6/1 kV COPPER XLPE POWER CABLE (UNARMOURED)

CU/XLPE/PVC

GEN. TO AS/NZS 5000.1:2005

BEFORE YOU START


1. The current ratings indicated in this Specification Sheet have been based on the calculation procedures as
recommended in IEC 60287 and the following assumptions. Rating factors should be
a. Max continuous conductor temp = 90° C
b. Ambient air temperature = 40°C
c. Ambient ground temperature = 25°C
d. Depth of laying = 0.5m
e. Thermal resistivity of soil = 1.2K.m/W
2. The particulars given above are nominal & are subject to normal manufacturing tolerances.
3. Sequential length marking shall be provided at every one meter on outer sheath by hot foil indenting/Printing.
4. All the drums shall be packed by PP sheet over the outermost cable layer.

Parameter Specification
Annealed Plain Copper-Stranded Circular Class-2
Conductor Material & Shape (Phase & Earth Core)
(As Per AS/NZS 1125)
CONSTRUCTION

Separator Tape N/A


Insulation (Phase & Earth) XLPE (X-90) (As Per AS/NZS 3808)
Core Identification By Red, Black & Green70%/Yellow30% Coloured Insulation
Insulated Cores Laid-Up With Suitable Non-Hygroscopic Filler As
Laid-Up
Applicable
Outer Sheath Material Orange, PVC Type 5V-90 (UV Resistant) (As Per AS/NZS 3808)

Std. Packing Length In Mtrs 500 ± 1%


Type of Drum Wooden Drum
PACKING

Overall Quantity Tolerance + 0%/- 1%


Non - Standard Length Not Less Than 100 mtrs. Up To 5% Of Order
Non Standard Length
Qty.

Embossing/Printing AUSTRALASIAN CABLES INDIA 0.6/1 kV X-90 ELECTRIC CABLE "Cu"


'CABLE SIZE' ' CU/XLPE/PVC ' AS/NZS 5000.1 'YEAR OF MFG'

Australasian Cables (A Division of EESA Pty Ltd) 604/89, High Street, Kew 3101 Ph: 0437720513 / 0420 598 900
www.eesa.net.au / sales@eesa.net.au
PARAMETER SPECIFICATION
Max. Conductor Temperature at Rated Current 90°C
CARRYING Ambient Air Temperature 40°C
CAPACITY
CURRENT

Ambient Soil Temperature 25°C


Soil Thermal Resistivity 1.2k.m/W
Depth of Laying 0.5m

Voltage Grade 0.6/1 kV


Permissible Voltage Variation ± 10%
PROPERTIES
ELECTRICAL

Permissible Frequency Variation ± 5%


Combined Voltage & Frequency Variation ± 10%
Max. Conductor Temperature At Rated Current 90°C
Max. Conductor Temp. At The End Of Short Circuit 250°C

DIMENSIONS

No./Nom. Cross No. / Size Of Wire


Approx. Conductor Termite Protection Insulation (Nom./ Min
Sectional Area of (Before Stranding In
Diameter in mm (Nom. Thickness) In Thickness) In mm
Conductor in Nos. X Nos. / mm
mm
Sq.mm
Phase Earth Phase Earth Phase Earth
2 x 4 + 4 (E) 7/0.86 7/0.86 2.55 2.55 N/A 0.7/0.53 0.7/0.53

DIMENSIONS
No./Nom. Cross
Inner Sheath - (Nom. Outer Sheath - Approx. Overall
Sectional Area of Approx. Net Weight
/Min. Thickness) In (Nom. /Min. Dia. Of Cable In -
Conductor in Nos. X Of Cable In Kg/Km
mm Thickness) In mm mm
Sq.mm

2 x 4 + 4 (E) N/A 1.8 / 1.43 12.5 250 -

ELECTRICAL PROPERTIES

No./Nom. Approx. Short Circuit


Max. D.C Resistance Approx.
Cross Sectional Max. A.C Resistance Conductor Approx. Rating Of
Of Conductor At 20°C Reactance At
Area of At 90°C In Ohm/Km Inductance @ Capacitance Conductor
In Ohm/Km 50 Hz in
Conductor in 50Hz in In µF/km (Duration 1 Sec.)
Ohm/km
Nos. X Sq.mm mH/km In kA
Phase Earth Phase Earth
2 x 4 + 4 (E)) 4.61 4.61 5.90 5.90 0.301 0.095 0.28 0.57

CURRENT CARRYING CAPACITY

Australasian Cables (A Division of EESA Pty Ltd) 604/89, High Street, Kew 3101 Ph: 0437720513 / 0420 598 900
www.eesa.net.au / sales@eesa.net.au
Unenclosed Enclosed - Metallic Underground non-
Wiring Enclosure In Buried direct metallic wiring
No./Nom. Cross Spaced Touching Air enclosure
Sectional Area
of Conductor in
Nos. X Sq.mm

2 x 4 + 4 (E) 45 Amp 42 Amp 37 Amp 45 Amp 45 Amp

INSTALLATION

No./Nom. Cross Sectional Area Min. Safe Bending Radius Of Cable During Installation In mm
of Conductor in Nos. X Sq.mm During Installation Installed
2 x 4 + 4 (E) 75 50

MECHANICAL PROPERTIES
No./Nom. Cross Sectional
Area of Conductor in Nos. X Safe Pulling Force (When Pulled By Pulling Eye) In kN
Sq.mm
2 x 4 + 4 (E) 0.84

Notes

1. The particulars given above are nominal & are subject to normal manufacturing tolerances.
2. Sequential length marking shall be provided at every one meter on outer sheath by hot foil indenting/Printing.
3. All the drums shall be packed by PP sheet over the outermost cable layer.