This document summarizes the calculated electrical load and circuit breaker sizing for a facility. It details the lighting, outlet, and medical equipment loads totaling 238,749 volt-amperes. It then calculates the reference current as 454 amperes and selects a 400 ampere molded case circuit breaker. It specifies using 2 sets of 3 125mm square conductors for incoming/outgoing feeders along with neutral and grounding conductors installed in 100mm diameter PVC piping.
This document summarizes the calculated electrical load and circuit breaker sizing for a facility. It details the lighting, outlet, and medical equipment loads totaling 238,749 volt-amperes. It then calculates the reference current as 454 amperes and selects a 400 ampere molded case circuit breaker. It specifies using 2 sets of 3 125mm square conductors for incoming/outgoing feeders along with neutral and grounding conductors installed in 100mm diameter PVC piping.
This document summarizes the calculated electrical load and circuit breaker sizing for a facility. It details the lighting, outlet, and medical equipment loads totaling 238,749 volt-amperes. It then calculates the reference current as 454 amperes and selects a 400 ampere molded case circuit breaker. It specifies using 2 sets of 3 125mm square conductors for incoming/outgoing feeders along with neutral and grounding conductors installed in 100mm diameter PVC piping.