CT ROOM

GREEN AIR ROOM TYPE 1 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
Floor : FIRST Area : CT ROOM System No. : 1
Floor Area 407 Sq Ft Ceiling Ht 10 Ft Volume = 4070 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 23 0.81 0 DIFFERENCE 28 XXXX XXXX XXXX 81.7
NE - Glass 12 0.81 0
E -GLASS 12 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 3 People X 0 CFM/Person 5.00
S - Glass 12 0.81 0 407 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 39
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.99
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 5111
No. of Rows = 0
N - Wall 186 19 0.36 1272 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 2
E - Wall 33 0.36 0 'Min. cfm reqd. = 136
SE - Wall 33 0.36 0
S - Wall 31 0.36 0
SW - Wall 29 0.36 0
W - Wall 176 27 0.36 1711
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 3 persons
ITEM Area Temp. diff. U FRESH AIR 136
(Sq ft) (°F) (Btu/h.sq ft) Light 611 watt
All Glass 0 28 0.55 0 Equipment 611 watt
Glass Partition 23 0.55 0
Partition AC 459 23 0.3 3167
Partition N/AC 23 0.35 0
Ceiling 23 0.45 0
Floor 407 23 0.45 4212
INTERNAL HEAT GAIN
People 3 Nos X 230 690
Light 611 W X 1.25 3.412 2604
Eq. Load 611 W 3.412 67593
ROOM SENSIBLE HEAT (RSH) 81249
Supply duct heat Supply duct Heat gain from 2 1625
gain + leak. loss + fan HP(%)

Safety factor (%) 5.0 4062


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
136 28 0.12 1.08 492
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 87429
LATENT HEAT
People 3 Nos X 120 360
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
136 81.7 0.12 0.68 904
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 1264
Supply duct leakage loss + Safety factor % 5.0 63
EFFECTIVE ROOM LATENT HEAT (ERLH) 1328
EFFECTIVE ROOM TOTAL HEAT (ERTH) 88757
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 136
136 28 0.88 1.08 3610 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 8.41
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 248.1 Monsoon TR= 8.52
136 81.7 0.88 0.68 6633 CFM / Sq ft = 12.56 Deh. CFM= 5111
HEAT SUB TOTAL 99000 Sq ft / TR = 48 CFM(ACPH)= 75
Return duct heat HP Pump + Dehum. & Pipe 2.0 1980
gain & leak. loss + loss (%) CFM/ TR = 607
Selected TR = 8.5
TONS 8.41 GRAND TOTAL HEAT 100980 Selected CFM= 5150
CT ROOM
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 0 11 0.81 0 DIFFERENCE 26 XXXX XXXX XXXX 99
NE - Glass 0 11 0.81 0
E - Glass 0 11 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 3 People X 0 CFM/Person 5
S - Glass 0 11 0.81 0 407 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 39
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.98
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 5109
No. of Rows = 0
N - Wall 186 9 0.36 603 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 2.0
E - Wall 0 23 0.36 0 'Min. cfm reqd. = 136
SE - Wall 0 23 0.36 0
S - Wall 0 21 0.36 0
SW - Wall 0 19 0.36 0
W - Wall 176 17 0.36 1077
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 0 26 0.5500 0
Glass Partition 0 21 0.55 0
Partition glass-NAC 459 21 0.30 2892
Partition wall-NAC 0 10 0.35 0
Ceiling 0 10 0.45 0
Floor 407 10 0.45 1832
INTERNAL HEAT GAIN
People 3.0 Nos X 230 690
Light 610.5 W X 1.25 3.412 2595
Eq. Load 610.5 WX 3.412 67593
ROOM SENSIBLE HEAT (RSH) 77281
Supply duct heat Supply duct Heat gain from 2 5796
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 3864
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
136 26 0.12 1.08 457
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 87398
LATENT HEAT
People 3 Nos X 120 360
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
136 99 0.12 0.68 1096
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 1456
EFFECTIVE ROOM TOTAL HEAT (ERTH) 88854
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
136 26 0.88 1.08 3352
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
136 99 0.88 0.68 8037
HEAT SUB TOTAL 100243
Return duct heat HP Pump + Dehum. & Pipe 2.0 2005
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 8.52 TR
TONS 8.52 TOTAL HEAT 102248
CT EQUIPMENT

GREEN AIR ROOM TYPE 1 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
Floor : FIRST Area : CT EQUIPMENT System No. : 1
Floor Area 68 Sq Ft Ceiling Ht 10 Ft Volume = 680 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 23 0.81 0 DIFFERENCE 28 XXXX XXXX XXXX 81.7
NE - Glass 12 0.81 0
E -GLASS 12 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 1 People X 0 CFM/Person 5.00
S - Glass 12 0.81 0 68 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 9
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.95
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 295
No. of Rows = 0
N - Wall 19 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 2
E - Wall 33 0.36 0 'Min. cfm reqd. = 23
SE - Wall 33 0.36 0
S - Wall 85 31 0.36 949
SW - Wall 29 0.36 0
W - Wall 98 27 0.36 953
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 1 persons
ITEM Area Temp. diff. U FRESH AIR 23
(Sq ft) (°F) (Btu/h.sq ft) Light 102 watt
All Glass 0 28 0.55 0 Equipment 102 watt
Glass Partition 23 0.55 0
Partition AC 148 23 0.3 1021
Partition N/AC 23 0.35 0
Ceiling 23 0.45 0
Floor 68 23 0.45 704
INTERNAL HEAT GAIN
People 1 Nos X 230 230
Light 102 W X 1.25 3.412 435
Eq. Load 102 W 3.412 348
ROOM SENSIBLE HEAT (RSH) 4639
Supply duct heat Supply duct Heat gain from 2 93
gain + leak. loss + fan HP(%)

Safety factor (%) 5.0 232


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
23 28 0.12 1.08 82
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 5046
LATENT HEAT
People 1 Nos X 120 120
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
23 81.7 0.12 0.68 151
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 271
Supply duct leakage loss + Safety factor % 5.0 14
EFFECTIVE ROOM LATENT HEAT (ERLH) 285
EFFECTIVE ROOM TOTAL HEAT (ERTH) 5331
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 23
23 28 0.88 1.08 603 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 0.60
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 105.6 Monsoon TR= 0.54
23 81.7 0.88 0.68 1108 CFM / Sq ft = 4.34 Deh. CFM= 295
HEAT SUB TOTAL 7042 Sq ft / TR = 114 CFM(ACPH)= 26
Return duct heat HP Pump + Dehum. & Pipe 2.0 141
gain & leak. loss + loss (%) CFM/ TR = 493
Selected TR = 0.6
TONS 0.60 GRAND TOTAL HEAT 7183 Selected CFM= 300
CT EQUIPMENT
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 0 11 0.81 0 DIFFERENCE 26 XXXX XXXX XXXX 99
NE - Glass 0 11 0.81 0
E - Glass 0 11 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 1 People X 0 CFM/Person 5
S - Glass 0 11 0.81 0 68 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 9
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.93
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 234
No. of Rows = 0
N - Wall 0 9 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 2.0
E - Wall 0 23 0.36 0 'Min. cfm reqd. = 23
SE - Wall 0 23 0.36 0
S - Wall 85 21 0.36 643
SW - Wall 0 19 0.36 0
W - Wall 98 17 0.36 600
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 0 26 0.5500 0
Glass Partition 0 21 0.55 0
Partition glass-NAC 148 21 0.30 932
Partition wall-NAC 0 10 0.35 0
Ceiling 0 10 0.45 0
Floor 68 10 0.45 306
INTERNAL HEAT GAIN
People 1.0 Nos X 230 230
Light 102.0 W X 1.25 3.412 434
Eq. Load 102.0 WX 3.412 348
ROOM SENSIBLE HEAT (RSH) 3492
Supply duct heat Supply duct Heat gain from 5 262
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 175
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
23 26 0.12 1.08 76
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 4005
LATENT HEAT
People 1 Nos X 120 120
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
23 99 0.12 0.68 183
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 303
EFFECTIVE ROOM TOTAL HEAT (ERTH) 4308
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
23 26 0.88 1.08 560
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
23 99 0.88 0.68 1343
HEAT SUB TOTAL 6211
Return duct heat HP Pump + Dehum. & Pipe 5.0 311
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 0.54 TR
TONS 0.54 TOTAL HEAT 6522
CONSOLE

GREEN AIR ROOM TYPE 1 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
Floor : FIRST Area : CONSOLE System No. : 1
Floor Area 176 Sq Ft Ceiling Ht 10 Ft Volume = 1760 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 23 0.81 0 DIFFERENCE 28 XXXX XXXX XXXX 81.7
NE - Glass 12 0.81 0
E -GLASS 12 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 1 People X 0 CFM/Person 5.00
S - Glass 58 12 0.81 564 176 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 16
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.96
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 702
No. of Rows = 0
N - Wall 19 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 2
E - Wall 33 0.36 0 'Min. cfm reqd. = 59
SE - Wall 33 0.36 0
S - Wall 111 31 0.36 1239
SW - Wall 29 0.36 0
W - Wall 27 0.36 0
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 1 persons
ITEM Area Temp. diff. U FRESH AIR 59
(Sq ft) (°F) (Btu/h.sq ft) Light 264 watt
All Glass 58 28 0.55 893 Equipment 264 watt
Glass Partition 23 0.55 0
Partition AC 459 23 0.3 3167
Partition N/AC 23 0.35 0
Ceiling 23 0.45 0
Floor 176 23 0.45 1822
INTERNAL HEAT GAIN
People 1 Nos X 230 230
Light 264 W X 1.25 3.412 1126
Eq. Load 264 W 3.412 1981
ROOM SENSIBLE HEAT (RSH) 11021
Supply duct heat Supply duct Heat gain from 2 220
gain + leak. loss + fan HP(%)

Safety factor (%) 5.0 551


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
59 28 0.12 1.08 213
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 12006
LATENT HEAT
People 1 Nos X 120 120
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
59 81.7 0.12 0.68 391
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 511
Supply duct leakage loss + Safety factor % 5.0 26
EFFECTIVE ROOM LATENT HEAT (ERLH) 537
EFFECTIVE ROOM TOTAL HEAT (ERTH) 12542
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 59
59 28 0.88 1.08 1561 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 1.44
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 98.4 Monsoon TR= 1.41
59 81.7 0.88 0.68 2868 CFM / Sq ft = 3.99 Deh. CFM= 702
HEAT SUB TOTAL 16972 Sq ft / TR = 122 CFM(ACPH)= 24
Return duct heat HP Pump + Dehum. & Pipe 2.0 339
gain & leak. loss + loss (%) CFM/ TR = 486
Selected TR = 1.4
TONS 1.44 GRAND TOTAL HEAT 17311 Selected CFM= 750
CONSOLE
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 0 11 0.81 0 DIFFERENCE 26 XXXX XXXX XXXX 99
NE - Glass 0 11 0.81 0
E - Glass 0 11 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 1 People X 0 CFM/Person 5
S - Glass 58 11 0.81 517 176 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 16
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.95
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 617
No. of Rows = 0
N - Wall 0 9 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 2.0
E - Wall 0 23 0.36 0 'Min. cfm reqd. = 59
SE - Wall 0 23 0.36 0
S - Wall 111 21 0.36 839
SW - Wall 0 19 0.36 0
W - Wall 0 17 0.36 0
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 58 26 0.5500 829
Glass Partition 0 21 0.55 0
Partition glass-NAC 459 21 0.30 2892
Partition wall-NAC 0 10 0.35 0
Ceiling 0 10 0.45 0
Floor 176 10 0.45 792
INTERNAL HEAT GAIN
People 1.0 Nos X 230 230
Light 264.0 W X 1.25 3.412 1122
Eq. Load 264.0 WX 3.412 1981
ROOM SENSIBLE HEAT (RSH) 9202
Supply duct heat Supply duct Heat gain from 5 690
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 460
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
59 26 0.12 1.08 198
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 10550
LATENT HEAT
People 1 Nos X 120 120
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
59 99 0.12 0.68 474
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 594
EFFECTIVE ROOM TOTAL HEAT (ERTH) 11144
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
59 26 0.88 1.08 1450
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
59 99 0.88 0.68 3476
HEAT SUB TOTAL 16069
Return duct heat HP Pump + Dehum. & Pipe 5.0 803
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 1.41 TR
TONS 1.41 TOTAL HEAT 16873
MRI EQUIPMENT

GREEN AIR ROOM TYPE 1 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
Floor : FIRST Area : MRI EQUIPMENT System No. : 1
Floor Area 132 Sq Ft Ceiling Ht 10 Ft Volume = 1320 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 35 23 0.81 652 DIFFERENCE 28 XXXX XXXX XXXX 81.7
NE - Glass 12 0.81 0
E -GLASS 12 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 1 People X 0 CFM/Person 5.00
S - Glass 12 0.81 0 132 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 13
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.93
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 319
No. of Rows = 0
N - Wall 95 19 0.36 650 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 2
E - Wall 33 0.36 0 'Min. cfm reqd. = 44
SE - Wall 33 0.36 0
S - Wall 31 0.36 0
SW - Wall 29 0.36 0
W - Wall 27 0.36 0
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 1 persons
ITEM Area Temp. diff. U FRESH AIR 44
(Sq ft) (°F) (Btu/h.sq ft) Light 198 watt
All Glass 35 28 0.55 539 Equipment 198 watt
Glass Partition 23 0.55 0
Partition AC 23 0.3 0
Partition N/AC 23 0.35 0
Ceiling 23 0.45 0
Floor 132 23 0.45 1366
INTERNAL HEAT GAIN
People 1 Nos X 230 230
Light 198 W X 1.25 3.412 844
Eq. Load 198 W 3.412 676
ROOM SENSIBLE HEAT (RSH) 4957
Supply duct heat Supply duct Heat gain from 2 99
gain + leak. loss + fan HP(%)

Safety factor (%) 5.0 248


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
44 28 0.12 1.08 160
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 5464
LATENT HEAT
People 1 Nos X 120 120
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
44 81.7 0.12 0.68 293
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 413
Supply duct leakage loss + Safety factor % 5.0 21
EFFECTIVE ROOM LATENT HEAT (ERLH) 434
EFFECTIVE ROOM TOTAL HEAT (ERTH) 5898
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 44
44 28 0.88 1.08 1171 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 0.78
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 71.2 Monsoon TR= 0.72
44 81.7 0.88 0.68 2151 CFM / Sq ft = 2.42 Deh. CFM= 319
HEAT SUB TOTAL 9220 Sq ft / TR = 168 CFM(ACPH)= 15
Return duct heat HP Pump + Dehum. & Pipe 2.0 184
gain & leak. loss + loss (%) CFM/ TR = 408
Selected TR = 0.8
TONS 0.78 GRAND TOTAL HEAT 9404 Selected CFM= 350
MRI EQUIPMENT
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 72 65 55 65
N - Glass 35 11 0.81 312 DIFFERENCE 26 XXXX XXXX XXXX 99
NE - Glass 0 11 0.81 0
E - Glass 0 11 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 1 People X 0 CFM/Person 5
S - Glass 0 11 0.81 0 132 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 13
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.89
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 236
No. of Rows = 0
N - Wall 95 9 0.36 308 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 2.0
E - Wall 0 23 0.36 0 'Min. cfm reqd. = 44
SE - Wall 0 23 0.36 0
S - Wall 0 21 0.36 0
SW - Wall 0 19 0.36 0
W - Wall 0 17 0.36 0
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 35 26 0.5500 501
Glass Partition 0 21 0.55 0
Partition glass-NAC 0 21 0.30 0
Partition wall-NAC 0 10 0.35 0
Ceiling 0 10 0.45 0
Floor 132 10 0.45 594
INTERNAL HEAT GAIN
People 1.0 Nos X 230 230
Light 198.0 W X 1.25 3.412 842
Eq. Load 198.0 WX 3.412 676
ROOM SENSIBLE HEAT (RSH) 3461
Supply duct heat Supply duct Heat gain from 5 260
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 173
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
44 26 0.12 1.08 148
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 4042
LATENT HEAT
People 1 Nos X 120 120
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
44 99 0.12 0.68 355
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 475
EFFECTIVE ROOM TOTAL HEAT (ERTH) 4518
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
44 26 0.88 1.08 1087
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
44 99 0.88 0.68 2607
HEAT SUB TOTAL 8211
Return duct heat HP Pump + Dehum. & Pipe 5.0 411
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 0.72 TR
TONS 0.72 TOTAL HEAT 8622
MRI

GREEN AIR ROOM TYPE 1 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
Floor : FIRST Area : MRI System No. : 1
Floor Area 401 Sq Ft Ceiling Ht 10 Ft Volume = 4010 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 23 0.81 0 DIFFERENCE 28 XXXX XXXX XXXX 81.7
NE - Glass 12 0.81 0
E -GLASS 12 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 3 People X 0 CFM/Person 5.00
S - Glass 12 0.81 0 401 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 39
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.99
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 6417
No. of Rows = 0
N - Wall 271 19 0.36 1854 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 2
E - Wall 33 0.36 0 'Min. cfm reqd. = 134
SE - Wall 33 0.36 0
S - Wall 31 0.36 0
SW - Wall 29 0.36 0
W - Wall 54 27 0.36 525
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 3 persons
ITEM Area Temp. diff. U FRESH AIR 134
(Sq ft) (°F) (Btu/h.sq ft) Light 602 watt
All Glass 0 28 0.55 0 Equipment 602 watt
Glass Partition 23 0.55 0
Partition AC 23 0.3 0
Partition N/AC 23 0.35 0
Ceiling 23 0.45 0
Floor 401 23 0.45 4150
INTERNAL HEAT GAIN
People 3 Nos X 230 690
Light 602 W X 1.25 3.412 2565
Eq. Load 602 W 3.412 92352
ROOM SENSIBLE HEAT (RSH) 102136
Supply duct heat Supply duct Heat gain from 2 2043
gain + leak. loss + fan HP(%)

Safety factor (%) 5.0 5107


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
134 28 0.12 1.08 485
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 109771
LATENT HEAT
People 3 Nos X 120 360
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
134 81.7 0.12 0.68 891
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 1251
Supply duct leakage loss + Safety factor % 5.0 63
EFFECTIVE ROOM LATENT HEAT (ERLH) 1314
EFFECTIVE ROOM TOTAL HEAT (ERTH) 111085
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 134
134 28 0.88 1.08 3557 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 10.30
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 308.2 Monsoon TR= 10.85
134 81.7 0.88 0.68 6535 CFM / Sq ft = 16.00 Deh. CFM= 6511
HEAT SUB TOTAL 121176 Sq ft / TR = 39 CFM(ACPH)= 97
Return duct heat HP Pump + Dehum. & Pipe 2.0 2424
gain & leak. loss + loss (%) CFM/ TR = 623
Selected TR = 10.9
TONS 10.30 GRAND TOTAL HEAT 123600 Selected CFM= 6550
MRI
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 72 65 55 65
N - Glass 0 11 0.81 0 DIFFERENCE 26 XXXX XXXX XXXX 99
NE - Glass 0 11 0.81 0
E - Glass 0 11 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 3 People X 0 CFM/Person 5
S - Glass 0 11 0.81 0 401 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 39
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.99
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 6511
No. of Rows = 0
N - Wall 271 9 0.36 878 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 2.0
E - Wall 0 23 0.36 0 'Min. cfm reqd. = 134
SE - Wall 0 23 0.36 0
S - Wall 0 21 0.36 0
SW - Wall 0 19 0.36 0
W - Wall 54 17 0.36 330
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 0 26 0.5500 0
Glass Partition 0 21 0.55 0
Partition glass-NAC 0 21 0.30 0
Partition wall-NAC 0 10 0.35 0
Ceiling 0 10 0.45 0
Floor 401 10 0.45 1805
INTERNAL HEAT GAIN
People 3.0 Nos X 230 690
Light 601.5 W X 1.25 3.412 2556
Eq. Load 601.5 WX 3.412 92352
ROOM SENSIBLE HEAT (RSH) 98611
Supply duct heat Supply duct Heat gain from 5 7396
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 4931
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
134 26 0.12 1.08 450
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 111388
LATENT HEAT
People 3 Nos X 120 360
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
134 99 0.12 0.68 1080
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 1440
EFFECTIVE ROOM TOTAL HEAT (ERTH) 112828
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
134 26 0.88 1.08 3303
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
134 99 0.88 0.68 7919
HEAT SUB TOTAL 124050
Return duct heat HP Pump + Dehum. & Pipe 5.0 6202
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 10.85 TR
TONS 10.85 TOTAL HEAT 130252
MRI CONSOLE

GREEN AIR ROOM TYPE 1 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
Floor : FIRST Area : MRI System No. : 1
Floor Area 127 Sq Ft Ceiling Ht 10 Ft Volume = 1270 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 29 23 0.81 540 DIFFERENCE 28 XXXX XXXX XXXX 81.7
NE - Glass 12 0.81 0
E -GLASS 12 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 1 People X 0 CFM/Person 5.00
S - Glass 12 0.81 0 127 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 13
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.96
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 543
No. of Rows = 0
N - Wall 117 19 0.36 800 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 2
E - Wall 33 0.36 0 'Min. cfm reqd. = 42
SE - Wall 33 0.36 0
S - Wall 31 0.36 0
SW - Wall 29 0.36 0
W - Wall 27 0.36 0
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 1 persons
ITEM Area Temp. diff. U FRESH AIR 42
(Sq ft) (°F) (Btu/h.sq ft) Light 191 watt
All Glass 29 28 0.55 447 Equipment 191 watt
Glass Partition 23 0.55 0
Partition AC 23 0.3 0
Partition N/AC 174 23 0.35 1401
Ceiling 127 23 0.45 1314
Floor 127 23 0.45 1314
INTERNAL HEAT GAIN
People 1 Nos X 230 230
Light 191 W X 1.25 3.412 812
Eq. Load 191 W 3.412 1680
ROOM SENSIBLE HEAT (RSH) 8539
Supply duct heat Supply duct Heat gain from 2 171
gain + leak. loss + fan HP(%)

Safety factor (%) 5.0 427


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
42 28 0.12 1.08 154
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 9291
LATENT HEAT
People 1 Nos X 120 120
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
42 81.7 0.12 0.68 282
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 402
Supply duct leakage loss + Safety factor % 5.0 20
EFFECTIVE ROOM LATENT HEAT (ERLH) 422
EFFECTIVE ROOM TOTAL HEAT (ERTH) 9713
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 42
42 28 0.88 1.08 1127 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 1.10
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 103.7 Monsoon TR= 0.91
42 81.7 0.88 0.68 2070 CFM / Sq ft = 4.28 Deh. CFM= 543
HEAT SUB TOTAL 12909 Sq ft / TR = 116 CFM(ACPH)= 26
Return duct heat HP Pump + Dehum. & Pipe 2.0 258
gain & leak. loss + loss (%) CFM/ TR = 495
Selected TR = 1.1
TONS 1.10 GRAND TOTAL HEAT 13167 Selected CFM= 550
MRI CONSOLE
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 72 65 55 65
N - Glass 29 11 0.81 258 DIFFERENCE 26 XXXX XXXX XXXX 99
NE - Glass 0 11 0.81 0
E - Glass 0 11 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 1 People X 0 CFM/Person 5
S - Glass 0 11 0.81 0 127 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 13
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.93
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 372
No. of Rows = 0
N - Wall 117 9 0.36 379 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 2.0
E - Wall 0 23 0.36 0 'Min. cfm reqd. = 42
SE - Wall 0 23 0.36 0
S - Wall 0 21 0.36 0
SW - Wall 0 19 0.36 0
W - Wall 0 17 0.36 0
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 29 26 0.5500 415
Glass Partition 0 21 0.55 0
Partition glass-NAC 0 21 0.30 0
Partition wall-NAC 174 10 0.35 609
Ceiling 127 10 0.45 572
Floor 127 10 0.45 572
INTERNAL HEAT GAIN
People 1.0 Nos X 230 230
Light 190.5 W X 1.25 3.412 810
Eq. Load 190.5 WX 3.412 1680
ROOM SENSIBLE HEAT (RSH) 5524
Supply duct heat Supply duct Heat gain from 5 414
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 276
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
42 26 0.12 1.08 143
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 6357
LATENT HEAT
People 1 Nos X 120 120
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
42 99 0.12 0.68 342
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 462
EFFECTIVE ROOM TOTAL HEAT (ERTH) 6819
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
42 26 0.88 1.08 1046
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
42 99 0.88 0.68 2508
HEAT SUB TOTAL 10373
Return duct heat HP Pump + Dehum. & Pipe 5.0 519
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 0.91 TR
TONS 0.91 TOTAL HEAT 10892
EMRGNCY,ECS,21,DOC

GREEN AIR ROOM TYPE 1 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
EMERGENCY,EC
Floor : FIRST Area : System No. : 1
S,RM21,DOC RM
Floor Area 938 Sq Ft Ceiling Ht 10 Ft Volume = 9380 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 23 0.81 0 DIFFERENCE 28 XXXX XXXX XXXX 81.7
NE - Glass 12 0.81 0
E -GLASS 12 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 10 People X 0 CFM/Person 5.00
S - Glass 72 12 0.81 700 938 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 106
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.92
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 2276
No. of Rows = 0
N - Wall 19 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 2
E - Wall 33 0.36 0 'Min. cfm reqd. = 313
SE - Wall 33 0.36 0
S - Wall 300 31 0.36 3348
SW - Wall 29 0.36 0
W - Wall 213 27 0.36 2070
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 10 persons
ITEM Area Temp. diff. U FRESH AIR 313
(Sq ft) (°F) (Btu/h.sq ft) Light 1407 watt
All Glass 72 28 0.55 1109 Equipment 1407 watt
Glass Partition 23 0.55 0
Partition AC 172 23 0.3 1187
Partition N/AC 23 0.35 0
Ceiling 56 23 0.45 580
Floor 938 23 0.45 9708
INTERNAL HEAT GAIN
People 10 Nos X 230 2300
Light 1407 W X 1.25 3.412 6001
Eq. Load 1407 W 3.412 8320
ROOM SENSIBLE HEAT (RSH) 35323
Supply duct heat Supply duct Heat gain from 2 706
gain + leak. loss + fan HP(%)

Safety factor (%) 5.0 1766


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
313 28 0.12 1.08 1135
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 38930
LATENT HEAT
People 10 Nos X 120 1200
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
313 81.7 0.12 0.68 2084
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 3284
Supply duct leakage loss + Safety factor % 5.0 164
EFFECTIVE ROOM LATENT HEAT (ERLH) 3449
EFFECTIVE ROOM TOTAL HEAT (ERTH) 42378
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 313
313 28 0.88 1.08 8320 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 5.61
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 71.8 Monsoon TR= 5.41
313 81.7 0.88 0.68 15286 CFM / Sq ft = 2.43 Deh. CFM= 2276
HEAT SUB TOTAL 65985 Sq ft / TR = 167 CFM(ACPH)= 15
Return duct heat HP Pump + Dehum. & Pipe 2.0 1320
gain & leak. loss + loss (%) CFM/ TR = 406
Selected TR = 5.6
TONS 5.61 GRAND TOTAL HEAT 67305 Selected CFM= 2300
EMRGNCY,ECS,21,DOC
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 72 65 55 65
N - Glass 0 11 0.81 0 DIFFERENCE 26 XXXX XXXX XXXX 99
NE - Glass 0 11 0.81 0
E - Glass 0 11 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 10 People X 0 CFM/Person 5
S - Glass 72 11 0.81 642 938 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 106
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.90
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 1863
No. of Rows = 0
N - Wall 0 9 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 2.0
E - Wall 0 23 0.36 0 'Min. cfm reqd. = 313
SE - Wall 0 23 0.36 0
S - Wall 300 21 0.36 2268
SW - Wall 0 19 0.36 0
W - Wall 213 17 0.36 1304
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 72 26 0.5500 1030
Glass Partition 0 21 0.55 0
Partition glass-NAC 172 21 0.30 1084
Partition wall-NAC 0 10 0.35 0
Ceiling 56 10 0.45 252
Floor 938 10 0.45 4221
INTERNAL HEAT GAIN
People 10.0 Nos X 230 2300
Light 1407.0 W X 1.25 3.412 5980
Eq. Load 1407.0 WX 3.412 8320
ROOM SENSIBLE HEAT (RSH) 27399
Supply duct heat Supply duct Heat gain from 5 2055
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 1370
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
313 26 0.12 1.08 1054
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 31877
LATENT HEAT
People 10 Nos X 120 1200
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
313 99 0.12 0.68 2526
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 3726
EFFECTIVE ROOM TOTAL HEAT (ERTH) 35603
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
313 26 0.88 1.08 7726
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
313 99 0.88 0.68 18523
HEAT SUB TOTAL 61852
Return duct heat HP Pump + Dehum. & Pipe 5.0 3093
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 5.41 TR
TONS 5.41 TOTAL HEAT 64945
RECEPTION

GREEN AIR ROOM TYPE 1 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
RECEPTION,REG
Floor : FIRST Area : System No. : 1
ISTRATION
Floor Area 1073 Sq Ft Ceiling Ht 10 Ft Volume = 10730 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 23 0.81 0 DIFFERENCE 28 XXXX XXXX XXXX 81.7
NE - Glass 12 0.81 0
E -GLASS 30 12 0.81 292 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 41 People X 0 CFM/Person 7.00
S - Glass 210 12 0.81 2041 1073 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 351
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.86
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 2687
No. of Rows = 0
N - Wall 19 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 0
E - Wall 104 33 0.36 1236 'Min. cfm reqd. = 0
SE - Wall 33 0.36 0
S - Wall 31 0.36 0
SW - Wall 29 0.36 0
W - Wall 27 0.36 0
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 41 persons
ITEM Area Temp. diff. U FRESH AIR 351
(Sq ft) (°F) (Btu/h.sq ft) Light 1610 watt
All Glass 240 28 0.55 3696 Equipment 1610 watt
Glass Partition 124 23 0.55 1569
Partition AC 644 23 0.3 4444
Partition N/AC 23 0.35 0
Ceiling 23 0.45 0
Floor 648 23 0.45 6707
INTERNAL HEAT GAIN
People 41 Nos X 230 9430
Light 1610 W X 1.25 3.412 6865
Eq. Load 1610 W 3.412 5492
ROOM SENSIBLE HEAT (RSH) 41769
Supply duct heat Supply duct Heat gain from 2 835
gain + leak. loss + fan HP(%)

Safety factor (%) 5.0 2088


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
351 28 0.12 1.08 1275
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 45968
LATENT HEAT
People 41 Nos X 120 4920
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
351 81.7 0.12 0.68 2343
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 7263
Supply duct leakage loss + Safety factor % 5.0 363
EFFECTIVE ROOM LATENT HEAT (ERLH) 7626
EFFECTIVE ROOM TOTAL HEAT (ERTH) 53594
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 351
351 28 0.88 1.08 9351 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 6.81
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 76.2 Monsoon TR= 6.97
351 81.7 0.88 0.68 17179 CFM / Sq ft = 2.50 Deh. CFM= 2687
HEAT SUB TOTAL 80123 Sq ft / TR = 158 CFM(ACPH)= 15
Return duct heat HP Pump + Dehum. & Pipe 2.0 1602
gain & leak. loss + loss (%) CFM/ TR = 395
Selected TR = 7.0
TONS 6.81 GRAND TOTAL HEAT 81726 Selected CFM= 2700
RECEPTION
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 72 65 55 65
N - Glass 0 11 0.81 0 DIFFERENCE 26 XXXX XXXX XXXX 99
NE - Glass 0 11 0.81 0
E - Glass 30 11 0.81 267 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 41 People X 0 CFM/Person 7
S - Glass 210 11 0.81 1871 1073 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 351
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.85
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 2476
No. of Rows = 0
N - Wall 0 9 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 0.0
E - Wall 104 23 0.36 861 'Min. cfm reqd. = 0
SE - Wall 0 23 0.36 0
S - Wall 0 21 0.36 0
SW - Wall 0 19 0.36 0
W - Wall 0 17 0.36 0
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 240 26 0.5500 3432
Glass Partition 124 21 0.55 1432
Partition glass-NAC 644 21 0.30 4057
Partition wall-NAC 0 10 0.35 0
Ceiling 0 10 0.45 0
Floor 648 10 0.45 2916
INTERNAL HEAT GAIN
People 41.0 Nos X 230 9430
Light 1609.5 W X 1.25 3.412 6840
Eq. Load 1609.5 WX 3.412 5492
ROOM SENSIBLE HEAT (RSH) 36599
Supply duct heat Supply duct Heat gain from 5 2745
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 1830
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
351 26 0.12 1.08 1184
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 42358
LATENT HEAT
People 41 Nos X 120 4920
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
351 99 0.12 0.68 2839
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 7759
EFFECTIVE ROOM TOTAL HEAT (ERTH) 50116
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
351 26 0.88 1.08 8683
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
351 99 0.88 0.68 20816
HEAT SUB TOTAL 79615
Return duct heat HP Pump + Dehum. & Pipe 5.0 3981
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 6.97 TR
TONS 6.97 TOTAL HEAT 83596
BACK OFFICE

GREEN AIR ROOM TYPE 1 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
Floor : FIRST Area : BACK OFFICE System No. : 1
Floor Area 155 Sq Ft Ceiling Ht 10 Ft Volume = 1550 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 29 23 0.81 540 DIFFERENCE 28 XXXX XXXX XXXX 81.7
NE - Glass 12 0.81 0
E -GLASS 29 12 0.81 282 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 5 People X 0 CFM/Person 7.00
S - Glass 12 0.81 0 155 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 44
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.91
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 553
No. of Rows = 0
N - Wall 87 19 0.36 595 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 2
E - Wall 153 33 0.36 1818 'Min. cfm reqd. = 52
SE - Wall 33 0.36 0
S - Wall 31 0.36 0
SW - Wall 29 0.36 0
W - Wall 27 0.36 0
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 5 persons
ITEM Area Temp. diff. U FRESH AIR 52
(Sq ft) (°F) (Btu/h.sq ft) Light 233 watt
All Glass 58 28 0.55 893 Equipment 233 watt
Glass Partition 23 0.55 0
Partition AC 23 0.3 0
Partition N/AC 23 0.35 0
Ceiling 23 0.45 0
Floor 155 23 0.45 1604
INTERNAL HEAT GAIN
People 5 Nos X 230 1150
Light 233 W X 1.25 3.412 992
Eq. Load 233 W 3.412 793
ROOM SENSIBLE HEAT (RSH) 8667
Supply duct heat Supply duct Heat gain from 2 173
gain + leak. loss + fan HP(%)

Safety factor (%) 5.0 433


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
52 28 0.12 1.08 187
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 9461
LATENT HEAT
People 5 Nos X 120 600
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
52 81.7 0.12 0.68 344
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 944
Supply duct leakage loss + Safety factor % 5.0 47
EFFECTIVE ROOM LATENT HEAT (ERLH) 992
EFFECTIVE ROOM TOTAL HEAT (ERTH) 10453
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 52
52 28 0.88 1.08 1375 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 1.22
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 94.5 Monsoon TR= 1.13
52 81.7 0.88 0.68 2526 CFM / Sq ft = 3.57 Deh. CFM= 553
HEAT SUB TOTAL 14354 Sq ft / TR = 127 CFM(ACPH)= 21
Return duct heat HP Pump + Dehum. & Pipe 2.0 287
gain & leak. loss + loss (%) CFM/ TR = 453
Selected TR = 1.2
TONS 1.22 GRAND TOTAL HEAT 14641 Selected CFM= 600
BACK OFFICE
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 72 65 55 65
N - Glass 29 11 0.81 258 DIFFERENCE 26 XXXX XXXX XXXX 99
NE - Glass 0 11 0.81 0
E - Glass 29 11 0.81 258 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 5 People X 0 CFM/Person 7
S - Glass 0 11 0.81 0 155 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 44
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.88
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 439
No. of Rows = 0
N - Wall 87 9 0.36 282 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 2.0
E - Wall 153 23 0.36 1267 'Min. cfm reqd. = 52
SE - Wall 0 23 0.36 0
S - Wall 0 21 0.36 0
SW - Wall 0 19 0.36 0
W - Wall 0 17 0.36 0
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 58 26 0.5500 829
Glass Partition 0 21 0.55 0
Partition glass-NAC 0 21 0.30 0
Partition wall-NAC 0 10 0.35 0
Ceiling 0 10 0.45 0
Floor 155 10 0.45 698
INTERNAL HEAT GAIN
People 5.0 Nos X 230 1150
Light 232.5 W X 1.25 3.412 988
Eq. Load 232.5 WX 3.412 793
ROOM SENSIBLE HEAT (RSH) 6524
Supply duct heat Supply duct Heat gain from 5 489
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 326
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
52 26 0.12 1.08 174
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 7513
LATENT HEAT
People 5 Nos X 120 600
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
52 99 0.12 0.68 417
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 1017
EFFECTIVE ROOM TOTAL HEAT (ERTH) 8531
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
52 26 0.88 1.08 1277
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
52 99 0.88 0.68 3061
HEAT SUB TOTAL 12868
Return duct heat HP Pump + Dehum. & Pipe 5.0 643
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 1.13 TR
TONS 1.13 TOTAL HEAT 13512
CORRIDOR

GREEN AIR ROOM TYPE 3 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
Floor : FIRST Area : CORRIDOR System No. : 1
Floor Area 1562 Sq Ft Ceiling Ht 10 Ft Volume = 15620 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 76 65 55 74
N - Glass 23 0.81 0 DIFFERENCE 24 XXXX XXXX XXXX 72.7
NE - Glass 12 0.81 0
E -GLASS 12 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 21 People X 0 CFM/Person 7.00
S - Glass 60 12 0.81 583 1562 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 241
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.92
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 19.36 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 3326
No. of Rows = 0
N - Wall 19 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 2
E - Wall 33 0.36 0 'Min. cfm reqd. = 521
SE - Wall 33 0.36 0
S - Wall 440 31 0.36 4910
SW - Wall 29 0.36 0
W - Wall 27 0.36 0
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 21 persons
ITEM Area Temp. diff. U FRESH AIR 521
(Sq ft) (°F) (Btu/h.sq ft) Light 2343 watt
All Glass 60 24 1 1440 Equipment 2343 watt
Glass Partition 175 19 1.13 3757
Partition AC 19 0.3 0
Partition N/AC 3673 19 0.35 24425
Ceiling 19 0.42 0
Floor 495 19 0.59 5549
INTERNAL HEAT GAIN
People 21 Nos X 230 4830
Light 2343 W X 1.25 3.412 9993
Eq. Load 2343 W 3.412 7994
ROOM SENSIBLE HEAT (RSH) 63482
Supply duct heat Supply duct Heat gain from 2 1270
gain + leak. loss + fan HP(%)

Safety factor (%) 5.0 3174


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
521 24 0.12 1.08 1619
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 69546
LATENT HEAT
People 21 Nos X 120 2520
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
521 72.7 0.12 0.68 3089
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 5609
Supply duct leakage loss + Safety factor % 5.0 280
EFFECTIVE ROOM LATENT HEAT (ERLH) 5889
EFFECTIVE ROOM TOTAL HEAT (ERTH) 75435
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 521
521 24 0.88 1.08 11876 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 9.35
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 71.8 Monsoon TR= 8.73
521 72.7 0.88 0.68 22651 CFM / Sq ft = 2.13 Deh. CFM= 3326
HEAT SUB TOTAL 109962 Sq ft / TR = 167 CFM(ACPH)= 13
Return duct heat HP Pump + Dehum. & Pipe 2.0 2199
gain & leak. loss + loss (%) CFM/ TR = 356
Selected TR = 9.3
TONS 9.35 GRAND TOTAL HEAT 112161 Selected CFM= 3350
CORRIDOR
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 76 65 55 74
N - Glass 0 11 0.81 0 DIFFERENCE 22 XXXX XXXX XXXX 90
NE - Glass 0 11 0.81 0
E - Glass 0 11 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 21 People X 0 CFM/Person 7
S - Glass 60 11 0.81 535 1562 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 241
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.90
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 19.36 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 2605
No. of Rows = 0
N - Wall 0 9 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 2.0
E - Wall 0 23 0.36 0 'Min. cfm reqd. = 521
SE - Wall 0 23 0.36 0
S - Wall 440 21 0.36 3326
SW - Wall 0 19 0.36 0
W - Wall 0 17 0.36 0
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 60 22 1.0000 1320
Glass Partition 175 17 1.13 3362
Partition glass-NAC 0 17 0.30 0
Partition wall-NAC 3673 10 0.35 12856
Ceiling 0 10 0.42 0
Floor 495 10 0.59 2921
INTERNAL HEAT GAIN
People 21.0 Nos X 230 4830
Light 2343.0 W X 1.25 3.412 9958
Eq. Load 2343.0 WX 3.412 7994
ROOM SENSIBLE HEAT (RSH) 47101
Supply duct heat Supply duct Heat gain from 5 3533
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 2355
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
521 22 0.12 1.08 1485
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 54473
LATENT HEAT
People 21 Nos X 120 2520
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
521 90 0.12 0.68 3824
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 6344
EFFECTIVE ROOM TOTAL HEAT (ERTH) 60817
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
521 22 0.88 1.08 10887
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
521 90 0.88 0.68 28041
HEAT SUB TOTAL 99744
Return duct heat HP Pump + Dehum. & Pipe 5.0 4987
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 8.73 TR
TONS 8.73 TOTAL HEAT 104731
REPORT WRITING

GREEN AIR ROOM TYPE 1 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
REPORT
Floor : FIRST Area : System No. : 1
WRITING
Floor Area 57 Sq Ft Ceiling Ht 10 Ft Volume = 570 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 23 0.81 0 DIFFERENCE 28 XXXX XXXX XXXX 81.7
NE - Glass 12 0.81 0
E -GLASS 12 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 2 People X 0 CFM/Person 7.00
S - Glass 6 12 0.81 58 57 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 17
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.91
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 226
No. of Rows = 0
N - Wall 19 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 2
E - Wall 33 0.36 0 'Min. cfm reqd. = 19
SE - Wall 33 0.36 0
S - Wall 65 31 0.36 725
SW - Wall 29 0.36 0
W - Wall 27 0.36 0
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 2 persons
ITEM Area Temp. diff. U FRESH AIR 19
(Sq ft) (°F) (Btu/h.sq ft) Light 86 watt
All Glass 6 28 0.55 92 Equipment 86 watt
Glass Partition 23 0.55 0
Partition AC 23 0.3 0
Partition N/AC 121 23 0.35 974
Ceiling 23 0.45 0
Floor 57 23 0.45 590
INTERNAL HEAT GAIN
People 2 Nos X 230 460
Light 86 W X 1.25 3.412 365
Eq. Load 86 W 3.412 292
ROOM SENSIBLE HEAT (RSH) 3557
Supply duct heat Supply duct Heat gain from 2 71
gain + leak. loss + fan HP(%)

Safety factor (%) 5.0 178


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
19 28 0.12 1.08 69
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 3874
LATENT HEAT
People 2 Nos X 120 240
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
19 81.7 0.12 0.68 127
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 367
Supply duct leakage loss + Safety factor % 5.0 18
EFFECTIVE ROOM LATENT HEAT (ERLH) 385
EFFECTIVE ROOM TOTAL HEAT (ERTH) 4259
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 19
19 28 0.88 1.08 506 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 0.48
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 101.9 Monsoon TR= 0.42
19 81.7 0.88 0.68 929 CFM / Sq ft = 3.97 Deh. CFM= 226
HEAT SUB TOTAL 5694 Sq ft / TR = 118 CFM(ACPH)= 24
Return duct heat HP Pump + Dehum. & Pipe 2.0 114
gain & leak. loss + loss (%) CFM/ TR = 468
Selected TR = 0.5
TONS 0.48 GRAND TOTAL HEAT 5808 Selected CFM= 250
REPORT WRITING
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 72 65 55 65
N - Glass 0 11 0.81 0 DIFFERENCE 26 XXXX XXXX XXXX 99
NE - Glass 0 11 0.81 0
E - Glass 0 11 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 2 People X 0 CFM/Person 7
S - Glass 6 11 0.81 53 57 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 17
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.88
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 163
No. of Rows = 0
N - Wall 0 9 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 2.0
E - Wall 0 23 0.36 0 'Min. cfm reqd. = 19
SE - Wall 0 23 0.36 0
S - Wall 65 21 0.36 491
SW - Wall 0 19 0.36 0
W - Wall 0 17 0.36 0
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 6 26 0.5500 86
Glass Partition 0 21 0.55 0
Partition glass-NAC 0 21 0.30 0
Partition wall-NAC 121 10 0.35 424
Ceiling 0 10 0.45 0
Floor 57 10 0.45 257
INTERNAL HEAT GAIN
People 2.0 Nos X 230 460
Light 85.5 W X 1.25 3.412 363
Eq. Load 85.5 WX 3.412 292
ROOM SENSIBLE HEAT (RSH) 2426
Supply duct heat Supply duct Heat gain from 5 182
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 121
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
19 26 0.12 1.08 64
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 2793
LATENT HEAT
People 2 Nos X 120 240
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
19 99 0.12 0.68 153
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 393
EFFECTIVE ROOM TOTAL HEAT (ERTH) 3186
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
19 26 0.88 1.08 469
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
19 99 0.88 0.68 1126
HEAT SUB TOTAL 4782
Return duct heat HP Pump + Dehum. & Pipe 5.0 239
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 0.42 TR
TONS 0.42 TOTAL HEAT 5021
RADIOLOGIST

GREEN AIR ROOM TYPE 1 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
RADIOLOGIST
Floor : FIRST Area : System No. : 1
ROOM
Floor Area 83 Sq Ft Ceiling Ht 10 Ft Volume = 830 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 23 0.81 0 DIFFERENCE 28 XXXX XXXX XXXX 81.7
NE - Glass 12 0.81 0
E -GLASS 12 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 3 People X 0 CFM/Person 7.00
S - Glass 29 12 0.81 282 83 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 26
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.94
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 570
No. of Rows = 0
N - Wall 19 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 2
E - Wall 33 0.36 0 'Min. cfm reqd. = 28
SE - Wall 33 0.36 0
S - Wall 68 31 0.36 759
SW - Wall 29 0.36 0
W - Wall 27 0.36 0
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 3 persons
ITEM Area Temp. diff. U FRESH AIR 28
(Sq ft) (°F) (Btu/h.sq ft) Light 125 watt
All Glass 29 28 0.55 447 Equipment 125 watt
Glass Partition 23 0.55 0
Partition AC 23 0.3 0
Partition N/AC 66 23 0.35 531
Ceiling 23 0.45 0
Floor 83 23 0.45 859
INTERNAL HEAT GAIN
People 3 Nos X 230 690
Light 125 W X 1.25 3.412 531
Eq. Load 125 W 3.412 4925
ROOM SENSIBLE HEAT (RSH) 9024
Supply duct heat Supply duct Heat gain from 2 180
gain + leak. loss + fan HP(%)

Safety factor (%) 5.0 451


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
28 28 0.12 1.08 100
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 9756
LATENT HEAT
People 3 Nos X 120 360
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
28 81.7 0.12 0.68 184
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 544
Supply duct leakage loss + Safety factor % 5.0 27
EFFECTIVE ROOM LATENT HEAT (ERLH) 572
EFFECTIVE ROOM TOTAL HEAT (ERTH) 10327
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 28
28 28 0.88 1.08 736 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 1.06
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 152.6 Monsoon TR= 1.04
28 81.7 0.88 0.68 1353 CFM / Sq ft = 6.87 Deh. CFM= 570
HEAT SUB TOTAL 12416 Sq ft / TR = 79 CFM(ACPH)= 41
Return duct heat HP Pump + Dehum. & Pipe 2.0 248
gain & leak. loss + loss (%) CFM/ TR = 540
Selected TR = 1.1
TONS 1.06 GRAND TOTAL HEAT 12665 Selected CFM= 600
RADIOLOGIST
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 72 65 55 65
N - Glass 0 11 0.81 0 DIFFERENCE 26 XXXX XXXX XXXX 99
NE - Glass 0 11 0.81 0
E - Glass 0 11 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 3 People X 0 CFM/Person 7
S - Glass 29 11 0.81 258 83 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 26
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.94
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 527
No. of Rows = 0
N - Wall 0 9 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 2.0
E - Wall 0 23 0.36 0 'Min. cfm reqd. = 28
SE - Wall 0 23 0.36 0
S - Wall 68 21 0.36 514
SW - Wall 0 19 0.36 0
W - Wall 0 17 0.36 0
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 29 26 0.5500 415
Glass Partition 0 21 0.55 0
Partition glass-NAC 0 21 0.30 0
Partition wall-NAC 66 10 0.35 231
Ceiling 0 10 0.45 0
Floor 83 10 0.45 374
INTERNAL HEAT GAIN
People 3.0 Nos X 230 690
Light 124.5 W X 1.25 3.412 529
Eq. Load 124.5 WX 3.412 4925
ROOM SENSIBLE HEAT (RSH) 7936
Supply duct heat Supply duct Heat gain from 5 595
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 397
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
28 26 0.12 1.08 93
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 9021
LATENT HEAT
People 3 Nos X 120 360
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
28 99 0.12 0.68 224
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 584
EFFECTIVE ROOM TOTAL HEAT (ERTH) 9604
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
28 26 0.88 1.08 684
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
28 99 0.88 0.68 1639
HEAT SUB TOTAL 11927
Return duct heat HP Pump + Dehum. & Pipe 5.0 596
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 1.04 TR
TONS 1.04 TOTAL HEAT 12524
MAMMOGRAPHY

GREEN AIR ROOM TYPE 1 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
Floor : FIRST Area : MAMMOGRAPHY System No. : 1
Floor Area 109 Sq Ft Ceiling Ht 10 Ft Volume = 1090 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 23 0.81 0 DIFFERENCE 28 XXXX XXXX XXXX 81.7
NE - Glass 12 0.81 0
E -GLASS 12 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 2 People X 0 CFM/Person 7.00
S - Glass 12 0.81 0 109 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 21
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.92
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 541
No. of Rows = 0
N - Wall 19 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 4
E - Wall 33 0.36 0 'Min. cfm reqd. = 73
SE - Wall 33 0.36 0
S - Wall 31 0.36 0
SW - Wall 29 0.36 0
W - Wall 27 0.36 0
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 2 persons
ITEM Area Temp. diff. U FRESH AIR 73
(Sq ft) (°F) (Btu/h.sq ft) Light 164 watt
All Glass 0 28 0.55 0 Equipment 164 watt
Glass Partition 23 0.55 0
Partition AC 23 0.3 0
Partition N/AC 23 0.35 0
Ceiling 23 0.45 0
Floor 67 23 0.45 693
INTERNAL HEAT GAIN
People 2 Nos X 230 460
Light 164 W X 1.25 3.412 697
Eq. Load 164 W 3.412 6553
ROOM SENSIBLE HEAT (RSH) 8404
Supply duct heat Supply duct Heat gain from 2 168
gain + leak. loss + fan HP(%)

Safety factor (%) 5.0 420


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
73 28 0.12 1.08 264
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 9256
LATENT HEAT
People 2 Nos X 120 240
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
73 81.7 0.12 0.68 484
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 724
Supply duct leakage loss + Safety factor % 5.0 36
EFFECTIVE ROOM LATENT HEAT (ERLH) 761
EFFECTIVE ROOM TOTAL HEAT (ERTH) 10016
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 73
73 28 0.88 1.08 1934 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 1.32
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 145.1 Monsoon TR= 1.42
73 81.7 0.88 0.68 3553 CFM / Sq ft = 4.96 Deh. CFM= 541
HEAT SUB TOTAL 15503 Sq ft / TR = 83 CFM(ACPH)= 30
Return duct heat HP Pump + Dehum. & Pipe 2.0 310
gain & leak. loss + loss (%) CFM/ TR = 411
Selected TR = 1.4
TONS 1.32 GRAND TOTAL HEAT 15813 Selected CFM= 550
MAMMOGRAPHY
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 72 65 55 65
N - Glass 0 11 0.81 0 DIFFERENCE 26 XXXX XXXX XXXX 99
NE - Glass 0 11 0.81 0
E - Glass 0 11 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 2 People X 0 CFM/Person 7
S - Glass 0 11 0.81 0 109 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 21
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.92
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 541
No. of Rows = 0
N - Wall 0 9 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 4.0
E - Wall 0 23 0.36 0 'Min. cfm reqd. = 73
SE - Wall 0 23 0.36 0
S - Wall 0 21 0.36 0
SW - Wall 0 19 0.36 0
W - Wall 0 17 0.36 0
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 0 26 0.5500 0
Glass Partition 0 21 0.55 0
Partition glass-NAC 0 21 0.30 0
Partition wall-NAC 0 10 0.35 0
Ceiling 0 10 0.45 0
Floor 67 10 0.45 302
INTERNAL HEAT GAIN
People 2.0 Nos X 230 460
Light 163.5 W X 1.25 3.412 695
Eq. Load 163.5 WX 3.412 6553
ROOM SENSIBLE HEAT (RSH) 8009
Supply duct heat Supply duct Heat gain from 5 601
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 400
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
73 26 0.12 1.08 245
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 9255
LATENT HEAT
People 2 Nos X 120 240
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
73 99 0.12 0.68 587
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 827
EFFECTIVE ROOM TOTAL HEAT (ERTH) 10082
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
73 26 0.88 1.08 1796
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
73 99 0.88 0.68 4305
HEAT SUB TOTAL 16183
Return duct heat HP Pump + Dehum. & Pipe 5.0 809
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 1.42 TR
TONS 1.42 TOTAL HEAT 16992
BMD

GREEN AIR ROOM TYPE 1 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
Floor : FIRST Area : BMD System No. : 1
Floor Area 107 Sq Ft Ceiling Ht 10 Ft Volume = 1070 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 23 0.81 0 DIFFERENCE 28 XXXX XXXX XXXX 81.7
NE - Glass 12 0.81 0
E -GLASS 12 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 2 People X 0 CFM/Person 7.00
S - Glass 12 0.81 0 107 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 20
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.93
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 566
No. of Rows = 0
N - Wall 19 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 4
E - Wall 33 0.36 0 'Min. cfm reqd. = 71
SE - Wall 33 0.36 0
S - Wall 31 0.36 0
SW - Wall 29 0.36 0
W - Wall 27 0.36 0
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 2 persons
ITEM Area Temp. diff. U FRESH AIR 71
(Sq ft) (°F) (Btu/h.sq ft) Light 161 watt
All Glass 0 28 0.55 0 Equipment 161 watt
Glass Partition 23 0.55 0
Partition AC 23 0.3 0
Partition N/AC 23 0.35 0
Ceiling 23 0.45 0
Floor 107 23 0.45 1107
INTERNAL HEAT GAIN
People 2 Nos X 230 460
Light 161 W X 1.25 3.412 685
Eq. Load 161 W 3.412 6549
ROOM SENSIBLE HEAT (RSH) 8801
Supply duct heat Supply duct Heat gain from 2 176
gain + leak. loss + fan HP(%)

Safety factor (%) 5.0 440


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
71 28 0.12 1.08 259
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 9676
LATENT HEAT
People 2 Nos X 120 240
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
71 81.7 0.12 0.68 476
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 716
Supply duct leakage loss + Safety factor % 5.0 36
EFFECTIVE ROOM LATENT HEAT (ERLH) 751
EFFECTIVE ROOM TOTAL HEAT (ERTH) 10427
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 71
71 28 0.88 1.08 1898 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 1.34
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 150.7 Monsoon TR= 1.42
71 81.7 0.88 0.68 3487 CFM / Sq ft = 5.29 Deh. CFM= 566
HEAT SUB TOTAL 15813 Sq ft / TR = 80 CFM(ACPH)= 32
Return duct heat HP Pump + Dehum. & Pipe 2.0 316
gain & leak. loss + loss (%) CFM/ TR = 421
Selected TR = 1.4
TONS 1.34 GRAND TOTAL HEAT 16129 Selected CFM= 600
BMD
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 72 65 55 65
N - Glass 0 11 0.81 0 DIFFERENCE 26 XXXX XXXX XXXX 99
NE - Glass 0 11 0.81 0
E - Glass 0 11 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 2 People X 0 CFM/Person 7
S - Glass 0 11 0.81 0 107 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 20
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.92
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 551
No. of Rows = 0
N - Wall 0 9 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 4.0
E - Wall 0 23 0.36 0 'Min. cfm reqd. = 71
SE - Wall 0 23 0.36 0
S - Wall 0 21 0.36 0
SW - Wall 0 19 0.36 0
W - Wall 0 17 0.36 0
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 0 26 0.5500 0
Glass Partition 0 21 0.55 0
Partition glass-NAC 0 21 0.30 0
Partition wall-NAC 0 10 0.35 0
Ceiling 0 10 0.45 0
Floor 107 10 0.45 482
INTERNAL HEAT GAIN
People 2.0 Nos X 230 460
Light 160.5 W X 1.25 3.412 682
Eq. Load 160.5 WX 3.412 6549
ROOM SENSIBLE HEAT (RSH) 8173
Supply duct heat Supply duct Heat gain from 5 613
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 409
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
71 26 0.12 1.08 240
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 9435
LATENT HEAT
People 2 Nos X 120 240
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
71 99 0.12 0.68 576
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 816
EFFECTIVE ROOM TOTAL HEAT (ERTH) 10251
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
71 26 0.88 1.08 1763
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
71 99 0.88 0.68 4226
HEAT SUB TOTAL 16239
Return duct heat HP Pump + Dehum. & Pipe 5.0 812
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 1.42 TR
TONS 1.42 TOTAL HEAT 17051
USG

GREEN AIR ROOM TYPE 1 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
Floor : FIRST Area : USG System No. : 1
Floor Area 112 Sq Ft Ceiling Ht 10 Ft Volume = 1120 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 29 23 0.81 540 DIFFERENCE 28 XXXX XXXX XXXX 81.7
NE - Glass 12 0.81 0
E -GLASS 12 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 2 People X 0 CFM/Person 7.00
S - Glass 12 0.81 0 112 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 21
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.95
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 864
No. of Rows = 0
N - Wall 103 19 0.36 705 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 4
E - Wall 33 0.36 0 'Min. cfm reqd. = 75
SE - Wall 33 0.36 0
S - Wall 31 0.36 0
SW - Wall 29 0.36 0
W - Wall 27 0.36 0
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 2 persons
ITEM Area Temp. diff. U FRESH AIR 75
(Sq ft) (°F) (Btu/h.sq ft) Light 168 watt
All Glass 29 28 0.55 447 Equipment 168 watt
Glass Partition 23 0.55 0
Partition AC 23 0.3 0
Partition N/AC 120 23 0.35 966
Ceiling 23 0.45 0
Floor 112 23 0.45 1159
INTERNAL HEAT GAIN
People 2 Nos X 230 460
Light 168 W X 1.25 3.412 717
Eq. Load 168 W 3.412 8573
ROOM SENSIBLE HEAT (RSH) 13566
Supply duct heat Supply duct Heat gain from 2 271
gain + leak. loss + fan HP(%)

Safety factor (%) 5.0 678


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
75 28 0.12 1.08 271
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 14787
LATENT HEAT
People 2 Nos X 120 240
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
75 81.7 0.12 0.68 498
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 738
Supply duct leakage loss + Safety factor % 5.0 37
EFFECTIVE ROOM LATENT HEAT (ERLH) 775
EFFECTIVE ROOM TOTAL HEAT (ERTH) 15561
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 75
75 28 0.88 1.08 1987 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 1.80
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 193.1 Monsoon TR= 1.79
75 81.7 0.88 0.68 3650 CFM / Sq ft = 7.72 Deh. CFM= 864
HEAT SUB TOTAL 21199 Sq ft / TR = 62 CFM(ACPH)= 46
Return duct heat HP Pump + Dehum. & Pipe 2.0 424
gain & leak. loss + loss (%) CFM/ TR = 480
Selected TR = 1.8
TONS 1.80 GRAND TOTAL HEAT 21623 Selected CFM= 900
USG
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 72 65 55 65
N - Glass 29 11 0.81 258 DIFFERENCE 26 XXXX XXXX XXXX 99
NE - Glass 0 11 0.81 0
E - Glass 0 11 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 2 People X 0 CFM/Person 7
S - Glass 0 11 0.81 0 112 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 21
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.94
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 783
No. of Rows = 0
N - Wall 103 9 0.36 334 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 4.0
E - Wall 0 23 0.36 0 'Min. cfm reqd. = 75
SE - Wall 0 23 0.36 0
S - Wall 0 21 0.36 0
SW - Wall 0 19 0.36 0
W - Wall 0 17 0.36 0
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 29 26 0.5500 415
Glass Partition 0 21 0.55 0
Partition glass-NAC 0 21 0.30 0
Partition wall-NAC 120 10 0.35 420
Ceiling 0 10 0.45 0
Floor 112 10 0.45 504
INTERNAL HEAT GAIN
People 2.0 Nos X 230 460
Light 168.0 W X 1.25 3.412 714
Eq. Load 168.0 WX 3.412 8573
ROOM SENSIBLE HEAT (RSH) 11678
Supply duct heat Supply duct Heat gain from 5 876
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 584
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
75 26 0.12 1.08 252
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 13389
LATENT HEAT
People 2 Nos X 120 240
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
75 99 0.12 0.68 603
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 843
EFFECTIVE ROOM TOTAL HEAT (ERTH) 14232
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
75 26 0.88 1.08 1845
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
75 99 0.88 0.68 4423
HEAT SUB TOTAL 20501
Return duct heat HP Pump + Dehum. & Pipe 5.0 1025
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 1.79 TR
TONS 1.79 TOTAL HEAT 21526
CR & REPORTING ROOM

GREEN AIR ROOM TYPE 1 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
CR &
Floor : FIRST Area : REPORTING System No. : 1
ROOM
Floor Area 80 Sq Ft Ceiling Ht 10 Ft Volume = 800 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 29 23 0.81 540 DIFFERENCE 28 XXXX XXXX XXXX 81.7
NE - Glass 12 0.81 0
E -GLASS 12 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 2 People X 0 CFM/Person 7.00
S - Glass 12 0.81 0 80 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 19
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.95
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 457
No. of Rows = 0
N - Wall 64 19 0.36 438 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 2
E - Wall 33 0.36 0 'Min. cfm reqd. = 27
SE - Wall 33 0.36 0
S - Wall 31 0.36 0
SW - Wall 29 0.36 0
W - Wall 27 0.36 0
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 2 persons
ITEM Area Temp. diff. U FRESH AIR 27
(Sq ft) (°F) (Btu/h.sq ft) Light 120 watt
All Glass 29 28 0.55 447 Equipment 120 watt
Glass Partition 23 0.55 0
Partition AC 23 0.3 0
Partition N/AC 23 0.35 0
Ceiling 23 0.45 0
Floor 80 23 0.45 828
INTERNAL HEAT GAIN
People 2 Nos X 230 460
Light 120 W X 1.25 3.412 512
Eq. Load 120 W 3.412 3989
ROOM SENSIBLE HEAT (RSH) 7213
Supply duct heat Supply duct Heat gain from 2 144
gain + leak. loss + fan HP(%)

Safety factor (%) 5.0 361


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
27 28 0.12 1.08 97
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 7815
LATENT HEAT
People 2 Nos X 120 240
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
27 81.7 0.12 0.68 178
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 418
Supply duct leakage loss + Safety factor % 5.0 21
EFFECTIVE ROOM LATENT HEAT (ERLH) 439
EFFECTIVE ROOM TOTAL HEAT (ERTH) 8254
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 27
27 28 0.88 1.08 710 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 0.87
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 130.9 Monsoon TR= 0.85
27 81.7 0.88 0.68 1304 CFM / Sq ft = 5.71 Deh. CFM= 457
HEAT SUB TOTAL 10267 Sq ft / TR = 92 CFM(ACPH)= 34
Return duct heat HP Pump + Dehum. & Pipe 2.0 205
gain & leak. loss + loss (%) CFM/ TR = 523
Selected TR = 0.9
TONS 0.87 GRAND TOTAL HEAT 10472 Selected CFM= 500
CR & REPORTING ROOM
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 72 65 55 65
N - Glass 29 11 0.81 258 DIFFERENCE 26 XXXX XXXX XXXX 99
NE - Glass 0 11 0.81 0
E - Glass 0 11 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 2 People X 0 CFM/Person 7
S - Glass 0 11 0.81 0 80 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 19
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.94
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 413
No. of Rows = 0
N - Wall 64 9 0.36 207 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 2.0
E - Wall 0 23 0.36 0 'Min. cfm reqd. = 27
SE - Wall 0 23 0.36 0
S - Wall 0 21 0.36 0
SW - Wall 0 19 0.36 0
W - Wall 0 17 0.36 0
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 29 26 0.5500 415
Glass Partition 0 21 0.55 0
Partition glass-NAC 0 21 0.30 0
Partition wall-NAC 0 10 0.35 0
Ceiling 0 10 0.45 0
Floor 80 10 0.45 360
INTERNAL HEAT GAIN
People 2.0 Nos X 230 460
Light 120.0 W X 1.25 3.412 510
Eq. Load 120.0 WX 3.412 3989
ROOM SENSIBLE HEAT (RSH) 6199
Supply duct heat Supply duct Heat gain from 5 465
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 310
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
27 26 0.12 1.08 90
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 7064
LATENT HEAT
People 2 Nos X 120 240
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
27 99 0.12 0.68 215
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 455
EFFECTIVE ROOM TOTAL HEAT (ERTH) 7520
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
27 26 0.88 1.08 659
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
27 99 0.88 0.68 1580
HEAT SUB TOTAL 9758
Return duct heat HP Pump + Dehum. & Pipe 5.0 488
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 0.85 TR
TONS 0.85 TOTAL HEAT 10246
XRAY

GREEN AIR ROOM TYPE 1 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
Floor : FIRST Area : XRAY System No. : 1
Floor Area 202 Sq Ft Ceiling Ht 10 Ft Volume = 2020 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 29 23 0.81 540 DIFFERENCE 28 XXXX XXXX XXXX 81.7
NE - Glass 12 0.81 0
E -GLASS 12 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 2 People X 0 CFM/Person 7.00
S - Glass 12 0.81 0 202 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 26
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.99
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 2937
No. of Rows = 0
N - Wall 126 19 0.36 862 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 2
E - Wall 33 0.36 0 'Min. cfm reqd. = 67
SE - Wall 33 0.36 0
S - Wall 31 0.36 0
SW - Wall 29 0.36 0
W - Wall 27 0.36 0
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 2 persons
ITEM Area Temp. diff. U FRESH AIR 67
(Sq ft) (°F) (Btu/h.sq ft) Light 303 watt
All Glass 29 28 0.55 447 Equipment 303 watt
Glass Partition 23 0.55 0
Partition AC 23 0.3 0
Partition N/AC 23 0.35 0
Ceiling 23 0.45 0
Floor 202 23 0.45 2091
INTERNAL HEAT GAIN
People 2 Nos X 230 460
Light 303 W X 1.25 3.412 1292
Eq. Load 303 W 3.412 41034
ROOM SENSIBLE HEAT (RSH) 46726
Supply duct heat Supply duct Heat gain from 2 935
gain + leak. loss + fan HP(%)

Safety factor (%) 5.0 2336


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
67 28 0.12 1.08 244
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 50241
LATENT HEAT
People 2 Nos X 120 240
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
67 81.7 0.12 0.68 449
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 689
Supply duct leakage loss + Safety factor % 5.0 34
EFFECTIVE ROOM LATENT HEAT (ERLH) 723
EFFECTIVE ROOM TOTAL HEAT (ERTH) 50964
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 67
67 28 0.88 1.08 1792 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 4.76
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 283.0 Monsoon TR= 4.99
67 81.7 0.88 0.68 3292 CFM / Sq ft = 14.54 Deh. CFM= 2958
HEAT SUB TOTAL 56048 Sq ft / TR = 42 CFM(ACPH)= 88
Return duct heat HP Pump + Dehum. & Pipe 2.0 1121
gain & leak. loss + loss (%) CFM/ TR = 616
Selected TR = 5.0
TONS 4.76 GRAND TOTAL HEAT 57169 Selected CFM= 3000
XRAY
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 72 65 55 65
N - Glass 29 11 0.81 258 DIFFERENCE 26 XXXX XXXX XXXX 99
NE - Glass 0 11 0.81 0
E - Glass 0 11 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 2 People X 0 CFM/Person 7
S - Glass 0 11 0.81 0 202 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 26
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.98
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 2958
No. of Rows = 0
N - Wall 126 9 0.36 408 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 2.0
E - Wall 0 23 0.36 0 'Min. cfm reqd. = 67
SE - Wall 0 23 0.36 0
S - Wall 0 21 0.36 0
SW - Wall 0 19 0.36 0
W - Wall 0 17 0.36 0
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 29 26 0.5500 415
Glass Partition 0 21 0.55 0
Partition glass-NAC 0 21 0.30 0
Partition wall-NAC 0 10 0.35 0
Ceiling 0 10 0.45 0
Floor 202 10 0.45 909
INTERNAL HEAT GAIN
People 2.0 Nos X 230 460
Light 303.0 W X 1.25 3.412 1288
Eq. Load 303.0 WX 3.412 41034
ROOM SENSIBLE HEAT (RSH) 44772
Supply duct heat Supply duct Heat gain from 5 3358
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 2239
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
67 26 0.12 1.08 227
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 50595
LATENT HEAT
People 2 Nos X 120 240
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
67 99 0.12 0.68 544
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 784
EFFECTIVE ROOM TOTAL HEAT (ERTH) 51379
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
67 26 0.88 1.08 1664
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
67 99 0.88 0.68 3989
HEAT SUB TOTAL 57032
Return duct heat HP Pump + Dehum. & Pipe 5.0 2852
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 4.99 TR
TONS 4.99 TOTAL HEAT 59884
SHANNAYA HOSPITAL AC LOAD SUMMERY - GROUND FLOOR

MAINTAIN MAINTAIN MAINTAIN


SL.NO. FLOOR LOCATION AREA Dehumidified AC Load OCCUPANCY ROOM ROOM RELATIVE FRESH AIR LIGHTING EQ. LOAD UNIT TYPE
(Sqft) CFM (TR) HEIGHT TEMP IN HUMIDITY CFM LOAD W/SQ.FT
(FT) (F) IN (%) W/SQ.FT.

1 FIRST #REF! #REF! #REF! #REF! #REF! #REF! #REF! 55 #REF! 1.5 1.5 AHU
2 FIRST #REF! #REF! #REF! #REF! #REF! #REF! #REF! 55 #REF! 1.5 1.5 CASSETTE
3 FIRST #REF! #REF! #REF! #REF! #REF! #REF! #REF! 55 #REF! 1.5 1.5 HI WALL
4 FIRST #REF! #REF! #REF! #REF! #REF! #REF! #REF! 55 #REF! 1.5 1.5 HI WALL
5 FIRST CT ROOM 407 5150 8.5 3 10.0 72 55 136 1.5 1.5 HI WALL