Installation Guide

Hardie™ Axent™ Trim

EXTERIORS

Australia November 2022

Make sure your information is up to date.


When specifying or installing Hardie™ products, ensure you have the current
technical information and guides. If in doubt, or you need more information,
visit www.jameshardie.com.au or Ask James Hardie™ on 13 11 03.
Installation Guidelines
Ideal for edge treatment around windows, finishing touches to cladded internal and WARNING - DO NOT BREATHE DUST AND
external corners as well as a design enhancer for butt joints. CUT ONLY IN WELL VENTILATED AREA
Hardie™ fibre cement products contain sand, a source
The thickness of HardieTM AxentTM Trim helps create the impression of solidness, and it’s of respirable crystalline silica. May cause cancer if dust
crisp, chamfered edges highlight frames and openings. from product is inhaled. Causes damage to lungs and
HardieTM AxentTM Trim will maintain its integrity and general appearance significantly longer respiratory system through prolonged or repeated
than traditional soft wood. Mostly, timber is susceptible to cracking in external applications inhalation of dust from product.
which can lead to shrinking and warping. HardieTM AxentTM Trim will resist shrinking, Intact fibre cement products are not expected to result in
any adverse toxic effects. The hazard associated with fibre
swelling and cracking and hold paint longer than wood, when installed and maintained
cement arises from the respirable crystalline silica present
correctly, and can also be painted in dark as well as light colours. in dust generated by activities such as cutting, rebating,
drilling, routing, sawing, crushing, or otherwise abrading fibre
cement, and when cleaning up, disposing of or moving dust.
IMPORTANT NOTES When doing any of these activities in a manner that
Due to the product enhancements, Hardie™ Axent™ Trim must be treated carefully generates dust, follow Hardie™ instructions and best
during transit including avoiding bending and dropping of the trim and always carrying practices to reduce or limit the release of dust, warn
the product on edge. The trim must also be packed flat for storage. others in the area and consider rotating personnel across the
cutting task to further limit respirable silica exposure.
1. Failure to install, finish or maintain this product in accordance with applicable building codes, regulations, If using a dust mask or respirator, use an AS/NZS1716
standards and James Hardie’s written application instructions may lead to personal injury, affect system P1 filter and refer to Australian/New Zealand Standard
performance, violate local building codes, and void the Hardie™ product warranty. 1715:2009 Selection, Use and Maintenance of Respiratory
2. All warranties, conditions, liabilities (direct, indirect or consequential) and obligations whether arising in Protective Equipment for more extensive guidance and
contract, tort or otherwise other than those specified in the Hardie™ product warranty are excluded to more options for selecting respirators for workplaces. For
the fullest extent allowed by law. For Hardie™ product warranty information and disclaimers about the further information, refer to our installation instructions and
information in this guide, visit www.jameshardie.com.au. Safety Data Sheets available at www.jameshardie.com.au.
3. The builder must ensure the product meets aesthetic requirements before installation. James Hardie will FAILURE TO ADHERE TO OUR WARNINGS, SAFETY DATA
not be responsible for rectifying aesthetic surface variations following installation. SHEETS, AND INSTALLATION INSTRUCTIONS MAY
LEAD TO SERIOUS PERSONAL INJURY OR DEATH.

HARDIE™ AXENT™ TRIM JAMES HARDIE RECOMMENDED SAFE


WORKING PRACTICES
Product Length Width Thickness Weight per CUTTING OUTDOORS
Code (mm) (mm) (mm) unit (kg) 1. Position cutting station so wind will blow dust away from the
user or others in working area.
405260 3000 45 19 3 2. Warn others in the area to avoid dust.
3. Consider rotating personnel across cutting tasks to further
405257 3000 70 19 5 limit respirable silica exposures.
Material composite trim used for 4. Use one of the following methods based on the required
405258 3000 89 19 6
box corners and as decorative trim cutting rate:
around windows and doors. The front 405261 3000 45 38 6 Best n
Villaboard™ Knife Hand guillotine Fibreshear
n n

face of the trims are chamfered to Better Position the cutting station in a well-ventilated area.
n

improve their aesthetic appeal 405262 3000 89 38 12 Use a dust reducing circular saw equipped with
Hardie™ Blade Saw Blade or comparable fibre
Please call James Hardie on 13 11 03 to check availability. cement blade and well maintained M-class vacuum
or higher with appropriate filter for capturing fine
(respirable) dust. Wear a properly-fitted, approved
ACCESSORIES & TOOLS dust mask or respirator (minimum P1).
COMPONENTS SUPPLIED BY JAMES HARDIE CUTTING INDOORS
n
Cut only using Villaboard™ Knife, hand guillotine or
PRODUCT DESCRIPTION PRODUCT DESCRIPTION fibreshears (manual, electric or pneumatic).
n
Position cutting station in a well-ventilated area.
Hardie™ Joint Sealant.
Hardie Blade Saw Blade.
TM
300mL catridge
185mm diameter DRILLING/OTHER MACHINING
A general purpose, paintable, When drilling or machining you should always wear a P1 dust
Poly-diamond blade for Hardie™
exterior grade polyurethane joint mask and warn others in the immediate area.
fibre cement. Pack Size: 1 each.
sealant. 20 per box.
Part No. 300660 IMPORTANT NOTES
Part No. 305534 1. For maximum protection (lowest respirable dust production)
James Hardie recommends always using best practice
COMPONENTS NOT SUPPLIED BY JAMES HARDIE cutting methods where feasible.
James Hardie recommends the following products for use in conjunction with its products. 2. NEVER use a power saw indoors or in a poorly ventilated area.
James Hardie does not supply these products and does not provide a warranty for their use. Please contact 3. ALWAYS use a dust reducing circular saw equipped with
the component manufacturer for information on their warranties and further information on their products. a sawblade specifically designed to minimise dust creation
when cutting fibrecement - preferably a sawblade that carries
ACCESSORIES DESCRIPTION ACCESSORIES DESCRIPTION the Hardie™ Blade logo or one with at least equivalent
performance - connected to a M class or higher vacuum.
Finishing Nails Wing tip screw 4. NEVER dry sweep - Use wet suppression, or an M class
Pneumatic only 50 or 62mm 16 For 19mm thick trim, use a 52mm vacuum or higher with appropriate filter.
gauge stainless steel finishing nail class 3 wing screw by TRI-FIXX. 5. NEVER use grinders.
eg. C, ND or DA series. For 38mm thick trim, use a 75mm 6. ALWAYS follow tool manufacturers’ safety recommendations.
class 3 wing screw by Powers 7. ALWAYS wear a properly fitted, approved dusk mask, P1 or higher
Fasteners Australasia Pty Ltd. DUST MASKS AND RESPIRATORS
As a minimum, an AS/NZS1716 P1 respirator must be used
Screws when doing any activity that may create dust. For more extensive
Bullet head nails
8-10g x 50mm corrosion resistant guidance and options for selecting respirators for workplaces please
50 or 65mm x 2.8mm diameter
chipboard/wood screws. refer to Australian/New Zealand Standard 1715:2009 “Selection,
corrosion resistant bullet head nails.
8-10g x 65mm corrosion resistant Use and Maintenance of Respiratory Protective Equipment”.
Nail holes must be pre drilled. P1 respirators should be used in conjunction with the above cutting
chipboard/wood screws.
practices to minimise dust exposure. For further information, refer to
Dust-Reducing Saw with M class Drop Saw* Safety Data Sheet (SDS) available at www.jameshardie.com.au. If
Drop saw with aluminium blade. concern still exists about exposure levels or you do not comply with
or higher vacuum extraction the above practices, you should always consult a qualified industrial
Dust reducing saw used with *not to be used for cutting Hardie™
hygienist or contact James Hardie for further information.
Hardie™ Blade saw blade. Axent™ Trim.
Makita® 5057KB / Hitachi® C7YA STORAGE AND HANDLING
To avoid damage, all Hardie™ building products should be
stored with edges and corners of the product protected
from chipping. Hardie™ building products must be
installed in a dry state and protected from weather during
transport and storage. The product must be laid flat under
cover on a smooth level surface clear of the ground to
PAGE 1 OF 6 HARDIE™ AXENT™ TRIM INSTALLATION GUIDE avoid exposure to water, moisture, etc.
PREPARATION FIXINGS
Edges cut on site must be primed before installation.
Slight chamfering of cut edges is recommended to FIXING TO TIMBER
improve edge paint adhesion. Pneumatically Driven Finishing Nails (Gas power not recommended)
Trim Type Min. Edge Nailing
Clearances Thickness Fixing Distance Centres
Install Hardie™ Axent™ Trim with a minimum
150mm clearance to the earth on the exterior of the 50mm x 16 gauge brad (eg. C, ND or DA). 150mm
building or in accordance with local building codes if 19mm Pre drill 2.8 x 50mm dia corrosion resistant bullet or flat
greater than 150mm is required. 300mm
head nails.
22mm
Maintain a minimum 50mm clearance between 62mm x 16 gauge brad (eg. C, ND or DA). 150mm
Hardie™ Axent™ Trim and roofs, decks, paths, 38mm Pre drill 2.8 x 65mm dia corrosion resistant bullet or flat
steps and driveways. Adjacent finished grade must 300mm
head nails.
slope away from the building in accordance with
local building codes, typically a minimum slope of Screw Fix
50mm minimum over the first metre. 8 - 10g Corrosion resistant chipboard type screw. Predrill
19mm and
with a 3mm drill bit. For 19mm thick trim use 50mm long 22mm 300mm
Do not install Hardie™ Axent™ Trim such that it 38mm
screws and for 38mm thick trim use 65mm long screws’
may remain in contact with standing water.
NOTE Gas powered nail guns are not suitable for fixing Hardie™ Axent™ Trim. Fasteners must be corrosion
NOTE resistant, James Hardie recommends Stainless Steel finishing nails. Electro-galvanised nails are acceptable but may
Greater clearance may be required in order to exhibit premature corrosion. James Hardie is not responsible for the corrosion resistance of fasteners.
comply with termite protection provisions.
FIXING TO STEEL
TERMITE PROTECTION
The National Construction Code (NCC) specifies Wing Tip Screws
the requirements for termite barriers and must Thickness Screw Min. Edge Fixing Distance Nailing Centres
be complied with. Where the exposed slab edge
19mm 52mm class 3 by Tri-Fixx. 300mm
is used as part of the termite barrier system, a 22mm
minimum of 75mm of the exposed slab edge must 38mm 75mm class 3 by Powers Fasteners 300mm
be visible to permit ready detection of termite entry.
If a smooth surface appearance on the face of the Hardie™ Axent™ Trim must be fixed directly to
FRAMING trim is required, then the heads of the nails need to timber framing with two fasteners at either end of
Hardie™ Axent™ Trim can be fixed to either timber be finished or punched 2-3mm below the surface the trim. Intermediate fixings are also required at
or light gauge domestic type steel framing. The and filled with a water-proof exterior filling compound 150mm maximum staggered centres for finish nails.
framing used must comply with the relevant building as per the manufacturer’s recommendations. Punch All other nails require intermediate fixings at 300mm
regulations and standards and the requirements of below surface only suitable for bullet head and maximum staggered centres. Intermediate fasteners
this guide. Use only seasoned timber. brad nails. Flat head and screws must be finished are not staggered at corners where framing is
flush with the board surface. off-set, see Figure 2.
Unseasoned timber must not be used, as it is prone
to shrinkage and can cause Hardie™ Axent™ Trim When installing Hardie™ Axent™ Trim around
Drive screw flush Fill over head
and frames to move. The base metal thickness of a windows see Figure 1.
steel frame must be between 0.55 and 1.6mm (BMT).

Flashing HardieTM
Fastener durability Weather
Various grades of fastener finishes and durability Barrier
38mm
are available such as galvanised, stainless steel and HardieTM
HardieTM
fasteners with proprietary coatings. AxentTM Trim external
cladding
Fasteners must have the appropriate level of Flush nailing Over driven Unacceptable:
2-3mm max. under driven See nailing
durability required for the intended project. This is of centres in
particular importance in coastal areas, areas subject fixings table

to salt spray and other corrosive environments.


NOTE
Do not screw into the 38mm or 19mm edge of the Do not caulk 22mm min.
Fasteners must be fully compatible with all other along top edge
Hardie™ Axent™ Trim or cut Hardie™ Axent™ Trim
materials that they are in contact with to ensure
ends.
the durability and integrity of the assembly. Contact 25mm min.
fastener manufacturers for more information.
Flashings 6mm gap
Suitable weather barrier (in accordance with AS/ Caulk gap
between
NZS 4200.2) and flashings must be installed behind HardieTM AxentTM Trim
Flashing
wall and corner trims in order to drain water down (6mm gap between and cladding with
and out of the wall. Refer to the appropriate external cladding and flashing) HardieTM Joint Sealant

cladding technical documentation, building codes


and standards for requirements. Information is also FIGURE 1 19MM AND 38MM HARDIE™ AXENT™ TRIM
available from BRANZ regarding good flashing FIXING AROUND WINDOW
practices.
NOTE
INSTALLATION 1. Always ensure the thickness of the trim is
NOTES adequate for your selected cladding.
When using Hardie™ Axent™ Trim with Linea™
2. When the cladding around the window is a
n

Weatherboard, additional framing may be


flat sheet, the cladding can either be butted
required, see Linea™ Weatherboard Installation
to the HardieTM AxentTM Trim as shown
Guide.
in Figure 1 OR installed overlapping the
You must ensure the product is of acceptable
HardieTM AxentTM Trim.
n

quality prior to installation, see Important Note 3.

HARDIE™ AXENT™ TRIM INSTALLATION GUIDE PAGE 2 OF 6


CORNERS AND EAVES FINISHES PRODUCT INFORMATION
Preparation and priming General
22mm min. to edge
Hardie™ Axent™ Trim is pre-sealed and must The basic composition of Hardie™ building
be dry before painting. Where filling over fastener products is Portland cement, ground sand, cellulose
Up to 2mm heads refer to page 2. Priming of filled and sanded fibre, water and proprietary additives.
gap for sealant
patches may be required in accordance with paint
manufacturer’s specifications. Hardie™ building products are manufactured AS/
NZS 2908.2 ‘Cellulose-Cement Products-Flat
NOTE Sheet’. These are also compliant with equivalent
Care must be taken not to over-sand as it can standard ISO 8336 ‘Fibre-cement flat sheets
HardieTM affect the finish. - Product specification and test methods’. For
AxentTM Trim
product classification refer to the relevant Physical
HardieTM Sealants Properties Data Sheet.
Weather Application and use of sealants must comply with
Barrier
manufacturer’s instructions. Sealants, if coated, DURABILITY
Inside corner Outside corner
must be compatible with the paint system. Resistance to moisture/rotting
Hardie™ Axent™ Trim has demonstrated resistance
Leave up to 2mm
Painting to permanent moisture-induced deterioration
gap between Refer to the project specification for paint (rotting) by passing the following tests in
cladding and requirements. Hardie™ Axent™ Trim must be
trim then seal accordance with AS/NZS 2908.2:
with HardieTM painted within 3 months of being installed. James
Joint Sealant Hardie recommends the application of two coats n
Water permeability (Clause 8.2.2)
minimum of a quality acrylic paint over the n
Warm water (Clause 8.2.4)
FIGURE 2 CORNER DETAIL pre-sealed trim in accordance with the paint n
Heat rain (Clause 6.5)
manufacturer’s specifications. Some environments n
Soak dry (Clause 8.2.5).
require special coatings. Painting selection and
specifications are dependant on the paint chosen. Resistance to fire
Leave up to 2mm gap (caulk if using butt-to Refer to the paint manufacturer for information and Hardie™ Axent™ Trim is suitable where
joints, optional if applying trim over cladding details of their warranty. non-combustible materials are required in accordance
with C1.9 of the National Construction Code (NCC).
Staining
Stains containing linseed oil are specifically designed Hardie™ building products have been tested
for wood and may not be suitable for Hardie™ by CSIRO in accordance with AS/NZS 3837
cladding products, primed or unprimed. and are classified as conforming to Group 1
Semi-transparent stains can vary in uniformity of material (highest and best result possible), with
appearance depending on method of application an average specific extinction area far lower
38mm and conditions and will require a high level of skill than the permissible 250m2/kg, as referenced in
19mm
HardieTM
HardieTM and craftsmanship to achieve a uniform appearance. Specification C1.10a of the National Construction
AxentTM Trim
AxentTM Trim Clear coats have not proven durable in exterior Code (NCC).
25mm exposure and James Hardie considers them a
min. 25mm
min. maintenance item that may require application of a Resistance to termite attack
refurbishing sealer at regular intervals. James Hardie Based on testing completed by CSIRO Division
does not warrant the appearance or durability of of Forest Products and Ensis Australia, Hardie™
semi-transparent stains and clear coats. building products have demonstrated resistance to
termite attack.
Sealant MAINTENANCE
Regular cleaning and maintenance of the paint, Alpine regions
Trim over cladding ‘Butt-to’ detail
finished surface, joints, junctions, penetrations, In regions subject to freeze/thaw conditions, all
etc must be carried out at regular intervals to Hardie™ fibre cement external cladding must be
FIGURE 3 TOP OF WALL TRIM DETAILS maintain finish and weather-resistance of cladding. installed and painted in the warmer months of the
Maintenance must also meet the requirements of year where the temperature does not create freeze
the relevant component manufacturer. and thaw conditions or paint issues. The cladding
HardieTM Weather Barrier must be painted immediately after installation. In
addition, fibre cement cladding must not be in direct
HardieTM Flex Sheet
Continuous bead contact with snow and/or ice build up for extended
HardieTM AxentTM of HardieTM
Joint Sealant periods, e.g. external walls in alpine regions subject
Trim 45x19mm
to snow drifts over winter.

Furthermore, a reputable paint manufacturer must


be consulted in regards to a suitable product,
specifications and warranty. The paint application
must not be carried out if the air temperature or
the substrate temperature is outside the paint
manufacturer’s recommendation including the
12mm specified drying temperature range
min.

Hardie™ external cladding products are tested


for resistance to frost in accordance with AS/NZS
2908.2 Clause 8.2.3.

FIGURE 4 BATTEN ON BOARD SHEET JOINTING DETAIL

PAGE 3 OF 6 HARDIE™ AXENT™ TRIM INSTALLATION GUIDE


Notes

HARDIE™ AXENT™ TRIM INSTALLATION GUIDE PAGE 4 OF 6


Notes

PAGE 5 OF 6 HARDIE™ AXENT™ TRIM INSTALLATION GUIDE


HARDIE™ AXENT™ TRIM INSTALLATION GUIDE PAGE 6 OF 6
For information and advice
call 13 11 03 | jameshardie.com.au
Australia November 2022
© 2022 James Hardie Australia Pty Ltd ABN 12 084 635 558
™ and ® denote a trademark or registered trademark owned by James Hardie Technology Limited.
Powers®, Tri-fixx, Hitachi and Makita® are trademarks or registered trademarks of their respective owners
and are not owned by James Hardie Technology Limited.