2) after that start push button gets released and the supply to contactor coil
continued through latching contact provided to the main contractor of DOL
starter.
3) ) At the time of stopping the motor we need to press the stop push button
on DOL starter circuit, this disconnect supply to the coil and contactor coil gets
de-energized, and it releases the contactor latched pole, and the motor supply
gets disconnected.
Under voltage protection
• when the voltage falls below a certain value, or in the event of failure of
supply during motor operation, the coil C is de-energized. The motor is then
disconnected from the supply.
Overload protection
• In case of an overload on the motor, one or all the overload coils(O.L.C.) are
energized. The normally closed contact D is open and the contactor coil C is
de-energized to disconnect the supply to motor.
• Fuses are provided in the circuit for short-circuit protection.
• Direct-on-line starter is a simple and cheap method.