You are on page 1of 2

TECHNICAL DATA SHEET FOR XZ1(S) Document ID: TE/QMS/F/02

AL CABLE
Rev. No. : 01 Issued Date : 10/06/2021
Customer : Technimont

S.No Particulars 1 X 240


1 Name of Manufacturer Polycab India Ltd.
2 Type of cable AL/XLPE/PO
3 Voltage Grade kV 0.6/1 (1.2)
4 No of cores X size in sqmm 1 X 240
5 Conductor
a) Material Plain Aluminium (Class-2) to IEC 60228
Max. d.c. resistance of conductor at 20° C
b) 0.125
(ohm/km)
c) Shape of the conductor Stranded compacted Circular
6 Insulation
a) Material XLPE type DIX3 according UNE-HD 603 S1
b) Nominal thickness (mm) 1.7
7 Oversheath
a) Material Flame retardent polyolefin compound
b) Minimum thickness (mm) 1.16
c) Colour of outer sheath. Black
8 Electrical Parameters
Max. a.c. resistance of conductor at 90° C
a) 0.162
(ohm/km)
b) Calculated Cable reactance (ohm/km) 0.0800
c) Impedance of cable (ohm/km) 0.181
Maximum conductor temperature under
9 90°C
normal operating conditions
Maximum conductor temperature at the
10 250°C
termination of short circuit
Short Circuit rating of conductor for the
11 22.68
duration of 1 sec (kA)
12 Continuous Current carrying capacities :-
(a) In Ground at 30°C (A) 335
(b) In Air at 40°C (A) 434
13 Applicable Standard IEC 60502-1
14 Approx. overall diameter of the cable (mm) 24.5
15 Minimum bending radius 15 times Overall diameter
16 Max. Tensile strength

(i) for Cables pulled with stocking (kg.) 5x D2 where D is the overall diameter of the cable
ii) for Cables pulled with pulling eyes (kg) 734
POLYCAB ELECTRIC 0.6/1 (1.2) KV GRADE XLPE
17 Embossing
LSZH

YEAR POLYCAB ELECTRIC 0.6/1 (1.2) KV GRADE


18 Printing , CABLE SIZE, AL/XLPE/PO WITH SEQUENTIAL
MARKING at every one meter interval.

19 Flammability Test As per IEC:60332-I


20 Low smoke opacity As per IEC:61034
21 Water resistance category AD8
TECHNICAL DATA SHEET FOR XZ1(S) Document ID: TE/QMS/F/02
AL CABLE
Rev. No. : 01 Issued Date : 10/06/2021
Customer : Technimont

S.No Particulars 1 X 240


22 Low Smoke Halogen Free As per IEC 60754-1
23 Low emission of corrosive gases As per IEC 60754-2
24 Chemical protection IEC 60502-1
25 Shock resistance AG2
26 UV resistance As per BS EN:50618
27 Cold resistance - 5 Deg C
28 Resistance to chemical agents IEC 60502-1
29 Resistance to greases and oils IEC 60502-1
suitable for direct burial in the ground
30 Yes
installation.
31 Standard drum length 1000
Drum dimension as per standard drum
32 1400 x 650 x 650
length
33 Minimum / Maximum drum length 500 / 2000

Note:-Testing of cables shall be as per IEC:60502-1 only.

Prepared By : Shubham