User Guide EUROGAUGE EUROGAUGE User Guide

LAS Level Alarm System ...the level people ...the level people LAS Level Alarm System

Specification
LAS31Z1 - AC/DC Version LAS33Z1 - Battery Version
Supply: Battery:
85 to 265Vac; 50/60Hz; 4VA, +24Vdc +9V PP3 Alkaline 6 LR 61, 6 AM 6, MN 1604

Indicators: Indicators:
Tank Full - Red Tank Full - Red
Tank Empty - Red Tank Empty - Red
Bund Full - Red Bund Full - Red
Power - Amber Controls:
Controls: Test Button simulates alarm conditions
Test Button simulates alarm conditions Mute Button mutes alarm sounder
Mute Button mutes alarm sounder Sounder: Internal piezo-electric sounder (90db @ 0.6metre)
Relays: SPCO 250V; 3A non-inductive load. de-energises upon Sensor:
alarm – remains de-energised until alarm clears Floatswitch x 3, 5m cable with 1” BSP tank connector
Sounder: Internal piezo-electric sounder (90db @ 0.6metre) Housing: Polycarbonate ABS enclosure
Sensor: Dimensions: 176mm x 125mm x 76mm
Floatswitch x 3, 5m cable with 1” BSP tank connector Protection: IP65 The LAS3 Alarm provides Tank Full, Tank Empty and Bund Full audible and visual alarms for oil storage tanks.
Housing: Polycarbonate ABS enclosure Cable Entry: 5 Pg11 glands for 6-8mm cable The LAS31Z1 is powered from a 85 to 265Vac or 24Vdc supply and the LAS33Z1 from a 9V replaceable battery.
Dimensions: 176mm x 125mm x 76mm Weight: 0.60kg Simple floatswitches mounted in the tank and bund area are used to provide the alarm signals.
Protection: IP65
Cable Entry: 5 Pg11 glands for 6-8mm cable
Weight: 0.60kg
The LAS31Z1 provides a continuous display of alarm conditions while the LAS33Z1 is powered on by an alarm
signal or whenever the Test button is pressed. Once the LAS33Z1 has been powered on by an alarm signal the
corresponding alarm lamp lights and the sounder operates. If the alarm is not acknowledged by pressing the
Mute button the unit will sleep after 5 minutes and will wake every hour operating the sounder for 5 seconds and
WARNING: NOT FOR USE ON LIQUIDS IN STORED WITHIN HAZARDOUS AREAS the alarm lamp for 10 seconds. This continues until the alarm condition is cleared or until the battery is exhausted
(around 240hrs with a new battery). Acknowledging the alarm immediately turns the sounder off and the alarm
lamp off after 30 seconds and puts the LAS33Z1 into sleep mode. When there are no alarms present the
LAS33Z1 is switched off.
On pressing the Test button all alarm lamps light and the sounder operates, releasing the Test button turns
A Flameproof version (EEX D) is available to order, please contact Afriso Eurogauge Ltd for further details. the alarms off. Any existing alarms will be displayed for 30 seconds before turning off.

Note: We reserve the right to amend these specifications without prior notice.

Declaration of Conformity
LAS Unit - Battery
LAS Series Level Alarm System or AC/DC Version
Tank Full
Unit 4, Satellite Business Village This is to certify that the above named product(s) fully complies with the Alarm Point
Electromagnetic Compatability Directive 89/336/EEC and the Low Voltage Directive
Fleming Way, Crawley 73/23/EEC of the European Union and with the requirements of the normative
West Sussex. RH10 9NE sections of the following harmonised European Standards.

Tel: +44 (0)1293 658360 EN61000-6-3: Electromagnetic Compatibility - Generic Emission Standard.
Residential, Commercial and Light Industry.
Fax: +44 (0)1293 528270 EN61000-6-1: Electromagnetic Compatibility - Generic Immunity Standard.
www.eurogauge.co.uk Residential, Commercial and Light Industry.
EN 61010-1: Safety requirements for electrical equipment for measurement,
sales@eurogauge.co.uk control and laboratory use.
· RADAR and MICROPULSE Tank Empty Tank
· ULTRASONICS Alarm Point
Signed : FillPoint
· PRESSURE TRANSMITTERS
· VIBRATION SWITCHES
D. C Ward
· CAPACITANCE
· Float Level Switches
Position: Technical Services Manager
· Conductivity
Date: 12/12/2005 Bund Full
· Rotary Paddle
Alarm Point
· Magnetostrictive
This declaration applies to the following part number(s):
· Self-powered gauges
LAS31Z1: LAS 3 85-265Vac/24Vdc version.
· Oil/water Alarms
· Leak Detectors
LAS33Z1: LAS 3 9V Battery Version. LAS3 Typical Installation
· Pressure and Temperature

4/4 1/4
User Guide EUROGAUGE EUROGAUGE User Guide
LAS Level Alarm System ...the level people ...the level people LAS Level Alarm System
Installation & Electrical Connections Battery Version Float Switch Installation
The alarm unit is designed for Float Switch Assembly
LAS 3
four-screw wall mounting on a Pass the float switch lead through the tank/cable
Alarm Unit
160mm x 110mm pitch. gland assembly to give the desired alarm switchpoint
and tighten the cable gland.
It is recommended that the unit PKVA
is not mounted in a location where Fit the float switch assembly through the 1" BSP Extension
tank gland in the tank. Cable
it is exposed to direct sunlight. Connector
Cable Gland
All wiring must be in suitable cable Should the float switch lead require extension, fit a Adjust Cable
PVKA extension cable connector to the float switch Gland to set
for the site conditions. Alarm Point
lead and run the length of additional cable from the Extension
PKVA connector to the TA3 unit. Turn Float Weight Cable
The installation must comply with upside down (2 Core)
the relevant regulations of the for Low supplied
electrical supply authority Level Alarm by
(remove Float Installer
concerned together with any other
statutory requirements which may Circlip
to alter)
affect the complete installation. Circlip

IP1 IP2 IP3 Dimensions

Tank Full
Float Switch

125
Tank Empty
Float Switch

Bund Full
Float Switch

IP1 IP2 IP3

Live

Neutral Tank Full Tank Empty Bund Full


Fixing centres:- 160 x 110mm

Earth Alarm Alarm Alarm


Contacts Contacts Contacts

0V Open when Bund Full


Tank Full

76
+24Vdc Common Float Switch
Closed when Bund Full
Closed when Tank Full
Common Open when Tank
Tank Empty
Empty Float Switch
Open when Tank Full Common
Closed when Tank Empty

Bund Full
24Vdc or 85-265Vac Version ‘All Alarm contacts are voltage free’
Float Switch
175

2/4 3/4