Professional Documents
Culture Documents
TİC AŞ
TUZLA FABRİKA/TUZLA PLANT
MGT-XLPE/OSCR/LSZH/SWA/LSZH
FIRE RESISTANT, FLAME RETARDANT
INSTRUMENTATION CABLE
500 V
Design
Max. Core Temperature : 90°C
1.Conductor
Stranded annealed copper to IEC 60228 (Class 2)
2
Cross section: 2,5 mm (7/0,67 mm) 3 2 1
3.Insulation
Cross Linked Polyethylene (XLPE)
Laying-up: Twisted pairs
4.Overall Screen
Polyester (PEPT) Tape
2
Tinned stranded copper 0,5 mm
Aluminum backed polyester foil
6.Armour
Galvanized steel wire armour
Polyester (PEPT) Tape (optional)
7.Outer Sheath
Low Smoke Zero Halogen Compound
Outer sheath Colour: Red
Core Identification
Pair : Black - White
(For single and multi pair cables, number printing with their
respective pair number on the White core)
Fire Resistant Flame Retardant Operating Temp. UV Resistant Low Smoke Halogen Free Minimum
IEC 60331-23 IEC 60332-1 -30oC +70oC IEC 61034 IEC 60754-1 Bending
Installation Temp. Radius
-5oC +50oC 10xD
Standards
Generally to EN 50288-7 (Where applicable)..
Marking (ink-jet)
NEXANS - Year - cable definition- No. of pair& cross-section –-Voltage rating - + metrage
Example: NEXANS 2015 MGT-XLPE/OSCR/LSZH/SWA/LSZH 1x2x1.5 mm² 500 V 0050
2
Electrical Properties 2,5 mm
o
o Max. DC Resistance (Ohm/km) @ 20 C 7,56
o Max. Mutual Capacitance @1000 Hz (pF/m) <150
o
o Insulation Resistance @ 20 C 1 G Ohm x km
o Test Voltage (V) 1 minute 2,000 V ac or 3,000 V dc
Layer arrangement
st nd rd th
Central 1 2 3 4
Layer Layer Layer Layer
1P 1P
2P 2P
P: Pair
*Dummies may be used to maintain the cable in circular formation