You are on page 1of 1

Rolling Sphere Method Design Distance Between Area # of Perimeter # of

Radius = 30.5 100.1 Air Terms = 99 Sq.Ft. M2 Downs Feet Meters Downs
Rod Height Distance Separation Penetration check 33221 3089.6 1 123 37.392 1
Meters Inches Meters Feet Feet Inches H vs. P 2989.6 1 7.392 1
0.25 9.8 7.8 25.6 13.1 157.2 Bad 2889.6 1 0 0
0.5 19.7 11.0 36.1 13.1 157.2 Bad 2789.6 1 0 0
0.61 24.0 12.1 39.8 13.1 157.2 Bad 2689.6 1 0 0
0.67 26.4 12.7 41.7 13.1 157.2 Bad 2589.6 1 0 0
1 39.4 15.5 50.8 13.1 157.2 Bad 2489.6 1 0 0
1.5 59.1 18.9 62.0 13.1 157.2 Bad 2389.6 1 0 0
2 78.7 21.7 71.3 13.1 157.2 Bad 8 2
2.25 88.6 23.0 75.4 ** 13.1 157.2 Bad
Minimum Number of Down Conductors = 2
ROLLING SPHERE RADIUS 30.5 M Max Perimeter Dist. Between 99
Air Terminals
* Building Height is less than 30m the lessor of the above is required.
Instructions: Enter values in the highlighted cells ** Above 2 Meters requires extra support and structural review
1. The radius of the sphere in Meters.
2. The roof area in Sq.Ft.
3. The linear length around the perimter in Ft.
4. The distance between air terminals in Ft. (<Radius)

You might also like