You are on page 1of 3

Power and Control Cable IEC 60502-1

Flame Retardant, Sunlight Resistant 90 °C / Uo/U 0,6/1 kV


XLPE-Insulation, Armour, PVC-Sheath

2XYRY-fl
Application
For electricity supply and control in public networks and industrial plants; suitable for use in zone 1 and zone 2 group II classified areas (IEC 60079-14).
(Please note possible additional or special installation requirements of IEC 60079-14).
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; for direct burial. Indoor installation is allowed in
areas where the construction products regulation (CPR) acc. to EN 50575 of fire class is not required. (Please note the relevant legal / local installation
requirements)
Construction
Conductor plain annealed copper wire , class 1 (circular solid, RE) or class 2 (circular
................................................. stranded, RM) according to IEC 60228
Insulation cross-linked polyethylene XLPE
.................................................
Colour black, continuously numbered
................................................. * (other colours on request)
Laying cores twisted in layers (if necessary with filling element(s))
.................................................
Wrapping at least 1 layer of plastic tape
.................................................
Inner polyvinyl chloride PVC, black
.................................................
Armour galvanised round steel wires
.................................................
Outer polyvinyl chloride PVC, black
.................................................
Cable LEONI KERPEN ELECTRIC CABLE SIZE 0.6/1 kV IEC 60502-1
................................................. YEAR PRODUCTION LOT CODE LENGTH MARKING
Technical data Abbreviations
Flame propagation Temperature range Power and Control Cable
- Test on single cable IEC 60332-1-2 -30°C up to +90°C 2X XLPE insulation
- Test on bunched cables IEC 60332-3-24 (Cat. C) (during operation) Y PVC inner sheath
-5°C up to +50°C R galvanised round steel wires
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
(during installation) Y PVC outer sheath
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 ° C) max. +250°C -fl reduced flame propagation
Amount of halogen acid gas IEC 60754-1 (max. 17 %) (under short circuit)
Oil resistance ICEA S-73-532 Minimum bending radius
Sunlight resistance UL 1581 section 1200 10 x cable diameter

Electrical Properties at 20 °C
Conductor resistance max. Ω/km according to IEC 60228
Test voltage Urms (core : core) V 3500
Test voltage Urms (core : armour) V 3500
Nominal Voltage U0 / U 0,6 / 1 kV
Highest system voltage Um max. V 1200 (for three phase systems)

Technical datasheet © LEONI Kerpen GmbH · Phone: +49 24 02 17 1 · www.leoni-process-industry.com/en/


Print date: 27.08.2020 Transfer to third parties only by authority of LEONI Kerpen GmbH Creator: TF/MY
Date of version: 23.03.2020 Printing errors excepted. Subject to alterations. Image serves as an example. Page: 1/3
For cable disposal please note the relevant local legal disposal requirements.
2001230000_IEC_60502-1_ 2XYRY-fl_black_RE-RM-Multicore_en.pdf
Power and Control Cable IEC 60502-1

Flame Retardant, Sunlight Resistant 90 °C / Uo/U 0,6/1 kV


XLPE-Insulation, Armour, PVC-Sheath

2XYRY-fl
Geometrical data
Size RT of insulation Dia. over Dia. of armour wire RT of outer sheath Outer dia. Weight Part No.
inner sheath
nom. approx. nom. nom. approx. approx. Colour
mm mm mm mm mm kg/km black
5
5 x 1,5 RE 0,70 9,2 0,9 1,8 14,6 389 LKX200500930000
5 x 1,5 RM 0,70 9,8 0,9 1,8 15,2 412 LKX200500340000
5 x 2,5 RE 0,70 10,2 0,9 1,8 15,6 462 LKX200501240000
5 x 2,5 RM 0,70 10,9 0,9 1,8 16,3 493 LKX200500290000
7
7 x 1,5 RE 0,70 10,0 0,9 1,8 15,4 441 LKX200500940000
7 x 1,5 RM 0,70 10,7 0,9 1,8 16,1 468 LKX200500350000
7 x 2,5 RE 0,70 11,2 0,9 1,8 16,6 547 LKX200501250000
7 x 2,5 RM 0,70 11,9 0,9 1,8 17,3 570 LKX200500300000
10
10 x 1,5 RE 0,70 12,8 1,25 1,8 18,9 674 LKX200500950000
10 x 1,5 RM 0,70 13,7 1,25 1,8 19,8 713 LKX200500360000
10 x 2,5 RE 0,70 14,3 1,25 1,8 20,4 813 LKX200501260000
10 x 2,5 RM 0,70 15,3 1,25 1,8 21,4 872 LKX200500310000
12
12 x 1,5 RE 0,70 13,2 1,25 1,8 19,3 727 LKX200500960000
12 x 1,5 RM 0,70 14,1 1,25 1,8 20,2 762 LKX200501100000
12 x 2,5 RE 0,70 14,9 1,25 1,8 21,0 897 LKX200501270000
12 x 2,5 RM 0,70 15,9 1,25 1,8 22,0 949 LKX200500320000
12 x 10 RM 0,70 25,2 1,6 1,9 32,2 2429 LKX200502810000
19
19 x 1,5 RE 0,70 15,6 1,25 1,8 21,7 934 LKX200500990000
19 x 1,5 RM 0,70 16,7 1,25 1,8 22,8 992 LKX200501130000
19 x 2,5 RE 0,70 17,6 1,6 1,8 24,4 1301 LKX200501300000
19 x 2,5 RM 0,70 19,3 1,6 1,8 26,1 1406 LKX200501430000
27
27 x 1,5 RE 0,70 19,2 1,6 1,8 26,0 1350 LKX200501020000
27 x 1,5 RM 0,70 20,6 1,6 1,8 27,4 1449 LKX200501160000
27 x 2,5 RE 0,70 21,6 1,6 1,8 28,4 1704 LKX200501330000
27 x 2,5 RM 0,70 23,2 1,6 1,9 30,2 1815 LKX200501460000
37
37 x 1,5 RE 0,70 21,6 1,6 1,9 28,6 1643 LKX200501050000
37 x 1,5 RM 0,70 23,1 1,6 1,9 30,1 1760 LKX200501190000
37 x 2,5 RE 0,70 24,3 1,6 1,9 31,3 2102 LKX200501360000
37 x 2,5 RM 0,70 26,1 1,6 2,0 33,3 2249 LKX200501490000
48
48 x 1,5 RE 0,70 24,8 1,6 2,0 32,0 2002 LKX200501090000
48 x 1,5 RM 0,70 26,6 1,6 2,0 33,8 2116 LKX200501230000
48 x 2,5 RE 0,70 28,4 2 2,1 36,6 2892 LKX200501400000
48 x 2,5 RM 0,70 30,4 2 2,2 38,8 3058 LKX200501410000
48 x 2,5 RM 0,70 30,4 2 2,1 38,6 3055 LKX200511320000

Technical datasheet © LEONI Kerpen GmbH · Phone: +49 24 02 17 1 · www.leoni-process-industry.com/en/


Print date: 27.08.2020 Transfer to third parties only by authority of LEONI Kerpen GmbH Creator: TF/MY
Date of version: 23.03.2020 Printing errors excepted. Subject to alterations. Image serves as an example. Page: 2/3
For cable disposal please note the relevant local legal disposal requirements.
2001230000_IEC_60502-1_ 2XYRY-fl_black_RE-RM-Multicore_en.pdf
Power and Control Cable IEC 60502-1

Flame Retardant, Sunlight Resistant 90 °C / Uo/U 0,6/1 kV


XLPE-Insulation, Armour, PVC-Sheath

2XYRY-fl
RT = Radial Thickness

Technical datasheet © LEONI Kerpen GmbH · Phone: +49 24 02 17 1 · www.leoni-process-industry.com/en/


Print date: 27.08.2020 Transfer to third parties only by authority of LEONI Kerpen GmbH Creator: TF/MY
Date of version: 23.03.2020 Printing errors excepted. Subject to alterations. Image serves as an example. Page: 3/3
For cable disposal please note the relevant local legal disposal requirements.
2001230000_IEC_60502-1_ 2XYRY-fl_black_RE-RM-Multicore_en.pdf