1 Conductors
Single conductor lines with plastic (PVC) enclosure with 25 or 50 mm² conductor
cross-section in 6 m standard lengths.
For ambient temperatures from -30 to +60° C. IP23 enclosure for horizontal and IP20
for vertical mounting arrangements.
2 Current collectors
Single or double current collector pantographs from 15 to 40 A at 100 % CDF for
travel speeds up to 400 m/min. Connection cross-sections up to 6 mm².
3 Power feed
Universal power feed for end or line power feed arrangements.
Connection cross-sections up to 50 mm².
42315044.eps
1 Technical data
Enclosure material PVC Max. continuous current at 100 % CDF (A) 40, 25
Standard lengths (mm) 6000 Max. continuous current at 30 % CDF (A) 50, 30
Continuous current IN at 100 % CDF (A) 100, 200 Fuses max. (A) 100
Ambient temperature
-30 to +60
max. continuous (°C)
+70 for short periods
max. 1 hour (°C)
Max. length of one straight
conductor section (m) 200 ¹)
2
2 Component parts/accessories
42315144.eps
SSE 150 current collector pantograph 42315244.eps SSD 50 current collector pantograph 42315344.eps
202673k1.p65/311000
End cap/entry section 42316244.eps Conductor connector with 50 mm² power feed 42316344.eps
4
Conductor connector 42316444.eps Section rail with suspension 42316544.eps
Straight section
Cu conductor with PVC enclosure 42316644.eps 45° funnel lead attachment 42316744.eps
202673k1.p65/311000
5
3 Basic structure
DEL
Straight sections
Curved sections
Conductor connector
Isolating section
Suspension
Connecting cable
Carrier plate
Enclosure: PVC
Nominal Cu conductor cross-section in mm²
Number of conductors (including PE conductor)
Conductor
Single
6 Demag
4 General arrangement
1000 A 500
DEL conductors
250 400
7
200 6.4 7.1
15
65
5.1 Straight sections Straight sections are 5945 mm long. A length of 6000 mm should be used for design
purposes. Shorter length sections are made using a straight cut. The green/yellow
protective earth (PE) conductor should be arranged to face the crane girder web.
The maximum permissible distance between brackets is 1000 mm, and 200 mm for
conductor connectors, isolating sections and end caps.
Two stop plates must be ordered for each conductor to secure against longitudinal
displacement.
± 0,5
L2 5.3
17
9
55 L1 55 13
Enclosure type IP 23
Design
Grey enclosure, green/yellow PE conductor section, Cu conductor material, alterna-
tive conductor materials on request.
1) Well suited for data and control lines after checking the operating conditions.
8
202673k1.p65/311000
9
6 DEL curved sections
Curved sections can be made in the factory or on site using a bending device. They
are supplied with 100 mm long straight ends for connection to the straight sections.
These straight ends must be removed if not required. A bending device for on-site
installation for horizontal and vertical curved sections can be supplied on request. The
maximum permissible distance between brackets is 500 mm, and 200 mm for con-
ductor connectors, isolating sections and end caps.
Curve A
Opening on the outside
C Section C – D
±0,5
5,3
17
13
0 10
10 0
R
41032744.eps
Curve I
Opening on the inside
Section C – D
C 13
17
R
±0,5
5,3
0 10
10 0
41032844.eps
202673k1.p65/311000
10
Curve H
Horizontal arrangement, Section E – F
17
Opening facing downwards
5,3 ±0,5
13
E
13
19
0 10
10 0
Rm
n
-R
R3
R2
R4
R1
41032944.eps
Radius R ³ 500 mm
11
7 Conductor connectors and power feeds
100
28,5
DEL rail 50 - 55 DEL rail
41033044.eps
92
46
41033144.eps
Isolating or air-gap interrupt sections are available. Air-gap interrupt sections should
be used for increased demands and arduous operating conditions.
Isolating sections have the same dimensions as conductor connectors. Isolating
sections feature one and air-gap interrupt sections two M5 power feed screws (see
also conductor connectors).
100
150
28,5
26,5
DEL rail 55 no current DEL rail DEL rail 100 no current DEL rail
Isolator
41032144.eps 41032244.eps
9 Suspensions
Universal 6-conductor suspension Bolted 6-conductor suspension Bolted single
50
suspension
Ø10 M8 X .... DIN 933 hexagon bolt,
5.5 optionally 1 in the middle or 2 outside 5.5
3
2)
1,5
1,5
1)
13
13
13
50
33
33
33
20
20
20
19 19 19
119 5.1 5.1 6-cond. suspension 119
5.2 8-cond. suspension
152 5.2
The number of suspension fittings must be selected in accordance with the maximum
distance between suspension centres of 1000 mm and the conductor length.
Isolators to increase the electrical safety on request. 13
10 Section rail
M8
41,5
34
26
Universal 6-cond. susp.
41032544.eps
The number of suspension fittings for section rails (M8x45 screw) must be selected in
accordance with the distance between suspension centres. One package contains
screws, nuts and plates for 5 complete suspension points.
Item Designation Length in kg/unit Part no.
mm
or ME
6.4 Section rail for power feed 16 – 50 mm² 590 mm 1 876 010 44
41032644.eps
2
[mm ] 25 50 25 - 50 25 50 25 - 50
"A"
3 2 1 2 1, 5 1
[m]
[m] 2,5 1) 1,5 1) - 1,5 1) 1,0 1) -
202673k1.p65/311000
Note: The distance between the plastic suspensions (see page 7, item 5) must not exceed
1000 mm and does not increase when section rails are used.
End caps are used at the ends of track sections and as straight transfer sections.
They can be used as end power feeds up to 10 mm² connection cross-section.
Section rail 6.3 is used for attachment to steel superstructures.
Set the DEL expansion joints as described in the assembly instructions before fixing
end caps/transfer sections into place.
45
18,5
26,5
45 no current
65
41033244.eps
Note: During transfer operations, use 2 current collector pantographs with a minimum
centre distance of 140 mm.
Item Designation kg/unit Part no.
7.1 Funnel transfer section / end cap 0,024 876 046 44
6.3 Section rail 120 1) 0,11 979 508 44
45° funnel lead attachment Funnel lead attachment for transfer section. Used for angular (45°) transfer operations
e.g. switches for horizontal DEL mounting arrangements. Funnel lead attachments
are clipped onto funnel transfer sections (item 7.1). Dead section 69 mm.
30
23,5 no current 19
Transfer section
202673k1.p65/311000
41033344.eps
39 110 A
M8
25
64
5
173
218
111
7.1
B
A
41033444.eps
Funnel entry sections can only be used with funnel transfer sections (item 7.1, see
page 15).
Transfer speed : max. 100 m/min dead section 218 mm
Horizontal offset : max. ± 30 mm
Vertical offset : max. ± 25 mm
Note: During transfer operations, use 2 current collector pantographs with a minimum
centre distance (item 10.1, page 19) of 485 mm.
202673k2.p65/311000
16
14 Expanding section
41768344.eps
Phase/data line
Conductor cross-section
Number of poles
17
15 Stop
Symbols:
x = Stop
o = Joint
a) = Line half a) a) b)
b) = Line half b)
> = Funnel/end cap 41034844.eps
18
16.2 150 current collector L1
10.1.5
+30
106 +30
7,5
49
21
7,5
1) Max. connecting
cable see type
+12
10.1.4 183 +12
10.1.3 M6 hexagon nut (integrated) 41033544.eps
10.1.2 M6 hexagon bolt (22 mm + clamping length)
2) Highly flexible connecting cable with double insulation must also be ordered (see page 21, item 16.4). The
smallest required conductor cross-section (2,5 – 6 mm²) must be used to keep the reaction forces on the
current collector pantograph as low as possible.
3) Current collector pantographs with graphite sliding contacts for operation outdoors, near salt water and
chemicals. Use double current collector pantographs for operation near salt water and chemicals.
4) For 3 mm max. material thickness.
5) For operation under arduous conditions.
6) Not suitable for entry / transfer.
202673k2.p65/311000
19
16.3 50 current collector
pantograph
+8 +8 +8
52,5 -8 52,5 -8 52,5 -8
66 66
12,5 42 42
12
59 +- 12
12
59 +- 12
max. 6 mm²
max. 6 mm²
41033644.eps
1) Highly flexible connecting cable with double insulation must also be ordered (see page 21, item 16.4). The
smallest required conductor cross-section (2,5 – 6 mm²) must be used to keep the reaction forces on the
current collector pantograph as low as possible.
2) Current collector pantographs with graphite sliding contacts for operation outdoors, near salt water and
chemicals. Use double current collector pantographs for operation near salt water and chemicals.
Spacers
1)
15.8
19
Spacers for current collector pantographs for unguided entry and transfer operations.
202673k2.p65/311000
19 mm 876 142 44
10.3 Spacer
15,8 mm 876 143 44
20
Item Cross-section in Part no. 1) Type Colour Outside dimension
16.4 Connecting cable mm² mm
for current collector 2,5 895 120 44 black
4,1
pantographs 2,5 895 121 44 green, yellow
4,0 895 122 44 black
10.4 YFFM 5,1
4,0 895 123 44 green, yellow
6,0 895 124 44 black
5,6
6,0 895 125 44 green, yellow
= = 19 = =
41033944.eps
A current collector bracket is available for 50 and 150 current collector pantographs
(see data sheet 206 630 44). Part no. 876 260 44
An angle mounting section with bore holes is also available for 150 current collector
pantographs, e.g. for fitting to C rails. Part no. 991 218 44
5
(6 with PE)
= = 19 = =
16.6 Spare parts for current Designation For current collector pantograph
SSE 40/6.0/50 SSE 20/6.0/50 SSE 40/6.0/150 SSE 20/6.0/150
collector pantographs
202673k2.p65/311000
Type
SSD 40/6.0/50 SSD 20/6.0/50 - -
Sliding contact 876 173 44 876 174 44 - -
Sliding contact with holder - - 876 124 44 876 126 44
a min. 119
32
41034144.eps
32
41034244.eps
a
36
41034344.eps
202673k2.p65/311000
22
Bolted 6-conductor suspension on a steel angle section
DIN 933
a min. 119
M8 DIN 934
32
(Dimension a must be specified by the customer)
41034444.eps
32
DIN 933
M8 DIN 934
41034544.eps
a a a a
DIN 933
M8 DIN 934
20
41034644.eps
202673k2.p65/311000
23
PE PH
41034744.eps
Remark: The electrical safety of 4-pole installations and 6-pole suspensions, for example, can
be improved by leaving a section empty between the three phases (PH) if the protec-
tive earth conductor (PE) is arranged on the outside of the suspension bracket.
Unguided entry operations into these arrangements are not possible.
202673k2.p65/311000
24
18 Regulations
Please note:
Conductor lines must be operated in line with generally recognised engineering
standards. Reference is made to the VDE regulations, particularly to VDE 0100.
Reference is also made to the following relevant extracts:
18.1.2 Protection against direct Protection against direct contact is defined as all measures to protect persons from
contact hazards resulting from contact with live parts of electrical equipment. This may be
partial or complete protection.
Partial protection only offers protection against accidental contact. Protection against
accidental contact does not constitute protection against deliberate contact.
Enclosure IP 2X to DIN 40 050 offers protection against accidental contact. Complete
protection only begins with IP 5X to DIN 40 050.
18.2.2 Protection with safety If a nominal voltage of 25 V AC or 60 V DC is exceeded, protection against accidental
extra-low voltage contact must be ensured by means of:
• covers or enclosures with at least IP 2X type of protection to DIN 40 050 or
• insulation which is resistant to a test voltage of 500 V AC for 1 minute.
If a nominal voltage of 25 V AC or 60 V DC is not exceeded, protection against acci-
dental contact is not usually required.
18.2.3 Protective barriers Protective barriers such as mesh screens, perforated plates, etc. may only be consid-
ered as protection against accidental contact if they do not have any openings which
allow live parts to be touched with a mobile test finger according to VDE 0470 Part 1
(minimum enclosure IP 2X to DIN 40 050).
18.2.4 Mechanical strength Covers, protective mesh screens, enclosures and similar must be reliably fixed and
mechanically robust.
18.3 Arrangement for hoists Conductor lines must be arranged or clad in such a way that no accidental contact is
possible in normal operation, e.g. when mounting or walking onto crane runway and
(see VDE 0100 Part 726) crane girder walkways including all access points.
202673k2.p65/311000
Conductor lines must be arranged or protected in such a way that they cannot come
into contact with load supporting means even if loads sway.
25
19 Part no. overview
Conductors
Isolating section
Air-gap interrupt section 876 055 44
Isolating section 876 037 44
Suspensions
Universal 6-conductor suspensions 876 080 44
Bolted 6-conductor suspensions 876 081 44
Single suspension 876 082 44
Retaining plate 876 083 44
Section rail
Section rail 6000 (mm) 979 506 44
Section rail 3000 (mm) 979 503 44
Section rail 120 (mm) 979 508 44
Suspension for section rail 979 520 44
Joint connector for section rail 979 525 44
Funnel transfer section / end cap 876 046 44
45° funnel lead attachment 876 043 44
Funnel entry sections
1-pole 876 151 44
2-pole 876 152 44
3-pole 876 153 44
4-pole 876 154 44
5-pole 876 155 44
6-pole 876 156 44
Connecting cables
Cross-section mm² 2,5 4,0 6,0
Colour black green/yellow black green/yellow black green/yellow
Connecting cables for current collector
895 120 44 895 121 44 895 122 44 895 123 44 895 124 44 895 125 44
pantographs
202673k2.p65/311000
26
20 Resistance to acids, chemicals and fuels
Ethyl acetate Å
Butanol -
Butyl acetate -
Methanol -
Tuluol -
202673k2.p65/311000
Xylene -
The following applies for all chemicals:
Carbon tetrachloride Å
Increased oxidation (corrosion) on con- -
Acetone
ductors (Cu).
Bleaching lye Å
Information on resistance applies to
room temperature (20° C). + resistant + resistant within limits - not resistant 27
Printed in Germany MBR/041001/1T