Professional Documents
Culture Documents
Retrofit Guide
P1
(LO) (LOW)
AIR FLOW
8xx-V
P2 INPUT
(HI) (HIGH)
CAUTION
MORE THAN ONE DISCONNECT SWITCH
MAY BE REQUIRED TO DE-ENERGIZE THIS
EQUIPMENT BEFORE SERVICING.
This equipment complies with part 15 of the FCC rules. COM 21
1 IN 1 Operation is subject to the following two conditions.
(1) This device may not cause harmful interference. RS-485
(2) This device must accept any interference received, COM 20
2 IN 2 including interference that may cause undesired PORT
operation.
SHIELD 19
3 RET UNIVERSAL
INPUTS A07 18
4 IN 3 ANALOG
OUTPUTS RET 17
5 IN 4
0-10 VDC
AO6 16
6 RET
TRIAC REF 15
7 SPWR
DIGITAL
SMART OUT5 14
8 RET OUTPUTS
SENSOR 24VAC , OUT4 13
9 IN 5 0.5A
USE COPPER CONDUCTORS ONLY OUT3 12
10 2 4VAC
INPUT: CLASS 2 POWER ONLY
11 24VAC , 0.42A, 10VA, 50/60HZ
© 2018, Schneider Electric
Product Names are trademarks of Schneider Electric. All other trademarks are the prop-
erty of their respective owners.
The information in this document is furnished for informational purposes only, is subject
to change without notice, and should not be construed as a commitment by Schneider Elec-
tric. Schneider Electric assumes no liability for any errors or inaccuracies that may appear
in this document.
On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider
Electric. This document reflects the visual identity of Schenider Electric. However, there
remain references to TAC as a corporate brand throughout the Andover Continuum soft-
ware. In those instances, the documentation text still refers to TAC - only to portray the
user interface accurately. As the software is updated, these documentation references will
be changed to reflect appropriate brand and software changes. All brand names, trade-
marks, and registered marks are the property of their respective owners.
Schneider Electric
800 Federal Street
Andover, MA 01810
i2/b3 865/866/885-V Controller
Retrofit Guide
30-3001-988
Revision D.1
July, 2018
Contents
6 Schneider Electric
Regulatory Notices
Note: The following regulatory notices are for the new i2/b3 865, 866
and 885-V Controllers, not for the older controllers they are
replacing.
Industry Canada
ICES-003
CAUTION
All pertinent state, regional, and local safety regulations must be
observed when installing and using this product.
For reasons of safety and to assure compliance with documented product information,
repairs to components should be performed only by the manufacturer or an authorized
dealer.
Failure to observe this precaution can result in injury or equipment
damage.
8 Schneider Electric
About this Manual
Related Documentation
For additional or related information, refer to these documents.
Document Document
Number
For new replacement controllers:
i2/b3 865/866/885-V Installation Instructions 30-3001-985
i2 Controller Technical Reference 30-3001-861
b3 and b4920 Controller Technical Reference 30-3001-862
For older controllers being replaced:
i2/b3 865/866 VAV Controller Installation Sheet 30-3001-810
i2/b3 885 VAV Controller Installation Sheet 30-3001-848
TCX 865/866 VAV Installation Guide 30-3001-497
Symbols Used
The Notes, Warnings and Cautions that may be used in this manual
are listed below.
CAUTION or WARNING
Type of hazard
How to avoid hazard.
Failure to observe this precaution can result in injury or equipment
damage.
DANGER
ELECTRIC SHOCK HAZARD
How to avoid hazard.
Failure to observe these instructions will result in death or serious
injury.
10 Schneider Electric
Chapter 1
Mechanical Installation
This chapter discusses the physical removal of the older unit and the
mounting of the replacement controllers. Chapter 2 discusses the
connections you must make to complete the installation.
Mechanical Installation
Removing an old i2/b3 865/866/885 model or TCX 865/866 model VAV
controller and replacing it with the new “-V” model consists of two
procedures.
Remove Replace
(LO)
(HI)
P2
P1
11
10 2 4VAC
1
8
3
9
(HIGH)
(LOW)
IN 5
RET
RET
IN 4
IN 3
RET
IN 2
IN 1
INPUT
AIR FLOW
INPUTS
UNIVERSAL
INPUT: CLASS 2 POWER ONLY
24VAC
SENSOR
SMART
USE COPPER CONDUCTORS ONLY
V
CAUTION
EQUIPMENT BEFORE SERVICING.
MAY BE REQUIRED TO DE-ENERGIZE THIS
MORE THAN ONE DISCONNECT SWITCH
p
This device may not cause harmful interference.
operation.
operation.
including
q p
, 0.42A,
0.42A, 10VA,
is ssubject
g interference that may cause undesired
g two conditions.
866-V
0-10 VDC
24VAC ,
OUTPUTS
OUTPUTS
ANALOG
DIGITAL
RS-485
PORT
0.5A
TRIAC REF 15
COM
COM
SHIELD 19
OUT3 12
OUT4 13
OUT5 14
AO6 16
RET 17
A07 18
20
21
i2/b3 865/866/885 or
TCX 865/866 VAV Controller i2/b3 865/866/885-V Controller
Step 1: Remove the mounting screw located by the input and output
terminals.
Step 3: Disconnect all the inputs and outputs, including the Infinet or
BACnet, power, digital output, analog output, smart sensor
and universal input connections
Step 4: Unscrew the nuts on the U-bolt clamp to loosen the grip on the
VAV shaft and remove the entire unit.
12 Schneider Electric
Chapter 1: Mechanical Installation
Damper Shaft
Hex Mounting Screws Damper Position Indicator
Alternate
Damper Shaft Mounting Bracket
Battery Location
Cover Release
(Remove cover)
4-Position Dipswitch
Service Port Location
(Remove cover)
P1
Velocity Sensor
Inputs
(LO) (LOW) 866-V Jumper for Actuator
P2
AIR FLOW
Direction
(Barbed fittings) INPUT
(HI) (HIGH)
CAUTION
MORE THAN ONE DISCONNECT SWITCH TD LED = Yellow
MAY BE REQUIRED TO DE-ENERGIZE THIS
Two CPU LEDs EQUIPMENT BEFORE SERVICING. RD LED = Green
This equipment complies with part 15 of the FCC rules. COM 21
1 IN 1
Green = b3 controller Operation is subject to the following two conditions.
(1) This device may not cause harmful interference.
(2) This device must accept any interference received,
RS-485
COM 20 Wireless LED = Red
2 IN 2 including interference that may cause undesired PORT
Yellow = i2 controller operation.
SHIELD 19
3 RET UNIVERSAL
INPUTS A07 18
4 IN 3 ANALOG
OUTPUTS RET 17
5 IN 4
0-10 VDC
AO6 16
6 RET
TRIAC REF 15
7 SPWR
DIGITAL
Note: Input, Output, and 8 RET
SMART
SENSOR
OUTPUTS
OUT5 14
24VAC , OUT4 13
Smart Sensor connections will 9 IN 5 0.5A
USE COPPER CONDUCTORS ONLY OUT3 12
vary per controller model. 10 2 4VAC
INPUT: CLASS 2 POWER ONLY
11 24VAC , 0.42A, 10VA, 50/60HZ
Cover Release
Mounting Bracket
Note: Installing the controller to the right (with the barbed fittings
pointing down) will help to prevent condensate from migrating
into the on-board velocity sensor.
Step 2: If the exposed damper shaft is less than 2” (51 mm) but at
least 1” (25.4 mm) long, move the two damper shaft mounting
screws to the alternate lower damper shaft positions (see
Figure 1).
Step 3: Select the mounting bracket location that will provide the
most stability for the operation of the actuator. Position the
mounting clip in the desired mounting bracket. Do not insert
the clip more than half-way into the bracket. This will allow
the clip and the back of the actuator to properly align with the
VAV box (see Figure 1).
Step 4: Rotate the VAV damper shaft by hand to the fully closed
position. Note whether the damper is rotated clockwise (CW)
or counter-clockwise (CCW) to close.
Step 5: Slip the controller over the damper shaft. Position the actuator
and, using a self tapping sheet metal screw, secure the
mounting clip to the VAV box.
Step 6: Press the actuator toward the box until the actuator comes
into contact with the VAV box, or the mounting clip snaps into
the bracket, or the back of the actuator comes into contact with
the VAV box.
Step 7: Press and hold the green actuator clutch release (see Figure 1)
and rotate the actuator collar to a nearly closed position, the 5°
index mark, if the damper shaft was rotated counter-clockwise
to close (Step 5). Rotate the actuator collar to the 85° index
14 Schneider Electric
Chapter 1: Mechanical Installation
Step 8: Tighten the two damper shaft hex mounting screws, using a
1
/8-inch Allen wrench. The minimum torque required to secure
the controller to the damper shaft depends on the shaft
material. The maximum torque for the socket screws is 30
inch-pounds (3.4 Nm).
Note: The damper should rotate freely when the clutch is released. If it
does not, the actuator may not be properly aligned with the
damper shaft – it may be necessary to repeat Steps 4 through 9
using a new orientation.
Step 9: If the damper does not provide a mechanical stop in the open
direction, or it is not desirable to use the damper’s open stop,
set the adjustable stops on the i2/b3 865/866/885-V controller
to the desired position. Use a 1/4-inch hex driver to adjust the
screw stop on the controller.
Note: For the 866-V model only, the damper position feedback
reporting option can be enabled by changing the Andover
Continuum attribute, LCDState, from DISABLED to
ENABLED. The attribute, OverrideValue, indicates the
damper position as a fractional value from 0 (at the closed stop)
to 1 (at the open stop).
Note: The new 8xx-V controllers all use the same actuator jumper
settings to control the direction of the actuator motor. These
Tri-State settings are as follows:
Jumper Connected:
+ (On) = Clockwise (CW)
- (-On) = Counter Clockwise (CCW)
Off
Jumper Disconnected:
+ (On) = Counter Clockwise (CCW)
- (-On) = Clockwise (CW)
Off
CAUTION
Connections
To complete the installation, you will need to make the correct power, input,
output and airflow connections. Although the location of the connections are
different between older and newer models, the only significant difference
is in the wiring required for the digital triac outputs. Continue to
Chapter 2 for more information and refer to the installation instructions
supplied with your controller.
Failure to observe this precaution can result in injury or equipment
damage.
16 Schneider Electric
Chapter 2
Connections
Topics include:
z Power connections
z Universal Input connections
z Smart Sensor connections
z Digital Output connections
z Analog Output connections
z Airflow connections
Power Connections
Although the power connections for the older and newer controllers are
located in different places, they are clearly labelled and are all 24 VAC
connections.
P1
(LO) (LOW)
AIR FLOW
866-V
P2 INPUT
(HI) (HIGH)
CAUTION
MORE THAN ONE DISCONNECT SWITCH
MAY BE REQUIRED TO DE-ENERGIZE THIS
EQUIPMENT BEFORE SERVICING.
This equipment
q p complies with ppart 15 of the FCC rules. COM 21
1 IN 1 p
Operation subject to the following
is subject g two conditions.
(1) This device may not cause harmful interference. RS-485
(2) This device must accept any interference received, COM 20
2 IN 2 includingg interference that may cause undesired PORT
operation.
operation.
SHIELD 19
3 RET UNIVERSAL
INPUTS A07 18
4 IN 3 ANALOG
OUTPUTS RET 17
5 IN 4
0-10 VDC
AO6 16
6 RET
TRIAC REF 15
7
DIGITAL
SMART OUT5 14
8 RET OUTPUTS
SENSOR 24VAC , OUT4 13
9 IN 5 0.5A
Power
USE COPPER CONDUCTORS ONLY OUT3 12
10 2 4VAC
INPUT: CLASS 2 POWER ONLY
L
11 24VAC
V , 0.42A,
0.42A, 10VA,
V 550/60HZ
0/60HZ
Previous Generation
885
24VAC 1
0.42A, 10VA
Power
50/60HZ L 2
USE COPPER
CONDUCTORS ONLY
SERVICE
+ 3 PORT
INFINET - 4 GND
PORT +
-
Power
SHIELD 5
OUT 3 6
DIGITAL
OUTPUTS OUT 4 7
24VAC , 0.5A
GND 8
IN1 9
UNIVERSAL 10
RET
INPUTS
IN2 11
MODEL
S/N
DATE
INSTALLATION
For detailed instructions reviewdocument 30-3001-849 date
MOTOR DIRECTION
Previous Generation
Power
18 Schneider Electric
Chapter 2: Connections
New 8xx-V The power and ground connections for the i2/b3 8xx-V controllers are
Terminal located on the following terminals, which are labelled on each
Locations controller.
You need to be aware of the differences between the old controller you
are replacing and the new one. For example, if you are replacing a TCX
865 with a new i2/b3 865-V controller, you have two additional input
connections available. If you are replacing an old i2/b3 865 VAV with
the new i2/b3 865-V, you only have two returns, instead of three, to
complete the circuits for the four universal inputs.
New 8xx-V The universal input connections for the i2/b3 8xx-V controllers are
Terminal located on the following terminals:
Locations
Controller Universal Input Return Terminals
Terminal
i2/b3 865/866-V 1, 2, 4, 5 3, 6
i2/b3 885-V 3 1, 2
20 Schneider Electric
Chapter 2: Connections
The controllers that have Smart Sensor inputs are listed in the table
below.
New 8xx-V The Smart Sensor connections for the i2/b3 8xx-V controllers are
Terminal located on the following terminals:
Locations
Controller Smart Sensor Return and SPWR
Input Terminal Terminals
i2/b3 865/866-V 9 8 - Return
7 - SPWR
i2/b3 885-V Not Available Not Available
New 8xx-V The digital output connections for the i2/b3 8xx-V controllers are
Terminal located on the following terminals:
Locations
Controller Digital Output Triac Reference
Terminals Terminal
i2/b3 865/865-V 12, 13, 14 15
i2/b3 885-V 6, 7 9
22 Schneider Electric
Chapter 2: Connections
New 8xx-V The new i2/b3 865/866-V controllers use three Form A triac output
Digital Outputs terminals with a single triac reference. This configuration gives you the
flexibility to wire the single triac reference as either a hot or ground
connection. On these new controllers, all three outputs must be wired
the same, as either hot or ground switch applications.
24 VAC Step-Down
Transformer TRIAC REF 15
DIGITAL
OUT5 14
OUTPUTS
X1 24VAC , OUT4 13
24 VAC 0.5A
AC Line GND OUT3 12
Power
X2
24 VAC Step-Down
Transformer TRIAC REF 15
DIGITAL
OUT5 14
OUTPUTS
X1 24VAC , OUT4 13
24 VAC 0.5A
AC Line GND OUT3 12
Power
X2
The new i2/b3 885-V controller, which only has two output terminal
connections, works the same, allowing for either two hot or ground
switch applications.
Old i2/b3 The previous generation of i2/b3 865/866-VAV controllers also used
8xx-VAV Digital three triac output terminals, but were internally referenced to ground
Outputs and cannot be wired as hot. All outputs are ground switch applications.
The old i2/b2 885-VAV controller used two output terminals that were
also internally referenced to ground and cannot be wired as hot.
24 Schneider Electric
Chapter 2: Connections
TCX 865/866 Two product generations ago, the TCX 865/866 controllers also used
Digital Outputs three triac output terminals, but allowed you to pair each output with
one of three isolated returns. This combination allowed you to create
either a hot or ground switch application for each individual output
load. The TCX controller could accommodate a combination of both hot
and grounded connections simultaneously.
Form K Triac All of the controllers, past and present, offer the ability to wire two of
Connections the Form A outputs to create one Form K Tri-State output.
OUT4
Load
OUT3
Load
24 VAC Step-Down
Transformer TRIAC REF 15
DIGITAL
OUT5 14
OUTPUTS
X1 24VAC , OUT4 13
24 VAC 0.5A
AC Line GND OUT3 12
Power
X2
Note: i2/b3 885-V Controller only has two digital outputs
885
24VAC 1
0.42A, 10VA
50/60HZ L 2
USE COPPER
CONDUCTORS ONLY
SERVICE
+ 3 PORT
INFINET - 4 GND
PORT +
SHIELD 5 -
OUT 3 6
DIGITAL
OUTPUTS OUT 4 7
24VAC , 0.5A
GND 8
IN1 9
UNIVERSAL 10
RET
INPUTS
IN2 11
MODEL
S/N
DATE
INSTALLATION
For detailed instructions reviewdocument 30-3001-849 date
MOTOR DIRECTION
From the old i2/b3 865/866-VAV controller To the new i2/b3 865/866-V controller
OUT 3 (terminal 7) OUT3 (terminal 12)
OUT 4 (terminal 8) OUT4 (terminal 13)
OUT 5 (terminal 9) OUT5 (terminal 14)
GND (terminal 10 and 11) - Should not be
associated with Triac connections TRIAC REF (terminal 15)
From the old i2/b3 885-VAV controller To the new i2/b3 885-V controller
OUT 3 (terminal 6) OUT3 (terminal 6)
OUT 4 (terminal 7) OUT4 (terminal 7)
GND (terminal 8) - Should not be associated with TRIAC REF (terminal 9)
Triac connections
26 Schneider Electric
Chapter 2: Connections
Since the new i2/b3 8xx-V controllers are capable of both hot or ground
switching applications, you do have the option of rewiring all your
digital output connections to accomodate a hot switching application,
but this may cause problems with your existing circuits and loads.
For more information, refer to the hot switching diagram earlier in this
section, as well as the i2/b3 865/866/885-V Controller Installation
Instructions that came with the new controller.
Therefore, before replacing the unit and reconnecting the outputs, you
must understand how each output was wired. Since the replacement
i2/b3 8xx-V controller requires either all hot or all ground switch
connections, you may need to revise how some loads are wired to
complete the replacement installation.
Replacement
i2/b3 865/866-V Controller
TRIAC REF 15
DIGITAL OUT3
OUT5 14
OUTPUTS
24VAC , OUT4 13 DIGITAL
0.5A OUT4 OUTPUTS
OUT3 12 24 VA C , 0. 5 A
OUT5
For more information refer to the hot and ground switching diagrams
earlier in this section, as well as the i2/b3 865/866/885-V Controller
Installation Instructions that came with the new controller.
28 Schneider Electric
Chapter 2: Connections
New 8xx-V The analog output connections for the i2/b3 8xx-V controllers are
Terminal located on the following terminals:
Locations
Controller Analog Output Return Terminal
Terminals
i2/b3 865-V Not Available Not Available
i2/b3 866-V 16 and 18 17
i2/b3 885-V Not Available Not Available
Airflow Connections
The airflow sensors on both the old generation and the new “-V”
controllers have very similar connections, which include HI and LO
ports to match the HI and LO connections of the velocity sensor.
Airflow
Inputs
30 Schneider Electric
i2/b3 865/866/885-V Controller Retrofit Guide
Document Number 30-3001-988
Revision D.1