Section 2.3
Cabling Recommendations
Siemens recommends using SIMATIC NET industrial Ethernet shielded cables for all Ethernet ports.
CONTENTS
• Section 2.3.1, “Protection On Twisted-Pair Data Ports”
• Section 2.3.2, “Gigabit Ethernet 1000Base-TX Cabling Recommendations”
Section 2.3.1
Section 2.3.2
5e Yes No action required. New installations should be designed with Category 5e or higher.
Follow these recommendations for copper data cabling in high electrical noise environments:
• Data cable lengths should be as short as possible, preferably 3 m (10 ft) in length. Copper data cables should
not be used for inter-building communications.
• Power and data cables should not be run in parallel for long distances, and should be installed in separate
conduits. Power and data cables should intersect at 90° angles when necessary to reduce inductive coupling.
Cabling Recommendations 7