PROJECT

LOCATION U.A.E (ABU DHABI)


CLIENT XYZ
CONSULTANT ABC
126.00
Area or Sun Gain or
Item
Quantity Temp. Diff.
ROOM HEAT Q= U*A*ΔT
ROOM SENSIBLE HEAT
Solar Gain - Glass Area ΔT
Glass - N SqFt x x
Glass - NE SqFt x x
Glass - E SqFt x x
Glass - SE 15.50 SqFt x 13.00 x
Glass - S SqFt x x
Glass - SW 11.62 SqFt x 100.00 x
Glass - W SqFt x x
Glass - NW SqFt x x
Skylight SqFt x x
Solar & Transmission Gain - Walls & Roof
Wall - N SqFt x F x
Wall - NE SqFt x F x
Wall - E SqFt x F x
Wall - SE 138.33 SqFt x 37.50 F x
Wall - S SqFt x F x
Wall - SW 128.35 SqFt x 35.50 F x
Wall - W SqFt x F x
Wall - NW SqFt x F x
Roof 300.00 SqFt x 45.50 F x
Transmission Gain - Except Walls & Roof
All Glass 27.10 SqFt x 36.00 F x
Partition 46.15 SqFt x 31.00 F x
Ceiling SqFt x F x
Floor 300.00 SqFt x 31.00 F x
INFILTRATION AND BY PASSED AIR
Infiltration CFM x 36.00 T.Diff x
Outside Air 28.00 CFM x 36.00 x
Internal Heat
People 2.00 Nos. x 230.00 Btu/Hour Per Person
Lighting 300.00 SqFt x 1.00 W/SqFt x
Equipments 1.00 200.00 Watts x
Power kW/Hp x
Sub Total
Factor
Effective Room Sensible Heat
ROOM LATENT HEAT
Infiltration 0.00 CFM x 6.00 Gr/Lb x
Outside Air 28.00 CFM x 6.00 Gr/Lb x
People 2.00 Nos. x 120.00 Btu/Hour Per Person
Sub Total
Factor
Effective Room Latent Heat
EFFECTIVE ROOM TOTAL HEAT
OUTSIDE AIR HEAT
Sensible 28.00 CFM x 36.00 F(TD) x
Latent 28.00 CFM x 6.00 Gr/Lb x
OUTSIDE AIR TOTAL HEAT
GRAND SUB-TOTAL HEAT
Factor
GRAND TOTAL HEAT

TONS=GRAND TOTAL HEAT/12000


INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY
FLOOR Ground Floor
HABI) SPACE REFERENCE R-01, Flat-1, Bedroom,Residen
AREA ( SqFt) (WxH) 300.00
Falce Ceiling Height (Ft) 9.40
Volume (CuFt) 2,820.00
Estimate for Summer
Factor (U) Btu/Hour Watts
Design Conditions DB (°F)
Q= U*A*ΔT Ambient(Out Side) 111.00
Room (InDoor) 75.00
U Difference Δ 36.00
0.00
0.00
0.00 By Pass Factor (BF)
0.30 60.45 Contact Factor (CF = 1 - BF)
0.00 CFM Ventilation
0.30 348.60 CFM Per Person 5.00 No
0.00 CFM Per SqFt 0.06 Sqft
0.00 Air Change Per Hour (CFM)
0.00 CFM Cu.ft 2,820.00 x
CFM Infiltration
0.00 Swinging x
0.00 Revolving Doors (People) x
0.00 Open Doors x
0.05 259.37 Crack (feet) x
0.00
0.05 227.82 Supply CFM from Machine
0.00 Effective Room Sensible Heat Factor =
0.00 Effective Room Sensible Heat/Eff Room Total Heat
0.05 614.25 Apparatus Dew Point (ADP)
Indicated ADP (°F)
0.30 292.68 Selected ADP (°F)
0.50 715.32 Dehumidified Rise
0.00 (Room DB - ADP) x CF
0.27 2,511.00 DEHUMIDIFIED AIR QUANTITY
Effective Room Sensible Heat
1.08 0.00 Dehumidified Rise x 1.08
130.64

460.00 TOTAL HEAT CAPACITY


3.41 1,023.00 Grand Total Heat
3.41 682.00
0.00
7,325.13
5-15% 1,098.77
8,423.90 1.00 SENSIBLE HEAT CAPACITY
Grand Sensible Heat
0.68 0.00 12,000.00
BFx0.68 13.71
240.00
253.71
2.5 - 5% 12.69
266.39 2.00
8,690.30

CF x 1.08 958.00 3.00


CF x 0.68 100.53 4.00
1,058.53 Notes:
9,748.83
1 - 3% 292.46
10,041.30
TMBH 10.04
TKW 2.91
TSMBH 9,381.90
TSKW 2,720.75
0.84
Ground Floor
01, Flat-1, Bedroom,Residential (ABU DHABI)
300.00
9.40
2,820.00
Summer
WB (°F) RH (%) HR (Gr/Lb)
75.00 19.00 74.00
63.00 50.00 68.00
12.00 31.00 6.00

= 0.12
= 0.88
tion
= 2.00 = 10.00
x 300.00 = 18.00
=
0.00 x1/60 = 0.00
ion
cfm/door = 0.00
cfm/door = 0.00
1.00 cfm/door = 0.00
cfm/ft = 0.00
0.00
Machine

= 0.97
oint (ADP)
=
= 54.60
Rise
= 17.95

= 434.49 CFM

= 204.21 L/s

= 0.84 TR

= 0.84 TR