EXTENSION OF SUPPLY TO RA COACH FROM POWER CAR

RSW1
TO HOG I/L PANEL 120303
BSW3
S2K12
HOGA S2K01
C2 ACB 1 F9
BK1 6A
BSW2
C1 CTRO5
BK1 CTR09

BSW3
BSW2
BSW1

24V +VE 24V -VE


R R
Y Y
B B
S2S14

S2K01 S2K15
210301 210318 210306 210308 210314 210316
24V +VE S2K12 24V -VE
S2K16 S2K21 S2S13

BSW1
S2K12 RSW1
1 F8 1 M1
6A

1D1 1D10
24V 1 F9
16A BSW1 DC1S1 RSW1

120113 120211 120211

R S2K20 RSW1

BSW2
ACB1

N 120112 120112 120212

HOGA S2K08
MATERIAL : SS 304L, IS:6911 EXTENSION OF SUPPLY TO RA COACH FROM POWER CAR
SPECIFICATION : RDSO/PE/SPEC/AC/0184-2015(REV-1)
SWITCH BOARD CABINET - S2
RDSO DRG NO : LW70020 SHEET 2 (SWITCH BOARD CABINET - POWER CAR)

00 FOR APPROVAL R.K. GSR SK


HRSW.1/6 LOCATED AT ENGINE TERMINAL BOARD (TERMINAL NO.4 & 61)
HOTEL LOAD CONVERTER - A

A18X1 P1X3 P1X3


S2K12 POS.0 : OFF 1D3
TB1 TB2 PB A RESET
( NON-VESTIBULE END )

SWITCHES - SBC2 SWITCHES - SBC2 R 1 2 POS.1 : DG A - ON


1 150 SQ.MM / 1.8KV A1 POS.2 : OFF 1D4 NC-1 P2A
P2A
IV COUPLER PLUG

Y 3 4 13 14 P2A P2A
2 150 SQ.MM / 1.8KV S2K01 TB16 TB17 TB7 1D4 1D3 1D11 TB9 211004.04

F9-6A
MSSW1 VOLTMETER SELECTION SWITCH-A S2S11 PLANT SELECTOR SWITCH B 5 6 1D10

MSSW2 VOLTMETER SELECTION SWITCH-B S2S12 BUS COUPLER ON


3
4
N
150 SQ.MM / 1.8KV FEEDER1
A2 ELECTRICAL SCHEMATIC DIAGRAM DCIS1
P2A-TB4
J
1D4
1D4 NC-2 P2A
1D11
1D11 1D11 1F10 P2A
+24V 1D1
FROM HOG

1D2 ENGINE P2A TB43


FOR POWER & CONTROL CIRCUITS - SBC S2

TR5-F3

TR5-F4
SE M-TB8 M-TB7 1D10 1F9 1D2 1D4 1D4 1D4 1D4 1D4 1D4 1D11 TB8 1D11 1D11 1D11 211004.06 1D11 1D11 1D11 1D11 1TM2
TB15

1D11

S2K01 COIL SUPPLY


S2S13 FEEDER-1 OFF

500V
S2S03 NWP FEEDER-1 OFF P2A
P1A

C1 STOP / TB6
PANEL

2A
7 TB1 PB P1A PB

FEEDER-1 CONT.
S2S14 FEEDER-1 ON C2 P1X3 J RESET P1A

HOGA
S2S04 NWP FEEDER-1 ON TR9-F2 TR9-F4 ACB1 A2 A1 1D4 43 LOP 1 OSR 5 OSR 33 LOP 1D11 1 ELR 6 ELR 13
10
(FOR LHB AC POWER CAR WITH HOG COMPLIANCE) TS-1 TB4 TS-2 AR

S2K16

S2K21
TB28 M-TB25 P2A NC-1 1D4 NO NO TB1 NO NO
NO NO 13 13 13 CFR 13 AFR

HRSW.1/9
7 NO
CONTROL

S2S05 NWP FEEDER-2 OFF S2S15 FEEDER-2 OFF CONTROL TB2 1D4 44 3 34 3 7 14

S2A5 (FEL1)
1D11

NO-1
NO-2
31 32

S2A4 (FOL1)
P1A-TB24 1D11 ACB-1 1D11 PB
P1A-T13

J 1D1 1D1

NO-1
NO-2
NO-3

NO-1
NO-2
POS.0 : OFF M-TB26 1D4 7 AEL 1D4 14 14 14 NO 14 NO

S2S17
TR-5

S2K16

S2K25
TR-9

2A 2A MAIN 11 AEL 25 UVR H OFF

PB RAISE
21 21 95 13 12 P2A ICHT 1CFR1 8

ICOS
S2S16 FEEDER-2 ON POS.1 : OFF 18 FSR

1TM1
S2S06 NWP FEEDER-2 ON

TO ACB CKT.
1.2KV 500V P1A-TB23 M-TB27 TB3 1F8 1F14 1D4 1D112 PANEL NO-1

TR5-F1

TR5-F2
POS.2 : HOGA-ON 17 FSRD NO-1 1OS1 1OS 12 26 1G1

1.2KV
S2S17 SAFETY LOOP-1 OFF 22 22 96 14 14 1CFR1 1CFR1
S2S07 60KVA TRANSFORMER-1 OFF 1HT P1A

S2K01
2A
P1A-TB22 1D3 1D3 1D5 P1A 1EL 1EL 1UVR

POS.1 : S2K01-ON (WITH S2S14-NO)


POS.2 : S2K05-ON (WITH S2S14-NO)
P1X3 CURRENT 21 1D5 PB-EN PB-EN 210417.01 1G1
21 CFR P2A-TB13 TB6 TB17 1EL1
TB14

TB27 ON A ON A 1D112
P1A

S2S08 60KVA TRANSFORMER-1 ON S2S18 SAFETY LOOP-1 ON TR9-F1 TR9-F3 F23-6A TRANSFORMER CORE BALANCE 1LOP P1A P1A
22 22 NC

S2K21
NO-1 NC-2

210417.02
TRANSFORMER A17X1 21 16 TB5 TB3
CURRENT P2A 1D6 UVR

S2V2
S2S09 60KVA TRANSFORMER-2 OFF S2S19 SAFETY LOOP-2 OFF HOG NET-1 CONT.
1 2 T7 T10 R P2A 1D6 1OS1 1OS 15 1EL 1UVR 1AR
CORE BALANCE AIR CIRCUIT BREAKER 1 TRANSFORMER TB48 1D4

IV COUPLER SOCKET
22

211004.05
HOGA COIL SUPPLY 150 SQ.MM / 1.8KV 1 1AFR1

1D2
S2S18
TB39 PB-EN

S2K01

S2K15

S2K16

S2K21
S2S20 SAFETY LOOP-2 ON TRANSFORMER P1A 1UVR

(VESTIBULE END)
S2S10 60KVA TRANSFORMER-2 ON S2A3 3 4 T8 Y 71 13 13 13 13 1E1 P2A

1TM1

1TM3

1TM2
L1A T3 L1 1 2 T4,T5,T6 150 SQ.MM / 1.8KV 2 HRSW.1/7 1D6 ON B 1HT 1HT 1CFR1 1CFR1 1OS1 TB2
5 6 T9 B TB36 P2A P2A
S2S21 24V BATT. CHARGER-1 SWITCH 72 14 14 14 14

S2S13
ALT-A L2A L2 3 4 150 SQ.MM / 1.8KV 3 21 NC-3 P2A P2A P2A TB12 TB11 P2A
1 2 N EM 1E1 DIODE 1 DIODE 2 1AFR1

F19
POS.0 : S2K01-OFF
P1X3 TB41 TB42A 1OS TB42 TB27

1A
S2S21a 24V BATT. CHARGER-2 SWITCH 750V L3A L3 5 6 120 SQ.MM / 1.8KV 4 P1X3 1M1 PB-EN 1D7 PB-EN OFF
SAFETY RELAYS TB19 22 1EL1 1AR 1AR

1SB3
ON A ON A ICLOP P2A 1AFR1 1G1

S2K15
SE TB20 51 1LOP
S2S22 TEST INDICATION LAMP SWITCH 3 NA 1 2 NC-1 NO-2 TB10 21 AR
1E1 DIODE 3

S2V1
1M2 1E2 P2A

PB LOWER
OVR OVER VOLTAGE RELAY 7 52

S2S14
22 NC

S2K12

S2K01
S2S23 POWER SUPPLY (24V) ON/OFF P1A-TB23 13 53 1D8 1D12 13 LOP TB37

: BCNA-ON
EARTH BLOCK
10

P1X3
OVR 16 FSRD 14 NO 1E2 1HT 1CFR1 1OS1 1AFR1

EARTH BLOCK
TB5
1G2

POS.1 : FNA-ON
AEL ALTERNATOR EARTH LEAKAGE RELAY P1A-TB24 P1A P1A P1B PB PB 1EL1 1EL 1UVR TM-1

M-TBPE
S2S24 HOOTER-1 OFF 14 54 A1 15 NC-1 1E3

TB25

S2S18
TB25 TB25 TB25
OVR11

OVR12

P1A

POS.1 : S2K05-ON (WITH S2S4-NO)


50 SQ.MM / 1.8KV
50 SQ.MM / 1.8KV
50 SQ.MM / 1.8KV
50 SQ.MM / 1.8KV
TS-1 TS-2

S2K15
18 FSRD

POS.2 : S2K05-ON (WITH S2S4-N0)


P1A-TB22 21

M-TBPE
M-TB8 M-TB7

DC SUPPLY ON
POS.0 : OFF

POS.2 : OFF
UVR UNDER VOLTAGE RELAY

NO-1
NO-2
1OS 1F13

POS.0 : S2K05-ON (DIRECT WITH


HRSW.1/5
S2S25 HOOTER-2 OFF 1D9 17 NO-2 NC-1 NC-1
F1A
F2A
F3A
(6A EACH)

P2A

ENGINE LOW OIL


S2K15
22
F1
F2
F3

CONTROL CONT.
ENGINE OVER
FOL FEEDER OVERLOAD RELAY 1E3

SPEED FAULT
16 17 23 TB25 P2A P2A

ENGINE HIGH
SC 81 82 A2 1CFR 1AFR

TEMP. FAULT
FEEDBACK SUPPLY)
1D12 OSR 1G3

VOLTAGE
P2A P2A TB39 TB40 AR

LEAKAGE
TR3-F1

CAR FEEDER1 CONT.


NON WORKING PWR.
1.2KV

HOOTER1
AOL

S2K05 COIL SUPPLY


FEL FEEDER EARTH LEAKAGE RELAY

HOOTER
RELAY A1

TR3-F2
41 FEL1 24

UNDER
TB59

PRESSURE
TB60 RELAY

P1X3
1D12

2A

S2K25
FOL1

EARTH
1TM3

TB6

FAULT
3 1

LAMP
S2A5 M-TB23 P2A LOP CFR AFR ELR
1SB2

AOL (ACB) ALTERNATOR OVER LOAD RELAY ACB1 S2A4


1D2

P1A-TB20 -24V TB33 SC FSS RELAY RELAY RELAY RELAY P2A


OVR-A A1 A1 A1

S2K14
M-TB22

S2K12

S2K16

S2K21
42 A2 A1 A2 5 7 CONTROL J FSRD A2 TB44
ON P1A-TB19 HRSW.1/11 P2A

1SB2
M-TB23

1SB2
DC 24V FNA P1X3 P1X3 M-TB21 TR-3 TB32 1SB2 1SB2
P1A-TB18

S2K01
TB33 ACB1 TB34 13 M-TB22 A2 A2 A2
DG

TR3-F4

S2K04 S2S3 F11-2A TR3-F3


X3 P2A J
A1 1SB1 1F11 1SB2 1SB2 1F12 1SB3

500V
4 2 1SB2 1SB2 1SB2 1SB2 1SB2 1SB2 1SB2 1SB2 1SB2 1SB2 1SB2 1SB2 1SB2

2A
14 M-TB21 TB31

( THROUGH
ACB1-NC )
5 6 23 24

S2K12

S2K05
TO C1 34 TO ACB1 NO-24 14

( DIRECT )
POS.1 : S2K04-ON

POS.2 : S2K04-ON
VOLTAGE P2A-TB45 P2A-TB23
21 J
SET-A

150 SQ.MM / 1.8KV


150 SQ.MM / 1.8KV
150 SQ.MM / 1.8KV
HRSW.1/1 AEL1 P2A 1SB2 1SB2 1SB2
MSSW1

POS.1 : ACB1-ON

(TB-A18X1) 31 TO S2K44 COIL-A2 TR-750/24VAC 13 FEEDER-1 (S2K01) SAFETY LOOP-1 (S2K14 FEEDER-1 FEEDER-1
+24V A2 TB46
S2K09 (FEEDER-2)

POS.0 : OFF 1 2 22 210811.03


P1X3

CONTROL CONT. & S2K15) CONTROL RLY. OVERLOAD EARTH LEAKAGE

7
1
3
5
M-TB11
TB4

28 TO HOG-A COIL-A1 -24V

POS.0 : OFF
POS.1 : OFF A1

F10-6A
S2K05
F7-6A

HRSW.1/3
POS.0 : OFF
POS.2 : OFF

HRSW.1/10 POS.1 : S2K44-ON


S2K10
POS.2 : HOG-A ON SIGNAL 21 TO S2K05 NO 1 2 3 22 S2K04 & CONT. RESPECTIVELY. CONT. CONT. 1M2
NWP FEEDER1 P2A-TB25 +24V
ACB1

21

TB9 BUS COUPLER CONT.


11
TR7-F1

TR7-F2
WP FEEDER1

S2K02
8
2
4
6
21
1.2KV

S2K02 COIL SUPPLY


19 TO S2S14 NO
HRSW.1/AUX

P1A-TB28 A1 21 31

F8A-6A
P1A 2M2
2A
HRSW.1/2 A2 S2K20

POS.0 : OFF
POS.2 : OFF
12 22 A2 P2B-TB25 M-TB11
P1X3

E3 E2 D3 C1 F3 P1A-TB27 TB8 22 32
TB3

POS.0 : OFF

TR1-F3

TR1-F4

CAR FEEDER1 CONT.


1 S2K44 M-TB25

S2K04 COIL SUPPLY


500V
P1A 12

F9A-6A HOGA
POS.1 : HK10-ON ( INTERUPT P1A-TB26 21

2A

WORKING POWER
HOG-A ON SIGNAL ) 53 52 43 3 63 TB7 CONTROL A1 P1X3

S2S22
1D14

S2K01

S2K03

S2K02

S2K05

S2K07
50 SQ.MM / 1.8KV
50 SQ.MM / 1.8KV
50 SQ.MM / 1.8KV
50 SQ.MM / 1.8KV

S2K47

S2K46

S2K16

S2K21

S2K19

S2K22
X1 P1X3 P1X3 11 P2A

ACB1

ACB2
POS.2 : HOG-A ON INDICATION 1S 2S 3S TR-7 22 TB22 1D14 M-TB26 13 23 23 43 43 43 43 43 53 53 43 43 43 43
X2 TB17 TB18 TB22

S2S21A
VOLTAGE
1/11

HH5 20 TO S2K12 NO
1/10

S40F1 S40V1

S40F2 S40V2
S2S21
L1 L2 L3 VR VY VB
1/9

1/8

1/7

TB31
P1X3

S2K44
14 24 24 44 44 44 44 44 54 54 44 44 44 44
TR7-F3

P1X3 TR7-F4
241

HRSW.1/8
3N KWM P5 CONTROL 14 14 43 AFR 43 CFR

S2K11

S45K1
TR-750/415VAC

S2S8
13
S2K20

HOGA

43
500V

1 22 TO S2K02 NC UVR1 33 21

S2K05
TR-1 13 P2A NO 44 NO
2A

Y/Y 1SB2 44 M-TB27

S2S4
CON-A O/P AVL V P1 13 13
27 TO F23 O/P 1L L1 2L L2 3L L3 L4 34 22 44 TB24 1SB2

TR1-F1

TR1-F2
CON-A ON 14

1.2KV
P2A ALT-A P2A +24V
F4
F5
F6

HH3 33 TO ACB1 NO-23 J

10A

10A
2A
V P2 14 ACB-1 ACB-2

1M2

2M2
TB14 ON TB15 22 P2A

S2S7
P1X3
TB6
2 HH1 4 TO ACB1 COIL-A1 CONTROL CONT. CONTROL CONT. TB23

STARTER MOTOR-1
21
HRSW.2/4

CON-A FAULTY A2 V P3 P1X3-TB21

S2S23
22 8 TO ACB1 NC
HK10

24V SUPPLY TO CONTROL CIRCUITS & DIAGNOSIS CIRCUIT


M-TB25
F8-6A

P1A-TB9 POS.0 : S2K02-ON

COACH LOAD
HK10 1 2 L1.N1

NETWORK 1
3 21 POS.1 : OFF 50 SQ.MM / 1.8KV 50 SQ.MM / 1.8KV
VY P1A-TB10 POS.2 : OFF
A1 6 TO FNA NO (P1A-TB25) 3 4 L2.N1 M-TB26 M-TB34 M-TB35
P4 FM VB 50 SQ.MM / 1.8KV 50 SQ.MM / 1.8KV

S2S14H1

S2S16H1

S2S12H1

S2S04H1

S2S06H1

S2S08H1

S2S10H1
CON-A P1A-TB11
P1X3

FEEDER-1

FEEDER-2
TB10

TO
S40K1

S2H10

S2H11

S2H12

S2H13

S2H14
1 TO DCIS1 5 6 L3.N1 A1 A1

S2H1

S2H2
S40F3 S45

S2S12

S2K02
RESET

HOGA

HOGB
P1A-TB12 A1 50 SQ.MM / 1.8KV 50 SQ.MM / 1.8KV 13 13 13 13 24V
HRSW.3

HRSW.1

1 3 5 A3 A2 B3 B2 A1 C2 D2 7 8 N.N1 M-TB27 S2K08 S2K09 M1


4 BCNA 50 SQ.MM / 1.8KV 50 SQ.MM / 1.8KV 14 14 14 14 BATTERY CHARGER-1 13 14
S2K11

+24V 13 22 100A
ACB2

HH7 A2 A2 AC 240V / DC 24V 14 7 12 9 20 11 10 2 5 19 13 8 1 6


2 4 6 13 12,23 22 1 32 42 A2
R Y B 14 21 1 2
10 2 TO FUSE-1F9 S1F44 L1A1
1/1

1/2

1/3

1/4

1/5

1/6

25 SQ.MM / 1.8KV 25 SQ.MM / 1.8KV ACB1 ACB2 FEEDER1 FEEDER2 BUS FEEDER1 FEEDER2 60KVA TR-1 60KVA TR-2 24V O.K. OVER EARTH OVER EARTH
TO UIC COUPLER 1 & 2

60 KVA TR.2 60 KVA TR.1


I/P CONTACTOR M-TB25 3 4 S1F45 L2A1 1D14 2D14

ECR(PCC1)

ECR(PCC2)
S2S01

5 TO FNA COIL-A2 P1A 25 SQ.MM / 1.8KV 25 SQ.MM / 1.8KV ON ON ON ON COUPLER NON WORKING WORKING WORKING LOAD FAULT LOAD FAULT
ON M-TB26 TB25 5 6 S1F46 L3A1 PH N 1D1 2D1 ON POWER CAR ON FEEDER1 FEEDER1 FEEDER2 FEEDER2
A

TO
7 TO CONTROL TR-8 P6 25 SQ.MM / 1.8KV 25 SQ.MM / 1.8KV P2A-TB22 P2B-TB22 ON 24V+
M-TB27 A1 7 8 NA1 FROM DEFECT

S2S11
3 TO S2K20 NO 25 SQ.MM / 1.8KV 1 2 3 P2A-TB1,2,3 P2B-TB1,2,3
TO 24V+ A A
1
3
5

5 17 S2K02
EA1 S1F10 (TO DIAGNOSIS) (TO DCIS1) (TO DCIS2)
HF1 24V+ A1 A4 B1 B4 C1 C4
18 BUS COUPLER 230V AC
TO 24V- PE EB1 A2 A3 B2 B3 C2 C3
2
4
6

A A A2 25 SQ.MM / 1.8KV PLANT S40K2


11 13 TO S2K20 NO M-TB23 S40F4
HF2 110V+ 7 8 NB1 SELECTOR 24V

TO
S2S02

9 TO CONTROL TR-7 M-TB22 P12 A 25 SQ.MM / 1.8KV 25 SQ.MM / 1.8KV SWITCH TO STARTER BATTERY CHARGER 1&2
120 SQ.MM / 1.8KV 5 6 S1F49 L3B1 BATTERY CHARGER-2 100A 13 14
12 15 TO FNB COIL-A2 25 SQ.MM / 1.8KV 25 SQ.MM / 1.8KV

S2K10

S2K11
110V- M-TB21 3 4 S1F48 L2B1
2/1

AC 240V / DC 24V
2/2

2/3

2/4

2/5

2/6

HF3 21 21
12 TO FUSE-2F9 25 SQ.MM / 1.8KV 25 SQ.MM / 1.8KV

S46K1

S2K15

S2K18
13 R Y B 1 2 S1F47 L1B1 33 33 FROM STARTER FROM STARTER
S2K10

ACB1

14 21 22 22
HRSW.4

HRSW.2

HH6 2 4 6 13 12,23 22 1 32 42 A2 BATTERY CHARGER 1 BATTERY CHARGER 2 SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE

FEEDER-1

FEEDER-2
M-TB23 34 34
A1 A1

COACH LOAD
-24V 13 22

NETWORK 2
6 BCNB M-TB30 M-TB31 M-TB32 M-TB33
50 SQ.MM / 1.8KV 50 SQ.MM / 1.8KV PH N

ST. BATTERY-1

ST. BATTERY-2
1 3 5 A3 A2 B3 B2 A1 C2 D2 7 8 N.N1 S2K11 S2K10 ON 24V+
P1X3

CON-B O/P AVL P1B-TB12 50 SQ.MM / 1.8KV 50 SQ.MM / 1.8KV M-TB22 DEFECT
TB8

24V 290AH

24V 290AH
A1 FROM

TO

STARTER MOTOR-2
HH4 11 TO DCIS2 5 6 L3.N1 A2 A2 A1 A1 A1

S40K1

S40K2

S2K20
P10 FM VB P1B-TB11
HRSW.1/4

A1 50 SQ.MM / 1.8KV 50 SQ.MM / 1.8KV S1F10A (TO DIAGNOSIS)


F17-6A

7 16 TO FNB NO (P1B-TB25) POS.0 : S2K02-ON 3 4 L2.N1


21 VY P1B-TB10 50 SQ.MM / 1.8KV 50 SQ.MM / 1.8KV M-TB21
HK12

HK12 POS.1 : OFF 1 2 L1.N1 230V AC A2 A2 A2


CON-B FAULTY P1B-TB9 POS.2 : OFF
22 10 TO ACB2 NC V P9 P1X3-TB26

P1X3
A2

TB16

S2S9
TR8-F4 P1X3

21 -24V
BUS COUPLER CONT. TB7

BUS COUPLER (S2K02) S46

CAR FEEDER2 CONT.


TR2-F1
8

POS.1 : S2K46-ON HRSW.2/10

50 SQ.MM / 1.8KV
50 SQ.MM / 1.8KV
50 SQ.MM / 1.8KV
50 SQ.MM / 1.8KV
TR2-F2
1.2KV
HH2 -24V

S2K06 COIL SUPPLY


14 TO ACB2 COIL-A1 M1

2A
P2B ALT-A P2B CONTROL CONTACTORS

S2S18H1

S2S20H1
M-TB23

WORKING POWER
V P8 22

HRSW.2/8
CON-B 14 P2B 2D14
F15
F16
F17

S2H17

S2H18

S2H19

S2H20
35 TO ACB2 NO-23 TB14 ON TB15 2D14
HOGB F18B-6A

S2K07
S2S6
CON-B ON 14 TB22
S2K20

RESET
TR8-F3

S2K10
HOGB

S2S10
1L L1 2L L2 3L L3 L4 44 22
500V

44
S2K02 COIL SUPPLY

29 TO F24 O/P

S2K46
V P7 13 13 43 AFR 43 CFR
2A

M-TB22

P1X3
CONTROL

TB32
VOLTAGE 13
9 25 TO S2K02 NC UVR2 43 21 43 P2B NO 44 NO
2/11

2SB2 44
2/10

TR-750/415VAC 244 2N KWM P11 TR-2 14 14 13 3 4 16 15 17 18


2/9

2/8

2/7

23 TO S2K13 NO L1 L2 L3 VR VY VB Y/Y TB24 2SB2


HRSW.2/AUX

TB17 TB18

TR2-F3

TR2-F4

TR4-F3 F22-2A S2S5 S2K06


HRSW.2/1 CONTROL 22 P1X3 ICHT ENGINE HIGH TEMPERATURE SWITCH M-TB21
J

500V
1S 2S 3S 11
S2K08 (FEEDER-1)

X1 53 52 43 3 63 P1X3 P1X3 TR-8 A1 1SB1 2SB1 SAFETY SAFETY ST.BATT. ST.BATT. ST.BATT. ST.BATT.
P1B TB25

2A
POS.0 : OFF 21 ICOS ENGINE OVER SPEED SWITCH P2B
P1X3

POS.0 : OFF
POS.2 : OFF
DC CONTROL SUPPLY
TB13

150 SQ.MM / 1.8KV


150 SQ.MM / 1.8KV
150 SQ.MM / 1.8KV

LOOP1 LOOP2 CHARGER1 CHARGER1 CHARGER2 CHARGER2


POS.1 : ACB2-ON

POS.1 : OFF P1B-TB26 TB7 12 TB23


F17B-6A

2 S2K46
TR8-F1

TR8-F2

24V ON CONT.

S2K02
DEFECT DEFECT
1.2KV

+24V
HRSW.2/3

POS.2 : HOG-B ON SIGNAL E3 E2 D3 C1 F3 P1B 22 42 ICLOP UNDER VOLTAGE RELAY P2A-TB31,32,33 P2B-TB31,32,33
( THROUGH

P1B-TB27
ACB1-NC )

11 A2
2A
ACB2

22
( DIRECT )
POS.1 : S2K06-ON

POS.2 : S2K06-ON
F18-6A

TB8 A2
POS.0 : OFF
POS.2 : OFF

S2K11

F21-6A
24 TO S2S16 NO P1B-TB28 21 A1 21 41 FSR AUX. CONTACT OF FSRD
S2K06

2
4
8

6
12 HRSW.2/2 21
26 TO S2K07 NO WP FEEDER2 S2K07 HRSW.2/6

POS.1 : S2K07-ON (WITH S2S6-NO)


1 2 3
MSSW2

TB14
P1X3

LOCATED AT ENGINE TERMINAL BOARD (TERMINAL NO.4 & 61)

POS.2 : S2K07-ON (WITH S2S6-N0)


POS.0 : OFF 22
POS.0 : OFF

NWP FEEDER2 POS.0 : OFF P1X3

POS.0 : S2K07-ON (DIRECT WITH


30 TO HOG-B COIL-A1 A1 P1X3
POS.1 : HK12-ON ( INTERUPT M-TB11 2D3

1
POS.1 : DG B - ON

3
5
22 TB11 TB12

S2K07
1 2 A2 PB A RESET
S2K13

HOG-B ON SIGNAL ) 32 TO S2K46 COIL-A2 VOLTAGE 13 +24V POS.2 : OFF

FEEDBACK SUPPLY)
TO C1 AEL2 2D4 NC-1 P2B
POS.2 : HOG-B ON INDICATION

CAR FEEDER2 CONT.


21 P2B

NON WORKING PWR.


P2B P2B

TR4-F4
(TB-A19X1) TR-750/24VAC

S2K07 COIL SUPPLY


500V
36 TO ACB2 NO-24 14 2D4 2D3 2D11 TB9 211104.04
5 6 TB7

S2K03
23 24 TB16 TB17

2A
14 2D10
A1 +24V 2D4 2D11
ACB2 13 M-TB10 M-TB9 DCIS2
P1B-TB18 FNB P1X3 P1X3 J 2D11 2D11 2F10 P2B
DC 24V M-TB21 CONTROL P2B-TB4 2D4 NC-2 P2B
TB35 TB36 2D1 TB43
POWER CONTACTORS - SBC2 CONTROL CONTACTORS - SBC2 OVR-A P1B-TB19 HRSW.2/11 TR-4 P2B 2D10 2F9 2D2 2D2 ENGINE P2B 2D4 2D4 2D4 2D4 2D4 2D4 2D11 TB8 2D11 2D11 2D11 2D11 211104.06 2D11 2D11 2D11 2D11 2TM2

50 SQ.MM / 1.8KV
50 SQ.MM / 1.8KV
50 SQ.MM / 1.8KV
50 SQ.MM / 1.8KV
42 A2 A1 A2 5 7 M-TB25 STOP / TB6
2D2
2SB2

M-TB22

TR4-F2
ON P1B-TB20

S2A10 (FEL2)
TB1 PB P1B PB

TR4-F1
TB16
P1X3

-24V

S2A9 (FOL2)
RESET P1B

1.2KV
ACB2 FOL2 J 2D11
1 OSR 5 OSR 1 ELR 6 ELR
(6A EACH)

: BCNB-ON

S2K01 FEEDER-A MAIN CONTACTOR FEL2 M-TB23 M-TB26 TS-1 2D4 TB443 LOP 33 LOP TS-2 13 AR

2A

S2K19

S2K22
S2S19
S2K19

S2K26
S2K08 ACB-A CONTROL P2B NC-1 TB1
HRSW.2/5
POS.1 : FNB-ON

S2A10 NO NO
EARTH BLOCK

P2B P2B 41 S2A6 21 21 95 13 12 1D4 NO NO NO NO 13 13 13 CFR 13 AFR


AOL 2D4 44 3 7 34 3 7 14 NO
EARTH BLOCK

TB2 ACB-2 2D11

NO-1
NO-2
S2K02 BUS COUPLER MAIN CONTACTOR M-TB27 1D11 2D11 PB
J 2D1 2D1

NO-1
NO-2
NO-3

NO-1
NO-2
M-TBPE

S2K09 ACB-B CONTROL TB59 TB60 2D4 7 AEL 2D4 14 14 14 NO 14 NO


POS.0 : OFF

POS.2 : OFF

20 ICOS
SC 81 82 22 22 96 14 14 2CFR1 MAIN H OFF
OVR11

F12
F13
F14

11 AEL 25 UVR

PB RAISE
19 ICHT
F12A
F13A
F14A
OVR12

16 17 P2B

S2K03
18 FSR

2TM1
8

POS.1 : S2K03-ON (WITH S2S16-NO)


POS.2 : S2K03-ON (WITH S2S16-NO)
21 PANEL
M-TBPE

S2K03 FEEDER-B MAIN CONTACTOR

TO ACB CKT.
2F8 2F14 2D4 1D112 NO-1
TB25

S2K10 BUS COUPLER (K02) CONTROL TB3


P1B

17 FSRD NO-1 2OS1 2OS 12 26 2G1


P1B-TB22 M-TB10 M-TB9 2CFR1 2CFR1
22 2HT P1B

S2K22
S2K04 SBC WORKING NET-1 P1B
TB15

2D3 2D3 2D5


P1X3

S2K11 BUS COUPLER (K02) CONTROL P1B 21 2D5 PB-EN PB-EN 2EL 2EL 2UVR 210517.01
21 CFR TB6

S2V6
TB17

IV COUPLER SOCKET
P1B-TB24 TB25 ON B ON B P2B-TB13 2LOP 2D112 2EL1 P1B P1B
S2K05 SBC NON-WORKING NET-1 OVR 10

(VESTIBULE END)
22 22 NC

210517.02
S2K12 FEEDER-A (K01) CONTROL P1B-TB23 NO-1 NC-2 16 TB5 TB3

S2S20
S2K03

S2K18

S2K19

S2K22
7 71 13 13 13 13 P2B 2D6 2OS UVR 2AR
S2K06 SBC WORKING NET-2 S2K13 FEEDER-B (K03) CONTROL HRSW.2/7 TB48 P2B 2D6 2D4 2OS1 15 2EL 2UVR

211104.05
ALT-B NB 1 2 SE

2D2
72 14 14 14 14 TB39 PB-EN

S2S15
21 P2B 2AFR1 P1B 2UVR
S2K07 SBC NON-WORKING NET-2 2E1

2TM1

2TM3

2TM2
S2K14 SAFETY LOOP-A CONTROL 750V L3B L3 5 6 2D6 ON A 2HT 2HT 2CFR1 2CFR1 2OS1 2G1

F20
120 SQ.MM / 1.8KV 4

POS.0 : S2K03-OFF
P1X3 TB2

1A
1 2 N P1X3 TB36 P2B P2B
FNA FEEDER-A NEUTRAL CONTACTOR 3 L2B L2 3 4 150 SQ.MM / 1.8KV 3 TB23 22 NC-3 P2B P2B P2B TB12 TB11 P2B

S2K18
S2K15 SAFETY LOOP-A CONTROL 5 6 T19 B TB24 51 EM 2E1 DIODE 1 DIODE 2 2AFR1
T14,T15,T16 TB41 TB42A 2OS TB42 TB27
L1B T13 L1 1 2 150 SQ.MM / 1.8KV 2 2M1 PB-EN 2D7 PB-EN OFF

S2V5
FNB FEEDER-B NEUTRAL CONTACTOR 2EL1 2AR 2AR

2SB3
S2K16 FEEDER-A OVERLOAD AIR CIRCUIT BREAKER 2 3 4 T18 Y 52 ON B ON B 211 ICLOP P2B 2AFR1 2G1

S2S16
CORE BALANCE 2LOP

S2K13

S2K03
HOG NET-2 CONT. 150 SQ.MM / 1.8KV 1 13 53 TB10
BCNA BUS COUPLER NEUTRAL CONTACTOR-A TRANSFORMER S2A6 CURRENT 1 2 T17 T20 R NC-1 NO-2 2E1 DIODE 3 21 AR
S2K17 SAFETY LOOP-B CONTROL 2M2 2E2 P2B

PB LOWER
HOGB COIL SUPPLY TRANSFORMER 14 54
TB14

CORE BALANCE A1 2D8 2D12 13 LOP 22 NC


P1B

A16X1 TB37

S2S20

S2K18
BCNB BUS COUPLER NEUTRAL CONTACTOR-B S2K18 SAFETY LOOP-B CONTROL CURRENT TRANSFORMER 21 16 FSRD NO 2HT 2CFR1 2OS1 2AFR1
TR6-F1

TR10-F1 TR10-F3 F24-6A P1X3 14 2G2


TR6-F2

2EL1 2EL 2UVR


1.2KV

2E2
S2K03 COIL SUPPLY

TRANSFORMER PB PB TM-2
TB29 15 NC-1 2E3
2A

S2K18
S2K44 60KVA TRANSFORMER-1 P1B-TB22 22 18 TS-1 TS-2
CONTROL

S2K19 FEEDER-B OVERLOAD FSRD


HRSW.2/9

23 A2
P1B-T13

DC SUPPLY ON
FEEDER-2 CONT.

NO-1
NO-2
2OS 2F13
TR-10

POS.0 : OFF 2D9 17 NO-2 NC-1 NC-1


P2B

ENGINE LOW OIL


S2K46 60KVA TRANSFORMER-2 S2K20 DC CONTROL SUPPLY 24V ON 2A 2A P1B-TB23 24

CONTROL CONT.
POS.1 : OFF

ENGINE OVER
2E3

SPEED FAULT
P2B P2B
HOTEL LOAD CONVERTER - B

TB25

ENGINE HIGH
2CFR 2AFR

TEMP. FAULT
1.2KV 500V POS.2 : HOGB-ON CONTROL CONDITIONAL RELAYS & SWITCHES 3 1 2D12 OSR 2G3

VOLTAGE
TB39 TB40 AR

LEAKAGE
HOG A HOG A CONTACTOR
( NON-VESTIBULE END )

P1B-TB24
HOGB
FROM HOG

HOOTER2
S2K21 FEEDER-A EARTH LEAKAGE 31 32 TR-6

HOOTER
RELAY A1

UNDER
RELAY

PRESSURE
2D12

S2K26
A1 A1 A1

EARTH
S2K17
TB30 2TM3
IV COUPLER PLUG

PANEL

FAULT
S2K13

S2K19

S2K22

LAMP
HOG B HOG B CONTACTOR 10 P2B LOP CFR AFR ELR
TR10-F4 ACB2 A2 A1
TR6-F3

TR6-F4

S2K22 FEEDER-B EARTH LEAKAGE TR10-F2 P1X3 DCIS DC CONTROL ISOLATION SWITCH OSR ENGINE OVER SPEED RELAT
500V

C2
TB15

M-TB23
P1B

TB33 RELAY RELAY RELAY RELAY P2B


2A

7 SC FSS
S2K25 FEEDER-A HOOTER CONTROL C1 FSRD TIME DELAY RELAY FOR STARTER ELR EARTH LEAKAGE INDICATION RELAY M-TB22 A2 A2 A2 J FSRD A2 TB44
SE P2B

2SB2
2SB2
4 2 TB32 2SB2 2SB2
S2K26 FEEDER-B HOOTER CONTROL
F18-6A

4 A2 SOLENOID LOP ENGINE LOW OIL PRESSURE RELAY M-TB21


N
S40K1 ST. BATT.-1 CONTACTOR 3
2
B 5 6
150 SQ.MM / 1.8KV
150 SQ.MM / 1.8KV
S2K03
FEEDER2
CFR COMMON FAILURE RELAY AR FAULT INDICATION RELAY FEEDER-2 (S2K03) SAFETY LOOP-2 (S2K17 FEEDER-2 FEEDER-2
P2B
TB31
J
2SB1 2F11 2SB2 2SB2 2SB2 2SB2 2SB2 2SB2 2SB2 2SB2 2SB2 2SB2 2SB2 2SB2 2SB2 2SB2 2SB2 2F12 2SB3 DG
3 4 CONTROL CONT. & S2K18) CONTROL RLY. OVERLOAD EARTH LEAKAGE P2B-TB45 2SB2 P2B-TB23
S40K2 ST. BATT.-2 CONTACTOR
1
Y
R 1 2
150 SQ.MM / 1.8KV
13 14 A1

S2K13
AFR ALTERNATOR FAILURE RELAY -24V
& CONT. RESPECTIVELY. CONT. CONT.
P2B
TB46
J 2SB2 2SB2
210911.03 SET-B
A19X1
+S2-X3
21 DC110V/ 32040701
1SB2 -VE
O
3
210303.04

4 ACB K4 +S1F50/51/52-63A
2 TR-K1 +S2K12
21-K9
SET A O O

750V

750V
K1-B
210308.04
NET 1

DISCONNECTING AND EARTHIING DEVICE


K1-415
PS 6.3A O

330201
K1-Y O

330202
210314.03
19

120307.01
120112.04
AFR CFR Sw1/3 O
O
S1F72
1
F-K1

750V
K1-0
F1-AuxS
21-K9
+S2K12
F1
+S2K1 20
210308.03
K01 12021003
S1K43 S1K44

O
O
210302.01 1D14 A2 120308.01 S.LOOP

210308.01

210318.01
.02

210301.08
.02

O
210314.01
FEEDER A

O
210306.01
12020902

O
O
O

O
SL Aux
NWP SET A K5
O
FEL-Aux
S2K8 21-K12 FOL-Aux POWER SUPPLY
V
(+S2-X3-11)
PsA =21-K5 ON OFF 21-K20 21-K13

O
O

O
+S2K15

K1-0
210303.09
_ 210316.01
S2K21 S2K16
+ +S1-F44/45/46-100AMP ON/OFF SW
(+S2-X3-11) 210301.05
CONV-A
CONV A MMR
K44

O
O

O
O

O
.02 K1 .02
A1 120212.01 (S2-X3-21)
60KVA

320603
O X1/18 +S1F90/91/93-1A O O
SUPPLY 415V 32060201 32060401
S2K20 Sw-1/3
&+S2-K4 FOL 300Ams FEL1 +S1F94/95/96-1A SUPPLY

O
120113.06
=21-K19
120211.01 415vac O X1/17 +S2A4 +S2A5 +S2-K5 TRF
O O
A/C

OV

O
120212.01
D/E/D=12-A1

O
O
210301.14=11
210301.12=11
D/E/D=12-A1

120301.05
MMR CONTACTOR

120302.05

120303.05
210413.01=14

120309.02
41

120310.02

120311.02
POWER SUPPLY ON/OFF 42
K1 210411.01=14

O
ACB A2 -A1 A2- K L A1

O
O

O
ACB K6

120320.01
120319.01
210303.01
210301.01
120316/7.01
320609

120312/3.01
120321.01

120314/5.01
UVR

O
O

O
E

O
O

O
+S2K1
CBCT1
1R 120101.01
O
S2X3-25
R
SET B O O
NET 2 320610 NET 1 LOCAL NET-2
32060501
120301.01 - +(+S2-X3-21/11) 210301.02 O O

O
K02

O
O O
O O
1Y 120102.01
120309.01 S1K02 S1KO1 S1-K44
120302.01 Y

O
ALT

O
O
O
120310.01
O
NWP SET B K7 +S1F53/54/55-63A
320601 320606 320607 S1K43
1B 120103.01 120303.01 B S1K01 S1KO2
A

O
O O O

1N 120104.01 1N
ACB 12010406
120311.01

CBCTF1 N
210101 210201 320608

O
O O O O

O
.02 .02 O
.02 .02 12010404 05 X1/19 X1/20

O
1AELCBCT1 1AELCBCT2 120104.06A 210414.02 MMR- S1K04 MMR-K45
K L
FNA Sw-1/5 MMR - S1K03
F2 F3

O
F1 210414.01

O
C1/C2 210415.02 210303.26
BATTERY
V TRAN750/415V 750/24 1D4/1CFR1 NO SC O X1/14
32041001

O
+S2-X3-7/8 LOCO CHARGER 230VAC 32041002 32041003

120304.05A
MAGNETIC

120301.02

120303.02
ACB-A

120302.02
200VA 1D11/1EL1 NO O
END
210602.01
SHUNT 120307.04 210415.04 210415.01 STARTER

1S2F8A
V
L N O E STOP RESET MOTOR 1D4 A RESET F10
AEL1 K2A-B
TR-K2A
O S2K12
K1 SUPPLY TO INDICATION LAMP X1/7 X1/8 1D11

O
O =21-K9 O 1D4 Sw-1/6 1D4

1D10
120116.01

ISO SW
750V K2A-Y O
CHANGE 120105.01
F4 F5 F6 F7 F-K2A 21030139
F9
120106.01 O
OVER 210301.10
V 120307.03 +S2-X3-25 FSRD ICHT LOP AEL OSR OSR ICOS LOP ACB ACB ELR ELR1 AEL UVR Ts2 CFR AFR

O
O
SWITCH ALT ON 120304.02 210401.01
H OFF AR HIGH

.210605.04
120107.01
O K2A-415 O S2K10 =21-V2 210301.16/7 1D1
120111 O O S2V2 1D2

O O
3 PHASE FROM FEEDER A F-K2A S2K11
1D5

O O
120114 120113 =21-K7
120117.01 F-K2A =21-K8 O K1 S LOOP =21-K19 S40-X1-4
O Ts1
O 120112 FEEDER A O SW OFF 210416.01
S40 1D1

OO
120112.03 O S2K20 S40
FQ 120304.01 120304.03
120307.02
S2F19 F8 S40-K1
N F2 F1
FOR B.
CFR

1S2F9A
120305.01
120111.03
210303.08
210406.01
21-F7 CHARGING 1D112
O O 10AMP 210601.01 10AMP EO N

BCNA
S2K11 .02 1A 1M1
1D6
T
210604.01

O O
=21-K8 210402.01 E ASET ON
U O .03 A UVR Tm3

O O
210313.01

O O
O O
.04 O O O
1D11/1UVR NC 21-S12 S LOOP =21-K19

O
L1
TRDRL2 .04
V S2K10=21-K7
S LOOP
SW ON
RELAY
S2K20 1M2
S2A2-11 EM O 1G1

O
NC S2K12 S40V2 S40V1 E ON B 1 E1
+ L3
.04
.04 1AFR1/1D112 R
O
O O 120303.04
O
210407.01 .02
O
S2-X3
210603.05 210701.01
OFF 1LOP1
O
L AFR2
1EL1 1AR Tm1 TM

O
S40-X1-2

O
S2-X3-13

O
N O
KW S2K15 S2V1 210301.13 210603.03
11
3 O 1D7 O O O O O

O
=21-K12
- 1
120203.01 O 21-V1 .02 210602.01
LOP AR Tm2
S LOOP 210603.01 S40-X1-1
UVR1

O
O
S2-X3-11
1HT Ts2

O
.12 .14

O
RELAY ,41 BATTERY
O

O
6 S40-X1-2

O
O O
120204.01 O O O 1G2

O O
4 A4 A5 CHARGING
210403.01 210408.01 S2K25
1G1 210603.04
1E2

O
9 FOL 21-K24 FEL ON/OFF SW
K2A-0

O
120205.01 1CFR1

O
7
120306.02 21-S12
O
041202
210417.01 POWER
SUPPLY
.03 210605.03/1D1 1D8 1D12 1OS1
.01 .02 O
LOP F13
O

120206.01 S2S18 ON/OFF SW


Ts1

O
O S2-X3-12
+ VE DC

O
FSRD
120306.01

120210.01 S LOOP
AM CHANGE CT WIRE FROM FEEDER A CONVERTER S2K15 .02
IC HT OSR UVR FAULT

O O
ASW 120207.01 SW .01

O O
O
OVER =21-K12 FOL FOL FEL ON FSRD
S40-X1-9
OS

O
S LOOP .01 FEL S2K16 S2K21
AFR1 ELR

FSS
120208.01 SWITCH
RELAY STARTER

O
21-K13
1G3

O
120209.01 21-K20
210410.01 210702.01 O 1CFR 2 LOW
.06
210704.01
MOTOR 1D9 1E3

O
210311 210413.02 211004.05 .04
210411.02

MG SW
S40-K1
210414.04
FOL FEL
1D11 LOP CFR H

210303.13
O 2

POWER
O1

O
1 S2K16 S2K25 SUPPLYRELAY
S2K21 21-K24
21-K13 21-K20 21-K19
S2K20 FSRD TIMER AFR ELR AR
O3

K2 /BC 2
210811.03
1SB2
210303.55 -VE 1SB1
210301.11 K2/BC
210305.01
S2K14=21-K11
210303.11
210303.17 210303.57 210303.18/56/16/15/50 S2-X3-21 .62 S40-X1-7 .62 O 21030324/3/1
1SB2 1SB3

O
24V DC
O

O
O

O
O

O
.61
4O

+S40-X1-5
120605.01
P.S S40-X1-8 S40-X1-6
F11 F12
.07
.02 210303.25
O

210515.04
120318.01

210310
210515.01
K3
O
210602.01 X2/7 X2/8 2D4 B RESET 2D11 F10
PUSH SW

O
O 210301.15
ISO SW Sw-2/6

210301.16 2D10 F9 2D2 Ts2 CFR AFR


FSRD ICHT LOP AEL OSR OSR ICOS ACB ACB ELR ELR1 AEL UVR AR HIGH

O
210501.01 O O
H OFF
.02

N 2D1
=21-V6
O
O S2V6 E STOP 2D5
120608.01 K3 O
2D1 O Ts1 LOP
120104.24B

210516.01
120610.01 O S LOOP S40-K2 RESET
120607.01 CHANGE CT WIRE FROM FEEDER B CONVERTER SW OFF O F8 FOR B.
O
ACB2

ACB1

OVER =21-F8 CHARGING


AM AS SWITCH S2F20 210602.01 O S40-X1
CFR 2D112
120606.01 210506.01
.02 1A .03 EON
120609.01 210502.01
.03 2G1 2M1
2D6 UVR Tm3
12030405B O O O E B SET ON A 15 25 O O

LINE CON.
O O

12010425 21-S14 S LOOP 210517.01


1
TRDR 120605.01 S2K11=21-K8 X2/21 O EM O 2LOP1 2G1
T T
3 x1-21 RELAY
O S LOOP
O .02
O E ON A 2E1
O

+ 4 Sw-2/4 120703.04 SW ON S2K18 O 2M2 O


120604.01 210507.01
2AR Tm1 TM
1S2F18B

O S2A2-21
6 O O
X1/21
S2K18
O .02 FOL O O FEL 210703.01 OFF O 2EL1
O

X2/22
2D7
KW
7 S2K19 O O O O
120603.01 K2A-0 Sw-1/4 O 21-K15 S2V5 210301.16 S2K22
28 AR O
21031201 O 21-K16 O S2-X3-15 O 18
BCNB

9
120512.04 L3
O X1/22 S LOOP 21-V5
O O
21-K21
.02 LOP 2HT Ts2 UVR1 Tm2
_ L1
120513.04 L2
2D11/2UVR
NC U 120306.02 K2B-0 O
RELAY
O
.16 O ,42
OS2K26 O A10
.16
.06 .04 O BATTERY O O O
O
2G2
120705.03

210503.01 210508.01 A9 CHARGING

N L3
L2
120514.04 L1 2AFR1/2D112
NC
V O
120707.02
O
FOL
O O
21-K25
O
FEL
211104.06
O
2D11 O ON/OFF SW
210605.01/1D1 2D12
2E2 2CFR1 2OS1
RAD.
R
S2K10
=21-K7
21-S14
.01 051202 S2K26
.03 2D8 O F13
F-K2B S2S14
120511.03 210303.58 O O S2K11
S LOOP
O
S2K18
21-K25 O S2-X3-14 + VE DC FSRD Ts1
O =21-K8 SW 210911.03 .02 IC HT OSR LOP UVR FAULT
FQ F-K2B S2K10 O =21-K15 O O .01
ON FSRD
120707.03

=21-K7 FOL 2SB2


K2B-B
O S LOOP .01 FEL OS AFR1 ELR

FSS
120512.03 RELAY STARTER
120513 120511 K2B-Y 120705.02 O O O S40-X1-10 O 2G3 LOW
3 PHASE FROM FEEDER B 120512
120517.01 210510.01
210704.01
MOTOR 2D9 2E3 2CFR 2
120514 O O
O S2K13
1S2F17B

K2B-0
V
120104.24A

MG SW
F-K2B 210511.02 210513.02 S40-K2
CHANGE
O =21-K10
210514.04 LOP CFR H
OVER
TR-K2B FOL FEL

.210303.14
S2K17=21-K14
3
SWITCH
F15 F16 F17 F18 ALT ON
750V S2K19 S2K22
120707.04
120701.02

1 O
120702.02

21-K16
120703.02

V AEL2 FEEDER B 21-K21


FSRD TIMER AFR ELR AR
4 2 2SB1
12-0516.01 O S40-X1-8
120704.01

210303.18
210303.56 21030329/6/8 2SB2 2SB3
120505.01 06.01 07.01
TRAN750/415V 750/ 2D4/2CFR1 NO SC 210303.16 210303.15/50
O
S2-X3-21
V MAGNETIC 210514.01
O S40-X-5
200VA 24 2D11/2EL1 NO
210515.01 S2-X3-9/10 F11 210514.02 F12
F12 F13 F14 K L SHUNT O C1/C2
X2/14
LOCO

O
X2/19
2ACBT1/2 X2/20
O

O
O

FNB 120104.26A 210515.02 ACB-B FEEDER A NWP A FEEDER B NWP B


Sw-2/5
.03 .03 .03
.23
120104.24 .25
END 750V 750V 750V 750V
120104.26
O O O O
O

120104.21 F-K6 F-K7

ALT
F-K4 F-K5

120503.01 120703.01 CBCTF2 N


120709.01
O O O O
K4-0 K5-0 K6-0 K7-0
B
120502.01

B
120702.01
120710.01
O O O

ACB Y

K5-415

K7-415
K4-415 K6-415
120501.01 120701.01 120711.01
O O _ O F K4 F K5 F K6 Fk7
120702.05

120703.05

+ (+S2-X3-
120714/501
120701.05

120716/7.01
120712/3.01

11/21) R
210303.02
21030103

(+S2-X3-25) 120302.06 120310.03 120702.06 120710.03


120719.01

120720.01

AELCBCT2 O 210301.04
120407.01 120807.01
A CB
120711.02

120710.02

120709.02

+S2K3
O
UVR K3
POWER SUPPLY NO/OFF
120513..06 12061101 CONV-B A1/2 A10 120721.01 NWP OFF NWP OFF
K3-0

A2 K L A1 210205.01 210205.01
12D11
120708.01

S2K20 42 2FOL NO 210301.16=11


21-K19
41
415vac 120612.01
+S2-K6 F-K3 210513.01=14 +S2-K7 120401.01 120408.01 120801.01 120808.01
O X2/17 K3-B
FOL A9 ACB ACB
Sw-2/3 K3-0
300Ams FEL2 TR A OFF
(+S2-X3-21)

K3-Y TR B OFF K4 K6
210303.10

O X2/18 SET A SET B


120612.01 S2K13
210301.06 (+S2-X3-11)
+ _ 21-K10 K3 210106.01 21020601 120409.01
S2K9
.02 .02 + 120402.01 120802.01 120809.01
TR-K3 210317.01 .02
210307.01

210301.09

(+S2-X3-11) .02 .02 .02


210319.01
210309.01
210315.01

S2K22
2D14 Ps2 =21-K6 750V S2K19
ON

P.S. PLANT SELECTOR SWITCH S2K18


OFF

210304.01 FEEDER B 21-K21 21-K16


=21-K15 FEL-Aux FOL-Aux TR.A TR. B NWP NWP
1 S.LOOP .02 .04 TR.A CON TR. B CON. K5 K5 K7 K7
12 O CLOCK OFF Aux
ON ON ON
120707.01

ON
3 O CLOCK PLANT A 2R1120511.05 S2K13
=21-K10 S2K3=12-K3 210309.03
210315.03

6 O CLOCK PLANT A/B AFR CFR 210104.04 210204.04 120403.01 120410.02 120803.01 120810.02
2 PS K3-415
F-K3
120703.04
19
Sw-2/3 .01 .01
+S2K13
9 O CLOCK PLANT B =21-K10 20 TR. A TR. B K4 WP K5 NWP K6 WP K7 NWP
3 4 2SB2 K4-0 K5-0
H R C FUSE 09.04 O +S2-X3-6
O +S2-X3-6
K6-0 K7-0
-VE 210204.04 -VE 210204.04
F1-F8,F10,F12-F15- 6AMP F K4 F K5 F K6 Fk7

210303.06 +S2-X3-21
-VE K4-0 K5-0 K6-0 K7-0
F9,F11-10AMP
F16-F20- 6AMP
.29 .31 .32 .33 .36 210301.35 330503.01 330504.01

CONV SELECTOR SWITCH PANEL .23 .24 .25 .26 .27 .38 .28 210301.30

SCHEMATIC DIAGRAM OF POWER


.21 .22 O 30 S2-X3-31O
420401.01 .02 .02
-45.00 ANGLE ENGINE ENABLE O
TEST
-90.00 ANGLE PLANT A OR B BUS COUPLER ON
45.00 ANGLE CONVERTER ENABLE
LAMP
O SW.
.02 .03
AND CONTROL CIRCUIT FOR LHB
210301.19

.04 .05 .06 .07


ACB1 ACB2 K16 K21 K19 K22 K15 K18

HEAD ON GENERATION POWER CAR


K1 K3 K2 K5 K7 Tr1 Tr2

24V OK
X1- X1- X1- X1- X1-02 X2- X2- X2- X2- X1-6 X1-09 X2- X1- X2- .08 .09 .10 420505.02 .12 .13 .14 .15 .16 .17 .18 420401.19

WESTERN RAILWAY MUMBAI DIVISION ELECTRICAL COACHING DEPOT BCT


420402.01 420504.02 420601.01 420602.01 420603.01 420604.01 420605.01 420606.01 BATTERY
420403.01 420404.01 420405.01 420501.01 420502.01 420503.01
05 04 15 16 05 04 15 16 09 11 11 FEL2 SAFETY SAFETY
BATTERY
CHARGER
CHARGER
ACB1 ACB2 F1 F2 -BC NWP1 NWP2 Tr1 Tr2 FOL1 FEL1 FOL2
DEFECT
H5 H3 CONV A FUSE H6 H4 CONV B H7 110V 110V 0V 0V ON ON ON ON ON ON ON ON ON LOOP1 LOOP 2 ON

REST 24 V RESET DRN ANAND REF THIS DRG IS TRACED FROM ORIGINAL
210303.31 .34 .35 .41 210303.48
CKD K G BAJAJ
.32 .33 .36 .37 .38 .39 .40 .42 .43 .44 SSE-PC BCT
CONV A OP

SCHALTBAU AG AND MODIFIED BY SrDEE(CHG)BCT


CONV B OP

.45 .46
I/P CONV ON

.47
CONV A FAULTY

CONV B FAULTY

SSE-PC-BCT

AEE RAJ BCT


DRG. NO RAJ-LHB-231-04 SrDEE(CHG)BCT