The building has been located at ground level in a such maner ensuring easy access
for gas cylinder supply vechicles. No parking should be permitted within the
delivery and storage area, other than for loading and unloading cylinders.
Location of the building should be marked clearly on the site plan for ease of
identification in the event of an emergency.
The floor and hard standing should be level and constructed of concrete or other
non-combustible and non-porous material. A concrete finish is preferred and is
likely to have a longer life.
The ambient temperature in rooms for supply systems shall be in the range of 10 to
40 °C. Max. allowed room temperature with sound-insulated compressors is
+35°C.
The ventilation air with air-cooled compressors and vacuum-pumps contains close
to 100% of the energy consumed by their electric motors in the form of heat.
Artificial ventilation increases the flow speed of cooling air inside the installation
room and guarantees the required flow of air by forced ventilation.
Lighting
Oxygen and nitrous-oxide manifold rooms should be provided with lighting to an
illumination level of 150 lux (15 lumens/sq ft) by means of bulkhead lighting
fittings to IP 54 BS 5490:1977.
Compressed air and vacuum plant room should be provided with a lighting level of
200 lux (20 lumens/sq ft).
Noise control
Manifold and plant rooms should be designed and constructed to ensure the
satisfactory control of noise emission. The effect of vacuum pumps or compressors
running together will be to increase the free-field noise level outside the plantroom
by 5 dB(A) for each additional pump or compressor operation over and above the
specified limits.
The minimum size of the air inlet and outlet apertures is calculated according to
Health Technical Memorandum 02-01, Part A - Separated ventilation openings
should be equivalent to at least 1.5 % of the total area of the walls and floor.
3600 · Σ P
V = --------------- (m3/h)
ρ · cp · Δt
The ventilator output must be approx. 15 % greater than the required flow of
cooling-air in order to provide a satisfactory cooling, even at high summer
temperatures.
The maximum temperature of the compressed air and vacuum room must not
exceeded + 35 oC. This temperature must be kept by an air-conditioning system
which is not the subject of this project design.
The maximum air intake of 162 m3/h for 3 compressor may be neglected in this
calculation. The minimum ventilator (fan) output is therefore
The minimum size of the air inlet aperture is calculated with the aid of the
following formula:
Q 10322
Ain = -------------- = ------------ = 2.867 m2 > 1.457 m2
3600 x ws 3600 x 1
The calculated inlet air aperture is assumed for all the three rooms.
The outlet aperture for the compressed air and vacuum plant room is the aperture of
the cooling air fan outlet.
* * *
Grejanje
Prostorija stanice komprimovanog vazduha se greje recirkulisanim toplim vazduhom iz
vazdušnih kompresora. Potrebna količina toplog vazduha, se preko rešetke sa regulatorom
protoka vazduha ubacuje u prostoriju iz odsisnog kanala otpadnog vazduha kompresora.
Ventilacija
Vazduh za hlađenje kompresora izvlači se iz komresorske prostorije preko limenih vazdušnih
kanala pomoću jednog trobrzinskog aksijalnog ventilatora. Ventilator se uključuje kada se bilo
koji od kompresora aktivira, tj. počne sa kompresijom vazduha, a isključije se kada se i
kompresori za vazduh isključuju.
Režim rada ventilatora je sledeći:
I brzina
- Ventilator se uključuje kada je u pogonu jedan kompresor.
- Protok vazduha iznosi V = 11000 m3/h
- Napor ventilatora Hst = 100 Pa
II brzina
- Ventilator se uključuje kada su u pogonu dva kompresora.
- Protok vazduha iznosi V = 18000 m3/h
- Napor ventilatora Hst = 100 Pa
III brzina
- Ventilator se uključuje kada su u pogonu tri kompresora.
- Protok vazduha iznosi V = 26000 m3/h
- Napor ventilatora Hst = 100 Pa
Kompresorska prostorija se ventiliše (hladi) pomuću jednog aksijalnog ventilatora koji je ugrađen
u spoljni zid prostorije. Ventilator se uključuje pomoću termostata kada temperatura vazduha u
prostoriji dostigne t = 36ºC (max. dozvoljena temperatura vazduha u prostoriji iznosi 40°C). U
spoljnim vratima prostorije ostaviti otvor za usisi svežeg vazduha minimalne efektivne površne
od 3,5 m2.
Prostorije vakuum stanice se ventiliraju (hlade) pomuću aksijalnih ventilatora koji su ugrađeni u
spoljni zid prostorija. Ventilatori se uključuju pomoću termostata kada temperatura vazduha u
prostorijama dostigne t = 36ºC (max. dozvoljena temperatura vazduha u prostorijama iznosi
40°C).
U spoljnim vratima prostorija ostaviti otvor za usis svežeg vazduha minimalne efektivne površne
od 1,5 m2.