You are on page 1of 2

Power and Control Cable IEC 60502-1

Flame Retardant, Sunlight Resistant 90 °C / Uo/U 0,6/1 kV


XLPE-Insulation, PVC-Sheath

2XY-fl
Application
For electricity supply and control in public networks and industrial plants; suitable for use in zone 1 and zone 2 group II classified areas (IEC 60079-14).
(Please note possible additional or special installation requirements of IEC 60079-14).
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; for direct burial. Indoor installation is allowed in
areas where the construction products regulation (CPR) acc. to EN 50575 of fire class is not required. (Please note the relevant legal / local installation
requirements)
Construction
Conductor plain annealed copper wire , class 1 (circular solid, RE) or class 2 (circular
................................................. stranded, RM) according to IEC 60228
Insulation cross-linked polyethylene XLPE
.................................................
Colour black
................................................. * (other colours on request)
Outer polyvinyl chloride PVC, black
.................................................
Cable LEONI KERPEN ELECTRIC CABLE SIZE 0.6/1 kV IEC 60502-1
................................................. YEAR PRODUCTION LOT CODE LENGTH MARKING

Technical data Abbreviations


Flame propagation Temperature range Power and Control Cable
- Test on single cable IEC 60332-1-2 -30°C up to +90°C 2X XLPE insulation
- Test on bunched cables IEC 60332-3-24 (Cat. C) (during operation) Y PVC outer sheath
-5°C up to +50°C -fl reduced flame propagation
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
(during installation)
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 ° C) max. +250°C
Amount of halogen acid gas IEC 60754-1 (max. 17 %) (under short circuit)
Oil resistance ICEA S-73-532 Minimum bending radius
Sunlight resistance UL 1581 section 1200 8 x cable diameter

Electrical Properties at 20 °C
Conductor resistance max. Ω/km according to IEC 60228
Test voltage Urms (core : core) V 3500
Nominal Voltage U0 / U 0,6 / 1 kV
Highest system voltage Um max. V 1200 (for three phase systems)

Technical datasheet © LEONI Kerpen GmbH · Phone: +49 24 02 17 1 · www.leoni-process-industry.com/en/


Print date: 27.08.2020 Transfer to third parties only by authority of LEONI Kerpen GmbH Creator: TF/MY
Date of version: 05.05.2020 Printing errors excepted. Subject to alterations. Image serves as an example. Page: 1/2
For cable disposal please note the relevant local legal disposal requirements.
2001210000_IEC_60502-1_ 2XY-fl_black_RE-RM-Core_en.pdf
Power and Control Cable IEC 60502-1

Flame Retardant, Sunlight Resistant 90 °C / Uo/U 0,6/1 kV


XLPE-Insulation, PVC-Sheath

2XY-fl
Geometrical data
Size RT of insulation RT of outer sheath Outer dia. Weight Part No.
nom. nom. approx. approx. Colour
mm mm mm kg/km black
1
1 x 10 RM 0,70 1,4 8,3 152 LKX208103970000
1 x 16 RE 0,70 1,4 8,7 198 LKX208100060000
1 x 16 RM 0,70 1,4 9,4 213 LKX208100070000
1 x 25 RM 0,90 1,4 10,8 308 LKX208100080000
1 x 35 RM 0,90 1,4 11,9 407 LKX208100090000
1 x 50 RM 1,00 1,4 13,2 535 LKX208100100000
1 x 70 RM 1,10 1,4 15,2 732 LKX208100110000
1 x 95 RM 1,10 1,5 17,0 1006 LKX208100120000
1 x 120 RM 1,20 1,5 18,5 1227 LKX208100130000
1 x 150 RM 1,40 1,6 20,5 1514 LKX208100140000
1 x 185 RM 1,60 1,6 22,7 1872 LKX208100150000
1 x 240 RM 1,70 1,8 25,6 2436 LKX208100160000
1 x 300 RM 1,80 1,8 28,4 3045 LKX208100170000
1 x 300 RM 1,80 1,8 28,4 3153 LKX208105470000
1 x 400 RM 2,00 1,9 32,0 3889 LKX208100180000
1 x 500 RM 2,20 2,0 36,9 4972 LKX208100190000
1 x 630 RM 2,40 2,2 43,1 6601 LKX208100200000
1 x 800 RM 2,60 2,3 47,8 8399 LKX208100900000
1 x 1000 RM 2,80 2,4 51,9 10322 LKX208100890000
RT = Radial Thickness

Technical datasheet © LEONI Kerpen GmbH · Phone: +49 24 02 17 1 · www.leoni-process-industry.com/en/


Print date: 27.08.2020 Transfer to third parties only by authority of LEONI Kerpen GmbH Creator: TF/MY
Date of version: 05.05.2020 Printing errors excepted. Subject to alterations. Image serves as an example. Page: 2/2
For cable disposal please note the relevant local legal disposal requirements.
2001210000_IEC_60502-1_ 2XY-fl_black_RE-RM-Core_en.pdf