DEL single conductors

1 Conductors
Single conductor lines with plastic (PVC) enclosure with 25 or 50 mm² conductor
cross-section in 6 m standard lengths.
For ambient temperatures from -30 to +60° C. IP23 enclosure for horizontal and IP20
for vertical mounting arrangements.

2 Current collectors
Single or double current collector pantographs from 15 to 40 A at 100 % CDF for
travel speeds up to 400 m/min. Connection cross-sections up to 6 mm².

3 Power feed
Universal power feed for end or line power feed arrangements.
Connection cross-sections up to 50 mm².

42315044.eps

311000 EN/DE 202 673 44 714 IS 962


Companies are constantly having to meet the demands of rising costs. Improved
efficiency in all parts of production is the logical answer.
Demag conductor systems are an important part of the solution, offering versatility
and efficiency.
Demag DEL single conductors provide a high-performance power supply for mobile
equipment such as cranes and monorails. They can be easily integrated into existing
installations for lasting economical benefits.

• Compact and versatile


• High electrical safety due to large spacing between conductors
• Easy to install and maintain
• Reliable power transmission by current collector pantographs
• Variety of suspension possibilities
• Adapts to customer-specific requirements
• Cost-effective spacing between suspensions
• Expansion joints between conductor sections absorb differences in length due to
temperature variations
• Patented connector system

1 Technical data

Conductors 150/50 current collector arms

Enclosure material PVC Max. continuous current at 100 % CDF (A) 40, 25

Standard lengths (mm) 6000 Max. continuous current at 30 % CDF (A) 50, 30

Conductor cross-section (mm²) 25, 50 Min. curve radius R (mm) 500

Continuous current IN at 100 % CDF (A) 100, 200 Fuses max. (A) 100

Max. voltage UN (V) 690, 1000 Connection cross-section (mm²) 6

Enclosure to DIN 40050 IP 2x Travel speed (m/min) 400

Number of conductors 1-¥ Mounting position horizontal + vertical

Suspension centres max. (mm) 1000, 3000

Curve section radius R min. (mm) 500

Ambient temperature
-30 to +60
max. continuous (°C)
+70 for short periods
max. 1 hour (°C)
Max. length of one straight
conductor section (m) 200 ¹)

Mounting position horizontal + vertical

1) Longer sections on request


202673k1.p65/311000

2
2 Component parts/accessories

42315144.eps

Component parts Current collector arrangement


Conductor connectors Current collector pantographs
Conductor connectors with Carrier plate
power feed
Isolating sections Accessories
Transfer sections e.g. suspensions
• Funnel lead section
• Entry funnel Spare parts
Spacers Sliding contact with spring
End cap Sliding contact bracket

SSE 150 current collector pantograph 42315244.eps SSD 50 current collector pantograph 42315344.eps
202673k1.p65/311000

Isolating section Conductor connector with 10 mm² power feed


42315444.eps 42315544.eps
3
Air-gap interrupt section 42315644.eps Bolted 6-conductor suspension 42315744.eps

Transfer funnel (6-pole) 42315844.eps Universal 6-conductor suspension 42315944.eps

Spacer 42316044.eps Bolted single suspension 42316144.eps


202673k1.p65/311000

End cap/entry section 42316244.eps Conductor connector with 50 mm² power feed 42316344.eps
4
Conductor connector 42316444.eps Section rail with suspension 42316544.eps

Straight section
Cu conductor with PVC enclosure 42316644.eps 45° funnel lead attachment 42316744.eps
202673k1.p65/311000

5
3 Basic structure

DEL

Straight sections

Curved sections

Conductor connector

Conductor connector with power feed

Isolating section

Suspension

with section rail without section rail

Funnel transfer section/end cap

45° funnel attachment End cap Funnel entry section

Current collector pantograph Spacer

Connecting cable

Carrier plate

Example for type designation: DEL 6 – 25 – PVC


202673k1.p65/311000

Enclosure: PVC
Nominal Cu conductor cross-section in mm²
Number of conductors (including PE conductor)
Conductor
Single
6 Demag
4 General arrangement

1000 A 500
DEL conductors
250 400
7
200 6.4 7.1

15
65

500 250 250 1000 500


3
3.1
3.2
3.3
8 7 6.1 6 6.2 4 9 10 3.4 5 1 6.3
7.1 2 41032044.eps

Item Designation Dimensions


1 DEL straight section 5945 mm
2 DEL curved section R ³ 500 mm
3 Conductor connectors
3.1 Conductor connector 25 mm²/100A
3.2 Conductor connector with power feed 1,5 to 10 mm²
55 mm
3.3 Conductor connector 50 mm²/200 A
3.4 Conductor connector with power feed 16 to 50 mm²
3.5 Cover for power feed (not illustrated)
4 Isolating section/air-gap interrupt section 55, 100 mm
5 Suspensions
5.1 Universal 6-conductor suspension
5.2 Bolted 6-conductor suspension
5.3 Single suspension
6 Section rail 120, 3000, 6000 mm
6.1 Suspension for section rail
6.2 Joint connector for section rail
6.3 Section rail for fixing funnel transfer section 120 mm
6.4 Section rail for power feed 16 to 50 mm²
7 End cap, funnel transfer section, end power feed
7.1 Funnel transfer section/end cap
7.2 45° funnel lead attachment
8 Funnel entry section
9 Stops
10 150 or 50 mm current collector pantograph

4.1 Technical data Criteria


Conductor cross-section 25 mm² 50mm ²
Continuous current at 100 % CDF 100 A 200 A
Max. service temperature -30 to + 60 °C
Enclosure material PVC
Enclosure type for horizontal arrangement IP 23
Enclosure type for vertical arrangement IP 20
Continuous max. conductor line length 200 m ¹)
Curved section radius R ³ (mm) 500
1) Longer sections on request

4.2 Literature Designation Part no.


202673k1.p65/311000

DEL conductor lines 208 018 44


DEL components 202 673 44
Assembly instructions 206 382 44
Cross section calculation 201 856 44
DEL components for KBK III 203 087 44
DEL components for DZW position measuring system 208 152 44
7
5 Component parts

5.1 Straight sections Straight sections are 5945 mm long. A length of 6000 mm should be used for design
purposes. Shorter length sections are made using a straight cut. The green/yellow
protective earth (PE) conductor should be arranged to face the crane girder web.
The maximum permissible distance between brackets is 1000 mm, and 200 mm for
conductor connectors, isolating sections and end caps.
Two stop plates must be ordered for each conductor to secure against longitudinal
displacement.

5.2 DEL straight sections

± 0,5
L2 5.3

17
9
55 L1 55 13

1) L1 = Straight section length


2) L2 = Design length
41034944.eps

Conductor cross-section 25 mm² 50 mm²

Continuous current at 100 % CDF 100 A 200 A


Voltage U max 690 V

Voltage within normal arm’s reach 400 V

Conductor material Copper

Service temperature max. -30 to +60 °C

Enclosure type IP 23

Design
Grey enclosure, green/yellow PE conductor section, Cu conductor material, alterna-
tive conductor materials on request.

Item Designation kg Part no.

DEL 1-25-PVC PH, 100 A 876 206 44


1,78
DEL 1-25-PVC PE, 100 A 876 216 44

1 DEL 1-50-PVC PH, 200 A 876 096 44


2,97
DEL 1-50-PVC PE, 200 A 876 106 44

DEL 1-25-PVC D, 40 A 1) 1,78 876 208 44

9 Stop plate 0,01 876 100 44

1) Well suited for data and control lines after checking the operating conditions.

Example for designating and ordering a


straight section for a DEL 1-25-PVC phase, 5945 mm:
Straight section DEL 1-25-PVC PH Part no.: 876 206 44
202673k1.p65/311000

8
202673k1.p65/311000

9
6 DEL curved sections

Curved sections can be made in the factory or on site using a bending device. They
are supplied with 100 mm long straight ends for connection to the straight sections.
These straight ends must be removed if not required. A bending device for on-site
installation for horizontal and vertical curved sections can be supplied on request. The
maximum permissible distance between brackets is 500 mm, and 200 mm for con-
ductor connectors, isolating sections and end caps.

Curve A
Opening on the outside

C Section C – D
±0,5
5,3

17
13

0 10
10 0
R

41032744.eps

Curve I
Opening on the inside

Section C – D

C 13
17
R

±0,5
5,3

0 10
10 0

41032844.eps
202673k1.p65/311000

10
Curve H
Horizontal arrangement, Section E – F
17
Opening facing downwards

5,3 ±0,5

13
E

13

19
0 10
10 0

Rm

n
-R
R3
R2

R4
R1
41032944.eps

Radius R ³ 500 mm

Max. suspension distance 500 mm

The following information is required for ordering curved sections:


Conductor type (e.g. DEL 6-25-PVC)
Curved section type (e.g. curve A)
Radius R in mm
Angle a in degrees

The average radius Rm or individual radii R1 – Rn must be specified for H curves


(horizontal).
The distance between the curved sections must be determined and the radii of the
individual curved sections specified when designing conductor arrangements with
individual suspensions.
Bending device available on request.
Section rails cannot be used with curved sections.
202673k1.p65/311000

11
7 Conductor connectors and power feeds

Conductor connectors with expansion compensation are pushed into conductors.


Conductor connectors with power feed must be additionally provided with an M5
connecting screw to connect ring terminal ends.

100

28,5
DEL rail 50 - 55 DEL rail

41033044.eps

1) M5 connection screw only for conductor connector with power feed.

Conductor connector 25 mm² 50 mm²

Continuous current at 100 % CDF 100 A 200 A


Duty factor 100 % CDF
Expansion compensation + - 2,5 mm

Conductor connector with power feed


Connection cross-section max. 10 mm²
Connecting screw M5
Connecting cable cross-section max. 7,5 mm²

Item Designation ME kg Part no.

3.1 Conductor connector 100 A 24 1,0 876 240 44


Conductor connector 100 A with power
3.2 12 0,55 876 242 44
feed 1,5 to 10 mm²

Conductor connector 200 A with power 4 0,5 876 245 44


3.3
feed 1,5 to 10 mm² 3 0,4 876 244 44

ME = Quantity per package


200 A conductor connectors can also be used for 25 mm² cable cross-sections.

92
46

DEL rail 51 DEL rail

41033144.eps

Conductor connector with power feed


Connection cross-section 16 to 50 mm²
Cable diameter max. 15 mm
202673k1.p65/311000

Type Box terminal

Item Designation ME kg Part no.


Conductor connector 200 A
3.4 4 0,5 876 247 44
with power feed 16 to 50 mm²
3.5 Cover for power feed 1 0,3 876 062 44
12 ME = Quantity per package
8 Isolating sections

Isolating or air-gap interrupt sections are available. Air-gap interrupt sections should
be used for increased demands and arduous operating conditions.
Isolating sections have the same dimensions as conductor connectors. Isolating
sections feature one and air-gap interrupt sections two M5 power feed screws (see
also conductor connectors).

Isolating section Air-gap interrupt section

100
150

28,5

26,5
DEL rail 55 no current DEL rail DEL rail 100 no current DEL rail

Isolator

41032144.eps 41032244.eps

Item Designation ME kg Part no.

4.1 Isolating section 12 0,43 876 250 44


4.2 Air-gap interrupt section 1 0,04 876 055 44

ME = Quantity per package

9 Suspensions
Universal 6-conductor suspension Bolted 6-conductor suspension Bolted single
50
suspension
Ø10 M8 X .... DIN 933 hexagon bolt,
5.5 optionally 1 in the middle or 2 outside 5.5
3

2)
1,5

1,5
1)
13
13

13
50
33

33

33
20

20

20

19 19 19
119 5.1 5.1 6-cond. suspension 119
5.2 8-cond. suspension
152 5.2

5.3 5.4 41032344.eps

1) Can be fitted to 40 x 25 or 40 x 40 C rail section


2) 3,5 x 9,5 screw, ident. no. 350 340 99 for fixing section rail/suspension when section rails are used

Mounting screws and retaining plates must be ordered separately.


Item Designation kg/unit Part no.
5.1 Universal 6-conductor suspension 1) 0,03 876 080 44
5.2 Universal 6-conductor suspension 1) 0,04 876 214 44
5.3 Bolted 6-conductor suspension 0,025 876 081 44
5.4 Bolted single suspension 0,004 876 082 44
5.5 Retaining plate s = 1,5 mm 0,001 876 083 44
202673k1.p65/311000

1) Can be used with section rails

The number of suspension fittings must be selected in accordance with the maximum
distance between suspension centres of 1000 mm and the conductor length.
Isolators to increase the electrical safety on request. 13
10 Section rail

M8

41,5
34

26
Universal 6-cond. susp.
41032544.eps

A max. distance between suspension centres of 3000 mm is possible for horizontal


mounting arrangements and 2000 mm for vertical mounting arrangements with sec-
tion rails.

The number of suspension fittings for section rails (M8x45 screw) must be selected in
accordance with the distance between suspension centres. One package contains
screws, nuts and plates for 5 complete suspension points.
Item Designation Length in kg/unit Part no.
mm
or ME

Section rail 6000 6000 mm 5,50 979 506 44


6
Section rail 3000 3000 mm 2,75 979 503 44

6.1 Suspension for section rail 5 0,30 979 520 44

6.2 Joint connector for section rail 1) 1 0,15 979 525 44

6.3 Section rail 120 2) 120 mm 0,11 979 508 44

6.4 Section rail for power feed 16 – 50 mm² 590 mm 1 876 010 44

ME = Quantity per package

1) One connector is required per section rail joint.


2) Fixture for funnel transfer section

Horizontal arrangement Vertical arrangement

41032644.eps

2
[mm ] 25 50 25 - 50 25 50 25 - 50

"A"
3 2 1 2 1, 5 1
[m]
[m] 2,5 1) 1,5 1) - 1,5 1) 1,0 1) -
202673k1.p65/311000

Maximum suspension distance “A” (see diagram on page 7)

Note: The distance between the plastic suspensions (see page 7, item 5) must not exceed
1000 mm and does not increase when section rails are used.

14 1) Suspension distance for 8-conductor suspension


11 End cap, funnel transfer section and end power feed

End caps are used at the ends of track sections and as straight transfer sections.
They can be used as end power feeds up to 10 mm² connection cross-section.
Section rail 6.3 is used for attachment to steel superstructures.
Set the DEL expansion joints as described in the assembly instructions before fixing
end caps/transfer sections into place.

45
18,5

26,5
45 no current
65

41033244.eps

Transfer speed: max. 100 m/min dead section 45 mm


Horizontal offset: max. ± 4 mm
Vertical offset: max. ± 4 mm
Funnel spacing: max. 5 mm
Power feed on M5 screw possible (ring terminal end required)
Max. connection cross-section 10 mm²
Max. cable diameter 7,5 mm

Note: During transfer operations, use 2 current collector pantographs with a minimum
centre distance of 140 mm.
Item Designation kg/unit Part no.
7.1 Funnel transfer section / end cap 0,024 876 046 44
6.3 Section rail 120 1) 0,11 979 508 44

1) For fixing end cap, funnel transfer section

45° funnel lead attachment Funnel lead attachment for transfer section. Used for angular (45°) transfer operations
e.g. switches for horizontal DEL mounting arrangements. Funnel lead attachments
are clipped onto funnel transfer sections (item 7.1). Dead section 69 mm.
30

23,5 no current 19

Transfer section
202673k1.p65/311000

41033344.eps

Item Designation kg/unit Part no.


7.2 Funnel lead attachment 0,002 876 043 44

During transfer operations, use 2 current collector pantographs with a minimum


centre distance of 190 mm. 15
13 Funnel entry sections

39 110 A

M8

25
64

5
173
218
111
7.1

B
A

41033444.eps

1 – 10-pole funnel entry section Quantity of


Item Dimension A Dimension B Weight (kg) Part no.
conductors 1)
1 124 - 0,16 876 151 44
2 143 19 0,18 876 152 44
3 162 38 0,20 876 153 44
4 181 57 0,22 876 154 44
8 5 200 76 0,24 876 155 44
6 219 95 0,28 876 156 44
7 238 114 0,30 876 157 44
8 257 133 0,32 876 158 44
10 295 171 0,36 876 159 44

Example for designating and ordering a


6-pole DEL entry section:
DEL 6-pole entry section, Part no. 876 156 44

Funnel entry sections can only be used with funnel transfer sections (item 7.1, see
page 15).
Transfer speed : max. 100 m/min dead section 218 mm
Horizontal offset : max. ± 30 mm
Vertical offset : max. ± 25 mm
Note: During transfer operations, use 2 current collector pantographs with a minimum
centre distance (item 10.1, page 19) of 485 mm.
202673k2.p65/311000

16
14 Expanding section

41768344.eps

14.1 Explanation and exam- 1 / 25 / PH / LTG 10 mm2


ple for DEL expansion
section abbreviations Cable link

Phase/data line
Conductor cross-section
Number of poles

Use for track expanding joints of ± 30 mm


Item Designation Part no.
2
Expanding section 1/25/PH/LTG 10 mm 876 340 44
Expanding section 1/25/PE/LTG 10 mm2 876 341 44
not shown Expanding section 1/25/DL/LTG 2,5 mm2 876 342 44
Expanding section 1/25/PH/LTG 50 mm2 876 343 44
Expanding section 1/25/PE/LTG 50 mm2 876 344 44
202673k2.p65/311000

17
15 Stop

All straight DEL conductor lines must be


provided with a stop to secure them a) b)
against longitudinal displacement. Sec-
tions can be secured with end caps/
transfer funnel sections bolted at the
ends or secured with adhesive stop
plates stuck at the centre of the section.
Stop plates are self-adhesive.

Symbols:
x = Stop
o = Joint
a) = Line half a) a) b)
b) = Line half b)
> = Funnel/end cap 41034844.eps

Item Designation kg/unit Part no.


9 Stop plate 2) 0,01 876 095 44

2) Two stop plates are required for every conductor section

16 150 and 50 current collector pantographs

16.1 Explanation and exam- DEL – SSE 40 / 6.0 / 150 / Bz


ple for DEL current
collector pantograph Bz = Bronze sliding contact
abbreviations Gr = Graphite sliding contact
Pantograph length in mm
Max. connecting cross-section
Permissible continuous current
E = single
D = double
Current collector pantograph
Conductor
Single
Demag
202673k2.p65/311000

18
16.2 150 current collector L1

pantographs 18,8 10.1.1 L2

10.1.5

+30
106 +30
7,5
49
21
7,5
1) Max. connecting
cable see type
+12
10.1.4 183 +12
10.1.3 M6 hexagon nut (integrated) 41033544.eps
10.1.2 M6 hexagon bolt (22 mm + clamping length)

1) Pin ø 4 x 3 only for PE pantograph

Max. horizontal offset ± 30 mm


Max. vertical offset ± 30 mm
150 current collector pantograph suitable for unguided entry and transfer operations
see also item 10.3, page 20 (Spacers)
Example for designating and ordering a
DEL 150 current collector pantograph:
DEL-SSE 20/6.0/150/Gr. phase current collector pantograph Part no. 979 352 44

Item Designation Phase Protective Permissible kg/unit L1 L2


Part no. earth continuous current
Part no. for duty factor
100 % 60 % 30 %
SSE 40/6.0/150/Bz 2) 876 350 44 876 351 44 40 A 45 A 50 A 0,120
66 42
SSE 20/6.0/150/Gr 2) 3) 876 352 44 876 353 44 20 A 25 A 25 A 0,120
10.1
SSE 60/10/150/Bz 2) 6) 876 280 44 876 281 44 60 A 65 A 70 A 0,1
90 60
SSE 30/10/150/Gr 2) 3) 6) 876 282 44 876 283 44 30 A 35 A 40 A 0,1

Accessories: Item Designation DIN Part no.


10.1.1 Screw M 6 x 60 DIN 912 321 516 99
10.1.2 Screw M 6 x 25 4) DIN 933 307 408 99
10.1.3 Nut M 6 DIN 934 337 571 99
10.1.4 Spring ring A 6 DIN 127 343 806 99
10.1.5 Special tensile spring 5) - 876 145 99

2) Highly flexible connecting cable with double insulation must also be ordered (see page 21, item 16.4). The
smallest required conductor cross-section (2,5 – 6 mm²) must be used to keep the reaction forces on the
current collector pantograph as low as possible.
3) Current collector pantographs with graphite sliding contacts for operation outdoors, near salt water and
chemicals. Use double current collector pantographs for operation near salt water and chemicals.
4) For 3 mm max. material thickness.
5) For operation under arduous conditions.
6) Not suitable for entry / transfer.
202673k2.p65/311000

19
16.3 50 current collector
pantograph

+8 +8 +8
52,5 -8 52,5 -8 52,5 -8

66 66
12,5 42 42

12
59 +- 12

12
59 +- 12
max. 6 mm²
max. 6 mm²

41033644.eps

Max. horizontal offset ± 10 mm


Max. vertical offset ± 12 mm
Item Designation Phase D PE D Duty factor kg /
Part no. Part no. unit
100 % 60 % 30 %

SSE 25/6.0/50/Bz 1) 876 365 44 876 366 44 25 A 30 A 30 A


50 0,04
current SSE 15/6.0/50/Gr 1)2) 876 367 44 876 368 44 15 A 15 A 20 A
10.2 collector 5 6
panto- SSD 50/6.0/50/Bz 1) 876 370 44 876 371 44 50 A 60 A 60 A
graph 0,07
SSD 30/6.0/50/Gr 1)2) 876 372 44 876 373 44 30 A 30 A 40 A

1) Highly flexible connecting cable with double insulation must also be ordered (see page 21, item 16.4). The
smallest required conductor cross-section (2,5 – 6 mm²) must be used to keep the reaction forces on the
current collector pantograph as low as possible.
2) Current collector pantographs with graphite sliding contacts for operation outdoors, near salt water and
chemicals. Use double current collector pantographs for operation near salt water and chemicals.

Example for designating and ordering a


DEL 50 current collector pantograph:
DEL – SSE 25/6.0/50/Bz. Phase current collector pantograph Part no. 979 645 44

Spacers
1)
15.8
19

1) Dimensions when fitted 41033844.eps

Spacers for current collector pantographs for unguided entry and transfer operations.
202673k2.p65/311000

(One spacer is required for each current collector pantograph).

Item Designation DEL centres Part no.

19 mm 876 142 44
10.3 Spacer
15,8 mm 876 143 44
20
Item Cross-section in Part no. 1) Type Colour Outside dimension
16.4 Connecting cable mm² mm
for current collector 2,5 895 120 44 black
4,1
pantographs 2,5 895 121 44 green, yellow
4,0 895 122 44 black
10.4 YFFM 5,1
4,0 895 123 44 green, yellow
6,0 895 124 44 black
5,6
6,0 895 125 44 green, yellow

1) Length must be specified

16.5 Bore hole template 150 current collector pantographs


for current collector
ø 4,5 only for PE conductor 6
pantographs
7.5

= = 19 = =

Arrangement of bore holes in the carrier plate

41033944.eps

A current collector bracket is available for 50 and 150 current collector pantographs
(see data sheet 206 630 44). Part no. 876 260 44
An angle mounting section with bore holes is also available for 150 current collector
pantographs, e.g. for fitting to C rails. Part no. 991 218 44

50 current collector pantograph

5
(6 with PE)

= = 19 = =

Arrangement of bore holes in the carrier plate


41034044.eps

16.6 Spare parts for current Designation For current collector pantograph
SSE 40/6.0/50 SSE 20/6.0/50 SSE 40/6.0/150 SSE 20/6.0/150
collector pantographs
202673k2.p65/311000

Type
SSD 40/6.0/50 SSD 20/6.0/50 - -
Sliding contact 876 173 44 876 174 44 - -
Sliding contact with holder - - 876 124 44 876 126 44

Type - - SSE 60/10/150 SSE 30/10/150


Sliding contact with holder - - 876 295 44 876 296 44
21
17 Mounting examples

Bolted 6-conductor suspension on a C rail

a min. 119

32
41034144.eps

Bolted 6-conductor suspension on a C rail


a

32

41034244.eps

Universal 6-conductor suspension on a C rail

a
36

41034344.eps
202673k2.p65/311000

22
Bolted 6-conductor suspension on a steel angle section

DIN 933
a min. 119
M8 DIN 934

32
(Dimension a must be specified by the customer)

41034444.eps

Bolted 6-conductor suspension on girder web

32

DIN 933
M8 DIN 934

41034544.eps

Single suspension on a steel angle section

a a a a
DIN 933
M8 DIN 934

20

41034644.eps
202673k2.p65/311000

23
PE PH

41034744.eps

Remark: The electrical safety of 4-pole installations and 6-pole suspensions, for example, can
be improved by leaving a section empty between the three phases (PH) if the protec-
tive earth conductor (PE) is arranged on the outside of the suspension bracket.
Unguided entry operations into these arrangements are not possible.

202673k2.p65/311000

24
18 Regulations

Please note:
Conductor lines must be operated in line with generally recognised engineering
standards. Reference is made to the VDE regulations, particularly to VDE 0100.
Reference is also made to the following relevant extracts:

18.1 Definitions (see


VDE 0100, Part 200)
18.1.1 Arm’s reach Arm’s reach is the area in which a person can reach in all directions without any spe-
cial equipment from places in which he or she would normally walk or stand. From
the position in which a person is standing, arm’s reach is usually defined as at least
2,5 m in height and at least 1,25 m to the side and downwards (see DIN 31 001
Sheet 1).
In places where long or bulky, non-insulated objects are usually handled, the mini-
mum arm’s reach dimension must be correspondingly increased.

18.1.2 Protection against direct Protection against direct contact is defined as all measures to protect persons from
contact hazards resulting from contact with live parts of electrical equipment. This may be
partial or complete protection.
Partial protection only offers protection against accidental contact. Protection against
accidental contact does not constitute protection against deliberate contact.
Enclosure IP 2X to DIN 40 050 offers protection against accidental contact. Complete
protection only begins with IP 5X to DIN 40 050.

18.2 Protection against


direct contact (see
VDE 0100 Part 410-5)
18.2.1 Live electrical parts The live parts of electrical equipment must either be insulated along their entire length
or protected against direct contact by means of their design, position, arrangement
or special devices.

18.2.2 Protection with safety If a nominal voltage of 25 V AC or 60 V DC is exceeded, protection against accidental
extra-low voltage contact must be ensured by means of:
• covers or enclosures with at least IP 2X type of protection to DIN 40 050 or
• insulation which is resistant to a test voltage of 500 V AC for 1 minute.
If a nominal voltage of 25 V AC or 60 V DC is not exceeded, protection against acci-
dental contact is not usually required.

18.2.3 Protective barriers Protective barriers such as mesh screens, perforated plates, etc. may only be consid-
ered as protection against accidental contact if they do not have any openings which
allow live parts to be touched with a mobile test finger according to VDE 0470 Part 1
(minimum enclosure IP 2X to DIN 40 050).

18.2.4 Mechanical strength Covers, protective mesh screens, enclosures and similar must be reliably fixed and
mechanically robust.

18.3 Arrangement for hoists Conductor lines must be arranged or clad in such a way that no accidental contact is
possible in normal operation, e.g. when mounting or walking onto crane runway and
(see VDE 0100 Part 726) crane girder walkways including all access points.
202673k2.p65/311000

Conductor lines must be arranged or protected in such a way that they cannot come
into contact with load supporting means even if loads sway.

25
19 Part no. overview

Conductors

Conductor cross-section (mm²) 25 50

Continuous current at 100 % CDF (A) 100 200


Straight section
Phase, grey 876 206 44 876 096 44
PE conductor, green/yellow 876 216 44 876 106 44
Data conductor, grey 876 208 44
Stop plate 876 100 44
Conductor connector 876 240 44 876 245 44 (with power feed)
Conductor connector with power feed

Conductor connector 100 A with


876 242 44
power feed 1,5 – 10 mm²

Conductor connector 200 A with


876 247 44
power feed 16 – 50 mm2

Isolating section
Air-gap interrupt section 876 055 44
Isolating section 876 037 44
Suspensions
Universal 6-conductor suspensions 876 080 44
Bolted 6-conductor suspensions 876 081 44
Single suspension 876 082 44
Retaining plate 876 083 44
Section rail
Section rail 6000 (mm) 979 506 44
Section rail 3000 (mm) 979 503 44
Section rail 120 (mm) 979 508 44
Suspension for section rail 979 520 44
Joint connector for section rail 979 525 44
Funnel transfer section / end cap 876 046 44
45° funnel lead attachment 876 043 44
Funnel entry sections
1-pole 876 151 44
2-pole 876 152 44
3-pole 876 153 44
4-pole 876 154 44
5-pole 876 155 44
6-pole 876 156 44

Current collector pantographs 50 150


Type bz = Bronze sliding contact
SSE GR SSE BZ SSD GR SSD BZ SSE GR SSE BZ SSE GR SSE BZ
gr = Graphite sliding contact
Permissible continuous current (A) 15 25 30 50 20 40 60 30
Phase 876 367 44 876 365 44 876 372 44 876 370 44 876 352 44 876 350 44 876 280 44 876 282 44
Protective earth 876 368 44 876 366 44 876 373 44 876 371 44 876 353 44 876 352 44 876 281 44 876 283 44
Spacer, 19 mm centres 876 142 44

Connecting cables
Cross-section mm² 2,5 4,0 6,0
Colour black green/yellow black green/yellow black green/yellow
Connecting cables for current collector
895 120 44 895 121 44 895 122 44 895 123 44 895 124 44 895 125 44
pantographs
202673k2.p65/311000

26
20 Resistance to acids, chemicals and fuels

20.1 Acids Agent Remarks


Acid Conc.
Chromic acid 40 % Å
Avoid direct contact.
Chromic sulphuric acid 20 % Å
Nitric acid 10 % +
Sulphuric acid 10% +
Acetic acid 5% +
Increased sliding contact wear.
Carbonic acid 10 % +
Oleic acid +
Tartaric acid 10 % +
Formic acid 20 % +
Arsenic acid 20 % +
Boric acid 10 % +
Max. temperature
Hydrofluoric acid + + 30°C
Lactic acid 10 % + Increased current collector
wear from +30°C to +60°C.
Phosphoric acid 50 % +
Oxalic acid 10 % +
Hydrochloric acid 20 % Å
Citric acid 10 % +

20.2 Fuels, oils, grease etc. Agent Remarks


Cleaning petrol Å
Normal grade petrol Å
Super grade petrol Å
Avoid direct contact.
Kerosene Å
White spirits Å
Diesel oil Å
Benzene -
Oils, greases (non-aromatic) +
Drilling oil Å Avoid direct contact.
ATE brake fluid Å
Foodstuffs and consumables +
Distance < 5km + Use double current collector
Salt water
Distance > 5km + pantographs.

20.3 Chemicals Agent Remarks


<1% +
Alkaline solutions
>1% Å/- Min. distance 5 m.
Ammoniacal water -
Alcohols +
alipathic -
Hydrocarbons
aromatic -
Chloric solvents -
Esters -
Ketone -
Trichlorethylene -

Alkaline solvents Cannot be generally answered.

Ethyl acetate Å
Butanol -
Butyl acetate -
Methanol -
Tuluol -
202673k2.p65/311000

Xylene -
The following applies for all chemicals:
Carbon tetrachloride Å
Increased oxidation (corrosion) on con- -
Acetone
ductors (Cu).
Bleaching lye Å
Information on resistance applies to
room temperature (20° C). + resistant + resistant within limits - not resistant 27
Printed in Germany MBR/041001/1T

Demag Cranes & Components GmbH


P.O. Box 67 · D-58286 Wetter
Telephone (+49/2335) 92-0 · Telefax (+49/2335) 927676
Internet http://www.dematic.com

Reproduction in whole or in part only with prior consent of Demag Cranes & Components GmbH, D-58286 Wetter Not liable for errors or omissions. Subject to change.