You are on page 1of 9

17554543, 2016, 15, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-pel.2016.0310 by EBMG ACCESS - KENYA, Wiley Online Library on [20/02/2023].

See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
IET Power Electronics

Research Article

ISSN 1755-4535
Design and application of a thyristor Received on 19th April 2016
Revised on 17th August 2016
switched capacitor bank for a high harmonic Accepted on 11th September 2016
doi: 10.1049/iet-pel.2016.0310
distortion and fast changing single-phase www.ietdl.org

electric welding machine


Wei-Hsiang Ko ✉, Jyh-Cherng Gu
Department of Electrical Engineering, National Taiwan University of Science and Technology, No. 43, Keelung Road, Sec. 4,
Da’an District, Taipei City 10607, Taiwan
✉ E-mail: d10107101@mail.ntust.edu.tw

Abstract: A single-phase electric machine invokes a great reactive power demand in operation, resulting in a large voltage
fluctuation in the supply system. Furthermore, the frequent and rapid operating characteristics of an electric welding
machine cause a serious voltage flicker problem. The operation of welding equipment also generates significant
harmonic current distortion, and distorts the voltage waveform of the supply system. Hence, this study focused on
designing and applying a thyristor switched capacitor (TSC) bank for voltage flicker improvement. However, the single-
phase TSC should also satisfy the reactive power demand and compensation speed, considering proper ratings of TSC
to bear high harmonic distortion. This study shows the calculation results and discusses the impact of different
capacities and different step numbers on TSC design. In addition, thyristor switches and a single-phase power factor
controller were designed and implemented. The experimental results are also presented.

1 Introduction low impedance path, which shunts harmonic currents out of the
system and thereby further reduces losses and improves power
A load that has rapid and significant changes causes voltage quality. Because the operation of a welding machine produces
fluctuation in the power system. Loads such as electric arc high harmonic current and significant reactive power demand, if a
furnaces and steel plant rolling mills produce significant load passive filter is used for improving power quality, then the
current changes, resulting in serious voltage flicker, which is an required capacity and quantity will become considerable in order
important threat to power quality [1]. In fact, static var to fulfil the reactive power demand and harmonic current
compensator (SVC) or static synchronous compensator requirement. Thyristor switched capacitor banks (TSC) can be
(STATCOM) systems are usually employed for power quality applied for compensating the fast changing characteristics of
improvement in steel plants [2–7]; these systems not only electric welding machines, provide a maximum response of
compensate voltage flicker and harmonic distortion, but also one-cycle of system frequency [27–29]. Furthermore, common
compensate the imbalance voltage problem [8–10]. However, this automatic power factor controllers, typically used in three-phase
study focused on a single-phase electric welding machine, which systems, regulate the power factor with an assumption of a
has periodic and rapid changes, large reactive power demand, and well-balanced three-phase system, and calculate power from one
high harmonic current distortion characteristics, which result in a phase voltage and current as the reference. However, currently there
serious voltage flicker and harmonic distortion problem while the are no commercial power factor controllers for single-phase systems.
welding machine is operated. It is also difficult to apply an SVC For the reasons above, this study focused on the design and
or STATCOM system to improve power quality in a single-phase implementation of a TSC for a single-phase electric welding
low-voltage distribution system. machine. The proposed TSC can mitigate the voltage flicker
Rapidly advancing power electronics technology and mature problem and compensate the power factor; at the same time, the use
semiconductor technology have proved beneficial for the of thyristor switches can implement rapid compensation to meet the
development of power electronics-based equipment that is fast changing characteristics of the welding machine. Furthermore,
indispensable in industrial applications. Many studies have the designed TSC also considers the background harmonic voltage
investigated the application of shunt active harmonic filters for the and harmonic currents from the welding machine. This study not
harmonic filtering of power systems [11, 12]. Shunt active only designed a reactive power compensation device for the
harmonic filters can implement instantaneous dynamic electric welding machine, but also developed and implemented a
compensation, which can improve the system harmonic distortion single-phase power factor controller and thyristor switches.
and compensate the reactive power demand [13, 14], and balance The main contributions of this research are as follows: (i) Design
the asymmetrical load currents [15–17]. An active filter is suitable of a low-voltage TSC for voltage flicker improvement; (ii)
for compensating the rapid changing characteristics of electric development of a power factor controller for single-phase systems;
welding machines. However, the actual industrial applications of (iii) development of transient-free thyristor switches for capacitors;
commercial active filters are mainly three-phase active filters, (iv) implementation of the proposed TSC; and (v) the
although there are some special single-phase active filter implementation results, as shown in the experimental result section.
applications and researches [18–20]. However, there is no
commercialised single-phase active filter for the time being.
The passive harmonic filter is also a common solution for 2 Study of the existing system
harmonic filtering, and there are many studies on passive filter
design [21–24]. The actual applications are presented in [25, 26]. The simplified system configuration and measurement point are
The series resonance frequency of the filter provides an extremely depicted in Fig. 1. A V-connected transformer transforms a

IET Power Electron., 2016, Vol. 9, Iss. 15, pp. 2751–2759


& The Institution of Engineering and Technology 2016 2751
17554543, 2016, 15, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-pel.2016.0310 by EBMG ACCESS - KENYA, Wiley Online Library on [20/02/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
system equivalent resistance (Ω), XS is the system equivalent
reactance (Ω).
|ΔV| can be expressed as follows

|DV |  XS × DS, (2)



where ΔS is calculated from DQ2 + DP2 . Therefore, the required
reactive power to meet the expected maximum voltage fluctuation
(ΔVt), that is, the total output reactive power (QC) of the TSC, can
be formulated as

2
 2  
    DV   DP 
QC = DQ −  t  −   . (3)
XS (1 − DVt )2 

3.2 Component ratings

From the total output reactive power and the total step number (M),
the capacitance (C ) of each step can be expressed as
Fig. 1 Power system configuration of the electric welding machine
(1 − p)QC
C= (4)
vMVS2
three-phase power source to one single-phase power source for
supplying an electric welding machine. The primary and where p is the percentage of series reactor (%), M is the total step
secondary voltage ratings are 11.4 kV and 440 V, respectively. number of the capacitor bank, VS is the system voltage (V ), ω is
Fig. 2a depicts the measured welding machine current and voltage the angular frequency (rad/s).
waveforms of the single-phase 440 V system. The active power and The impedance of the series reactor can be calculated by
power factor are 773 kW and 0.44 lagging, respectively; the total XL = pXC , and the inductance (L) of each step can be expressed as
harmonic voltage distortion is approximately 14%, and the total
harmonic current is approximately 1242 A. The measured system
voltage and reactive power demand statistic result is shown in pMVS2
L= . (5)
Fig. 2b. The reactive power demand of the load is approximately v(1 − p)QC
between 1400 and 1900 kvar. During the operation of the welding
machine, the measured load current and voltage rms value of the From Fig. 4b, the harmonic impedance, seen from the load terminal,
single-phase 440 V system are shown in Figs. 2c and d. can be expressed as
The welding machine has rapid and periodically changing features;
the maximum current fluctuation is approximately 6000 A within V (f ) Z ( f )ZC ( f )
1.8 s. The measured voltage drop is 11.37%, refer to the rated ZTH ( f ) = = S . (6)
voltage 440-V, during load operation. Furthermore, Figs. 2e and f I(f ) ZS ( f ) + ZC ( f )
shows the measured harmonic voltage and current spectrum, where
the third harmonic is the main component. The simulated phase The definition of the current dividing factor into capacitor branch is
voltage rms values in the 11.4 kV side is shown in Fig. 3, the given by
maximum voltage fluctuation is approximately 3.12% while
welding machine operated. ZS ( f ) Z (f)
Fcf ( f ) = = TH (7)
ZS ( f ) + ZC ( f ) ZC ( f )

3 TSC design Then, the harmonic currents from the load into the capacitor branch
can be calculated as
From the existing system study result, the electric welding machine
produced high harmonic current, large reactive power demand, and ZTH ( f )
rapid changes. In this study, the proposed low-voltage TSC can be Iload ( f ) = Ih ( f )Fcf ( f ) = Ih ( f ) (8)
ZC ( f )
incorporated into this rapid changing and high harmonic distortion
system for voltage flicker improvement.
where Ih is the harmonic current source. The harmonic current that
comes from the upstream side harmonic voltage distortion (Vhv)
3.1 Reactive power capacity and flows into the capacitor branch can be expressed as

The low voltage single-phase equivalent circuit is shown in Fig. 4a, Vhv ( f )
Ihv ( f ) = . (9)
including a system voltage source, a system equivalent impedance, ZS ( f ) + ZC ( f )
and the electric welding machine. When the TSC is incorporated
into the system, the system equivalent circuit can be simplified as If the phase of the harmonics are in phase, the total harmonic current
shown in Fig. 4b, where the welding machine is regarded as a in the capacitor branch is given by
harmonic current source.
The voltage fluctuation can be expressed as follow [30]
IC ( f ) = Ihv ( f ) + Iload ( f ). (10)

DES = (RS + jXS ) × DI + DV , (1) From the IEEE and IEC shunt capacitor standards [31, 32], when
considering harmonic voltages, the definition of the rated voltage
where ES is the equivalent system voltage source (V), RS is the of the capacitors is the arithmetic sum of the rms values of the

IET Power Electron., 2016, Vol. 9, Iss. 15, pp. 2751–2759


2752 & The Institution of Engineering and Technology 2016
17554543, 2016, 15, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-pel.2016.0310 by EBMG ACCESS - KENYA, Wiley Online Library on [20/02/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License

2753
IET Power Electron., 2016, Vol. 9, Iss. 15, pp. 2751–2759
& The Institution of Engineering and Technology 2016
Fig. 2 Measured in the existing 440-V system

b Voltage and reactive power demand statistic


a Voltage and current waveforms

e Harmonic voltage spectrum


f Harmonic current spectrum
d Voltage rms value
c Current rms value
17554543, 2016, 15, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-pel.2016.0310 by EBMG ACCESS - KENYA, Wiley Online Library on [20/02/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
Fig. 3 Simulated 11.4 kV phase voltage rms values in the existing system

harmonic voltage and the fundamental ( f1) voltage, as given by switch configuration consists of a bipolar thyristor module and a
control circuit module. When the thyristor switch receives an

1
external conducting control signal from the power factor
VC = VC (f ). (11) controller, the zero-cross triggering technology of the control
f =f1 circuit module will switch on the capacitor without excessive
inrush current and switch off at the instant when the current is
In addition, the rated current of the capacitors is the square root of the reduced to zero.
sum of the squared values of the currents at the fundamental and
harmonic frequencies, as given by (12). The rated current is also
the rating of the series reactors and the thyristor switches. 3.4 Single-phase power factor controller


1  To control the single-phase reactive power, the power factor
IC = IC2 (f ). (12) controller must be suitable for a single-phase system and exhibit
f =f1 fast control performance. Therefore, a single-phase power factor
controller was developed; the signal process diagram of each cycle
3.3 Thyristor switch is shown in Fig. 5a. The controller calculates the instantaneous
power from the single-phase voltage and current signals every
If a magnetic contactor is applied for the capacitor switching, the cycle, and the controller can control the required reactive power on
mechanical lifetime will be significantly shortened because of the the basis of the configurable power factor target, as shown in
frequent switching. Furthermore, the contactor is controlled by an Fig. 5b. A default one-cycle delay time was used.
exciting coil, and the switching time is heavily limited by its
mechanical structure; the switching time is generally longer than
several hundred milliseconds. Therefore, the contactor is not 4 Simulation and discussion
suitable for rapid and frequent switching applications. In order to
meet the fast switching requirement, this study employed thyristor In this study, an 11.11 and a 14.80% series reactor for the capacitor
switches for the capacitor switching. Owing to the firing and bank were calculated as discussed in this section. The voltage
cut-off characteristics of thyristors, the shortest switching time is fluctuation before improvement was 11.37%, and the average
one cycle of the power system frequency. The developed thyristor reactive power demand was 1440 kvar. The 440-V system
equivalent short-circuit capacity was 12.96 MVA. The calculated
voltage fluctuation with different total reactive power output of

Fig. 4 Equivalent system circuit Fig. 5 Developed single-phase power factor controller
a Single-phase circuit a Signal process diagram of each cycle
b Harmonic impedance circuit b Reactive power control diagram

IET Power Electron., 2016, Vol. 9, Iss. 15, pp. 2751–2759


2754 & The Institution of Engineering and Technology 2016
17554543, 2016, 15, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-pel.2016.0310 by EBMG ACCESS - KENYA, Wiley Online Library on [20/02/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
Fig. 6 Calculated voltage fluctuation against total installed reactive power

Table 1 Capacitor bank calculation parameters In this research work, the final implemented TSC had a total of
660 kvar output capacity, owing to the limited budget and
Reactor, p 11.11% 14.80%
restricted installation space. The capacitor bank was split to 12
equivalent capacitance 16009.93 µF 15345.52 µF
steps, with 14.80% reactors. All steps will be switched on
equivalent inductance 0.049 mH 0.068 mH simultaneously by the controller. From the calculated result, the
tuning frequency 180 Hz 165 Hz voltage fluctuation can be improved from 11.27 to 7.28% with a
total output capacity 1314.55 kvar 1314.55 kvar total installed capacity of 660 kvar. A 0.25% of third-harmonic
voltage and a 0.50% of fifth-harmonic voltage distortion from the
upstream side were considered. The designed fundamental and
TSC is shown in Fig. 6. When the installed total reactive power harmonic components of each step are listed in Table 2.
output exceeds 1300 kvar, the voltage fluctuation can be reduced Furthermore, the designed capacitor bank took an allowed
to 5.42%, mainly from the active power. The total reactive power overvoltage factor of 1.05 into account; the fundamental voltage
output of 1315 kvar was used for the simulation, which showed a and the total harmonic voltage were 542 and 88 V, respectively.
reduction in voltage fluctuation from 11.37% to 5.42%. Hence, the designed rated voltage of the capacitor was required to
The tuning frequency of the capacitor bank is 180 Hz when p = be at least 630 V. The designed maximum fundamental current
11.11%; that is, a third-harmonic filter bank. When p = 14.80%, and the total harmonic currents were 131 and 58 A, respectively.
the tuning frequency is 156 Hz, and the capacitor bank is mainly Hence, the designed rated current values were required to be at
for reactive power compensation. Because of the harmonic least 143 A for each step.
impedance characteristic, some part of the third-harmonic current The actual parameters of the implemented TSC are listed in Table 3,
will flow into the capacitor bank. The parameters for calculation where the rated capacity of each capacitor unit is 105 kvar, and the
are listed in Table 1. designed quality factor of the series reactors is 37.47. Some
The calculated capacitor rated voltage with different installed considerations of the TSC design are as follows: (i) The
reactive power output values is shown in Fig. 7a. When the consideration of harmonic voltage and current followed the
capacitor is in series with the 11.11% reactor, which provides a definition of the rated voltage and current of the IEEE and IEC
third-harmonic current with an extremely low impedance, most of shunt capacitor standards; (ii) the designed rated voltage of the
the third-harmonic current flows through the capacitor branch, thus capacitor took an allowed system overvoltage factor into account;
producing an extremely large voltage drop on the capacitor (iii) low tolerances of the components were used in order to control
terminals. The rated voltage of the capacitor must be at least performance and frequency shifts; (iv) the proper capacitor unit
2.2 kV when the total reactive power is only 50 kvar; when the temperature category were chosen for the ambient temperature
total reactive power is 1315 kvar, the rated voltage can be reduced on-site [31, 32]; and (v) an individual fuse for each step provided
to 593 V. Nevertheless, when a 14.80% reactor is in series with protection to the components against fault current.
the capacitor, only some part of the third-harmonic current goes
through the capacitor. When 1315 kvar output capacity is installed,
the rated voltage of the capacitors must be at least 597 V. Fig. 7b 5 Implementation and experimental results
shows the calculated total harmonic current into the capacitor bank
vs. total installed output capacity. A total harmonic current of 830 The TSC configuration is shown in Fig. 8. The total installed output
A flows into the capacitor bank with the 14.80% reactor when the capacity was 660 kvar, each step had approximately 55 kvar;
total reactive power of 1315 kvar is installed. When 11.11% furthermore, each step included a fuse, single-phase reactor,
reactors are involved, most of third-harmonic current will flow thyristor switch, and single-phase capacitor unit. The current
through the capacitor bank, regardless of the installed total signal of the controller came from the secondary side of the
capacity. However, when the total reactive power output capacity transformer.
of 1315 kvar is installed in the system, the fundamental current of
the capacitor bank is approximately 3137 A. Therefore, the
capacitor bank is mandatorily split into several small steps, in 5.1 TSC measurement results
order to reduce the required ratings of the components. The
calculated total harmonic current into each capacitor with different The measured voltage and current rms value at the capacitor terminal
total step number is shown in Fig. 7c. When the total step number of one step are shown in Figs. 9a and b From the measurement
is greater than 12, the total harmonic current into each capacitor is results in Fig. 9a, the transient voltage exceeded the rated voltage
less than 100 A. However, the larger the total step number, the of the capacitor unit during the switching period; however, the
greater the component cost and required installation space; overvoltage was still in the allowed operating range of capacitor
the smaller the total step number, the higher the required unit [30, 31]. The experimental measurement results of proposed
component current ratings; the smaller the total installed output TSC are listed in Table 4. Fig. 9c shows the measured transient
capacity, the higher the required component rated voltage. Thus, current waveform of the TSC. The inrush current of the capacitor
the improvement in voltage flicker is restricted. Therefore, the bank was eliminated, and the transient was damped within two
capacitor bank design needs to consider the tradeoffs between the cycles. The measured current waveforms while the TSC was
improvement requirement, installation cost, and installation space. switched on are illustrated in Fig. 9d. The system current is the

IET Power Electron., 2016, Vol. 9, Iss. 15, pp. 2751–2759


& The Institution of Engineering and Technology 2016 2755
17554543, 2016, 15, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-pel.2016.0310 by EBMG ACCESS - KENYA, Wiley Online Library on [20/02/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
Fig. 7 Calculated results
a Rated voltage of the capacitor against total installed capacity
b Total harmonic current into the capacitor bank against total installed capacity
c Total harmonic current into each capacitor against total installed step number

measured current at the secondary side of transformer, and the


capacitor current is the measured current of a one-step capacitor.
From the measurement results, the controller sent a switching

Table 2 Designed fundamental and harmonic components of each step


Parameters Voltage, V Current, A

fundamental 542.25 130.71


3rd-harmonic 79.50 57.50
5th-harmonic 4.90 5.90
7th-harmonic 2.10 3.60
9th-harmonic 0.81 1.76
11th-harmonic 0.61 1.62
13th-harmonic 0.29 0.89
rms value 630.46 142.99

Table 3 Parameters of the implemented TSC


Parameters Capacitor Reactor Thyristor switch

rated voltage 660 V 135 V 460 V


rated current 124.48 A 143.00 A 143.00 A
capacitance 639.40 µF – –
inductance – 1.629 mH –
quantity 12 12 12
Fig. 8 Implementation of the TSC configuration

IET Power Electron., 2016, Vol. 9, Iss. 15, pp. 2751–2759


2756 & The Institution of Engineering and Technology 2016
17554543, 2016, 15, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-pel.2016.0310 by EBMG ACCESS - KENYA, Wiley Online Library on [20/02/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
Fig. 9 Measured in the TSC
a Voltage rms value of a one-step capacitor
b Current rms value of a one-step capacitor
c Inrush current waveform of the 660- kvar TSC
d Transient current waveforms while the TSC was switched on

‘ON’ signal after approximately two cycles (t1 + t2) from load t3 is the time for the thyristor switch finding a voltage
operated, where t1 is the sampling and calculation period of zero-crossing timing.
controller, and t2 is the default one-cycle delay time. The period

Table 4 Parameters of the implemented TSC 5.2 System measurement results

Parameters Designed Measured Error The measured voltage fluctuation was reduced from 11.37 to
6.40%, after a 660 kvar TSC was installed in parallel with the
rated current 143.00 A 136.67 A −6.33 A (−4.43%) welding machine; the measured system voltage is shown in
rated voltage 630.00 V 589.65 V −40.35 V (−6.40%)
3rd-harmonic voltage 79.50 V 73.51 V −5.99 V (−7.53%)
Fig. 10a. The measured system voltage and reactive power
5th-harmonic voltage 4.90 V 5.61 V 0.71 V (14.48%) demand statistic with the TSC are illustrated in Fig. 10b. The
7th-harmonic voltage 2.10 V 1.03 V −1.07 V (−50.95%) reactive power from the system side was approximately between
3rd-harmonic current 57.50 A 53.44 A −4.06 A (−7.06%) 900 and 1500 kvar. If an extra 660 kvar TSC can be installed in
5th-harmonic current 5.90 A 6.69 A 0.79 A (13.39%)
7th-harmonic current 3.60 A 1.38 A −2.22 A (−61.66%)
parallel, then the expected reactive power demand from the
system side will shift to between 400 and 900 kvar, hence

IET Power Electron., 2016, Vol. 9, Iss. 15, pp. 2751–2759


& The Institution of Engineering and Technology 2016 2757
17554543, 2016, 15, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-pel.2016.0310 by EBMG ACCESS - KENYA, Wiley Online Library on [20/02/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License

Fig. 10 Measured in the 440-V system


a Voltage rms value with and without the TSC
b Voltage and reactive power demand statistic with the TSC
c Voltage and current waveforms with the TSC
d Harmonic voltage spectrum with the TSC
e Harmonic current spectrum with the TSC

providing a better voltage fluctuation improvement. The measured 6 Conclusion


system voltage and current waveforms with the TSC are shown in
Fig. 10c. The measured system harmonic voltage and current This paper presented a unique TSC to compensate voltage flicker in a
spectrum with the TSC are shown in Figs. 10d and e, single-phase system. The design of the TSC was proposed and
respectively. The total harmonic voltage distortion was reduced discussed. The designed TSC can provide fast switching
approximately from 14 to 8%. performance, and has sufficient ratings to bear harmonic currents

IET Power Electron., 2016, Vol. 9, Iss. 15, pp. 2751–2759


2758 & The Institution of Engineering and Technology 2016
17554543, 2016, 15, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-pel.2016.0310 by EBMG ACCESS - KENYA, Wiley Online Library on [20/02/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
from the load and upstream sides. Furthermore, thyristor switches 14 Corasaniti, V.F., Barbieri, M.B., Arnera, P.L., et al.: ‘Hybrid active filter for
and a single-phase power factor controller were also developed. reactive and harmonics compensation in a distribution network’, IEEE Trans.
Ind. Electron., 2009, 56, (3), pp. 670–677
From the practical experimental results, the proposed TSC 15 Sakorn, P.N.: ‘The simplified control of three-phase four-leg shunt active power
performed a fast reactive power compensation, and operating of filter for harmonics mitigation, load balancing and reactive power
the components were within the designed ratings. As a result, this compensation’. Proc. Int. Conf. on Electrical Engineering/Electronics, Computer,
design improves the voltage fluctuation caused by a high harmonic Telecommunications and Information Technology, Nakhon Ratchasima,
Thailand, May 2014, pp. 1–6
distortion and fast changing single-phase electric welding machine. 16 Ribeiro, R.L.A., Azevedo, C.C., Sousa, R.M.: ‘A robust adaptive control strategy
of active power filters for power-factor correction, harmonic compensation, and
balancing of nonlinear loads’, IEEE Trans. Power Electron., 2012, 27, (2),
pp. 718–730
7 References 17 Luo, A., Peng, S., Wu, C., et al.: ‘Power electronic hybrid system for load
balancing compensation and frequency-selective harmonic suppression’, IEEE
1 Dionise, T.J.: ‘Assessing the performance of a static var compensator for an electric Trans. Ind. Electron., 2012, 59, (2), pp. 723–732
arc furnace’, IEEE Trans. Ind. Appl., 2014, 50, (3), pp. 1619–1629 18 Santos, W.R.N., Silva, E.R., Jacobina, C.C.B., et al.: ‘The transformerless
2 Al-Mubarak, A.H., Khan, M.H., Al-Kadhem, M.Z.: ‘Dynamic reactive power single-phase universal active power filter for harmonic and reactive power
compensation for voltage support using static var compensator (SVC) in Saudi compensation’, IEEE Trans. Power Electron., 2014, 29, (7), pp. 3563–3572
Arabia’. Proc. IEEE Int. Conf. Electrical Power and Energy, London, Ontario, 19 Miret, J., Castilla, M., Matas, J., et al.: ‘Selective harmonic-compensation control
Canada, October 2015, pp. 484–490 for single-phase active power filter with high harmonic rejection’, IEEE Trans. Ind.
3 Kumar, P.: ‘Application of FACT devices for voltage stability in a power system’. Electron., 2009, 56, (8), pp. 3117–3127
Proc. IEEE 9th Int. Conf. Intelligent Systems and Control, Coimbatore, India, 20 Shu, Z., Xie, S., Li, Q.: ‘Single-phase back-to-back converter for active power
January 2015, pp. 1–5 balancing, reactive power compensation, and harmonic filtering in traction power
4 Han, C., Yang, Z., Chen, B., et al.: ‘Evaluation of cascade-multilevel-converter-based system’, IEEE Trans. Power Electron., 2011, 26, (2), pp. 334–343
STATCOM for arc furnace flicker mitigation’, IEEE Trans. Ind. Appl., 2007, 43, (2), 21 Zobaa, A.F., Abdel Aleem, S.H.E.: ‘A new approach for harmonic distortion
pp. 378–385 minimization in power systems supplying nonlinear loads’, IEEE Trans. Ind.
5 Kanchanaharuthai, A., Chankong, V., Loparo, K.A.: ‘Transient stability and Inf., 2014, 10, (2), pp. 1401–1412
voltage regulation in multimachine power systems vis-à-vis STATCOM and 22 Nassif, A.B., Xu, W., Freitas, W.: ‘An investigation on the selection of filter
battery energy storage’, IEEE Trans. Power Syst., 2015, 30, (5), pp. 2404–2416 topologies for passive filter applications’, IEEE Trans. Power Deliv., 2009, 24,
6 Kashani, M.G., Babaei, S., Bhattacharya, S.: ‘SVC and STATCOM application in (3), pp. 1710–1718
electric arc furnace efficiency improvement’. Proc. IEEE Int. Conf. Symp. on 23 Julio, C.B., Jose, M.M.O.: ‘Comprehensive design methodology of tuned passive
Power Electronics for Distributed Generation Systems, Rogers, Arkansas, USA, filters based on a probabilistic approach’, IET Transm. Distrib., 2014, 8, (1),
June 2013, pp. 1–7 pp. 170–177
7 Pereira, R.M.M., Ferreira, C.M.M., Barbosa, F.P.M.: ‘Comparative study of 24 Beres, R.N., Wang, X., Blaabjerg, F., et al.: ‘Optimal design of high-order
STATCOM and SVC performance on dynamic voltage collapse of an electric passive-damped filters for grid-connected applications’, IEEE Trans. Power
power system with wind generation’, IEEE Latin America Trans., 2014, 12, (2), Electron., 2016, 31, (3), pp. 2083–2098
pp. 138–145 25 Badrzadeh, B., Smith, K.S., Wilson, R.C.: ‘Designing passive harmonic filters for
8 Lee, S.Y., Wu, C.J.: ‘Reactive power compensation and load balancing for an aluminum smelting plant’, IEEE Trans. Ind. Appl., 2011, 47, (2), pp. 973–983
unbalanced three-phase four-wire system by a combined system of an SVC and 26 Das, J.C.: ‘Design and application of a second-order high-pass damped filter for
a series active filter’, IET Electr. Power Appl., 2000, 147, (6), pp. 563–578 8000-hp ID fan drives—a case study’, IEEE Trans. Ind. Appl., 2015, 51, (2),
9 Alsulami, A., Bongiorno, M., Srivastava, K., et al.: ‘Balancing asymmetrical load pp. 1417–1426
using a static var compensator’. Proc. IEEE PES Int. Conf. Innovative Smart Grid 27 Kallaste, A., Kutt, L., Bolgov, V., et al.: ‘Reactive power compensation for spot
Technologies Europe, Istanbul, Turkey, October 2014, pp. 1–6 welding machine using thyristor switched capacitor’. Proc. Int. Conf. Power
10 Li, K., Liu, J., Wang, Z., et al.: ‘Strategies and operating point optimization of Quality and Supply Reliability, Pärnu, Estonia, August 2008, pp. 241–245
STATCOM control for voltage unbalance mitigation in three-phase three-wire 28 Jalali, S.G., Lasseter, R.H., Dobson, I.: ‘Dynamic response of a thyristor controlled
systems’, IEEE Trans. Power Deliv., 2007, 22, (1), pp. 413–422 switched capacitor’, IEEE Trans. Power Deliv., 1994, 9, (3), pp. 1609–1615
11 Alfonso-Gil, J.C., Pérez, E., Ariño, C., et al.: ‘Optimization algorithm for selective 29 Ghassemi, A., Fazel, S.S., Maghsoud, I., et al.: ‘Comprehensive study on the power
compensation in a shunt active power filter’, IEEE Trans. Ind. Electron., 2015, 62, rating of a railway power conditioner using thyristor switched capacitor’, IET
(6), pp. 3351–3361 Electr. Syst. Transp., 2014, 4, (4), pp. 97–106
12 Lee, T.L., Hu, S.H.: ‘An active filter with resonant current control to suppress 30 Guan, J.L., Gu, J.C.C., Wu, J.: ‘A noval method for estimating voltage flicker’,
harmonic resonance in a distribution power system’, IEEE Trans. Power IEEE Trans. Power Deliv., 2005, 20, (1), pp. 242–247
Electron., 2016, 4, (1), pp. 198–209 31 IEC Standard 60831-1: ‘IEC Shunt Power Capacitors of the Self-Healing Type for
13 Campanhol, L.B.G., Silva, S.A.O., Goedtel, A.: ‘Application of shunt active power a.c. System Having a Rated Voltage Up to and Including 1000 V’, 2014
filter for harmonic reduction and reactive power compensation in three-phase 32 IEEE C1531: ‘IEEE guide for application of power application and specification of
four-wire systems’, IET Power Electron., 2014, 7, (11), pp. 2825–2836 harmonic filters’, 2003

IET Power Electron., 2016, Vol. 9, Iss. 15, pp. 2751–2759


& The Institution of Engineering and Technology 2016 2759

You might also like