Both ends of electrical cable on reels shall be regularly inspected by the Bidder
who shall ensure they are well sealed such as with several wraps of electrical
tape before and during outdoor storage.
Protection against sun ageing, for cable on reels stored outdoors, shall be
provided by a protective covering around the outer layers and furnished by the
Bidder if not already provided by the cable manufacturer.
The Bidder shall ensure that installed items are protected with the same level of
protection accorded them while in storage.
Heaters shall be energized with temporary power and provided with external
pilot lights to monitor the feeds. Dust contamination shall be avoided by suitable
temporary coverings, with provisions for re-sealing on control panels and
similar items.
Protection shall be provided by the Bidder for electrical cables in trays, ducts,
risers and other electrical equipment when and where required, by means of
fireproof covers or barriers to prevent damage from weld splatters, fires, water
damage, falling debris, moving equipment, etc.