You are on page 1of 8

IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 38, NO.

6, NOVEMBER/DECEMBER 2002 1633

System Grounding and Ground-Fault Protection


in the Petrochemical Industry: A Need for a
Better Understanding
John P. Nelson, Fellow, IEEE

Abstract—This paper provides an in-depth discussion of system


grounding and ground fault protection on systems from 480 V
and above. The paper also discusses modeling of ground faults,
the proper design for ground-fault protection, and common
problems associated with ground-fault protection. The paper will
address many real-life problems associated with system grounding
and ground-fault protection, including safety issues and how to
avoid those problems. The topics to be included in the paper
include low-voltage systems, under 600 V, through high-voltage
transmission systems.
Index Terms—Ground-fault protection, high-resistance
grounding, impedance grounded, solidly grounded, system
grounding.

I. INTRODUCTION
Fig. 1. Three CTs and residual circuit.

M OST electrical faults in the petrochemical industry, es-


timated to be over 90%, are, or begin as, ground faults.
(Many of these faults involve high impedances which allows the
II. GROUND-FAULT MODELING

fault to exist longer than desired before being removed by stan- Ground-fault modeling is important in analyzing the effects
dard circuit breakers). Unfortunately, few engineers and practi- of various types of grounding in the petrochemical facilities and
cally no plant operators totally understand ground faults and the in predicting the effects of ground faults on the system. Probably
means to protect against them. System grounding and ground- the most commonly used model involves the use of symmetrical
fault protection in the petrochemical industry are important fac- components [1] and, in particular, the use of the zero-sequence
tors in the design, construction, and operation of a petrochem- circuit. Historically, the use of zero-sequence current vector
ical facility. The safety of plant personnel and the reliability and zero-sequence voltage vector have been used with pro-
of the equipment are highly dependent on the type of system tective relays for ground-fault protection. Part of the reason for
grounding selected and the type of ground-fault protection se- the long-time use of these components has been due to the fact
lected. that the zero-sequence values are directly proportional to the
The basic types of system grounding include the following: sum of the three phase currents and voltages as shown in (1)
and (2)
• ungrounded;
• solidly grounded;
• impedance grounded. (1)
The basic types of ground-fault protection include:
(2)
• none;
• indication; where
• alarming; zero-sequence current vector;
• tripping; zero-sequence voltage vector;
• alarming and tripping. , , three phase current vectors;
, , three phase voltage vectors.
Paper PID 02–17, presented at the 2001 IEEE Petroleum and Chemical In- The zero-sequence current component of the current can be
dustry Technical Conference, Toronto, ON, Canada, Septmeber 24–26, and ap- found by summing the three currents from a current transformer
proved for publication in the IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS
by the Petroleum and Chemical Industry Committee of the IEEE Industry Ap- as shown in Fig. 1. Note that the neutral connection of the three
plications Society. Manuscript submitted for review September 15, 2001 and currents transformers, often referred to as the residual circuit, is
released for publication August 16, 2002. equal to .
The author is with NEI Electric Power Engineering, Inc., Arvada, CO 80001
USA (e-mail: jnelson@neiengineering.com). The zero-sequence voltage component can be similarly found
Digital Object Identifier 10.1109/TIA.2002.804754 by summing the three voltages in a circuit called a broken delta
0093-9994/02$17.00 © 2002 IEEE
1634 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 38, NO. 6, NOVEMBER/DECEMBER 2002

Fig. 3. Delta–wye grounded.

Fig. 2. Three PTs in broken delta.

as shown in Fig. 2. Note that exists across the portion of


the three voltage transformers which has been left open. Fig. 4. Delta–impedance grounded wye.
Ground faults also create values in the positive- and negative-
sequence circuits which have historically been of less value to
the protection engineer than zero sequence. The reason is that
the positive- and negative-sequence circuits required complex
positive- or negative-sequence filtering in order to develop those
sequence components. As can be seen in (3)–(6), the equations
are more complex
positive sequence
Fig. 5. Wye grounded–delta–wye grounded.

(3)

(4)

negative sequence
Fig. 6. Wye grounded–wye grounded.
(5)
• wye grounded primary–delta tertiary–wye grounded sec-
(6) ondary;
• wye grounded primary–wye grounded secondary.
where
, positive- and negative-sequence currents, respec- IV. LOW-VOLTAGE GROUNDING
tively;
Low voltage in this paper will consider everything 600 V and
, positive- and negative-sequence voltages, respec-
below. The three means of grounding include the following:
tively;
an operator equal to and . • solidly grounded;
With the modern microprocessor-based relays and their • impedance grounded;
mathematical capabilities for processing of the phase currents • ungrounded.1
and voltages, positive-, negative-, and zero-sequence quantities Most recent petrochemical low-voltage transformer designs
are readily available for use in the protection schemes. There- consist of delta-connected primary, grounded wye secondary.
fore, the protection engineer now has practically unlimited This type of connection establishes the grounding plane on the
capabilities for providing the kind and type of protection secondary of the transformer. Therefore, grounding is indepen-
schemes needed for proper ground-fault protection. dent of the type of grounding upstream from the transformer.
Some grounded-wye primary, grounded-wye secondary-con-
III. EQUIVALENT ZERO-SEQUENCE CIRCUITS FOR COMMON nected transformers are utilized in the petrochemical industry
since this is a commonly used utility transformer connection.
TRANSFORMER CONNECTIONS
Caution should be taken in use of this type of transformer con-
Many references exist which show the detailed zero-sequence nection since it is dependent on the primary system grounding.
equivalent circuits for the different transformer connections. This transformer can be cautiously used as a grounded-wye pri-
This paper will consider only those transformer connections mary to resistance grounded secondary, but should never be con-
commonly used in the petrochemical industry (see Figs. 3–6) nected ungrounded on either the primary or secondary side.
as follows:
1An ungrounded system is actually a special application of the impedance
• delta primary–wye grounded secondary; grounded system where the ungrounded system is grounded through its system
• delta primary–wye secondary with impedance grounding; capacitance.
NELSON: SYSTEM GROUNDING AND GROUND-FAULT PROTECTION IN THE PETROCHEMICAL INDUSTRY 1635

at the point of fault, it is quite common that the fault current is


limited to a point where the phase overcurrent protective device
will not properly operate, or may be extremely slow if it does.
Therefore, ground-fault protection has been required by code
in many instances and the use of ground-fault protection on
circuit breakers of 600 A and above is highly recommended.
Coordination of ground-fault protection can become difficult,
especially if there are more than three breakers in series. Also,
the selectivity of smaller downstream overcurrent devices
which do not have ground-fault protection is difficult at best.
Solidly grounded low-voltage systems of less than 150 V to
ground will typically have one of two events occur during a
Fig. 7. Resistance grounding addition to an ungrounded system. ground fault: 1) the fault will weld at the point of fault causing
a direct short to occur and the overcurrent device to operate iso-
Another system grounding connection which exists in the lating the fault, or 2) the fault will extinguish due to the arc
petrochemical industry is that of the corner grounded delta. This voltage being greater than the source voltage causing the fault
connection is found anywhere from production fields to some current to cease.
large chemical plants. The corner grounded delta provides the Therefore, these lower voltage faults do not pose any major
advantage of having the system grounded, but the disadvan- difficulties in protecting, that is, systems 150 V to ground or
tages: 1) that the two ungrounded phases will see full line-to-line less. However, once the line-to-ground voltages exceed 150 V,
voltage between the phase equipment and ground and 2) that a a different story exists. On the typical 480- and 560-V systems,
ground on any of the other two phases results in a phase-to-phase the arc resistance and arc voltage make proper sensing of ground
fault through ground. faults more difficult. Where reliability and continuity of ser-
As discussed in [2], the ungrounded system is a special appli- vice are important in the petrochemical industry, high-resistance
cation of the impedance grounded system in that the system is grounding should be applied. The reader is encouraged to review
grounded through its capacitance to ground. The main disadvan- the references for more detailed design information [2], [5].
tage to this system is with the propensity to allow transient over
voltages which can obtain voltage levels of five times or more VI. MEDIUM-VOLTAGE GROUNDING
normal line-to-ground voltage (see the Appendix). The author
Medium-voltage systems typically include voltages over 600
recommends that existing low-voltage ungrounded systems be
V through 15 000 V. The system grounding practices have in-
modified, most likely to a high-resistance grounded system, to
cluded the following:
minimize the probability of transient over voltages. On an un-
grounded-wye system, a resistor can be placed in the neutral • solidly grounded;
of the transformer and/or generator. On a delta system, this can • impedance grounded:
be accomplished at a relatively small cost using properly sized 1) low resistance;
control power transformers connected resistance grounded wye 2) high resistance;
primary to delta secondary (see Fig. 7). 3) reactance;
• ungrounded.
Medium-voltage solidly grounded systems are commonly
V. LOW-VOLTAGE GROUND-FAULT PROTECTION
used on field distribution systems and small plant electrical
Ground-fault protection on low-voltage systems has histori- systems. The solidly grounded medium-voltage transformer
cally taken the following two directions: 1) alarming/indication can have either high-side fuses or breakers for transformer
and 2) tripping. protection. Sufficient fault current is normally reflected through
On delta systems and some high-resistance grounded wye the transformer to allow the use of fuses.
systems, ground-fault detection lamps have been used to Ground-fault protection can take many forms, but alarming
indicate that a ground fault has occurred. On high-resistance is not normally one of the options. Fault currents of significant
grounded systems, an alarm circuit has usually been incorpo- values are present and tripping is the norm. Ground-fault pro-
rated. In either case, the system designer has chosen to keep tection using residual or current transformer neutral circuits are
the electrical circuit in service and provide only indication of common and problems can occur with the use of zero-sequence
a ground fault. Some designs have also incorporated a timing current transformers (due to the relatively low ratios on zero-se-
sequence that would trip a breaker if the fault is not cleared in quence current transformers and the relatively high fault cur-
a timely fashion. rents).
On solidly grounded systems, the normal means of For example, a solidly grounded system has an available
ground-fault protection is through tripping of the circuit ground-fault current of 1500 A, which is a relatively low value
breaker or blowing of a fuse. The intent is that the ground fault of ground-fault current. The expected secondary current using
should have sufficiently high current to cause normal and se- a 50:5 zero-sequence CT is 150 A. This may be greater than
lective operation of the overcurrent protective device. However, the thermal or mechanical rating of the CT which often times
due to the resistance of the arc and the arc voltage developed is in the 100-A range.
1636 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 38, NO. 6, NOVEMBER/DECEMBER 2002

Medium-voltage impedance grounded systems are com- fault of 400 A, only 2/3 of an ampere is available for
monly used for plant operations with the low-resistance a ground fault of 400 A. Therefore, sensitive ground
grounded system being the most common. Low-resistance CTs in the neutral of the main power transformer and
grounded systems typically limit the ground-fault current to a zero-sequence CTs are best for ground-fault protection.
range of 200–1000 A. Some reactance grounded systems are
in existence, but they are rare. However, they do follow some VIII. GENERATION GROUNDING
of the same principles as the resistance grounded system. For
the resistance grounded system, the fault currents are relatively Generator grounding can consist of the following:
constant for faults throughout the system. This is due to the fact • solidly grounded;
that the per-unit resistance is typically much greater than the • low-resistance grounding;
per-unit reactance of the system. • high-resistance grounding;
High-resistance system grounding has been successfully used • ungrounded.
on systems through approximately 7200 V. However, problems First, practically all generators are wye connected. Ground-
have occurred on higher voltages primarily as a result of the fault currents cannot flow from the rare delta-connected gener-
increased capacitive current causing greater arc damage. ator. However, ground-fault current can and does flow from the
Ungrounded medium-voltage systems present the same wye-connected generator and, based on the type of grounding
transient overvoltage problems as discussed in Section IV. of the neutral of the generator, the system can be as classified as
Ungrounded medium-voltage systems should be avoided above.
and existing ungrounded medium-voltage systems should be Caution should be taken in using a solidly grounded gen-
modified to incorporate some type of system grounding. erator. The reason is that a generator typically has a zero-se-
It should be noted that grounded-wye power-factor-correc- quence reactance much less than the subtransient reactance
tion capacitor banks should not be used on low- or high-resis- . As such, a bolted ground fault can produce currents in ex-
tance grounded systems. A grounded-wye capacitor bank ap- cess of a bolted three-phase fault. The generator is designed for
pears as a parallel path to the resistor in the zero-sequence cir- withstanding a bolted three-phase fault, but not necessarily a
cuit, and may cause overheating of the resistor and ground- bolted ground fault. Therefore, good practice dictates that some
fault coordination problems. This problem has been noticed in type of neutral impedance needs to be placed in the circuit to
petrochemical facilities, especially where overhead distribution minimize the ground fault currents to a value lower than the
lines are present. The two most common options for installing three-phase fault. Due to the nature of the zero-sequence circuit,
power-factor-correction capacitors would be ungrounded wye any impedance placed in the neutral of the generator is multi-
and delta. Both eliminate the overheating problem with the re- plied by three for zero-sequence modeling. Therefore, the neu-
sistor and the path for zero-sequence fault current. tral impedance appears to be . As such, the ground cur-
rent which flows for a three-phase and a phase-to-ground fault
are as shown in the following equations:
VII. MEDIUM-VOLTAGE GROUND-FAULT PROTECTION
Medium-voltage ground-fault protection usually involves co- (7)
ordinated ground-fault tripping. That is, selective tripping of the
circuit breakers is typically used where the breaker closest to
(8)
the fault senses the fault and selectively trips, isolating the fault.
Consider the following different types of grounding.
1) A 4.16-kV solidly grounded system has an available where
ground-fault current of 5000 A. A zero-sequence CT with subtransient impedance;
a 50/5 ratio is being considered for feeder ground fault positive-sequence generator impedance;
protection. The problem with using this zero sequence negative-sequence generator impedance;
CT is that the ratio is 10:1 which equates to a secondary zero-sequence generator impedance;
fault current of 500 A for a 5000—A primary fault. Many neutral impedance.
current transformers have a secondary rating of 100 A The minimum positive- and negative-sequence impedances
and few, if any, relays can withstand 500 A. Therefore, of the generator are approximately equal to the subtransient
this is not a good application for a zero-sequence CT. impedance of the generator. The typical range of positive-
In this particular application, a residual CT circuit with and negative-sequence impedance is in the 10%–20% range.
a minimum ratio of 50:1 or 250:5 should be used to limit A typical generator zero-sequence impedance is in the range
the secondary fault current to less than or equal to 100 A. of 1%–5%. The neutral impedance often times is the most
2) A 4.16-kV resistance grounded system with a 400-A significant impedance limiting the ground-fault current.
grounding resistor will have 400 A for practically all A low-resistance grounded generator has many of the same
ground faults. Zero-sequence CTs are a good application characteristics of a low- and medium-voltage system. Generator
for medium-voltage low-resistance grounding. Another voltages in the petrochemical industry are typically classified as
problem which exists is that of sensitivity of ground-fault low and medium voltage. In fact, even large utility generators
protection. For example, using the residual of a 3000/5 are rated less than 25 kV and considered medium-voltage gen-
CT provides a ratio of only 600:1. That is, for a ground erators. Therefore, the low-resistance grounding of generators
NELSON: SYSTEM GROUNDING AND GROUND-FAULT PROTECTION IN THE PETROCHEMICAL INDUSTRY 1637

ground overcurrent relays, both directional and nondirectional.


Loop systems typically require the use of directional ground
overcurrent relays. There are also ground-fault distance relays
that are a type of impedance relay.

XI. TRANSMISSION SYSTEM GROUND-FAULT PROTECTION


Transmission system relaying is typically high speed, often
times using a communications system as a means of helping
Fig. 8. Generator ground fault over voltage protection options.
to identify the actual location of the fault. Fault clearing times
in the range of 4–6 cycles is quite common. Sophisticated
is typically used on medium-voltage generators. The low-resis- modern-day relaying can sense the fault within 1–2 cycles and
tance grounding of a medium generator is typically limited to a breaker clearing times of 3 cycles are common.
range of 200–1000 A. Ground directional relays require some type of polarization.
Similarly, a high-resistance grounded generator has many of Historically, this was normally through the use of zero-se-
the same characteristics of a low- and medium-voltage system. quence current and zero-sequence voltage polarizing units.
Special precautions must be taken when paralleling solidly Both zero-sequence current and zero-sequence voltage values
grounded and low-resistance grounded generators [3]. are readily available in power systems. With the digital micro-
processor-based relays, polarizing can take additional forms
IX. GENERATION GROUND-FAULT PROTECTION such as both zero- and negative-sequence polarizing. This can
be accomplished digitally for negative-sequence polarizing
Ground-fault protection of generators usually takes two or the use of the common zero-sequence voltage and current
forms: 1) ground current detection and 2) ground overvoltage polarizing as previously shown. The basis for ground-fault
detection. Also, generator ground fault protection can take the protection is similar to that of lower voltage systems.
form of alarming and tripping.
Similarly to low- and medium-voltage systems, a solidly
grounded or low-resistance grounded generator should be XII. GROUND-FAULT SHIELDING CONSIDERATIONS FOR
tripped offline. However, a high-resistance grounded gener- MEDIUM-VOLTAGE CABLES
ator can be either alarmed or tripped. With a high-resistance Once the voltage on a power cable exceeds 600 V, the user and
grounded generator, it may be advantageous to alarm for a cable manufacturer become concerned with safely maintaining
ground fault. That way, important generation may be kept the electric potential or field within the insulation. At the lower
online for critical loads. range of medium-voltage cables, through 5 kV, shielding is not
On low-resistance grounded generators, ground faults are required. However, shielding of power cables is commonly used
commonly protected using ground-current-sensing devices. For on 5-kV medium-voltage cables and is required on all power
ground-fault currents originating in the generator, the current cables rated above 5 kV.
can be sensed using a current transformer in the neutral of There is one aspect of electric power cable shielding which in-
the generator. That method protects the generator as well as volves system grounding practices and ground-fault protection.
the system. A second method consists of placing a residual That deals with the ground-fault current withstand capability of
CT on the generator output. This protects the system from the the shield. There are three important variables which must be
generator and the generator from the system. However, it does considered when considering the proper shield for power cables
not provide generator protection from itself. As a backup, a for ground currents:
ground overvoltage relay can also be used. The overvoltage
• neutral current;
relay can be placed in the neutral of the generator or can be
• ground-fault current;
provided by a broken delta PT where the resultant value is
• time.
(see Fig. 8).
The neutral currents are common only in solidly grounded
three-phase four-wire systems. Three-phase four-wire systems
X. HIGH-VOLTAGE SYSTEM GROUNDING (ABOVE 15 kV) require a neutral conductor. Therefore, the concentric neutral is
While electric utilities primarily provide the transmission typically used for this application. The concentric neutral is the
systems for a petrochemical facility, there are some instances most commonly used power cable for the electric utility industry
where the facility has its own transmission system or it may on their distribution systems. Similar distribution systems can
be interconnected to a transmission system. Therefore, it is and do exist for the petrochemical industry in the oil fields. The
important for the petrochemical facility to have at least a size of the concentric neutral depends on the continuous and in-
working knowledge of transmission system grounding and termittent neutral/unbalance currents which will flow current in
transmission ground fault protection. the system. This will include both the steady-state and harmonic
With few exceptions, transmission systems are almost univer- currents which flow on the system. The concentric neutral on
sally solidly grounded. This is accomplished primarily through each power cable typically include the following:
grounded-wye source transformers. As such, ground-fault pro- • full concentric;
tection of high-voltage systems is normally accomplished by • 1/3 concentric;
1638 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 38, NO. 6, NOVEMBER/DECEMBER 2002

• 1/6 concentric. TABLE I


Single-phase and some three-phase four-wire applications re- 2/0 AWG COPPER (CURRENT IN AMPERES)

quire a full concentric neutral on each cable. The size of the full
concentric neutral equals the size of the power cable conductor.
Many typical three-phase power systems can use a power cable
with a 1/3 concentric. With the three power cables each having a
1/3 concentric neutral, the total neutral for the system is equal to
the size of the individual conductor. Finally, for three-phase sys-
tems with little or no neutral current, a 1/6 concentric could be
used. One of the main factors, if not the determining factor for
determining the type of concentric neutral will be the amount of
neutral current which can safely flow in the concentric neutral. TABLE II
500 MCM COPPER (CURRENT IN AMPERES)
On three-phase three-wire systems, neutral current is not a
concern for the shielding. The apparent solution would be to
use a simple tape shield, commonly a 5-mil copper tape with a
12.5% overlap. Since there is no neutral current flowing, the
common assumption is that the tape shield will be adequate.
Unfortunately, that is not always true.
Ground-fault current and ground-fault duration are impor-
tant in determining the size and type of shield. Unfortunately,
the tape shield has limited ground-fault time and current capa-
bility. The use of a tape shield for a petrochemical plant with
a medium-voltage low-resistance grounded system is usually a • Ungrounded systems are to be avoided. Transient over-
good design. The reason is that the ground-fault current is lim- voltages due to arcing ground faults can occur on the un-
ited to some value 1000 A or less. Usually, that value is in the grounded system.
range of 200–600 A. However, on a solidly grounded system, • Solidly grounded systems typically have relatively high
the ground-fault current can be in the thousands to tens of thou- fault currents and tripping is necessary.
sands of amperes. • Low-impedance grounded systems are typically used to
The maximum short-circuit current allowed in a copper limit ground-fault currents and typically allow sufficient
power cable shield is given by the following equation [4]: fault current for coordinated tripping.
• Low-resistance grounded systems are commonly used for
medium-voltage systems. The ground-fault current is nor-
(9) mally limited to the 200–1000 A range with many systems
operating at 400 A.
• High-resistance grounded systems are commonly applied
where to low-voltage systems with a line-to-neutral voltage in
amperes; excess of 150 V. Both alarming and tripping schemes are
shield area in circular mils; used for high-resistance grounded systems.
number of cycles; • Low- and high-resistance grounded generators are the
initial temperature of 65 C; norm. Special caution must be taken in using solidly
constant 0.288 (200 C temperature maximum tem- grounded generators. Ungrounded generators should be
perature). avoided.
The allowable current for cycles allows the temperature • Reactance grounding of medium-voltage distribution sys-
to rise from an initial shield temperature of 65 C to 200 C. tems can be found on electric utility systems where they
As can be seen from (9), which is also intuitively obvious, the are providing an effectively grounded system.
allowable current is proportional to the cross-sectional area of • Grounded-wye power-factor-correction capacitor banks
the shield and inversely proportional to the square root of the should not be used on low- or high-resistance grounded
time. Some examples of approximate allowable times and cur- systems.
rents for 2/0 AWG and 500 MCM Copper Cable are shown in • Most utility transmission systems are solidly grounded.
Tables I and II.
APPENDIX
XIII. CONCLUSIONS TRANSIENT OVERVOLTAGES DUE TO ARCING GROUND FAULTS
ON AN UNGROUNDED SYSTEM
System grounding and ground-fault protection are important
in the petrochemical industry. First, it is important to have the An arcing ground fault on an ungrounded system presents a
proper system grounding for the particular system application. unique problem: the possibility of transient overvoltages. While
Then, it is equally important to have the proper ground-fault this subject is briefly covered in a number of references, one of
protection. The combination of the two have been shown to be the best explanations requires the use of the zero-sequence cir-
essential. The following general conclusions can be made. cuit in symmetrical components. The capacitance to ground in
NELSON: SYSTEM GROUNDING AND GROUND-FAULT PROTECTION IN THE PETROCHEMICAL INDUSTRY 1639

Fig. 10. Capacitive current flow and system voltage.

(a)

(b)
Fig. 9. (a) Arcing fault equivalent circuit. (b) Approximate equivalent circuit.

the circuit shows up in the zero-sequence circuit as a capacitor.


The positive- and negative-sequence circuits can be represented Fig. 11. Transient overvoltages from restriking ground fault on “A” phase.
by equivalent impedances, primarily reactive.
The positive- and negative-sequence circuits for an arcing
ground fault are placed in series with the zero-sequence circuit
as shown in Fig. 9(a). However, in comparison with the imped-
ances between the positive-, negative-, and zero-sequence cir-
cuits, the positive- and negative-sequence impedances are neg-
ligible with respect to the zero-sequence impedance and the re-
sulting approximate equivalent circuit is shown in Fig. 9(b).
The first contact with ground will cause a 1-per-unit zero-se- Fig. 12. Zero-sequence circuit showing capacitance discharge.
quence voltage to appear in the circuit. This causes the neutral
of the system to be displaced from ground by a voltage ap- forth per-unit voltages. Theoretically, the overvoltage could
proaching line-to-neutral voltage of 1 per unit. Due to the na- go on unlimited except for the fact that the insulation on the
ture of a capacitive circuit, the fault current is predominantly unfaulted phases will probably fail, creating a fault on a second
capacitive and leads the voltage by 90 . Therefore, when the phase. This will result is a phase-to-phase fault and most likely
current goes to zero, the arc current stops flowing. At the same clearing of the fault through a fuse or breaker.
time, the capacitive voltage is maximum. Therefore, 1-per-unit One of the better options to an ungrounded system is to use
zero-sequence voltage exists across the capacitor and across the a high-resistance grounded system. The resistance is chosen to
system, effectively shifting the neutral of the circuit (see Figs. 10 provide a resistive fault current equal or greater that the zero-
and 11). sequence capacitive current as shown in (A1)
With the 1-per-unit voltage on the capacitor, the system
voltage travels another one-half cycle. With the voltage restored (A1)
across the faulted phase, a subsequent arc can occur, which,
because of the transient nature of the circuit will result in up The high resistance is placed in the zero-sequence circuit as
to 2-per-unit shift of the neutral plus the original 1-per-unit shown in Fig. 12.
voltage. Thus, the neutral can, within one-half cycle, create a As one can see in Fig. 12, the resistance will allow the voltage
shift of 3 per unit in the neutral of the circuit. Next, the same to decay based on a time constant equal to
thing can happen the next half cycle where 3-per-unit voltage
exists in the capacitance of the circuit and another 2-per-unit (A2)
voltage shift can occur during the next half cycle (see Fig. 11).
The transient overvoltage buildup can occur very rapidly, Using a 1000-kVA 5.75% impedance transformer as a source
creating subsequent overvoltages of 1-, 3-, 5-, 7-, 9-, and so reactance and a 277- neutral grounding resistor, the time con-
1640 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 38, NO. 6, NOVEMBER/DECEMBER 2002

stant is approximately 2.75 ms. Therefore, in one-half cycle the [4] “Engineering data for copper and aluminum conductor electrical ca-
voltage will have decayed to bles,” Okonite Co., Ramsey, NJ, Bull. EHB-88, 1988.
[5] P. Beltz and Vilcheck, “High resistance ground retrofits in pulp and paper
mills,” IEEE Ind. Applicat. Mag., vol. 7, pp. 19–27, Mar./Apr. 2001.
(A3)
Therefore, one can see that the transient overvoltages are lim-
ited with resistance, and the lower the resistance the lower the
John P. Nelson (S’73–M’76–SM’82–F’97) received
transient overvoltage. Experience has shown that the transient the B.S.E.E. degree from the University of Illinois,
overvoltage is limited to approximately 2.5 per unit if . Urbana, in 1970, and the M.S.E.E. degree from the
University of Colorado, Boulder, in 1975.
He is President and a Principal Engineer with
REFERENCES NEI Electric Power Engineering, Inc., Arvada, CO.
[1] E. Clark, Circuit Analysis of A-C Power Systems. New York: He has authored or coauthored numerous papers,
GE/Wiley, 1959. typically involving electric power systems in the
[2] J. P. Nelson and P. K. Sen, “High resistance grounding of low voltage petrochemical industry.
systems: A standard for the petroleum and chemical industry,” IEEE Mr. Nelson has been active with the Petroleum and
Trans. Ind. Applicat., vol. 35, pp. 941–948, July/Aug. 1999. Chemical Industry Committee of the IEEE Industry
[3] L. J. Powell, “Influence of third harmonic circulating currents in Applications Society for more than 20 years. He is a Registered Professional En-
selecting neutral grounding devices,” IEEE Trans. Ind. Applicat., vol. gineer in the States of Colorado, Arizona, California, Louisiana, New Mexico,
IA-9, Nov./Dec. 1973. Utah, Wisconsin, and Wyoming.

You might also like