19 - - -
14034487.01
removable
adjustment key
Process Dimensions in mm
connection h ±1 S2 S3 S4 S5 S6
G½B 103 6 20 3 17 17.5
G¼B 96 5 13 2 11 9.5
G⅜B 99 5.5 16 3 14 13
½ NPT 102 - 19 - - -
14034797.01
removable
adjustment key
Process Dimensions in mm
connection h ±1 S2 S3 S4 S5 S6
G½B 87 6 20 3 17 17.5
G¼B 80 5 13 2 11 9.5
G⅜B 83 5.5 16 3 13 13
½ NPT 86 - 19 - - -
14034471.01
removable
adjustment key
Process Dimensions in mm
connection h ±1 S2 S3 S4 S5 S6
G½B 112 6 20 3 17 17.5
G¼B 105 5 13 2 11 9.5
G⅜B 108 5.5 16 3 14 13
½ NPT 111 - 19 - - -
removable
adjustment key
For cable
socket
dimensions
see page 9
14021931.01
G ... Process connection
Process Dimensions in mm
connection h ±1 S2 S3 S4 S5 S6
G½B 118 6 20 3 17 17.5
G¼B 111 5 13 2 11 9.5
G⅜B 114 5.5 16 3 14 13
½ NPT 117 - 19 - - -
Ordering information
Model / Nominal size / Contact model / Contact version / Connection location / Process connection / Options
© 01/2009 WIKA Alexander Wiegand SE & Co. KG, all rights reserved.
The specifications given in this document represent the state of engineering at the time of publishing.
We reserve the right to make modifications to the specifications and materials.
07/2019 EN
- E+H
Magnetic Flowmeter
industry.
pressure loss.
Ideal for water measurement, e.g. drinking water, utility water and
industrial/municipal wastewater.
Output: 4 – 20 mA
- Siemens
Magnetic Flowmeter
Manufacturer: Siemens
flanged,
measurement of
wastewater treatment,
category C4
compact.
Output: 4 – 20 mA