SINODRIVE 100

INVERTER
User's manual
Preface
First of all,thank you for purchasing SD100 series inverter!
This manual introduce how to correctly use SD100 series inverter,
before using(instalation、run、maintenance、check,etc.),please understand
the safety precautions .
Upon unpacking , please confirm the followings :
1、Check whether there is any damage occurred during transportation ;
whether there is any damage or spalling in the componets;whether the
main body is bumpped.
.
2、Check whether the model and the rated values on the nameplate of the
inverter are in accordance with your order . The box contains the product , and
operation manual for the user .
Our corporation is strict in manufacturing , packing and quality assurance
system , but if you find some missing inspections , please contact our corpora-
tion or the supplier as soon as possible .

Note
● To illustrate the product details,the illustrations in this manual are sometimes to unload cloak or safety

cover of state。before using this product,please be sure to installed shell or cover by the regulation。and

operate according to the instruction.

Illustrations in this manual to illustrate only, and may be different from the product you ordered.

Because of upgrading or specification changes,and in order to improve the convenience and accuracy of

the specification,the contents of this manual will promptly make changes.

Order the manual when required due to damage or omissions,please contact the regional agents,or our

customer service center.

If there are still some problem when you are using,please contact our customer service center.

Unified national service hotline:400-8818-689

-I-
Contents

Preface … … … … … … … … … … … … … … … … … … i Chapter 5 Function Parameters


Group F0: Basic Function Group … … … … … … … … … 29
Chapter 1 Safety and Cautions Group F1: Motor Parameters … … … … … … … … … … … 30

1.1 Safety Cautions … … … … … … … … … … … … … … 1 Group F2: V/F Control Parameters … … … … … … … … 31

1.2 Cautions … … … … … … … … … … … … … … … … … 2 Group F3: Input Terminal … … … … … … … … … … … … 32


Group F4: Output Terminal … … … … … … … … … … … 33
Group F5: Start and Stop Control … … … … … … … … … 34
Chapter 2 Product Information
Group F6: Keyboard and Display … … … … … … … … … 35
2.1 Naming Rules........................................................... 4
Group F7: Auxiliary Function … … … … … … … … … … 35
2.2 Nameplate … … … … … … … … … … … … … … … … 4
Group F8: Fault and Protection … … … … … … … … … … 36
2.3 SD100 Series of Inverters … … … … … … … … … … 5
Group F9: PID Function … … … … … … … … … … … … 38
2.4 Technical Specifications … … … … … … … … … … … 6
Group FA: Swing Frequency 、Fixed-length、Count and
2.5 Product appearance and dimension of
Fixed-time … … … … … … … … … … … … … … … … 39
installation holes … … … … … … … … … … … … … … 7
Group FB: Muti-speed Function and Simple PLC Function
2.6 Optional Parts … … … … … … … … … … … … … … … 9
… … … … … … … … … … … … … … … … … … … … … … 40
2.7 Selection Braking Units …
…… … … … … … …11
Group FC: Communication Parameter … … … … … … … 42
2.8 Daily Maintenance of Inverter … … … … … … … …13
2.9 Warranty Group FD: Paticular Function … … … … … … … … … … 43
… …… … ……… … … … … … … … … …14
2.10 Model Selection … … …… … … … … … … … … …14 Group FV: Status Parameter … … … … … … … … … … … 44

Chapter 3 Mechanical and Electrical Installation Chapter 6 Parameter Description

3.1 Mechanical Installation ……… … … … … … …… …… 15


3.2 Electrical Installation ……… … … … … … … … …… 18 Chapter 7 SD100 Communication Protocol and
Description of Communication
Chapter 4 Operation and Display 7.1 SD100 Series Communication Protocol … … … … 71
4.1 Introduction to operation and display interface… … 25 7.2 Description of Communication Card … … … … … 81
4.2 Description of function code viewing and modification
methods … …… …… ……… … ………… …… … ……23
4.3 Method of Viewing Status Parameter ………… ……… 27 Chapter 8 Troubleshooting and
4.4 Digital Setup Modify on-line … … … … … … … …… 27 Countermeasures
4.5 Password Setting … … … …… … … … … … …… …… 27 8.1 Fault Alarm and Countermeasures … … … … … … 82
4.6 Suggestive Information… …… … … … … … … … ……27 8.2 Common Faults and the Resolution … … … … … … 89
Chapter 1 Safety and Cautions

Chapter 1 Safety and Cautions


Safety Definition:
To make sure your body、equipment and property are safe , please read this chapter thoroughly
before using the inverters made in our company .
These are two kinds of safety cautions in the manual :
! Danger : Operations which are not performed according to the requirements may cause severe
hurt or even death .
! Note : Operations which are not performed according to requirements may cause moderate hurt
or light hurt or equipment damage .

1.1 Safety Cautions


1.1.1 Before Installation
! Danger
Do not use the inverter which is damaged or has defects , or there will be danger of injury.
1.1.2 During Installation
! Danger
Please install the inverter on incombustible surface like metal , and keep away from flammable
substances !Otherwise it may cause fire .
! Note
When more than two inverters are to be installed in one cabinet , please pay attention to the installation
locations to ensure the cooling effect (refer to Chapter 3 Mechanical and Electrical installation ) .
Do not drop the lead wire stub or screw in the inverter , or the inverter may be damaged !
1.1.3 Wiring
! Danger
Only the qualified electrical engineer can perform the wiring , otherwise there will be danger of
electric shock !
A circuit breaker must be installed between the power supply and the inverter , otherwise there will
be danger of electric shock !
Wiring can only be done after the mains input is cut off , otherwise there will be danger of electric
shock!
Please connect the inverter to the ground according to the standard , otherwise there will be danger
of electric shock !
! Note
Do not connect the input terminals with the output terminals(U,V,W), otherwise the inverter may be
damaged!
The wire size should be determined according to the manual , otherwise accident may occur !

1
Chapter 1 Safety and Cautions

1.1.4 Before Power-on


! Danger
Please confirm the mains voltage level is consistent with that of the inverter and input and output
wirings are correct , and check if there is any short circuit in peripheral circuit and if the wiring is fixed
and fast , otherwise the inverter may be damaged !
Mount the cover plate properly before power-on the inverter , otherwise there will be danger of
electric shock !

! Note
Dielectric strength test had been done at factory . Therefore , user don`t need to do this test again .
All the peripheral parts shall be connected correctly according to the manual.

1.1.5 After Power-on


! Danger
Do not open the cover of the inverter after power-on , otherwise there will be danger of electric shock !
Do not touch the inverter and its circuit with wet hand , otherwise there will be danger of electric shock !
Do not touch the inverter terminals , otherwise there will be danger of electric shock !
! Note
Do not change the factory settings of parameter , otherwise the inverter may be damaged !
1.1.6 Running
! Danger
Do not approach the equipment when restart function is enabled , otherwise there will be danger of injury !
Do not touch the fan and the discharging resistor , otherwise burning may occur!
Non-professional person should not detect the signal of a running inverter , otherw ise there will be danger
of injury or inverter damage!
! Note
Do not start and stop the inverter by on/off of the contactor , otherwise the inverter may be damaged !
1.1.7 Maintenance
! Danger
Please do not repair or maintain the inverter with power on , otherwise there will be danger of electric
shock !

1.2 Cautions
1.2.1 Check the Insulation of the Motor
When the motor is used for the first time or reused after storing for a long time , you must check the
insulation of the motor . It is recommended to use a 500V Mega- Ohm-Meter to check and the measured
insulation resistance shall not be less than 5MΩ.

2
Chapter 1 Safety and Cautions

1.2.2 Thermal Protection of Motor


If the selected inverter is not matching the r ated capacity of the motor , especially when the rated power
of the inverter is higher than that of the motor ,make sure to adjust the parameters for motor protection in the
inverter or to install thermal relay to protect the motor .

1.2.3 Running above Rated Frequency


Please consider the capability of the mechanical devices when you need the inverter to run at the frequency
higher than 50Hz .

1.2.4 Vibration of the Mechanical Device


If the inverter encounters the resonance point of load device within a certain output frequency range .
You can avoid that by configuring the hopping frequency parameters in the inverter .
1.2.5 Pressure-sensitive Device or Capacitor Improving Power Factor at the
Output Side
Since the inverter output is PWM wave , the capacitor for improving the power factor or pressure-
sensitive resistor for lightening-proof shouldn`t be installed at the output side of the inverter ,otherwise
it is easy to cause transient over current and even damage the inverter . Don`t use it!
1.2.6 Switching Devices like Contactors Used at the Input and Output Ends
If the contactor is required to be installed between the inverter and the power supply , it is prohibited to
start or stop the inverter with the contactor . If the user has to use the contactor to start and stop the
inverter , the interval shouldn`t be less than an hour . Frequent charging and discharging may reduce
the service life of the capacitor . If the switches like contactors are equipped between the output
terminal and the motor , make sure to start and stop the inverter when it has no output ,otherwise the
modules in the inverter may be easily damaged .
1.2.7 Change three phase Input into two phase Input
It is not allowed to change the three phase inverter into two phase one . Otherwise , it may cause fault or
damage the inverter .
1.2.8 Altitude and Deration
When the altitude is higher than 1000m , the cooling effect of inverter is deteriorated due to the rarefaction
of air , the derating using is necessary and please consult our company for detailed technical support .
1.2.9 Check the Insulation of the Motor
The cooling fan and the rotor shaft of the non-variable-frequency motor are coaxially connected . When
the rotating speed is reduced , the cooling effect will be poorer . Therefore , a powerful exhaust fan should
be installed or the motor should be replaced with variable-frequency motor to avoid the over heat
of the motor .

3
Chapter 2 Product Information

Chapter 2 Product Information


2.1 Name Designation Rules

SD100 -4T 11 G /15 P C

Iverter series Mark Brake Unit


Null None

C Only brake
Mark Voltage Level
unit
2S single-phase 220V ●
2T Three-phase 220V
4T Three-phase 380V
Mark Function Type
P F an& Pump
Motor Power
G General
(KW)

Corresponding Relationship

Mark 0.4 0.7 1.5......22 30 37......110 132

Motor Power (KW)0.4 0.75 1.5......22 30 37......110 132

Fig.2-1 Name designation rules

2.2 Nameplate

MODEL: SD100-4T-7.5G/11PC Model of the inverter


INPUT: AC3PH 380V 50/60Hz 20.5A/26.0A Rated input voltage ,
frequency and current
OUTPUT: AC3PH 380V 0~650Hz 17A/25A Rated output voltage ,
frequency and current
S/N: Bar code

SHENZHEN SINOVO ELECTRIC TECHNOLOGIES CO.,LTD.


MADE IN CHINA

4
Chapter 2 Product Information

2.3 SD100 Series of Inverter

Model Input Voltage Power Capacity Input Current Output Current Adaptable Motor
(kVA) (A) (A) (kW)

SD100-2S-0.4 1.0 5.4 3.0 0.4


Single - phase
SD100-2S-0.7 220V range: 1.5 8.2 4.7 0.75
SD100-2S-1.5 3.0 14.0 7.5 1.5
-15% to 20%
SD100-2S-2.2 4.0 23.0 10.0 2.2
SD100-2T-0.7 1.5 5.5 5.0 0.75
SD100-2T-1.5 3.0 7.7 7.0 1.5
SD100-2T-2.2 4.0 12.0 11.0 2.2
SD100-2T-3.7 5.9 18.0 17.0 3.7
SD100-2T-5.5 Three-phase 8.9 26.0 25.0 5.5
SD100-2T-7.5 220V range: 11 34.0 33.0 7.5
SD100-2T-11 -15% to 15% 17 50.0 49.0 11
SD100-2T-15 21 66.0 65.0 15
SD100-2T-18.5 24 76.0 75.0 18.5
SD100-2T-22 30 91.0 90.0 22
SD100-2T-30 40 122.0 120.0 30
SD100-2T-37 57 147.0 145.0 37

SD100-4T-0.7 1.5 3.4 2.3 0.75


SD100-4T-1.5 3.0 5.0 3.7 1.5
SD100-4T-2.2 4.0 5.8 5.1 2.2
SD100-4T-3.7 5.9 10.5 8.5 3.7
SD100-4T-5.5 8.9 14.6 13 5.5
SD100-4T-7.5 11 20.5 17 7.5
SD100-4T-11 17 26.0 25 11
SD100-4T-15 21 35.0 32 15
SD100-4T-18.5 24 38.5 37 18.5
SD100-4T-22 30 46.5 45 22
SD100-4T-30 40 62.5 60 30
SD100-4T-37 Three - phase 57 76.0 75 37
380V range:
SD100-4T-45 69 92.0 91 45
SD100-4T-55 -15% to 20% 85 113 112 55
SD100-4T-75 114 157 150 75
SD100-4T-90 134 180 176 90
SD100-4T-110 160 214 210 110
SD100-4T-132 192 256 253 132
SD100-4T-160 231 307 304 160
SD100-4T-185 255 333 330 185
SD100-4T-200 287 380 377 200
SD100-4T-220 311 429 426 220
SD100-4T-250 355 470 465 250
SD100-4T-280 396 525 520 280
SD100-4T-315 439 605 600 315
SD100-4T-350 479 665 660 350


5
Chapter 2 Product Information

2.4 Technical Specification


Item Specification
Maximum output frequency 650Hz
Carrier frequency 1.0K to 15KHz ;According to the load characteristics, carrier frequency can be adjusted automatically

Input frequency resolution Digital setting : 0.01Hz Analog setting : Maximum frequency x 0.1%

Overload capability Type G : 150% rated current for 60s ; 180% rated current for 2s
Type P : 120% rated current for 60s ;

Torque boost Auto Torque boost


Basic Manual Torque boost 0.1% to 30%
Specification
V/F curve Three modes : Line , Multi-point , Square V/F curve

Line or S-curve Acc/Dec mode : four kinds of Acc/Dec times


Accelerate/Decelerate curve
Range of Acc/Dec Time : 0.0 to 6553.5s
DC brake frequency : 0.0Hz to Maximum frequency ; brake time : 0.0 to 36.0s
DC brake
brake current : 0.0 to 100%
Jog control Jog frequency range:0.00Hz to Maximum frequency ;Jog Acc/Dec time:0.1 to 6553.5s
Simple PLC Multi-speed 16-speed operating through built-in PLC or control terminal
running
Built-in PID Close loop control system can be formed easily by using PID .sleep and wake function are included.
Automatic voltage
regulating (AVR) Output voltage is regulated when voltage of the power network changes
Programmable key : meet the individual need
S key
Realize the jog/reverse command and clear data at exact stop
Individualized
Function Wobble frequency control Multi-triangle wave frequency control

Exact stop control Three exact stop modes : counter, fix-length, fix-time
Command channel Three channels to issue the command : operation panel , control terminal , serial port.
Frequency source Nine frequency sources , Auxiliary frequency sources .

Input/Output Six digital input terminals ( X1 to X6 ) and one of them can inputs high speed pulse(DI)
Input terminal
Two analog input terminals,one can be inputted voltage and the another can be inputted
features of current .

Two OC output terminals,One relay output terminal ;


Output terminal
Two analog output terminal , Ao1 can select 0/4~20mA or 0/2~10V respectively ,
AO2 can select 0/2~50V or 0~50K pulse respectively .

Operation panel display Can display 26 parameters such sa preset frequency , output frequency , output voltage ,
output current etc . Two method of reading the status parameters for the user .

Display and Double-rank LED operation You can display the debugging result when you are setting parameter ,and monitoring
panel (select component) two status parameters conveniently .
operation
Protection function Input/output phase failure protection ,Over current protection ;Over voltage protection;
Under voltage protection; Over heat protection ; Overload protection
Application environment In-door , free from direct sunlight , dust , corrosive gas , combustible gas ,oil mist ,
steam , water drop and salt .
Altitude Lower than 1000m

Environment Ambient temperature -10℃ to +40 ℃ (derated when used in the ambient temperature of 40℃ to 50℃ )
Humidity Less than 95%RH, without condensation
Vibration Less than 5.9m/s(0.6g)
Storage temperature - 20℃ to + 60℃

6
Chapter 2 Product Information

2.5 Product Appearance and Dimension of Installation Holes


2.5.1 Product Appearance :

Upper-cover
Middle chassis Operation panel

Lower-cover

Bottom
Input/Output hole

Bottom installation holes

Fig. 2-2 Appea r ance


D
H

Ø
W1
H1

W1

Fig. 2-3 7.5kw and inverter with lower level of Apperaance and Dimension of
Installation Holes

7
Chapter 2 Product Information

2.5.2 Dimension of Inverter Installation Holes

H W D H1 W1 Diameter Gross weight


Inverter Model
(mm) (mm) (mm) (mm) (mm)(mm) (kg)
SD100-2S-.04G 190 110 150 178 98 Ф5 2.4
SD100-2S-0.7G 190 110 150 173
8 98 Ф5 2.4
SD100-2S-1.5G 190 110 150 178 98 Ф5 2.4
SD100-2S-2.2G 190 110 150 178 98 Ф5 2.4
SD100-4T-0.7G/1.5P 190 110 150 178 98 Ф5 2.4
SD100-4T-1.5G/2.2P 190 110 150 178 98 Ф5 2.4
SD100-4T-2.2G/3.7P 190 110 150 178 98 Ф5 2.4
SD100-4T-3.7G/5.5P 210 130 160 198 118 Ф5 3.5
SD100-4T-5.5G/7.5P 250 155 176 236 141 Ф5 4.5
SD100-4T-7.5G/11P 250 155 176 236 141 Ф5 4.5
SD100-4T-11G/15P 280 170 158 266 135 Ф6 5.1
SD100-4T-15G/18.5P 330 220 210 316 140 Ф7 9.3
SD100-4T-18.5G/22P 380 250 210 316 150 Ф7 9.3
SD100-4T-22G/30P 380 250 222 366 150 Ф7 14
SD100-4T-30G/37P 440 270 246 426 180 Ф7 19
SD100-4T-37G/45P 550 300 255 534 200 Ф9 25
SD100-4T-45G/55P 550 300 255 534 200 Ф9 25
SD100-4T-55G/75P 650 370 285 625 250 Ф9 52
SD100-4T-75G/90P 650 370 285 778 300 Ф9 86
SD100-4T-90G/110P 800 500 306 778 300 Ф10 88
SD100-4T-110G/132P 800 500 306 778 300 Ф10 90
SD100-4T-132G/160P 960 524 310 936 320 Ф13 103
SD100-4T-160G/185P 960 524 310 936 320 Ф13 105
SD100-4T-185G/200P
基 1575 500 400 1175 283 Ф13 169
SD100-4T-200G/220P 1575 500 400 1175 283 Ф13 198
SD100-4T-220G/250P 1575 500 400 1175 283 Ф13 206

SD100-4T-250G/280P 1660 690 405 1260 Ф13 267
SD100-4T-280G/315P 1660 690 405 1260 Ф13 358

SD100-4T-315G/350P 1660 690 405 1260 Ф13 375
SD100-4T-350G/400P 1810 850 405 1410 Ф13 395

SD100-4T-400G/450P 1810 850 405 1410 Ф13 415

8
Chapter 2 Product Information

2.5.3 Dimension of Extra operation Panel Installation Holes

DIGITAL PANEL

Hz

. A
128.2

119.0
RUN LOCAL/REMOT FWD/REV

ENTER

PRG

STOP
RUN S RESET

79.0 35.1

74.8

Fig.2-4 SD100 KBA installation size

2.5.4 Extra operation panel install opening hole size diagram:


+0.5
119.0

+0.5
74.8

Fig.2-5 SD100 KBA install opening hole size

9
Chapter 2 Product Information

2.5.5 Dimension of Extra operation Panel Installation Holes

74.2

Fig.2-7 SD100 KBB operation panel install


opening hole size
80

Fig.2-6 SD100 KBBoperation panel


chassis stucture size

2.6 Optional Parts


Name Model Function
Built-in brake unit Product model Single phase:0.4 to 2.2kw built-in brake unit optional;3-phase:0.4 to 2.2kw
built-in brake unit optional .3-phase:3.7 to 15kw built-in brake unit(Standard
configuration)
External brake unit EH60-BU45 Restrain the high voltage because of velocity reducing too quickly , and meanwhile
EH60-BU55 have a brake effect on the load
Modbus EH60-485 RS485 communication port
communication port
External LED display and keypad
External LED panel EH60-KE1(2) 1:Single-range LED small keypan 2:double-rank LED big keypad
-A(B) A: with Potentiometers B:without Potentiometers
Copy and compare of the parameters and display the modification of the parameters
Copy keyboard EH60-CP after leave factory
Extend cable of the Can be connected to the external LED panel , provide 20m cable
operation panel EH60-CAB

10
Chapter 2 Product Information

2.7 Selection Braking Units


The data in this table is instructional , user can select different resistance value and power
according to actual situation .(Resistance values can not be lower than the recommended ones , the
power can be higher than recommended ones). Brake resistances can be selected according to the
power of motor in actual applied system .They are also related to system inertia,deceleration time,
energy of potential energy load . Customs should select the inverter according to actual situation .
The bigger the inertia ,the shorter the deceleration time ,the more frequent the brake , and should
select brake resistance with larger power and smaller resistance .

2.7.1 Table of Selecting Braking Units


Brake resistor Brake unit
Inverter Capacity(kw) Resistance Quantity Quantity(piece) Specification
Power
200 V level specification and type selection of reference

0.4 80W,
1 1
≥200Ω
0.75 80W, ≥150Ω 1 1 Built- in
1.5 100W, ≥100Ω 1 1 as standard
2.2 250W, ≥70Ω 1 1
400 V level specification and type selection of reference
0.4 150W, ≥300Ω 1 1
0.75 150W, ≥300Ω 1 1
1.5 150W, ≥220Ω 1 1
2.2 250W, ≥200Ω 1 1
3.7 300W, ≥130Ω 1 1
5.5 ≥9 0Ω 1 Built- in
400W, 1
as standard
7.5 500W, ≥65Ω 1 1
11 800W, ≥40Ω 1 1
15 1000W, ≥32Ω 1 1
18.5 1300W, ≥25Ω 1 1
22 1500W, ≥22Ω 1 1
30 2500W, ≥16Ω 1 1
37 3700W, ≥16Ω 1 1
45 4500W, ≥16Ω 1 1
55 5500W, ≥8Ω 1 1
75 3700W, ≥8Ω 2 2
90 4500W, ≥8Ω 2 2
EHBU70
110 5500W, ≥8Ω 2 2
132 3700W, ≥8Ω 3 3
160 5500W, ≥8Ω 3 3
185 4500W, ≥8Ω 4 4
200 5500W, ≥8Ω 4 4
220 5500W, ≥8Ω 4 4

11
Chapter 2 Product Information

2.7.2 Connection Method


2.7.2.1 Braking resistor connection
It is suitable for 30 kw and the SD100 series inverter with lower level power,besides of (Fig.2-8)

P+

Inverter Braking resistor

PB

Fig.2-8 Braking resistor connection

2.7.2.2 Brake unit connection(Fig.2-9)

P+ + B1

Sd100 series Brake unit


inverter Braking resistor

P- - B2

Fig.2-9 Brake unit connection

2.7.2.3 Braking resistor is connected in parallel


When unable to meet the energy needs in a single brake unit, you need two or more brake units in parallel

P+ + B1

Sd100 series Brake unit


inverter Braking resistor

P- - B2

+ B1

Brake unit
Braking resistor

- B2

Fig.2-10 Braking resistor is connected in parallel

12
Chapter 2 Product Information

2.8 Daily Maintenance of Inverter


2.8.1 Daily Maintenance
Since the influence of ambient temperature , humidity , dust and vibration , the components in
inverter may for aging and wearing ,which will give rise to the occurrence of potential faults and reduce
the life of inverter . Therefore , it is quite necessary to perform routine and periodic maintenance to the
inverter .

! Note : As the filter capacitor still has high voltage after the power supply to the inverter is
switched off , do not maintain or repair the inverter until the bus voltage is below 36V .
Daily Maintenance :
a、Check if there is any abnormal noise during the running of motor
b、Check if there is any vibration of motor
c、Check if the installation environment of inverter changes
d、Check if the cooling fan of inverter works normally
Daily Cleaning :
a、Keep the inverter in a clean status .
b、Clear the dust from the inverter and prevent the dust, especially the metal powder, from entering
the inverter .
c、Clear the oil dirt in the cooling fan of the inverter .
2.8.2 Periodical Checking
Periodically check the places that are hardly checked during the running.
Checking items :
a、Check the ventilation channels and clean them periodically
b、Check if the screws are loose
c、Check if the inverter is rusted
d、Check if the input/output terminals has burning mark
e、Check the insulating in main circuit
Note :Insulation test (use DC 500V Mega-Ohm-Meter)should be done separately after disconnecting
the input power cables from the inverter ; or else , the inverter will be damaged . The mega-ohm-Meter
test had been done at factory . Therefore ,users need not do this test again .
2.8.3 Replacement of Wearing Parts
The wearing parts of inverter mainly include the cooling fan and filtering electrolytic capacitor .
Their lifetime is closely related to the operating environment and maintenance . Generally, their lives are :

Component Life
Fan 2 to 3 years
Capacitor 4 to 5 years

User could determine to replace them according to their work time

13
Chapter 2 Product Information

a、Cooling fan
Possible damage causes : shaft bearing attrition and blade aging .
Judging criteria : no crack on fan blade , and no abnormal vibration noise at start .
b、Filtering electrolytic capacitor
Possible damage causes :poor quality of input power supply, high ambient temperature , big pulsating
currency due to frequent load fluctuation , electrolyte aging .
Judging criteria : no liquid leak , no protrusion of safety valve , electrostatic capacitance measurement,
and insulation resistance measurement .

2.8.4 Storage of Inverter


The following points must be following in inverter storage :
a、It is recommended to store the inverter in its original packing box .
b、Long-term storage will cause deterioration of electrolytic capacitor.Therefore, inverters
must be powered one time within half a year for test purpose , each time lasts at least for 5 hours ; in the
test , the input voltage must be boosted gradually with voltage regulator to the rated value .

2.9 Warranty
The warranty is only confined to the inverter
2.9.1 We provide warranty for a period of 18 months(start from the delivery date with reference to
the bar code on the inverter) for faults and damages under the condition of proper use , after 18
months, maintenance will be fairly charged .
2.9.2 Within the 18-month warranty period , maintenance will be fairly charged for the following
inverter damages :
a、Damage resulting from operations not in compliance with user manual ;
b、Damage resulting from fire ,flood ,abnormal mains voltage ,and so on ;
c、Damage resulting from use of functions outside specifications .
Service is charged according to the actual expenses , however , if there is contract , priority is given
to the contract .

2.10 Model Selection


The user must be familiar with the technical requirements for adjustable speed induction
motor drives , application and load characteristics before sellecting the inverters , and consider
the motor , output voltage and rated output current so as to select the correct model and operation
mode .The basic rule: Motor’s rated load current cannot exceed the rated current of the inverter.
Generally , Inverter’s overload capability is very important for the start and brake processes
according to the motor capacity. Please select the inverter with higher overload capability if short
time overload condition may occur or the application requires higher speed accuracy .

14
Chapter 3 Mechanical and Electrical Installation

Chapter 3 Mechanical and Electrical Installation


3.1 Mechanical Installation
3.1.1 Insatallation Environment
1) Ambient temperature : ambient temperature influences the life of inverters greatly , so it should be
within the range of -10℃ to 50℃ .
2) Mount the inverter in a flame retardant surface and the clearance around the inverter should be
enough because the inverter will generate lots of heat during running , besides mount the inverter vertically on
the base with screws .
3) Mount in the location where vibration is less than 0.6G;the inverter should be far away from
impacting lathe .
4) Please do not install the inverter in the place with direct sunlight,high humidity and water .
5) Mount the inverter in the location free of corrosive gas ,explosive gas of combustible gas .
6) Mount the inverter in the location free of oil dirt , dust , and metal powder .

3.1.2 Insatallation Location

≥1 0 0 m m

≥5 0 m m

Inverter

≥1 0 0 m m

Fig . 3-1

Insatallation of single inverter Up and down insatallation of inverter

N o t e : When the inverter power is not N o t e : Install an airflow-guidance plate for


higher than 22kw ,the“A”size can be the up and down installation of inverters .
omitted . When the inverter power is
higher than 22kw, the “A ”size should
be higher than 50mm .

15
Chapter 3 Mechanical and Electrical Installation

Heat sink should be taken into account during the mechanical installation . Due attention should be
paid to the following items :
1) Install the inverter vertically so that the heat may be expelled from the top , but do not install the
inverter upside down . If several inverters should be installed , they should be installed side by side .
When must be up and down , an air flow diverting plate should be fixed as shown in Fig.3-1 .
2) Installation space is shown in Fig.3-1 so as to ensure the heat dissipation space , but consider the
heat dissipation of other components when placing the inverter .
3) The installation bracket must be flame retardant .
4) In the applications where there are metal dusts , it is recommended to mount the heat sink outside
the cabinet . In this case , the space in the sealed cabinet should be large enough .

3.1.3 Install and Remove the Lower Cover

Hook
Lower Cover

Hook Groove

Fig.3-2 Remove the Plastic Lower Cover

16
Chapter 3 Mechanical and Electrical Installation

Note
● Verify whether the rated voltage of the inverter and AC power supply voltage is consistent.

● The power line and motor line must be permanent fastening .

3.1.4 Peripheral connection diagram


Three-phase AC power
(Please use inverter to allow the
power within the specifications)

No fuse breaker or leakage


circuit breaker(MCCB)
(Because when the power input, the drive will flow into
a large inrush current, so need to pay attention to the
selected short breaker ) Electromagnetic contactor
(In order to ensure safety, please use it,please don't
use electromagnetic contactor to start and stop the
inverter, this will reduce the life of inverter)

AC input reactor
(Inhibit highe harmonicr
and improve power factor)
Braking resistor

Input noise
filter Brake unit

Inverter DC reactor for improving


the power factor

Ground
AC output reactor

Output Noise
Filter

Motor

Ground

Fig.3-3 Peripheral connection diagram

17
Chapter 3 Mechanical and Electrical Installation

3.2 Electrical Installation


3.2.1、Guide to the external electrical parts :
Circuit breaker Contact Input cables Output cables Control cables
Inverter model (MCCB) 2
(A) (mm)
2
(mm)
2
(mm)
(A)
SD100-2S-0.4G 16 10 2.5 2.5 1.5
SD100-2S-0.7G 16 10 2.5 2.5 1.5
SD100-2S-1.5G 20 16 4 2.5 1.5
SD100-2S-2.2G 32 20 6 4 1.5
SD100-4T-0.7G/1.5P 10 10 2.5 2.5 1.5
SD100-4T-1.5G/2.2P 16 10 2.5 2.5 1.5
SD100-4T-2.2G/3.7P 16 10 2.5 2.5 1.5
SD100-4T-3.7G/5.5P 25 16 4 4 1.5
SD100-4T-5.5G/7.5P 32 25 4 4 1.5
SD100-4T-7.5G/11P 40 32 6 6 1.5
SD100-4T-11G/15P 63 40 10 10 1.5
SD100-4T-15G/18.5P 63 40 10 10 1.5
SD100-4T-18.5G/22P 100 63 16 16 1.5
SD100-4T-22G/30P 100 63 16 16 1.5
SD100-4T-30G/37P 125 100 25 25 1.5
SD100-4T-37G/45P 160 100 25 25 1.5
SD100-4T-45G/55P 200 125 35 35 1.5
SD100-4T-55G/75P 200 125 35 35 1.5
SD100-4T-75G/90P 250 160 50 35 1.5
SD100-4T-90G/110P 250 160 70 50 1.5
SD100-4T-110G/132P 350 350 120 120 1.5
SD100-4T-132G/160P 400 400 150 150 1.5
SD100-4T-160G/185P 500 400 185 185 1.5
SD100-4T-185G/200P 600 600 150*2 150*2 1.5
SD100-4T-200G/220P 600 600 150*2 150*2 1.5
SD100-4T-220G/250P 600 600 150*2 150*2 1.5
SD100-4T-250G/280P 800 600 185*2 185*2 1.5
SD100-4T-280G/315P 800 800 185*2 185*2 1.5
SD100-4T-315G/350P 800 800 150*3 150*3 1.5
SD100-4T-350G/400P 800 800 150*4 150*4 1.5

3.2.2、Use instruction to the external electrical parts :


Part Mounting location Function description
Curcuit breaker Front end of input loop Switch off the power supply when the equipment at the lower part is over current .
Connected between the Switch off the inverter , avoid switching on/off the inverter frequently by using the
Contactor circuit breaker an the
inverter input side contactor directly (less than twice in a minute)

18
Chapter 3 Mechanical and Electrical Installation

1) Improve the input power factor ;


2) Eliminate the higher harmonics of the input effectively and prevent other equipment
AC input reactor Inverter input
from damaging due to distortion of voltage wave ;
3) Eliminate the input current unbalance due to the unbalance between the power phases .
1) Improve the input power factor ;
Inverter DC Bus side 2) Improve the whole efficiency and thermal stability of the inverter ;
DC reactor
3) Eliminate the impact of higher harmonics of the input side in the inverter and reduce
the external conduction and radiation interference .

The inverter output side generally has higher harmonics.when the motor is far from the
Connected between the inverter , since there are many distributed capacitors in the circuit , certain harmonics
inverter output and
may cause resonance in the circuit and bring about the following two impacts :
motor , its location
AC output reactor 1) Degrade the motor insulation performance and damage the motor for the long run .
should be as close to the
inverter as possible . 2) Generate large leakage current and cause frequent inverter protection .
In general , the distance between the inverter and motor exceeds 50m . Installation of
output AC reactor is recommended .

Brake resistor
3.2.3、Wiring Mode
Circuit breaker
P- P+ PB
R Motor
U
3 - phase input S V M
T W
E
Ground
Main circuit

control circuit
X1
X2 0~50Hz/0~10V
AO2
X3 FM VO2
Multi - function digtal treminal GND
X4
X5 AO1 0~20mA/0~10V
X6 IO VO1
CM
Auxiliary DC source
Positive rotation instruction FWD 24V Relay
Reverse rotation instruction REV Semi-open collector
output / pulse output
Fault reset RST
CM OC2
OC1
DI Open collector output
Pulse input
GND
TA
+10V
DC:0~10V TB
AI1 Programmable relay output
TC
DC:0~10V/0~20mA
AI2
A
AI2 B
I V Standard Rs485 interface
GND

Note : This figure is suitable for SD100-4T-30G(37P)and lower equipment , inverter with other power levels
refer to the main circuit and wiring schematic diagram in next section.
Fig . 3-4 Basic Wiring Schematic Diagram

19
Chapter 3 Mechanical and Electrical Installation

3.2.4、Main circuit terminal and wiring

P+ P- PB R S T U V W E

The left diagram is suitable for


SD100-4T-22G/30P and the inverter
with lower level power
M
Ground
DC brake
resistor 3- phase source input
Motor

R S T P P+ P- U V W E
The left diagram is suitable for
SD100-4T-30G/37Pand the inverter
with higher level power
3-phase source input
DC reactor
M Groud

Motor
Brake unit

3.2.4.1Function description of main circuit terminal:

Terminal name Function


R、S、T 3-phase source input terminal

P(+) DC P(+) input terminal

P(-) DC P(-) output terminal

P(+)、P(-) External brake unit reserve terminal

P(+)、PB External braking resistor reserve terminal

U、V、W 3-phase AC output

E Ground terminal

3.2.4.2 The control circuit terminals are arranged as follows:

TA TC X2 CM X5 FWD CM REV OC2 10V AI1 AO1 A

TB X1 X3 X4 X6 24V RST OC1 DI GND AI2 AO2 B

Fig.3-5 Control circuit terminals and connection

20
Chapter 3 Mechanical and Electrical Installation

3.2.4.3 The main circuit source side of the connection


1) Circuit breaker
Between the three-phase AC source and source input terminals (R, S, T), the inverter must be connected for
suitable circuit breaker(MCCB).
The capacity of the circuit breaker selected 1. 5 to 2 times of rated current of inverter , details see "peripheral-
electrical component selection guide."
2)Electromagnetic contactor
In order to effectively cutt of the input power of inverter in system fault, You can install Electromagnetic
contactor to control the main control circuit power supply on and off,in order to ensure safety.

3)Input AC reactor
In order to the components not be damaged ,because of large current flows into the input power rectifier circuit
in the grid high voltage input you need install input AC reactor in the input side, at the same time also can
improve the input power factor .

4)Input noise filter


When using inverter may interfere with the surrounding equipment through the wire , you can use filter can
reduce the interference. as follow:
MCCR AC reactor
Source R
R

S S SD100
Filter inverter M

T T

MCCR

other control
equipments

F i g . 3 - 6 The main circuit source side of the connection

3..2.4.4 The main circuit inverter side of the connection


1)DC reactor
DC reactor can improve the power factor and avoid rectifier bridge damage by leaving access to the large
capacity transformer and make the inverter input current is too large, can also avoid the rectifier circuit
damage by grid voltage mutation or phased harmonic load .

2)Brake unit and brake resistor


SD100 series inverters have the model with built-in brake unit, in order to release the feedback energy in
braking runtime, brake resistor must be connected in P (+), PB end.

21
Chapter 3 Mechanical and Electrical Installation

Brake resistor wiring length should be less than 5M。


Braking resistor temperature was increased because of the release of energy, theinstallation should pay
attention to safety and well-ventilated.
Sd100 series inverter models require external brake unit, in order to release the feedback energy in
braking runtime must be P (+), P (-) terminal to connect the brake unit.

3.2.4.5 Connected to the main circuit motor side

1) Output reactor
When the distance between the inverter and the motor exceeds 50 meters ,beause the parasitic
capacitance effects long cable leads to the leakage current is too large, the drive easily occur frequently
over-current protection, and in order to avoid damage to the motor insulation, need to add output reactor
compensation.

2)The output side of the noise filter

To increase the output filter can reduce noise due to cable between inverter and motor radio noise and
leakage current of the wire .as follow:

MCCR AC reactor
R R U

S S SD100 V
Source Filter M
series
inverter
T T W

Fig.3- 7 Connected to the main circuit motor side

3.2.4.6 The connection of feedback unit


Feedback unit can Feedback the source of motor in regenerative braking state. feedback unit using
IGBT rectifier feedback , compared to the traditional three-phase inverse parallel bridge rectifier unit ,
feedback grid harmonic distortion component is less than 4% of the fundamental wave , Pollution of the grid
is very small, Feedback unit is widely used in oil field pumping units, centrifuges, hoists. etc.

22
Chapter 3 Mechanical and Electrical Installation

Energy feedback unit


DC(+)D C(-) R S T

D C(+ )D C(-)
R

S
Inverter
T

R T S

AC grid
AC3-P1O2W ER

Fig.3-8The connection of Energy feedback unit

3.2.4.7 The connection of DC bus P+、P-


When the two motors work at the same time (such as winding, unwinding motor),one is in a state of electric,
another is in a state of geberating power .as follows

SD100inverter SD100 inverter

3-phase input
380V
(±15%)

DC fuse DC fuse

(-)

DC bus(+)

Line filter

M M

Fig.3-9 The connection of DC bus

23
Chapter 3 Mechanical and Electrical Installation

3.3 Function description of control terminal :


Type Terminal Terminal name Function description
10V-GND External 10V Provide +10V power supply for external-units , and the maximum output
current is 10mA. It is generally used as the operating power supply for the
Power power supply external potentiometer . The potentiometer resistance range is 1kΩ ~5kΩ.
supply
24V-CM External 24V Provide +24V power supply for external units . It is generally used as the
operating power supply for digital input/output terminals and the external
power supply sensor . The maximum output current is 50mA .
AI1-GND Analog input terminal 1 Input voltage range : DC 0V~10V
Analog Analog input Input voltage range : DC 0V~10V Input current range : DC 0~20mA
input AI2-GND
terminal 2 It is determined by AI2 jumping wire . It is 500Ω at the time of current input .
Digital DI-GND High-speed Input voltage range : DC 5V~24V
input pulse output The maximum input frequency : 50kHz
Multi-functional input
X1-CM terminal 1
Multi-functional input
X2-CM terminal 2
Specific function of the Multi-function digital input terminals are set by
Multi-functional input
X3-CM terminal 3 parameter F3.00~F3.05
Multi-functional input
X4-CM terminal 4 The terminals work when close to CM terminal .
Control Multi-functional input
terminal X5-CM terminal 5
Multi-functional input
X6-CM terminal 6

FWD-CM Positive rotation


control terminal
Reverse rotation The terminals work when close to CM terminal .
REV-CM control terminal
Fault reset
RST-CM input terminal

The voltage or current output is determined by the AO1 jumping wiring


Analog output 1 on the control board .
AO1-GND
Output voltage range :0~10V
Analog Output current range :0~20mA
output
The voltage or high-speed pulse output is determined by the AO2 jumping
wiring on the control board .
AO2-GND Analog output 2 Output voltage range :0~10V
Output pulse range :0~50kHz

OC OC1 Open collector output 1


Output function selected by parameter F4.01 and F4.02
output OC2 Open collector output 2
Relay TA-TB Normally close terminal Output function selected by parameter F4.00
output TA-TC Contact driving capability : resistive load Contact rating : AC 250V 1A
Normally open terminal

24
Chapter 4 Operation and Display

Chapter 4 Operation and Display


4.1 Introduction to operation and display interface
The operation panel can perform such operations on the inverter as function parameter modification ,
inverter working status monitoring and inverter runnign control (startup and stop) .Refer to Fig.4-1
for the physical appearance and functional zone of the operation panel .

DIGITAL PANEL
Unit
indicator
Digital
Hz
display
. A
Function
Unit
indicator indicator
RUN LOCAL/REMOT FWD/REV
Hz:frequency
A:current
V:voltage
Hz、A:speed
A、V:Percentage Program
Potential ENTER Enter Potentiometer
Exit
Shift
Program PRG Shift Data confirm
S
Enter
Run STOP
RUN S Stop/Reset
RESET Stop
Run
Reset
Multi-function

Digital modification
Optional purchse part
Fig.4-1 Operation Panel Diagram

4.1.1 Description of function LED indictor :

RUN When it is ON , it indicates the inverter is in rotation status ;


When it is OFF , it indicates the inverter is in stop status .
LOCAL/REMOT When it is OFF , it indicates the keyboard operation control status ;
When it is ON , it indicates the terminal operation control status ;
When it flashes , it indicates the remote operation control status ;
FWD/REV When it is OFF , it indicates the inverer is in forward rotation status ;
When it is ON , it indicates the inverter is in reverse rotation status .
4.1.2 Unit indictor description
:
Hz Frequency unit
A
V Voltage unit
Hz
A Current unit

4.1.3 Digital display zone :


4-rom LED display, can display setting frequency, output frequency , other monitoring data
and alarm codes.

25
Chapter 4 Operation and Display

4.4.4 Keyboard button description


Button Name Function
PRG Program key Entry and exit of primary menu
ENTER Confirmation key Enter the menu interfaces level by level ,and confirm the set parameters .
Increase key Increase of the data or function code
Decrease key Decrease of the data or function code
Shift key Select the displayed parameters in turn on the stop display interface and running
display interface , and select the modification digit of parameters when modifying
parameters .
RUN Running key It is used to start the running of the inverter under keyboard control mode .
ST O P Press the button to stop the running in the running status and reset the operation in the
RESET Stop/Reset fault alarm status .
S key F6.00=0 S key disabled
S F6.00=1 Forward rotation jog operation(set outfactory)
F6.00=2 Reverse rotation operation
F6.00=3 Clear the data of exact stop process

4.2 Description of function code viewing and modification methods


The operation panel of inverter in our company adopts three-level menu structure to carry out operations
such as parameter setup .
The three-level menu includes function parameter set (level 1 menu) function code (level 2 menu)
function code setup value (level 3 menu) . Refer to Fig.4-2 for the operation procedure .
Parameter Set Function Code Function Code
Modification Modification Modification

Data Display First-level Menu Second-level Menu Third-level Menu

Fig.4-2 Operation Procedure of three-level Menu


Note : When operating on level 3 menu , press FUNC key or ENTER key to return to level 2 menu . The
difference between FUNC key and ENTER key is described as follows : Pressing ENTER key will save
the setup parameter and return to the level 2 menu and then automatically turn to the next function code ,
while pressing FUNC key will directly return to level 2 menu without saving the parameter , and it will
return to the current function code .
Example : Modify the function code FB.02 from 10.00Hz to 15.00Hz . (The bold-type word indicates
the flashing bit)
Stop Display

Fig.4-3 Examlpe of Parameter Editing Operation

26
Chapter 4 Operation and Display

4.3 Method of viewing status parameter


The inverter can provide 26 kinds status parameter for user . There are two kinds of methods to refer to .
1) When FV status parameter is a group that can only be read , you can use the same way to enter the
three-level menu to viewing the parameter , the detailed operation method shown in 4.2 section . And this
method is convenient to refer to the parameter which doesn’t need to inquire again and again.
2) In stop or running status , the status parameter which needs inquiring again and again is setting by
running parameter (F6.01 to F6.02) and stop parameter (F6.03 to F6.04) , and to reach to the common
status parameter is by controlling shift key ( >> ) to display in turns , the setting methods shown in description
of parameter group F6 of function code .
Our company provide double- range LED operate panel which is optional , the content of under range
is setting F6.05 by correspond to FV parameter number . This way is convenient for client to debug. User
might purchase it selectivity for small power inverters’external keyboard because it is common .
4.4 Digital setting numerical value on-line modification
Setup F6.01 to F6.04 properly , display Fv parameter ,which needs to modify on-line ,by pressing shift( >> )
key. Please refer to Group F6 correlative parameter explanation .
1 Open-loop running status speed reference on-line modification
When one of frequency source selective parameter (F0.03、F0.04) settled to digital setting Up、 DW,
at this time it is switched to display status parameter FV.00、FV.01、 FV.03、FV.04、FV.05、 FV.06 ,
you can modify the set frequency, the set rotate speed and the set line speed on-line through pressing
Increase key/Decrease key ( ).
2 Close-loop control status PID digital reference on-line modification
When PID reference source select PID digital reference , after switched display status parameter FV.13、
FV.14 , you can press Increase key /Decrease key( ) to modify F9.02 on-line rather than entering
three-level menu .
3 For correlative parameter of exact stop on-line modification
When it is shifted to display status parameter FV.16 to FV.21 , you can press Increase key / Decrease key
( )to modify correlative parameter on-line rather than entering three-level menu . Please read FA.11
parameter explanation to know about the operation details of exact stop .
4.5 Password setting
The inverter provides user password protection function . When F6.08 is set to non-zero value , it
indicates the user password , and the password protection turns valid after exited the function code editing
status . When pressing FUNC again ,“ 0000” will be displayed and indicated user input password , you
can modify parameter normally until user password is is input correctly , or else you can enter function
code programme status but all function codes cannot modify .
To cancel the password protection function , enter with password and set F6.08 to“0” .
4.6 Suggestive information
When operating the inverter , the operation panel provides full suggestive information .
P.LU: Suggest lack of voltage when upon power and shutdown .
CE : Since vibration or other casual factor lead to deyboard communication abnormity , you can retry
non-success operation after exceptional factor solution.as for parameter that cannot modified,there are
the following suggestive information:
RESE : parameter reserve , good for users’ expansion HIDE : parameter hidden
E-CH : parameter cannot be modified (function parameter that cannot be modified when status parameter
or function parameter in running status).

27
Chapter 5 Function Parameter Table

Chapter 5 Function Parameter Table


Function parameters grouping according to their function , they are from F0 to FD and FV ,
There are fifteen groups of my company inverter . Every function group contains some function codes ,
which adopt the mark way of function code group number add function code number . The other contents
of the manual appears word like FX.YZ , means that the YZ number function code in X group,
For example F6.08 means that the eighth function code in the sixth group.
In order to easy to set function code, when you are using operation panel , function group
number correspond to the level 1 menu , function code number correspond to the level 2 menu
and function code parameter correspond to level 3 menu .
Description of the row content in function table :
First Row “Function Code ”: It is function parameter group and parameter number .
Second Row “Name ”: It is the whole name of function parameter .
Third Row “Setup range ”: It is valid setting value of function parameter .
Forth Row “Minimum unit ”: It is the minimum unit of setup value of function parameter .
Fifth Row “Factory default value”: It is original setting value of function parameter when
it leaves factory.
Sixth Row “Modification”: It is modifiable property( means whether it is allowed to modify
and the modifiable condition) ,the description is as follows:
“○” :It indicates that the parmneter setup value can be modified when the inverter is
in stop status and running status .
“×”:It indicates that the parameter setup value cannot be modified when the inverter
is in the running status .
“ * ” : indicates that the numerical value of the parameter is the actually measured
It
value or reserved parameter , which cannot be modified .
In order to protect parameter more dffectively , the inverter provides password protection for
function code . After setting user password ( It means F6.08 parameter is set to non-zero ) , when
user presses FUNC key and enter the function code edit status ,the system will enter the status to
confirm user password firstly, and then“0000”will be displayed and suggest that user inputs password .
You cannot modify parameter normally until user password is input correctly , or else even though you entered
the function code programming status, all function codes cannot be modified .
In the unlock password protection status , you can change the user password at any time , it
takes the last input numerical value as the correct password .
If F6.08 is set to zero , you can cancel user password ; if F6.08 is set to non-zero , then the
parameter is protected by password when upon power .

28
Chapter 5 Function Parameter Table

Function Parameter Table


Function
code Name Setup range Minimum unit Factory default Modif-
value ication
Group F0 Basic Function Group
F0.00 Software version number 0~9999 1 Model dependent *
F0.01 Control mode 0 :V/ F 1 0 ×
1 :Reserved

F0.02 Command source 0 :operation panel running command channel 1 0 ○


selection (LED ON)
1 :terminal command channel /Keyboard
STOP disabled (LED OFF)
2 :terminal command channel /Keyboard
STOP enabled (LED OFF)
3 :serial port command channel / keyboard
STOP disabled (LED flashes )
4 :serial port command channel / keyboard
STOP enabled (LED flashes )

F0.03 Main Frequency source 0 :panel potentiometer 1 EH620A ○


X selection EH623A3.7G
1 :digital setup by UP and DW adjustment
EH640A7.5G
(panel or external terminal) and thereinafter
2 :AI1 3 :AI2 levels factory
4 :PULSE setting(DI) default value:0
5 :MS speed EH623A5.5G
6 :PLC EH640A11G
7 :PID and hereinbefore
8 :communication reference levels factory
default value:1

F0.04 Auxiliary Frequency 0 :panel potentiometer 1 2 ○


source Y selection 1 :digital setup by UP and DW adjustment
(panel or external terminal)
2 :Ai1 3 :Ai2
4 :PULSE setting(DI)
5 :MS speed
6 :PLC
7 :PID
8 :communication reference

F0.05 Auxiliary Frequency 0 :relative to upper limit frequency F0.11 1 0 ○


source Y range 1:relative to frequency source X
selection

F0.06 Auxiliary Frequency 0~100% 1% 100% ○


source Y range

29
Chapter 5 Function Parameter Table

Function
code Name Setup range Minimum unit Factory default Modif-
value ication
F0.07 Frequency source 0 :main frequency source X 1 0 ×
selection 1 :auxiliary frequency source Y
2 :main frequency source X plus auxiliary
frequency source Y

3 switching between main frequency source
X and auxiliary frequency source Y
4 :switching between main frequency source
X and (main frequency source X plus
auxiliary frequency source Y )
5 :switching between auxiliary frequency
source Y and (main frequency source X
plus auxiliary frequency source Y )

F0.08 Digital setting UP and 0.0Hz ~ Upper limit frequency F0.11 0.01Hz 50.00Hz ○
DW adjust preset (operation panel and terminal UP and DW is
frequency enabled)

F0.09 Preset frequency 0:setup frequency saving when power


failure 1 0 ○
control
1:setup frequency without saving when
power failure

F0.10 Running direction 0:direction is consistent 1 0 ○


1:direction is reverse

F0.11 Upper limit frequency Lower limit F0 .12 ~ 650. 0Hz 0.01Hz 50.00Hz ○

F0.12 Lower limit frequency 0. 0 Hz ~Upper limit F0.11 0.01Hz 0.50Hz ○

F0.13 Acceleration time 1 0. 1~ 6 5 5 3 . 5s 0.1s model ○


dependent
F0.14 Deceleration time 1 0.1~6553.5s 0.1s model ○
dependent
Group F1 Motor Parameters
F1.00 Load type 0:G model(constant torque load) 1 0 ×
1:P model(fan and pump load)
F1.01 Rated power 0.4 ~10 00 .0 kW(provide user viewing only ) 0.1kW model *
dependent
F1.02 Rated current 0. 1~1 0 00 .0 A(provide user viewing only ) 0.1A model *
dependent
F1.03 Rated voltage 1~ 250V 220V
1V ×
1~ 460V 380V
F1.04 Rated frequency 1.0Hz ~ Maximum frequency F0.11 0.01Hz 50.00Hz ×
F1.05 Rated rotation speed 0~9999rpm 1rpm 1460rpm ○
F1.06 Motor type selection 0: asyn common chronous motor 1 0 ×
1:Reserved
2:Reserved
F1.07 Motor no-load 10~90% 1.0% 40.0% ×
Current coefficient

30
Chapter 5 Function Parameter Table

Modif-
Function
code Name Setup range Minimum unit Factory default
value ication
Group F2 V/F Control Parameters
F2.00 V/F curve setup 0:straight V/F curve 1 0 ×
1:multiple-point V/F curve
2:square V/F curve 1(1.5 time power)
3:square V/F curve 2(2.0 time power)
F2.01 V/F frequency point 0.00Hz~F2 0.01Hz 0.00Hz ×
F1
F2.02 V/F voltage point V1 0.0%~V2 0.1% 0.0% ×
F2.03 V/F frequency point F1~F3 0.01Hz 25.00Hz ×
F2
F2.04 V/F voltage point V2 V1~V3 0.1% 50.0% ×
F2.05 V/F frequency point F2~rated motor frequency 0.01Hz 50.00Hz ×
F3
F2.06 V/F voltage point V3 V2~100.0% 0.1% 100.0% ×
F2.07 Torque boost 0.0% :automatic torque boost 0.1% model ○
0.1~20.0% :manual torque boost dependent
F2.08 Cutoff frequency of 0 ~ Maximum F0.11 0.01Hz 50.00Hz ×
torque boost
F2.09 Slip compensation 0 ~ 200% 1% 0% ○
coefficient
F2.10 Automatic voltage 0:disabled 1 2 ○
regulating (AVR) 1:active
selection 2:disabled only at the time of deceleration

F2.11 Oscillation 0 ~ 100 1 15 ○


suppression gain
F2.12 Carrier frequency 1.0 ~ 15kHz 0.1kHz model ○
dependent
F2.13 Carrier frequency 0:Fixed PWM,carrier frequency 1 2 ○
adjustment selection temperature adjustment disabled
1:Random PWM,carrier frequency
temperature adjustment disabled
2:Fixed PWM,carrier frequency
temperature adjustment actived
3:Random PWM,carrier frequency
temperature adjustment actived

31
Chapter 5 Function Parameter Table

Modif-
Function
code Name Setup range Minimum unit Factory default
value ication
Group F3 Input Terminal
F3.00 X1 terminal function 0:no function 1 0 ×
selection(0-30)
1:MS speed terminal 1
F3.01 X2 terminal function 2:MS speed terminal 2 1 ×
6
selection(0-30)
3:MS speed terminal 3
F3.02 X3 terminal function 1 0 ×
4:MS speed terminal 4
selection(0-30)
5:Three-line mode running control
F3.03 X4 terminal function
6:Forward rotation Jog ( JOGF) 1 0 ×
selection(0-30)
7:Reverse rotation Jog(JOGR)
F3.04 X5 terminal function 1 0 ×
selection(0-33) 8:Terminal UP
9:Terminal DOWN
F3.05 X6 terminal function 1 0 ×
selection(0-33) 10:Coast to stop 11: Pause
12: External fault normally open input
13: Acceleration / deceleration selection
terminal 1
14: Acceleration / deceleration selection
terminal 2
15: Frequency source switching
16: UP and DOWN setup clear (terminal
and operation panel )
17: DC brake input command DB of stop
18: Acceleration / deceleration disabled
19: PID pause
20: PLC status reset
21: Swing frequency pause
22: Counter reset
23: Length reset
24: Timer reset
25: PID second reference value enabled
switching terminal
26: PID action direction reverse terminal
27: External stop terminal
When keyboard / communication
control, use it for stop ,it is equivalent
to STOP key of keyboard .
28: Reserved
29: Broken wire reset terminal
30: Broken wire proximity switch input
3 1: Counter input
32: Length count input
33: Broken wire detective disabled
enabled terminal

F3.06 Terminal command 0: Two-line mode 1 1 0 ×


mode 1:Two-line mode 2
2:Three-line mode 1
3:Three-line mode 2

32
Chapter 5 Function Parameter Table

Modif-
Function
code Name Setup range Minimum unit Factory default
value ication
F3.07 Change rate of 0.01~100.0Hz/s 0.01Hz/S 1.00Hz/S ○
terminals UP / DW
F3.08 AI1 Minimum input 0.00V~10.00V 0.01V 0.00V ○
F3.09 AI 1 Minimum input -100.0~100.0% 0.1% 0.0% ○
corresponding setup
F3.10 AI1 Maximum input 0.00V~10.00V 0.01V 10.00V ○
F3.11 AI1Maximum input -100.0~100.0% 0.1% 100.0% ○
corresponding setup
F3.12 AI 2 Minimum input 0.00V~10.00V 0.01V 0.00V ○
when current inputs:1V corresponding 2mA
F3.13 AI2 Minimum input -100.0~100.0% 0.1% 0.0% ○
corresponding setup
F3.14 AI2 Maximum input 0.00V~10.00V 0.01V 10.00V ○
when current inputs:1V corresponding 2mA
F3.15 AI2 Maximum input -100.0~100.0% 0.1% 100.0% ○
corresponding setup
F3.16 PULSE input (DI) 0.000kHz~[F3.18] 0.001 kHz 0.0kHz ○
lower limit frequency
F3.17 PULSE input (DI) -100.0~100.0% 0.1% 0.0% ○
lower limit frequency
corresponding setup
F3.18 PULSE input (DI) [F3.16]~5 0.00kHz 0.001 kHz 10.00kHz ○
upper limit frequency
F3.19 PULSE input (DI) -100.0~100.0% 0.1% 100.0% ○
upper limitfrequency
corresponding setup
F3.20 Anolog input filter 0.01~10.00s 0.01 s 0.25 s ○
time
Group F4 Output Terminal
F4.00 Relay output selection 0:no output 1:Inverter is running 1 2 ○
2:Fault output
F4.01 OC1 output selection 3:Frequency level detection FDT1 output
1 1 ○
4:Frequency level detection FDT2 output
F4.02 OC 2 output selection 5:Frequency arrival 1 5 ○
6:at the zero speed operation
F4.03 Reserved function 7:Inverter overload pre-warning 1 0 ○
8:Setup counting value arrival
9:Designated counting value arrival
10:Setup length arrival
11:P LC circulation completion
12:P LC phase completion
13:Setup running time arrival
14:Output frequency arrive at upper limit
15:Output frequency arrive at lower limit
16: Output X1 17: Output X2

33
Chapter 5 Function Parameter Table

Modif-
Function
code Name Setup range Minimum unit Factory default
value ication
18: Running command indication
19: Limitative time output terminal X1
20: Dormant
21: Ready for running
22: Three-line running mode 1 start to
trigger information output by itself .
23: Band-type brake information output
24: Broken wire detection output
25: Reference length arrival

F4.04 OC1 close protract 0 ~1000 . 0 s 0.1s 0.0s ○


F4.05 OC1 break protract 0~1 000 .0s 0.1s 0.0s ○
F4.06 OC2 close protract 0~1000.0s 0.1s 0.0s ○
F4.07 OC2 break protract 0~1000.0s 0.1s 0.0s ○
The first part of LED:AO1 output selection
F4.08 AO output channel 1 00 ○
selection 0:0~10V or 0 ~ 20mA
1:2~10V or 4 ~ 20mA
The second part of LED:AO2 output
selection
0:0~10V 1:2~10V
2:0~50KHz high-speed pulse output
F4.09 AO 1 output gain 1.0~500.0% 0.1% 100% ○
F4.10 AO 2 output gain 1.0~500.0% 0.1% 100% ○
F4.11 AO 1 output selection 0:running frequency 0 0 ○
F4.12 AO 2 output selecton 1:setup frequency 0 0 ○
2:output current
3:output voltage
4:pulse reference (DI)
5: AI1
6: AI2
7:length
8:counting value
9:running time
10:output torque
11:output power
12:keyboard potentiometer reference

Group F 5 Start / Stop Control


F5.00 Start mode 0:start from start frequency 0 0 ○
1:perform braking prior to start
2:velocity tracking restart
F5.01 Start frequency 0.0Hz ~ 10.00Hz 0.01Hz 0.50Hz ○
F5.02 Start frequency 0.0 ~ 36.0s 0.1s 0.0s ×
retention time
F5.03 DC brake current at 0~100% 1% 0% ×
start
F5.04 DC brake time at start 0.0~36.0s 0.1s 0.0s ×

34
Chapter 5 Function Parameter Table

Modif-
Function
code Name Setup range Minimum unit Factory default
value ication
F5.05 Stop mode 0:deceleration to stop 1 0 ○
1:coast to stop
F5.06 DC brake beginning 0.0Hz ~ upper limit frequency F0.11 0.01Hz 0.00Hz ○
frequency at stop
F5.07 DC brake waiting time 0.0~36.0s 0.1s 0.0s ×
at stop
F5.08 DC brake current at 0~100% 1% 0% ×
stop
F5.09 DC brake time at stop 0.0~36.0s 0.1s 0.0s ×
F5.10 Beginning voltage of 115~140% 1V 130% ○
dynamic braking
F5.11 Use ratio of dynamic 0~100% 1% 30% ○
braking
F5.12 Acceleration / 0:straight acceleration / deceleration 1 0 ×
deceleration mode 1:S-curve acceleration / deceleration
F5.13 Start segment 0.0~40.0% 0.1% 30.0% ×
proportion of S-curve
F5.14 End segment 0.0~40.0% 0.1% 30.0% ×
proportion of S-curve

Group F6 Keyboard and Display


F6.00 S key function 0:S key function disabled 1 1 ○
selection 1:forward rotation jog command
2:reverse rotation run command
3:clear the data of exact stop process
F6.01 LED running display 0~8191 1 5 ○
parameter 1
F6.02 LED running display 0~8191 1 0 ○
parameter 2
F6.03 LED stop display 0~8191 1 1 ○
parameter 1
F6.04 LED stop display 0~8191 1 0 ○
parameter 2
F6.05 Auxiliary supervise 0~25 1 1 ○
item selection
F6.06 Load speed display 0.01~100.0 0.01 1.00 ○
coefficient
F6.07 Reserved function *
F6.08 User password 0~9999 1 0 ○
F6.09 Copy keyboard Please refers to the copy keyboard 1 0 ○
function selection description of my company .

Group F7 Auxiliary Function


F7.00 Jog running frequency 0.0Hz~the upper limit frequency F0.11 0.01Hz 5.00Hz ○
F7.01 Jog acceleration time 0.0~6553.5s 0.1s 20.0s ○
F7.02 Jog deceleration time 0.0~6553.5s 0.1s 20.0s ○

35
Chapter 5 Function Parameter Table

Modif-
Function
code Name Setup range Minimum unit Factory default
value ication
F7.03 Jog action selection 0: Active 1 0 ○
on running status 1: Disabled
It is avoid to lead jog command for error
operation by setting it as 1 in the inverter
running .
F7.04 Acceleration time 2 0.1~6553.5s 0.1s 20.0s ○
F7.05 Deceleration time 2 0.1~6553.5s 0.1s 20.0s ○
F7.06 Acceleration time 3 0.1~6553.5s 0.1s 20.0s ○
F7.07 Deceleration time 3 0.1~6553.5s 0.1s 20.0s ○
F7.08 Acceleration time 4 0.1~6553.5s 0.1s 20.0s ○
F7.09 Deceleration time 4 0.1~6553.5s 0.1s 20.0s ○
F7.10 Skip frequency 0.0Hz~the maximum frequency F0.11 0.01Hz 0.00Hz ○
F7.11 Skip frequency 0.0Hz~the maximum frequency F0.11 0.01Hz 0.00Hz ○
amplitude
F7.12 Forward / reverse 0.0~3000.0s 0.1s 0.0s ×
rotation dead-zone
time

F7.13 Reverse control 0:Actived 1 0 ×


1:Disabled
F7.14 Setup frequency 0:Run with frequency lower limit 1 1 ×
lower than frequency 1:Stop
lower limit action 2: Zero speed operation
F7.15 Frequency detection 0.0Hz~the upper limit frequency F0.11 0.01Hz 50.00Hz ○
value ( FDT1 level )
F7.16 Frequency detection 0.0Hz~the upper limit frequency F0.11 0.01 Hz ○
2.00 Hz
hysteresis
( FDT1 hysteresis )
F7.17 Frequency detection 0.0Hz~the upper limit frequency F0.11 0.01Hz 50.00Hz ○
value ( FDT2 level )
F7.18 Frequency detection 0.0Hz~the upper limit frequency F0.11 0.01Hz 2.00Hz ○
hysteresis
( FDT2 hysteresis )
F7.19 Frequency arrival 0.0Hz~the upper limit frequency F0.11 0.01Hz 2.00Hz ○
detection amplitude
Group F8 Fault and Protection
F8.00 Inverter overload 50~200% 1% 110% ○
pre-warning
F8.01 Inverter overload 0.0~20.0s 0.1s ○
pre-warning 2.0 s
delayed time
F8.02 Overload 、Overheat 0:Inverter locks output 1 0 ○
protective action 1:Limitative current running(alarm)
mode
F8.03 Motor overload 3 0 ~ 100 % 1% 100% ○
protection codfficient

36
Chapter 5 Function Parameter Table

Modif-
Function
code Name Setup range Minimum unit Factory default
value ication
F8.04 Stall protection 110%~200% 1% 150% ○
coefficient over
current
F8.05 Stall protection 120~150% 1% 130% ○
voltage
over voltage
F8.06 Restart setup after 0:no action 1 0 ×
power-off 1:action

F8.07 Restart waiting time 0.0~10.0s 0.1s 1.0s ×


after power-off
F8.08 Fault automatic 0~3 1 0 ×
reset times
F8.09 Fault automatic reset 0.1~100.0s 0.1s 1.0s ×
interval time
F8.10 First time fault type 0:no fault (- -) - - *
F8.11 Second time 1:Inverter unit protection (E.1) - - *
fault type 2:Acceleration over current (E.OC1)
3:Deceleration over current (E.OC2)
4:Constant speed over current (E.OC3)
5:Acceleration over voltage (E.OU1)
6:Deceleration over voltage (E.OU2)
7:Constant speed over voltage (E.OU3)
8:Stop over voltage (E.OU4)
9:Running under voltage (E.LU)
10:Inverter overload (E.OL1)
11:Motor overload (E.OL2)
12:Phase loss output (E.LF)
13:Inverter overheat (E.OH)
14:External equipment fault (E.EF)
15:Communication fault (E.CE)
16:Output grounding (E.GF)
17:CPU interference (E.2)
18:Current detect fault (E.3)
F8.12 Third time fault type 19:EEPROM read-write fault (E.4) - - *
20:Phase loss input (E.5)
21:PID feedback disconnection (E.6)
22:Reserved
F8.13 Output frequency - 0.01Hz - *
on fault
F8.14 Output current - 0.1A - *
on fault
F8.15 Bus voltage on fault - 1V - *
F8.16 Module temperature - 0.1℃ - *
on fault
F8.17 Terminal state on fault - 1 - *

37
Chapter 5 Function Parameter Table

Modif-
Function
code Name Setup range Minimum unit Factory default
value ication
Group F9 PID Function
F9.00 PID control mode The third part ot LED: PID action direction 1 001 ×
setup 0:positive action
1:reverse action
The second part of LED: PID feedback
source
0:AI1
1:AI2
2: AI1+ AI2
3: AI1- AI2
4:Min{AI1,AI2}
5:Max{AI1,AI2}
6:Pulse setup(DI)
7:Communication setup
The first part of LED: PID reference source
0:panel potentiometer
1:PID digial reference (F9.02)
2:AI1
3:AI2
4:Pulse setup(DI)
5:Communication setup
F9.01 PID reference 0~9999 1 1000 ○
feedback range
F9.02 PID digital reference 0~F9.01 1 500 ○
F9.03 PID second digital 0~F9.01 Note : To realize the switch 1 500 ○
reference with other PID reference source by
setting external terminal as 25 .

F9.04 Deviation limit 0.0~50.0% 0.1% 0.0% ○


F9.05 Reserved function - - - *
F9.06 Proportional gain P 0.0~100.0% 0.0% : close P 1 20.0% ○
F9.07 Integration time I 0.1~ 100.0s 100.0s : close I 0.1s 2.0s ○
F9.08 Differential time D 0.0~ 10.00s 0.0s : close D 0.01s 0.0s ○
F9.09 Differential amplitude 0.0 ~ 100.0% 0.1% 5.0% ○
F9.10 PID preset frequency 0.0Hz~upper limit frequency 0.01Hz 0.00Hz ○
F9.11 PID preset frequency 0.0~3600.0s 0.1s 0.0s ×
keep time
F9.12 Sleeping frequency 0.0Hz ~the maximum frequency 0.01Hz 0.0Hz ○
F9.13 Sleeping protract 0.0 ~ 3600s 0.1s 60.0s ○
F9.14 Awakening threshold 0.0 ~ 100.0% 0.1% 0.0% ○
F9.15 Awakening protract 0.0 ~ 60.0s 0.1s 0.5s ○
F9.16 PID feedback The second part of LED:action mode 1 00 ×
disconnection 0:enter PID feedback disconnetcion
detection fault state(display E.6)
1:according to F5.05 setup stop mode
to stop

38
Chapter 5 Function Parameter Table

Modif-
Function
code Name Setup range Minimum unit Factory default
value ication
2:keep current running frequency
The first part of LED:detection mode
0:no detection
1:detection according to PID feedback
signal
2:detection according to disconnection
proximity switch signal

F9.17 PID feedback 0.0~50.0% 0.1% 0.0% ○


disconnection result
F9.18 PID feedback 0~20.0s 0.1s 2.0s ○
disconnection and
judgement protract
F9.19 Reserved function - - - *
F9.20 Reserved function - - - *
F9.21 Reserved function - - - *

F9.22 The precision after 0~3 1 0 ○


PID range radix point

Group FA Swing Frequency , Fixed Length ,Count and Timing


FA.00 Swing amplitude setup The second part of LED:swing frequency 1 00 ×
mode function enabled
0:disabled 1:enabled
The first part of LED:swing amplitude
benchmark
0:relative to the central frequency
1:relative to upper limit frequency
FA.01 Swing frequency 0.0~100.0% 0.1% 0.0% ○
amplitude

FA.02 Kick frequency 0.0~50.0% 0.1% 0.0% ○


amplitude
FA.03 Swing frequency cycle 0.1~3000.0s 0.1s 10.0s ○
FA.04 Time constant of 0.1~100.0% 0.1% 50.0% ○
triangular wave boost
FA.05 Setup length 0.0~65.535(km) 0.001km 1.000km ○
FA.06 Designed length 0.0~65.535(km) 0.001km 1.000km ○
FA.07 Number of pulses 0.1~6553.5 0.1 100.0 ○
each meter
FA.08 Setup counting value 1~9999 1 1000 ○
FA.09 Designated counting 1~9999 1 1000 ○
value
FA.10 Internal timing setup 0.0~65.535h 0.001h 24.000h ○
running time
FA.11 Exact stop mode setup 0:disabled 1 0 ×
1:setup counting value arrival
2:setup length arrival
3:setup running time arrival

39
Chapter 5 Function Parameter Table

Modif-
Function
code Name Setup range Minimum unit Factory default
value ication
Group FB MS Speed / PLC
FB.00 MS speed 0 0.0Hz~upper limit frequency 0.01Hz 0.0Hz ○
FB.01 MS speed 1 0.0Hz~upper limit frequency 0.01Hz 0.0Hz ○
FB.02 MS speed 1 0.0Hz~upper limit frequency 0.01Hz 0.0Hz ○
FB.03 MS speed 3 0.0Hz~upper limit frequency 0.01Hz 0.0Hz ○
FB.04 MS speed 4 0.0Hz~upper limit frequency 0.01Hz 0.0Hz ○
FB.05 MS speed 5 0.0Hz~upper limit frequency 0.01Hz 0.0Hz ○
FB.06 MS speed 6 0.0Hz~upper limit frequency 0.01Hz 0.0Hz ○
FB.07 MS speed 7 0.0Hz~upper limit frequency 0.01Hz 0.0Hz ○
FB.08 MS speed 8 0.0Hz~upper limit frequency 0.01Hz 0.0Hz ○
FB.09 MS speed 9 0.0Hz~upper limit frequency 0.01Hz 0.0Hz ○
FB.10 MS speed 10 0.0Hz~upper limit frequency 0.01Hz 0.0Hz ○
FB.11 MS speed 11 0.0Hz~upper limit frequency 0.01Hz 0.0Hz ○
FB.12 MS speed 12 0.0Hz~upper limit frequency 0.01Hz 0.0Hz ○
FB.13 MS speed 13 0.0Hz~upper limit frequency 0.01Hz 0.0Hz ○
FB.14 MS speed 14 0.0Hz~upper limit frequency 0.01Hz 0.0Hz ○
FB.15 MS speed 15 0.0Hz~upper limit frequency 0.01Hz 0.0Hz ○
FB.16 PLC running mode The second part of LED:PLC running time 1 00 ×
unit selection
0:second 1:hour
The first part of LED:PLC action mode
0:Stop upon completion of one-time
running
1:Keep final value upon completion of
one-time running
2:Constant circulation

FB.17 PLC power failure 0:power failure without memory 0 0 ○


memory selection 1:power failure memory
FB.18 Phase 0 running time 0.0~6553.5s(h) 0.1s (h) 0.0s ○
FB.19 Phase 1 running time 0.0~6553.5s(h) 0.1s (h) 0.0s ○
FB.20 Phase 0/1 running The forth part of LED:phase 1 acceleration 1 0000 ○
mode / deceleration time selection : 0-3
The third part of LED:phase 1 direction
selection
0 :forward 1:reverse
The second part of LED:phase 0 acceleration
/ deceleration time selection : 0-3
The first part of LED:phase 0 direction
selection
0 :forward 1:reverse
FB.21 Phase 2 running time 0.0~6553.5s(h) 0.1s (h) 0.0s ○
FB.22 Phase 3 running time 0.0~6553.5s(h) 0.1s (h) 0.0s ○

40
Chapter 5 Function Parameter Table

Modif-
Function
code Name Setup range Minimum unit Factory default
value ication
FB.23 Phase 2/3 running The forth part of LED:phase 3 acceleration 1 0000 ○
mode / deceleration time selection : 0-3
The third part of LED:phase 3 direction
selection
0 :forward 1:reverse
The second part of LED:phase 2 acceleration
/ deceleration time selection : 0-3
The first part of LED:phase 2 direction
selection
0 :forward 1:reverse

FB.24 Phase 4 running time 0.0~6553.5s(h) 0.1s (h) 0.0s ○


FB.25 Phase 5 running time 0.0~6553.5s(h) 0.1s (h) 0.0s ○
FB.26 Phase 4/5 running The forth part of LED:phase 5 acceleration 1 0000 ○
mode / deceleration time selection : 0-3
The third part of LED:phase 5 direction
selection
0 :forward 1:reverse
The second part of LED:phase 4 acceleration
/ deceleration time selection : 0-3
The first part of LED:phase 4 direction
selection
0 :forward 1:reverse

FB.27 Phase 6 running time 0.0~6553.5s(h) 0.1s (h) 0.0s ○


FB.28 Phase 7 running time 0.0~6553.5s(h) 0.1s (h) 0.0s ○
FB.2 9 Phase 6/7 running The forth part of LED:phase 7 acceleration 1 0000 ○
mode / deceleration time selection : 0-3
The third part of LED:phase 7 direction
selection
0 :forward 1:reverse
The second part of LED:phase 6 acceleration
/ deceleration time selection : 0-3
The first part of LED:phase 6 direction
selection
0 :forward 1:reverse

FB.30 Phase 8 running time 0.0~6553.5s(h) 0.1s (h) 0.0s ○


FB.31 Phase 9 running time 0.0~6553.5s(h) 0.1s (h) 0.0s ○
FB.32 Phase 8/9 running The forth part of LED:phase 9 acceleration 1 0000 ○
mode / deceleration time selection : 0-3
The third part of LED:phase 9 direction
selection
0 :forward 1:reverse
The second part of LED:phase 8 acceleration
/ deceleration time selection : 0-3
The first part of LED:phase 8 direction
selection
0 :forward 1:reverse

41
Chapter 5 Function Parameter Table

Modif-
Function
code Name Setup range Minimum unit Factory default
value ication
FB.33 Phase 10 running time 0.0~6553.5s(h) 0.1s (h) 0.0s ○
FB.34 Phase 11 running time 0.0~6553.5s(h) 0.1s (h) 0.0s ○
FB.35 Phase 10 /11 running The forth part of LED:phase 11 acceleration 1 0000 ○
mode / deceleration time selection : 0-3
The third part of LED:phase 11 direction
selection
0 :forward 1:reverse
The second part of LED:phase 10
acceleration / deceleration
time selection : 0-3
The first part of LED:phase 10 direction
selection
0 :forward 1:reverse

FB.36 Phase 12 running time 0.0~6553.5s(h) 0.1s (h) 0.0s ○


FB.37 Phase 13 running time 0.0~6553.5s(h) 0.1s (h) 0.0s ○
FB.38 Phase 12 /13 running The forth part of LED:phase 13 acceleration 1 0000 ○
mode / deceleration time selection : 0-3
The third part of LED:phase 13 direction
selection
0 :forward 1:reverse
The second part of LED:phase 12
acceleration / deceleration
time selection : 0-3
The first part of LED:phase 12 direction
selection
0 :forward 1:reverse

FB.39 Phase 14 running time 0.0~6553.5s(h) 0.1s (h) 0.0s ○

FB.40 Phase 15 running time 0.0~6553.5s(h) 0.1s (h) 0.0s ○

FB.41 Phase 14 /15 running The forth part of LED:phase 15 acceleration 1 0000 ○
mode / deceleration time selection : 0-3
The third part of LED:phase 15 direction
selection
0 :forward 1:reverse
The second part of LED:phase 14
acceleration / deceleration
time selection : 0-3
The first part of LED:phase 14 direction
selection
0 :forward 1:reverse
Group FC Communication Parameters
FC.00 Baud rate 0:1200 bps 1 3 ○
1: 2400 bps
2:4800 bps
3:9600 bps
4:19200 bps
5: 38400 bps

42
Chapter 5 Function Parameter Table

Modif-
Function
code Name Setup range Minimum unit Factory default
value ication
FC.01 Data format The second part of LED : data frames check 1 00 ○
mode selection
0: CRC16
1: accumlate sum (16 bit )
The first part of LED: byte check mode selection
0: No parity check (8,N,2) Note:Two stop bit
1: Even parity check (8,E,1) One stop bit
2: Odd parity check (8,0,1) One stop bit
FC.02 Local address 0~ 247 1 1 ○
0: broadcast address When local address is
zero , it indicates that the local computer as
host send synchronous command and
frequency signal to all guests with broadcast
address forwardly . In the premise that it is
baud rate and data format are corresponding ,
guests accept command and execut it .
1 ~ 247: slave address
FC.03 Delayed-acknowledge 0~20ms 1ms 2 ms ○
FC.04 Communication 0.0(invalid),0.1~60.0s 0.1s 0.0 s ○
overtime time
FC.05 Communication 0: stop 1 0 ○
overtime action 1: keep current setup frequency
selection 2: stop and come forth communication
fault(E.CE)
Group FD Particular Function
FD.00 Droop control 0.00Hz~10.00Hz 0.01Hz 0.01Hz ○
FD.01 Automatic energy 0:no action 1:action 1 0 ×
conservation running
FD.02 Simple servo function The second part of LED: the precision after 1 10 ×
mode selection FA.07 radix point 0~3
The first part of LED: simple servo mode
selection
0: disabled 1: enabled
FD.03 Relay break protract 0~1000.0s 0.1s 0.0s ○
FD.04 Pulse input (DI) filter 0~10 1 4 ○
FD.05 Input phase loss 0:disabled 1:enabled 1 1 ○
protection selection
FD.06 Output phase loss 0:disabled 1:enabled 1 1 ○
protection selection
FD.07 MS 0 frequency 0:FB.00 1 :panel potentiometer 1 0 ○
source selection 2 :Digital setup by UP and DW adjustment
(panel or external terminal )
3 :AI1 4 :AI2
5 :Pulse reference (DI)
FD.08 Inner fan control 0:automatic 1 0 ○
1:constant open
FD.09 User password 0 ~9999 1 0 ×
FD.10 Parameter 0:no operation 1 0 ×
initialization 1:Restore factory default setup value
2:Clear the fault record

43
Chapter 5 Function Parameter Table

Modif-
Function
code Name Setup range Minimum unit Factory default
value ication
Grpup F V Status Parameter
FV.00 Output frequency 0.0Hz~upper limit frequency 0.01Hz *
FV.01 Setup frequency 0.0Hz~upper limit frequency 0.01Hz *
(flashes)
FV.02 Output current 0.1~1000.0A 0.01A *
FV.03 Running rev 0~9999rpm 1r/min *
FV.04 Setup rev (flashes) 0~9999rpm 1r/min *
FV.05 Running load speed 0.001~9999 0.01m/S *
FV.06 Setup load speed 0.001~9999 0.01m/S *
(flashes)
FV.07 Output voltage 0~rated voltage 1V *
FV.08 Bus voltage 1V *
FV.09 Input AC voltage 1V *
FV.10 AI1 0~10.00V 0.01V *
FV.
11 AI2 0~10.00V Note:when current input, 0.01V *
1V corresponding to 2mA
FV.
12 Pulse reference (DI) 0~50.00kHz 0.001kHz *
FV.
13 PID setup (Flashes) 0.1% *
FV.
14 PID feedback 0.1% *
FV.
15 Terminal status refer to the following detailed explanation *
FV.16 Actual counting value 0~setup counting value 1 0 ○
FV 17 Setup counting value 1~9999 1 1000 ○
. (flashes)
FV.18 Actual length 0.0~65.535km 0.001km 0.0km ○
FV.19 Setup length (flashes) 0.0~65.535km 0.001km 1.000km ○
FV.20 Actual running time 0.0~65.535h 0.001h ○
FV.21 Setup running time 0.0~65.535h 0.001h 24.00h ○
(flashes)
FV.22 Ao1 output 0~10.00V Note:when current output, 0.01V *
1V corresponding to 2mA
FV.23 Ao2 output 0~10.00V/0~50.00kHz 0.01V/0.001kHz *

FV.24 Radiator temperature 0. 1 C *
FV.25 Total running time total running time after leave factory 1h *
Display mode of terminal status parameter FV.15 / F8.16 ):
The information of display terminals contains multi-function terminal from X1 to X6 、FWD、REV、double direction open
collector output OC1 and OC2,and relay output terminal state , it adopt LED digital designed segment ON / OFF indicates every
function terminal state , digital segment ON indicates corresponding terminal state is enabled ,contrarily, it is disabled .
Shown in figure : multi-function terminal X1、X2、X4、X5、FWD input and OC1、relay output is enabled , others
are disabled . Digital has four constant ON segment for observe expediently .
X1 X2 X3 X4 X5 X6 FWD REV

Constant ON segment
for expediently observing

OC1 OC2 relay


Terminal status indication

44
Chapter 6 Parameter Description

Chapter 6 Parameter Description

Group F0 Basic Function Main frequency Factory Model


F0.03
Factory Model source X selection default value dependent
F0.00 Software version number
default value dependent Setup range 0 Panel potentiometer
Setup range Display the software version of the machine Digital setup by UP and DW adjustment
1
(panel or external terminal)
2 AI1
Factory 3 AI2
F0.01 Control mode default value 0
4 PULSE setting(DI)
0 V/ F Control
Setup range 5 MS speed
1 Reserved
6 PLC
7 PID
Command source Factory
F0.02 selection default value 0 8 Communication reference
0 Operation panel command channel Select the input channel of the main reference frequency of
Terminal command channel the inverter . There are nine types of main reference
1
Operation panel disabled frequency channels :
Terminal command channel 0 : Running frequency is set by potentiometer on the
2
Operation panel enabled operation panel .
Setup range Serial port communication 1:The initial value is the value of F0.08 , it can change
3 command channel the setup frequency value of the inverter by the data
Operation panel disabled modification key of the operation panel (when the
Serial port communication LED keyboard displays output frequency or setup
4 command channel frequency ) or UP and DW of the multifunctional input
Operation panel ensabled terminals ; it can make a selection whether the current
frequency setup value is saved to F0.08 while power
Select the channel for inverter control command : off through setting F0.09 .
Control command includes start , stop , forward rotation ,
reverse rotation and Jog . 2:The frequency setup is determined by analog input
0:operation panel command channel terminal AI1 , the input voltage range is DC:0~10V
Perform running command control with keys on the 3:The frequency setup determined by analog input terminal
operation panel ,such as RUN、STOP、S keys . AI2 , it can be used as either voltage input or current input ,
1(2) :terminal command channel which can be selected by the jumper .
Perform running command control by the multifunctional DC Voltage range:0~10V DC Current range:0~20mA
input terminals such as FWD、REV、JOGF、JOGR ,etc . 4: The frequency reference is given by external
3(4) :serial port command channel terminal (DI) input pulse .
The running command is sent by the host computer via the Frequency range:0~50kHz Voltage range:5~30V
communication mode . When selecting this item , it must be 5: To select MS speed running mode, you need to set Group
used together with Modbus of Shenzhen SINOVO ELECTRIC F3“Input Terminal”and Group FB “MS Speed and
TECHNOLOGIES CO.,LTD. PLC”parameters to determine the relative relationship
When parameter is set to 2/4(STOP enabled ),you can between the reference signal and the reference frequency .
press STOP key on the operation panel to stop ,if you want to 6:When the frequency source is simple PLC ,you need to set
restart it , you must first input stop command by Group FB“MS Speed and PLC”parameters to determine
multifunctional input terminal / Modbus interface, then the reference frequency ,veer and running time .
input running command . 7:Select process PID control .In this case , you need to set
As for the detailed setup method of terminal command ,please Group F9“PID Function” . The running frequency of
refer to the parameter explanation in F3.06, and refer to the inverter is based on the value after PID function .For
《 SD100 serial communication protocol 》to get the explanation the meanings of PID reference source , reference quantity
about Modbus communication command . and feedback source , please refer to Group F9 “PID
Function” .

45
Chapter 6 Parameter Description

8、Communication reference When the frequency source selection is auxiliary frequency


source Y(F0.07 is set to 1)and F0.05 is set to 1 , simple
It means that the main frequency source is given by the host and convenient synchronous control can be realized through
computer via the communication mode . setting the main frequency source X as the main frequency
Auxiliary frequency standard and the auxiliary frequency source as the synchronous
Factory
F0.04 2 coefficient to make corresponding setup .
source Y selection default value
Setup range 0 Panel potentiometer Frequency source Factory
F0.07 default value 0
Digital setup by UP and DW adjustment selection
1 (panel or external terminal) 0 Main frequency source X
Setup range
2 AI1 1 Auxiliary frequency source Y
3 AI2 Main frequency source X plus
4 PULSE setting(DI) 2
auxiliary frequency source Y
5 MS speed Switching between main frequency
6 PLC 3 source X and auxiliary frequency
7 PID source Y
8 Communication reference Switching between main frequency
4 source X and (main frequency source
When the auxiliary frequency source is used as independent X plus auxiliary frequency source Y )
frequency reference channel , its usage is as the same way as
Switching between auxiliary
that of the main frequency source .
frequency source X and (main
When the auxiliary frequency source is used as overlap 5 frequency source X plus auxiliary
reference , it has special points as follows: frequency source Y )
1:When the auxiliary frequency source is digital reference ,
the preset frequency(F0.08)has no action , and it can be This parameter is used to select the frequency
adjusted on the base of the main reference frequency by the keys “ ” reference channel . Frequency reference is realized
and “ ” (or UP and DW terminals ) . by the combination of the main frequency source X and
the auxiliary frequency source Y .
2:When the auxiliary frequency source is analog input
When 2 is selected ,it can realize frequency overlapping
reference (AI1 and AI2)or pulse input reference , the 100%
function .
of input setup is relative to the auxiliary frequency source range
( refer to F0.05 and F0.06 ) . If adjust on the base of the main When 3 or 4 or 5 is selected, the frequency source switching
reference frequency , please set the corresponding setup is realized by the X input terminal “frequency source
range of analog input into -n% to +n% (refer to F3.08 to F3.15). switching ” function .
In this way ,mutually switching between the frequency
3:When the frequency source is pulse input reference , it is
reference modes can be realized, for example, switching
similar to the analog value .
between PID running and common running , switching
Auxiliary frequency Factory between simple PLC and common running , switching
F0. 0 5 source Y range selection default value 0 betweenpulse setup and analog setup , and switching
0 Relative to upper limit between analog setup and common running .
Setup range frequency F0.11 Factory
Relative to frequency source X F0 . 08 Preset frequency default value 50.00Hz
1
Auxiliary frequency Factory 100% Setup range 0 .0Hz ~ upper limit frequency F0.11
F0. 0 6 default value (enabled when the frequency source
source Y range
selection mode is digital setup)
Setup range 0 ~ 1 0 0%
Factory
F0.09 Preset frequency control
default value 0
When the frequency source selection is frequency overlap
reference(F0.07 is set to 2),it is used to determine the Setup range 0 Setup frequency with memory when
adjustment range of auxiliary frequency source . F0.05 is power failure
used to determine the relative object of that range . If it is 1 Setup frequency without memory
relative to upper limit frequency F0.11 , this rangeis a fixed when power failure
value ; if it is relative to main frequency source X , well then
this range will vary along with the variety of the main When the main frequency source is selected as “Digital
frequency X . setup”or“Terminals UP/DW”,this function code is
the initial value of frequency digital setup of the inverter .

46
Chapter 6 Parameter Description

When F0.09 is selected as “Without memory when power Output Frequency


failure ”, it means that the setup frequency value is Fmax
recovered to the value of F0.08 “Digital setup preset Setup
frequency ”in case of inverter power failure. Frequency
WhenF0.09 is selected as “With memory when power
failure”, it means that when the inverter restarts, the Time
setup frequency remains the same as before . Actual Acceleration Time Actual Deceleration Time
Factory Setup Acceleration Time Setup Deceleration Time
F0.10 Running direction default value 0
Setup range 0 Dircetionis consistent Fig . 6-1 Schematic diagram for
1 Direction is reverse acceleration / deceleration time

By using this function code , the rotary direction of the


motor can be changed without changing any other Group F1 Motor Parameters
parameters . The role of this function code is to adjust Factory
F1.00 Load type default value 0
any two lines of the motor (U,V and W) so as to further
change the rotary direction of the motor. Setup range 0 G model:constant torque load
Prompt:After parameter initialization , the motor running 1 P model:fan and pump load
direction will restore to the original status . This action Factory Model
F1.01 Rated power default value dependent
should be carefully performed in the applications where the
rotary direction of the motor is not allowed to change upon Setup range (0.4~1000kW Only user viewing )
system debugging . Factory Model
F1.02 Rated current default value dependent
Factory Only user viewing )
F0.11 Upper limit frequency 50.00Hz Setup range (0.1~999.9A
default value
Factory
Setup range Lower limit frequency ~ 650.0 Hz F1.03 Rated voltage default value 220V/380V
Factory Setup range 1 ~220V / 1 ~460V
F0.12 Lower limit frequency default value 0.50Hz
Factory
Setup range 0 .0 Hz ~ Upper limit frequency F1.04 Rated frequency default value 50.00Hz
Setup range 1 .0 0 ~ Upper limit frequency F0.11
The inverter starts from the start frequency . If the reference
Factory
frequency is lower than frequency lower limit during the F1.05 Rated rotation velocity default value 1460rpm
running process ,the inverter will determine the relation Setup range 0~9999rpm
between actual output frequency and lower limit frequency Factory
in terms of F7.14 . F1.06 Motor type selection default value 0

Factory Model Setup range 0 common asynchronous motor


F0.13 Acceleration time 1 default value dependent
Setup range 0.0~6553.5s To ensure the control performance ,please carry out motor
Factory Model configurations in accordance with the standard adaptable
F0.14 Deceleration time 1 default value motor of the inverter . If there is big difference between
dependent
Setup range 0.0~6553.5s the motor power and the power of standard adaptable motor ,
the control performance of the inverter will decrease
Acceleration time refers to the time required for the inverter obviously .
to accelerate from 0 Hz to the maximum output frequency . motor no-load Factory
Deceleration time refers to the time required for the inverter F1.07 current coefficient
40%
default value
to decelerate from the maximum output frequency to 0 Hz . Setup range 0~100
There are still three groups of acceleration / deceleration time
for user selection . Refers to parameter descriptions from F7.04 In the automatic control mode , the parameter is enabled.
to F7.09 . (when F2.07=0.0%)
motor no-load current
F1.07 =
rated output current of the inverter
When the motor is not match the inverter , please setup
the parameter correctly .

47
Chapter 6 Parameter Description

Group F2 V/F Control Parameters F2.07 Torque boost Factory Model


default value dependent

F2.00
Factory Setup range 0.0~20.0%
V/F curse setup default value 0
Cutoff frequency of Factory
F2.08 torque boost default value 50.00Hz
Setup range 0 Straight V/F curve
1 Multiple-point V/F curve Setup range 0.0 Hz~rated frequency
2 Square V/F curve 1 (1.5 time power) To compensate the low frequency torque characteristics of
3 Square V/F curve 2 (2.0 time power) V/F control , it can boost the output voltage of the inverter at
the time of low frequency .
0:Straight V/F curve . It is suitable for common constant torque
load . If the torque boost is set to be too large , the motor may be over
1:Multiple-point V/F curve . It is suitable for the special loads heat , and the inverter may be over current .
such as dehydrator and。centrifugal machine . Adjust this parameter effectively can avoid over current upon
2 or 3 :Square V / F curve 1 or 2 .It is suitabled for the centrifugal startup . For the relatively large loads , it is recommended to
loads such as fan and pump . increase this parameter . For the small loads , this parameter
value could be reduced .
Factory
F2.01 V/F frequency point F1 default value 0. 00Hz When the torque boost is set to 0% , the inverter will adopt
Setup range 0.0 Hz~F2 automatic torque boost .
Factory Cutoff frequency of torque boost: Under this frequency , the
F2.02 V/F voltage point V1 default value 0. 0% torque boost is enabled . If it exceeds this setup frequency ,
Setup range 0. 0%~V2 the torque boost is disabled .Refer to figure for details .
Factory Output voltage
F2.03 V/F frequency point F2 25.00Hz
default value
Setup range F1~ F3
Factory
F2.04 V/F voltage point V2 default value 50.0%
Setup range V1~V3
Factory
F2.05 V/F frequency point F3 default value 50.00Hz
Output frequency
Setup range F2 ~ Motor rated frequency
Factory
F2.06 V/F voltage point V3 default value 100.0%
V1:Manual Torque Boost Voltage Vb:Rated Output Voltage
f 1: Cutoff Frequency of Torque Boost f b: Rated Frequency
Setup range V2~100.0%
Fig .6-3 Schematic Diagram for Manual Torque Boost
There are six parameters F2.01 to F2.06 to define MS V/F curve .
The setup value of V/F curve is generally set in accordance Slip compensation Factory
F2.09 default value 0%
with the load characteristics of the motor . coefficient
Note:In case of low frequency , higher setup voltage may Setup range 0~200%
cause over heat and even burning of the motor , the inverter
is likely to encounter stall over current or current protection. It is active only for V/F control . Set this parameter can
compensate the slip in the V/F control mode due to load
Voltage%
and reduce the variation of the motor rotation velocity
which is change with the variety of the load . In general ,
100% corresponds to the rated slip of the motor with rated
load . Slip coefficient adjustment can refer to the following
principles: When the load is rated load and the slip
compensation coefficient is set to 100% , the rotation velocity
of the motor in the inverter is close to the reference velocity .
If the actual rotation velocity is lower than the reference
velocity ,the coefficient should be increased accordingly and
vice versa .
Frequency Hz
V1-V3: Segments 1 to 3 Voltage Proportion MS V/F
F1-F3: Segments 1 to 3 Frequency Point of MS V/F
Fb: Rated Motor Frequency F1.04
Fig .6-2 Schematic Diagram for V/F Curve Setup

48
Chapter 6 Parameter Description

Automatic Voltage Model Carrier frequency Factory


F2.10 2 F2.13 2
Regulation (AVR) Selection dependent adjustment selection default value
Setup range 0 Disabled Setup range 0 Fixed PWM,and carrier frequency
1 Enabled temperature adjustment disabled .

2 Disabled only at the time of Random PWM,and carrier frequency


1 temperature adjustment disabled .
deceleration
AVR is output voltage regulate automatically , that means Fixed PWM,and carrier frequency
2 temperature adjustment actived .
when input voltage fluctuates, the inverter adjusts
automatically and keep the output voltage stable so as to Random PWM,and carrier frequency
3 temperature adjustment actived .
overcome motor radiation for higher output voltage and
power shortage for lower output voltage. The parameter Two PWM carrier frequency adjustment modes , fixed and
can choose the effective session of AVR. random , are provided . The random PWM motor noise has wide
When deceleration stopped , AVR selection disabled , frequency range , while the fixed PWM motor noise has fixed
deceleration time will shorten but running current will frequency .
become larger ,when AVR selection enabled , deceleration
When the carrier wave temperature adjustment is enabled ,
time will lengthen but running current will decrease .
the inverter can automatically adjust the carrier frequency
Oscillation Model according to its temperature . This function can reduce the
F2.11 suppression gain dependent 15
possibility of over heat alarm of the inverter .
Setup range 0~100
Group F3 Input Terminal
The function is used to suppress fixed oscillation while inverter
X1 terminal function Factory
is match for motor . If output current varied again and again F3.00 0
selection default value
while constant load running ,you can adjust the function code
X2 terminal function Factory 6 (Forward
that is base on the factory default value to eliminate oscillation F3.01 selection default value rotation Jog)
and make the motor running on an even keel .
X3 terminal function Factory
F3.02 selection default value 0
Factory Model
F2.12 Carrier frequency default value dependent X4 terminal function Factory
F3.03 selection default value 0
Setup range 1.0~15kHz
X5 terminal function Factory
This function is used to adjust the carrier frequency of the F3.04 selection default value 0
inverter . By adjusting the carrier frequency , the motor noise
X6 terminal function Factory
can be reduced , and the resonance of the mechanical system F3.05 selection default value 0
can be avoided , so that the leakage current to the earth and
the interference of the inverter can be reduced . This parameter is used to set the function of the
When the carrier frequency is low , the output current higher multifunctional digital input terminals .
Setup
harmonic component will increase , the loss of motor will Function Description
value
increase , and the motor temperature rise will also increase. No function Even if there is signal input , the
0
When the carrier frequency is high , the loss of motor is inverter still has no action . The no
reduced , and the motor temperature is decreased , but the operation function can be set on the
loss of the inverter and its temperature rise will increase unused terminals so as to prevent
and so will the interference . error action .

The adjustment of carrier frequency will have influences 1 MS speed It can realize 16S speed through the
terminal 1 combination of digital status of
on the following performances : these four terminals .
2 MS speed
Carrier frequency low to high
terminal 2 Details about the combination refers
Motor noise high to low to attached figure 1 .
Output current
3 MS speed
poor to good terminal 3
waveform
Motor 4 MS speed
high to low
temperature rise terminal 4
Inverter This terminal is used to realize
low to high 5 Three-line mode
temperature rise
running control three-line control mode of
Leakage current low to high terminal command. As for detailed
External radiation description, please refer to
low to high
interference F3.06 function code .
49
Chapter 6 Parameter Description

Forward rotation For details regarding frequency When the frequency reference
6 Jog(JOGF) is digital frequency reference ,
and Jog acceleration /
deceleration time during the 16 UP/DOWN setup this terminal can be used to
Reverse rotation clear the frequency value
7 Jog running , refer to function clear (terminal
Jog(JOGR) and keyboard) modified by UP/DOWN and thus
codes F7.00 to F7.02 .
restore the reference frequency
8 Terminal UP When the frequency is provided
to the setup value of F0.08 .
by the external terminals , then
modify the frequency UP/DOWN It can realize exigency stop of
Terminal DOWN command . When the frequency DC brake input motor and exact orientation .
9
source is set as the digital setup 17 command DB Brake start frequency , brake
, it can regulate the setup of stop waiting time and brake current
frequency up and down . are defined in F5.06 to F5.09 .
The inverter locks the output Protect the inverter from
Acceleration/
and loses control of the process affecting by the external signals
18 deceleration
of motor stop . It is the method (except stop command ), and
disabled
10 Coast to stop that is ofter adopted when there maintain the current frequency .
are large amount of loads and PID is disabled temporarily , and
no requirements for the stop 19 PID Pause the inverter maintains the
time . This mode has the same current frequency output .
meaning as that of F5.05 . PLCpauses during the execution
The inverter decelerates to stop process . When it resumes
PLC status
, but all the running parameters 20 running , it can effectively
reset restore to the initial status of
are all in memory status , such
simple PLC via this terminal .
11 as PLC parameter , swing
Running pause
frequency parameter and PID Swing frequency The inverter output with central
21 frequency . Swing frequency
parameter . When this signal pause pauses .
disappeared, the inverter restores Counter reset Clear the counter status .
22
to the status before stopping .
23 Length reset Length clear
When the external fault signal was
12 External fault 24 Timing reset Actual running time clear
sent to the inverter , the inverter
input PID second The PID setup value can be switched
reports fault (E.EF) and stops .
Acceleration/ It can select four kinds of reference value from the setup value selected by
25 enabled F9.00to the value selected by F9.03
13 deceleration time acceleration/deceleration time switching via this terminal .
selection terminal 1 through the combination of terminal
Acceleration/ digital status of these two
PID action It is as the same as the effect that
14 deceleration time terminals. Refer to attached direction
26 setup the third part of F9.00 to
selection terminal 2 Figure 2 . reverse
terminal change the PID action direction.
When the frequency source
selection (F0.07)is set as 3 , When keyboard / communication
it performs switching between External stop controls, this terminal can be used
the main frequency source X and 27
terminal for stop ,it is equivalent to the
Frequency the auxiliary frequency source Y STOP key.
15 source via this terminal . 28 Reserved
switching When the frequency source
Disconnection Exit disconnection status
selection(F0.07)is set as 4 29
reset terminal
or 5 , it performs switching
Disconnection Input terminal of Disconnection
between the frequency source X 30
proximity switch proximity switch
or Y and (X plus Y ) via this
31 Counter Input terminal of counting pulse .
terminal .
Input terminal of length counting
32 Length count
pulse .
Disconnection When the terminal is enabled ,
detective disconnection detective is
33 disabled enabled
terminal disabled .

50
Chapter 6 Parameter Description

1:Two-line running mode 2: When this mode is adopted ,


Frequency Corresponding
K4 K3 K2 K1 REV is enabled terminal . The direction is determined by the
setup parameter
status of FWD .
OFF OFF OFF OFF MS speed 0 FB.00
OFF OFF OFF ON MS speed 1 FB.01 K1 K2 Running Command
OFF OFF ON OFF MS speed 2 FB.02 0 0 Stop
K1
ON MS speed 3 1 0 Forward Rotation FWD
OFF OFF ON FB.03 K2
1 1 Reverse Rotation REV
OFF ON OFF OFF MS speed 4 FB.04
0 1 Stop CM
OFF ON OFF ON MS speed 5 FB.05
OFF ON ON OFF MS speed 6 FB.06
Fig.6-5 Two-line Running 2
OFF ON ON ON MS speed 7 FB.07
ON OFF OFF OFF MS speed 8 FB.08 2:Three-line running mode 1 :In this mode , Xn is enabled
ON OFF OFF ON MS speed 9 FB.09 terminal , and the direction is controlled by FWD and REV
respectively .However , the pulse is enabled by disconnecting
ON OFF ON OFF MS speed 10 FB.10
the signal of Xn terminal when the inverter stops .
ON OFF ON ON MS speed 11 FB.11
ON ON OFF OFF MS speed 12 FB.12
ON ON OFF ON MS speed 13 FB.13 SB2
ON ON ON OFF MS speed 14 FB.14
FWD
ON ON ON ON MS speed 15 FB.15
SB1
Attached Figure 1 Xn
SB3 REV
Terminal 2 Terminal 1 Acc/Dec time Corresponding
selection parameter CM
OFF OFF Acc/Dec time 1 F0.13、F0.14
OFF ON Acc/Dec time 2 F7.04、F7.05 Fig.6-6 Three-line Running Mode 1
ON OFF Acc/Dec time 3 F7.06、F7.07
Where:
ON ON Acc/Dec time 4 F7.08、F7.09 SB1:Stop button
SB2:Forward rotation button
Attached Figure 2 SB3:Reverse rotation button
Factory 3:Three-line running mode 2:In this mode, Xn is enabled
F3.06 Terminal command mode default value 0
terminal , and the running command is given by FWD(pulse
Setup range 0 Two-line mode 1
enabled), while the direction is determined by the status
1 Two-line mode 2 of REV .
2 Three-line mode 1 Stop command is performed by disconnecting the Xn signal .
3 Three-line mode 2

This parameter defines four different modes of controlling the Running Direction
K Sb2
operation of the inverter via the external terminal. Selection
F WD
0 Forward Rotation SB1
0:Two-line running mode
1 Reverse Rotation Xn
1:This mode is the most commonly used one . K
The forward/reverse rotation of the motor is decided by the REV
commands of FWD and REV terminals . CM
K1 K2 Running Command Fig.6-7 Three-line Running Mode 2
0 0 Stop
Forward Rotation K1 Where:
1 0 FWD
K2 SB1:Stop button
0 1 Reverse Rotation REV
1 1 Stop CM SB2:Running button

Fig.6-4 Two-line Running 1

51
Chapter 6 Parameter Description

Prompt: Steer Stick mode: The above parameters are set in reason ,
Xn is multifunctional input terminals . In this way , its it can realize the forward/reverse rotation of the motor through
corresponding terminal function should be defined as NO.5 changing the analog input ,this mode usually called JOYST
function “Three-line Mode Running Control”. mode ,the detailed setup is as follows :
In the terminal control mode , for two-line running mode 1 or 2 , though The minimum value of signal corresponding to the maximum
it is terminal level enabled , when stop command given by other source that reference of reverse , the maximum value of signal
makes the inverter stop ,it can’t give running command in spit of the still corresponding to the maximum reference of forward , and the
minimum input should be 0.3V (0.6mA) or a little bigger .
enabled control terminals FWD/REV.To make the inverter running again ,
Because by using the 0 to 10V signal as reference , once the
there is a necessity to trigger the enabled status of FWD/REVagain , such
reference signal lost , the inverter might run toward the reverse
as terminal function PLC single cycle stop , exact stop , and effective stop
at the highest speed by mistake . To avoid the mistake , the
of the STOP key under the command of terminal running channel.
minimum input can’t be too low so that when the reference
(Refer to the description of function code in F0.02 .) signal lost, the inverter will stop automatically.
Terminal UP/DOWN Factory Several setting examples are shown in the following figures:
F3.07 default value 1.00Hz/S
Velocity Corresponding Settings
Forward Maximum (Frequency,etc.)
Setup range 0.01~100.0Hz/s
Frequency

Terminals UP/DOWN is used to adjust the change rate when


setting the frequency .
Factory
F3.08 AI1 minimum input 0.00V
default value
0.0V~10.00V
Setup range
AI1 minimum input Factory
F3.09 corresponding setup default value 0.0%
Fig.6-8
Setup range -100.0~100.0%
Corresponding Relationship between Analog Reference as
Factory
F3.10 AI1 maximum input default value 10.00V Main Frequency Source Reference and Output Frequency
Setup range
0.0V~10.00V Corresponding Settings
Factory (Frequency,etc.)
F3.11 AI1 maximum input 100.0%
corresponding setup default value n%
Setup range -100.0~100.0%
Factory
F3.12 AI2 minimum input default value 4.00mA
Setup range 0.00V~10.00V
when current inputs:1V corresponding 2mA

AI2 minimum input Factory -n%


F3.13 default value 0.0%
corresponding setup
Setup range -100.0~100.0% Fig.6-9
F3.14 AI2 maximum input Factory
20.00mA Analog Reference as Auxiliary Frequency Source for
default value Main Frequency Source Micro Tuning
Setup range 0.00V~10.00V
when current inputs:1V corresponding 2mA Corresponding Settings
(Frequency,etc.)
Factory
F3.15 AI2 maximum input
-100.0~100.0%
default value 100.0%
corresponding setup Forward Maximum
Setup range -100.0~100.0% Frequency

The above function codes define the relations between the 0.3V
analog input voltage setup value and the analog input 0.6mA
representative setup value . When the analog input voltage
exceeds the setup maximum input , it will be calculated
according to the maximum input . When the analog input Reverse Maximum
Frequency
voltage is lower than the minimum input , the setup is 0 . The
nominal value of the analog setup 100%varies with the Fig.6-10
application situation . For details , please refer to the JOYST mode : Corresponding Relationship
description of each application part . between Analog Reference and Setup Value

52
Chapter 6 Parameter Description

Prompt:
Prompt: The above several
cutlinessettinh
are typical
examples
application
are typical
settings. Setup Function Description
application
As for the setting
setting details,
, for detailed
the adjustment
setting need
should
adjustment
be madeand
to value
according
meet the demand
to clientofdemand
customers.
. The output terminals does not
0 no output
have any function .
PULSE input (DI) Factory
F3.16 lower limit frequency default value 0.0kHz 1 Inverter is Inverter is running , and there is
Setup range 0.0kHz~[F3.18] running output frequency (can be zero),
and ON signal will be output at
PULSE input (DI)
F3.17 lower limit frequency Factory 0.0% this time .
default value 2 Fault output When the inverter is faulty , it
corresponding setup
outputs ON signal .
Setup range -100.0~100.0%
3 FDT1 output Please refer to function code
PULSE input (DI) Factory
F3.18 default value 10.00kHz F7.15 and F7.16 for details .
upper limit frequency
Setup range 4 FDT2 output Please refer to function code
[F3.16]~50.00kHz
F7.17 and F7.18 for details .
PULSE input (DI) Factory
F3.19 upper limit frequency default value 100.0% 5 Frequency arrival Please refer to function code
corresponding setup F7.19 for details .
Setup range -100.0~100.0% 6 at the zero When the inverter output
This group of function code defines the corresponding speed running frequency is less than the start
relationship between the input pulse signal frequency frequency , it outputs ON signal.
and the setup value when the select pulse reference 7 Inverter According to the warning system
enabled . overload of F8.00 setting , once the output
Factory 0.25s pre-warning current exceeds the pre-warning
F3.20 Analog input filter time default value
value , it outputs ON signal after
Setup range 0.01s~10. 0 0 s the setup time of F8.01 , .
8 Setup counting As for the action mode of output
The function code determines the sensitivity of analog input AI1 value arrival terminal, please refer to function
and AI2 . If error action is made due to prevent the analog input 9 Designated code FA.08 and FA.09 for details .
from interferences, this parameter can be increased to enhance counting value
the anti-interference capability . But the sensitivity of the analog arrival
input will be lowered.
10 Setup length When the measured actual length
arrival exceeds the setup value of FA.05
, it outputs ON signal .
Group F4 Output Terminal 11 PLC circulation When the simple PLC has been
completion running for one cycle , it outputs a
Inverter has following output terminals pulse signal with width of 500ms .
1:Two multifunctional digital output terminals 12 PLC phase When the simple PLC has been
2:One multifunctional relay output terminal completion running for one phase , it outputs a
3:AO1:Output voltage or current signal pulse signal with width of 500ms .
(through jumping wiring and setup F4.08 ) 13 Setup running When the actual running time of
4:AO2:Output voltage or current signal time arrival the inverter exceeds the setup
(through jumping wiring and setup F4.08 ) time FA.10 , it output s ON signal .
14 Output frequency When the running frequency
Factory arrive at upper limit reaches the frequency upper
F4.00 Relay output selection default value 2
limit , it outputs ON signal .
Factory
F4.01 OC1 output selection 1 15 Output frequency When the running frequency
default value
arrive at lower limit reaches the frequency lower
Factory
F4.02 OC2 output selection default value 5 limit , it outputs ON signal .
16 Output X1 The status of input terminal X1
The multifunctional output terminal function selection is as outputs through output terminal .
follows : The status of input terminal X2
17 Output X2
outputs through output terminal .

18 Running command When inverter recieved the running


command, the output enabled.

53
Chapter 6 Parameter Description

19 Limitative time When terminal X1 enabled , the F4.08 AO Output channel Factory
default value
00
output terminal output terminal enabled at once selection
X1 , then after the setup time of F4.05, The first part of LED:AO1 output
Setup range
selection
F4.07 and FD.03 , the output
0:0~10V or 0 ~ 20mA
terminal disabled .
1:2~10V or 4 ~ 20mA
20 Dormant When PID running is in dormant status .
The second part of LED:AO2 output
21 Ready for When the inverter in running selection
running status , it outputs ON signal . 0:0~10V 1:2~10V
2:0~50KHz high-speed pulse output
22 Three-line The inverter allows to run and
running mode 1 output the trigger signal when it Prompt:
Prompt:When AO1 AO1andAO2
and AO2 output output
different
different
physics
physics
quantity
quantity,
by
start to trigger is not at running status . jumping
setting jumping
wiring setting
wiring is,the
needed.
factoryThe
default
factory
output
default
is voltage
output
information is
signal
voltage
, if want
signal,
to if
output
you want
current
to output
or pulse
current
signalor, please
pulse signal,
placed
output by itself please
the jumping
placedwiring
the jumping
hat ot the
wiring
CPUhatonof
thethe
left
CPU. on the left.
23 Band-type brake It starts output when output
Factory
information frequency lower than FDT2 at F4.09 AO1 output gain default value 100.0%
output the first time , the time length is
Setup range 1.0%~500.0%
setting by OC break protract .
Factory
24 Disconnection It outputs when accords with F4.10 AO2 output gain default value 100.0%
detection output the disconnection judgement terms .
Setup range 1.0%~500.0%
25 Reference length When the measured actual
arrival length exceeds the setup value 1:When AO1 outputs voltage and current signals , and AO2
of FA.06, it outputs ON signal . outputs voltage signal selection , the output gain coefficient is
generally used to correct the analog output deviation .
Application examples of AO output analog signal are shown as
OC1 close protract Factory the following :
F4.04 default value
0.0s
Client hopes that AO1 outputs content selection:
Setup range 0~1000.0S running frequency (0.0Hz to the upper limit frequency)
F4.05 OC1 break protract
Factory
0.0s corresponding AO1 output : 0 to 5V voltage signal
default value
These are shown as the following figure .
Setup range 0~1000.0S
Factory 5V
F4.06 OC2 close protract default value 0.0s
Setup range 0~1000.0S
Factory
F4.07 OC2 break protract default value 0.0s
0V
Setup range 0~1000.0S 0.0Hz upper limit frequency

Setup : the first part of F4.08 is 0 、F4.09=50.0% 、F4.11=0


Prompt : Please make sure AO1 jumping wiring hat of CUP is
Select control placed on the right side .
signal 2:When AO2 selects to output 0 to 50KHz pulse signal
, it can change the maximum frequency through
OC terminal
adjusting AO2 gain coefficient , the actual output maximum
output status
frequency :Y = F4.10/100% * 10kHz (0~ 50kHz)
Client hopes that AO2 outputs content selection:
F4 . 0 4 ( F4 . 0 6 ) F4 . 0 5 ( F4 . 0 7 )
inverter output current (0 to twice rated current)
close protract break protract
corresponding AO2 output : 0 to 20KHz pulse signal
Fig.6-11 These are shown as the following figure .

Schematic Diagram for


OC Output Closed/Break Protract

54
Chapter 6 Parameter Description

1:Perform braking prior to start


20kHz Perform DC braking prior to start (refer to F5.04、F5.05) .
适用小惯性负载在启动时可能产生反转的场合。
It is applicable to the applications where reverse rotation is
likely to occur when small loads are started .
2: Velocity tracking restart
Track the rotation velocity and direction of the motor
0 twice rated current
automatically , and make the rotating motor working smoothly
without surge .
Setup : the second of F4.08 is 2、F4.10=200.0% 、F4.12=2 It is applicable to the restart upon transient power failure due
Prompt : Please make sure AO2 jumping wiring hat of CUP to large loads .
is placed on the left side .
Factory
Factory F5.01 Start frequency default value
0.50Hz
F4.11 AO1 output selection default value 0
Setup range 0.0Hz ~ 10.00Hz
Factory
F4.12 AO2 output selection 0 Start frequency Factory
default value F5.02 0.0s
retention time default value
The corresponding value range that it indicates is shown in
the table below : Setup range 0.0~36.0s

Setup Function Description To ensure the torque at the start of inverter , it needs to set a
value proper start frequency . In addition , to set up flux at the time
Running
0 frequency 0 ~ maximum frequencyF0.11 of starting motor , accelerate the start frequency after a
certain period of time . The start frequency value F5.01 is
Setup
1 frequency 0 ~ maximum frequency F0.11 not confined by the frequency lower limit .
When the frequency reference value (frequency source) is
2 Output 0 ~200% of the rated current of
current the inverter lower than the start frequency , the inverter cannot start and
is in standby status .
3 Output 0 ~ rated current of inverter
voltage When the forward rotation and reverse rotation switch to
Pulse 0.0~DI maximum pulse input each other , the start frequency retention time is disabled .
4
reference (DI) frequency (F3.18) The retention time is not included in the acceleration time
5 AI1 0~10V but in the running time of simple PLC .
6 AI2 0~10V / 0~20mA
7 Length 0 ~setup length DC brake current Factory
F5.03 default value
0%
8 Counting at start
0 ~ setup counting value
value Setup range 0~100%
9 Running time 0 ~FA.10 Factory
F5.04 DC brake time at start default value 0.0s
10 Output 0 ~200% of the rated torque of
torque the motor Setup range 0.0~36.0s
11 Output power 0~ twice rated power
12 Keyboard DC brake is generally used when the motor is restarted after it
potentiometer 0 ~ maximum value
stops completely .
F5.03 and F5.04 only enabled when the start running mode selects the
braking prior to start mode(F5.00=1), and when F5.04 is 0.0s , it has
no start DC braking process .
Group F5 Start/Stop Control The setup DC brake current at start is relative to the percentage
of the rated current of the inverter .
Factory
F5.00 Start mode 0 The higher the DC brake current is , the higher the brake force
default value
is .
Setup range 0 start from start frequency
When DC brake at start enabled ,the inverter firstly performs DC
1 perform braking prior to start
brake in accordance with the DC brake current at start , and then
2 velocity tracking restart start running after the setup time of DC brake at start .
0:start from start frequency
To start according to setup start frequency (F5.01) and setup
start frequency retention time (F5.02) .

55
Chapter 6 Parameter Description

The process of DC brake is shown as the following figure: Inverter has no output during the DC brake waiting time at stop.
As for high-power motor, the setup time can prevent the
Output over-high current at the brake beginning moment.
frequency The setup of DC brake current at stop is relative to the percentage
of rated current of inverter . The higher the value is , the better the
DC brake effect is .
When the DC brake time at stop is 0.0s ,there is no DC brake
Time
process .
Output
voltage F5.10 Beginning voltage of Factory
130%
dynamic braking default value
Setup range 1 15 ~1 40 %
DC brake
quantity Use ratio of dynamic Factory
Time F5.11 default value
30.0%
braking
DC
Setup range 0 ~1 00 %
brake
time
It is enabled for the inverter with built-in brake unit . It can be used
Running
to adjust the brake effect of the brake uint .
command
Fig.6-12 Schematic Diagram for DC Automatic Start Mode Acceleration/ Factory
F5.12 default value 0
deceleration mode
Setup range 0 Straight acceleration/deceleration
Factory 1 S-curve acceleration/deceleration
F5.05 Stop mode default value 0

Setup range 0 Deceleration to stop It is used to select the frequency changing mode during the
inverter’s start and stop process .
1 Coast to stop
0:straight acceleration /deceleration
0:deceleration to stop The output frequency increases or decreases along with the
After the inverter receives the stop command , the inverter straight line .The acceleration/deceleration time varies with the
reduces the output frequency in accordance with the setup acceleration/deceleration time .Our company provides four
deceleration mode and stops after the frequency reduces to types of acceleration/deceleration time . It can select
zero . acceleration/deceleration time by the multifunctional digital
1:coast to stop input terminals (F3.00 to F3.04).
1:S-curve acceleration/deceleration
After the stop command is enabled , the inverter will terminate The output frequency increases or decreases along with the
the output immediately . The load willFactory
DC brake beginning coast to stop according S curve. S curve is generally used in the applications where
F5.06
to the mechanical inertia . default value 0.00Hz
frequency at stop the process of start and stop are relatively flat , such as elevator
Setup range 0. 0Hz~Maximum frequency and conveyor belt . Refer to F5.13 and F5.14 for the meanings
of the parameters .
F5.07 DC brake waiting time Factory
0.0s
at stop default value
Start segment Factory
F5.13 default value
30.0%
Setup range 0.0~36.0s proportion of S curve
DC brake current Factory Setup range 0.0~40.0%
F5.08 default value 0%
at stop End segment Factory
F5.14 default value 30.0%
Setup range 0~100% proportion of S curve
Factory Setup range 0.0~40.0%
F5.09 DC brake time at stop default value 0.0s

Setup range 0.0~36.0s t1 in the following figure is the parameter defined in F5.13 ,
within which the change slope of the output frequency
During the deceleration to stop , when the running frequency increases gradually .t2 is the time defined in F5.14 , within
reaches DC brake beginning frequency , and after DC brake which the change slope of the output frequency gradually
waiting time at stop (F5.07),the DC brake quantity has been decreases to zero . Within the time between t1 and t2 , the
inflicted until DC brake time at stop (F5.09) finished . change slope of the output frequency remains fixed .

56
Chapter 6 Parameter Description

Frequency In stop or running status ,when the status parameter(FV) needs


to be inquired again and again, by setting running parameter
(F6.01 to F6.02) and stop parameter (F6.03 to F6.04) , and
Fmax realizing the common-using status parameter by controlling the
shift key( ) to display in turns .
The parameter value of F6.01 to F6.04 is set according to
binary system , input by transforming it into decimal system .
When there needs to display one parameter of FV, you
only need to set the corresponding binary bite of F6.01 to F6.04
as 1 .
t1 t2 t2 t1 The corresponding relationship between the binary bite of
Time
acceleration time deceleration time F6.01 、F6.02 running display parameter and FV parameter
number is shown as attached fig.3 .
Fig.6-13 Schematic Diagram for S curve There are two examples about the setup way of F6.01 to F6.04
Acceleration/Deceleration in the following.
1: Client wants to display FV.00 , FV.02 and FV.18 circularly
in the running state .
Group F6 Keyboard and Display Setting as following : F6 . 01=1+4=5 F6 . 02=32

S Key function Factory 2: Client wants to display the setup frequency (FV.01) in the
F6.00 1
selection default value stop state
Setup range 0 S Key function disabled Setting as following : F6 . 0 3 = 2
1 Forward rotation Jog command
F6.05 Auxiliary supervise Factory
default value 1
2 Reverse rotation run command item selection
3 Clear the data of exact stop Setup range 0~25
process
The parameter is used to set FV parameter number of underside
S Key refers to multifunctional key .The function of S key range LED display of the double range LED operation panel,
can be set and defined by the parameter . please refer to FV parameter of page 35 for the details .
0:This key has no function . It is the content of underside range LED display that convenience
1:Forward rotation Jog command the client to debug and monitor inverter running. As for users who
It can realize forward rotation Jog (FJOG) through the S using exact stop function can realize setup value displaying and
key on the keyboard . actual value displaying at the same time through the double range
2:Reverse rotation run command LED.
The S key of operation panel used as input of the reverse F6.06 Load speed display Factory
1
coefficient default value
rotation run command , when the keyboard control mode
(F0.02) is 0 , press the key, then the inverter will output Setup range 0.0~100.0
frequency from the reverse phase order.
3:When the exact stop mode is enabled (FA.11≠0), press S The output frequency of the inverter and the load speed are
key, then the data of the exact stop process will be clean out. corresponding together through this parameter . It is set when
Please refers to the detailed description of FA.11 for exact the load speed needs to be displayed .
stop mode. Factory
F6.07 Reserved function default value
-
LED running display Factory User Factory
F6.01 default value 5 F6.08 0~9999 0
parameter 1 password default value
Setup range 0~8191
LED running display Factory Once any non-zero number be set , the password protection
F6.02 default value 0 function will be enabled .
parameter 2
Setup range 1~8191 0:Clear the previous user password setup and make the
password protection function invalid.
LED stop display Factory
To view F6.08 under the status of password protection , the LED
F6.03 default value 1
parameter 1
will prompt user that the parameter is hidden , you can only view
Setup range 0~8191
and modify this parameter when the password input correctly.
LED stop display Factory Please remember the user password correctly . If the password
F6.04 default value 0
parameter 2 is set wrongly or forgotten ,please contact the manufacturer .
Setup range 1~8191 Please refer to the description of password setting in 4.5 section .

57
Chapter 6 Parameter Description

Corresponding relationship
F6.01 LED running display parameter 1 between binary and decimal
0
Setup range 1~8191 FV.00 : Output frequency 2 =1
1
FV.01 : Setup frequency (flashes) 2 =2
2
FV.02 : Output current 2 =4
3
FV.03 : Running rev 2 =8
4
FV.04 : Setup rev (flashes) 2 =16
5
FV.05 : Running load speed 2 = 32
6
FV.06 : Setup load speed (flashes) 2 = 64
7
FV.07 : Output voltage 2 =128
8
FV.08 : Bus voltage 2 = 256
9
FV.09 : Input AC voltage 2 = 512
10
FV.10 : AI1 2 =1024
11
FV.11 : AI2 2 =2048
12
FV.12 : Pulse reference (DI) 2 = 4096

If the above parameters need to be displayed during the operation , set the corresponding bit
as 1 , and set them into F6.01after changing the binary numbers into decimal numbers.

F6.02 LED running display parameter 2 Corresponding relationship


between binary and decimal
0
Setup range 1~8191 FV.13 : PID setup (Flashes) 2 =1
1
FV.14 : PID feedback 2 =2
2
FV.15 : Terminal status 2 =4
3
FV.16 : Actual counting value 2 =8
4
FV.17 : Setup counting value (flashes) 2 =16
5
FV.18 : Actual length 2 = 32
6
FV.19 : Setup length (flashes) 2 = 64
7
FV.20 : Actual running time 2 =128
8
FV.21 : Setup running time (flashes) 2 = 256
9
FV.22 : AO1 output 2 = 512
10
FV.23 : AO2 output 2 =1024
11
FV.24 : Radiator temperature 2 =2048
12
FV.25 :Total running time 2 = 4096

If the above parameters need to be displayed during the operation , set the corresponding bit
as 1 , and set them into F6.02 after changing the binary numbers into decimal numbers.

F6.03 LED stop display


parameter 1 The corresponding relationship between binary in F6.03 and FV parameter number is
Setup range 0~8191 as same as that of F6.01

F6.04 LED stop display


parameter 2 The corresponding relationship between binary in F6.04 and FV parameter number is
as same as that of F6.02
Setup range 1~8191

Attached fig.3

58
Chapter 6 Parameter Description

Copy keyboard Factory


0 Factory
F6.09 F7.07 Deceleration time 3 20.0s
function selection default value default value
Setup range 0.0~6553.5s
Please refer to the copy keyboard description of our
Factory
company . F7.08 Acceleration time 4 20.0s
default value
Setup range 0.0~6553.5s
F7.09 Deceleration time 4 Factory 20.0s
default value

Group F7 Auxiliary Function Setup range 0.0~6553.5s

Acceleration/deceleration time can select F0.13 and F0.14


F7.00 Jog running frequency Factory 5.00Hz and the above three types of acceleration/deceleration time .
default value
Their meanings are the same .
Setup range 0.00~the upper limit frequency F0.11 It can select acceleration/deceleration time 1 to 4 during the
Factory inverter running process through the different combination of
F7.01 Jog acceleration time default value 20.0s
multifunctional digital input terminal X . Please refer to the
Setup range 0.0~6553 .5s description of Group F3 (Input Terminal).
Factory The above acceleration/deceleration time can also be used to
F7.02 Jog deceleration time 20.0s
default value satisfy locale need under the mode of PLC running .
Setup range 0.0~6553 .5s
Factory
F7.10 Skip frequency default value 0.00Hz
It is used to define the reference frequency and acceleration/
Setup range 0.0Hz~the maximum frequency F0.11
deceleration time of the inverter during Jog .
The Jog process starts and stops according to the start Skip frequency Factory
F7.11 default value 0.00Hz
amplitude
mode 0 (F5.00=0 , start from start frequency )and the stop
Setup range 0.0Hz~the maximum frequency F0.11
mode 0 (F5.05=0 ,deceleration time to stop ).
The Jog acceleration time means the time required for the When the setup frequency is within the range of skip frequency ,
inverter to accelerate from 0Hz to the maximum output the actual running frequency will be in the skip frequency boundary
frequency (F0.11). close to the setup frequency .
The Jog deceleration time means the time required for the It can make the inverter run away from the mechanical resonance
inverter to decelerate from the maximum output frequency point of the load through setting the skip frequency .
(F0.11) to 0Hz . If the two skip frequency are set as zero , this function will be
disabled .
Jog action selection Factory
F7.03 default value 0
on running status Adjusted
setting
Setup range 0 actived frequency

1 disabled
Skip Skip frequency amplitude
frequency Skip frequency amplitude
It can avoid jog command for error operation by setting
it to 1 during the running process of inverter .

F7.04 Acceleration time 2 Factory


20.0s
default value
Setup range 0.0~6553.5s Frequency setting signal

Factory
F7.05 Deceleration time 2 20.0s
default value Fig.6-14 Schematic Diagram of Skip Frequency
Setup range 0.0~6553.5s
Factory
F7.06 Acceleration time 3 default value 20.0s

Setup range 0.0~6553.5s

59
Chapter 6 Parameter Description

Forward/reverse Factory Frequency detection Factory


F7.12 0.0s 2.00Hz
rotation dead-zone time default value F7.18 hysteresis default value
Setup range 0.0~3000.0s
( FDT2 hysteresis )
Setup range 0.0Hz~the maximum frequency F0.11
During the setting of forward/reverse rotation of the inverter ,
the transition time at the output zero frequency position. It is used to set the detection value of output frequency and
It is shown as the following figure : output the hysteresis value removed by the action .
Output frequency
Output frequency

FDT1 Level FDT1 Hysteresis

Running time

Time

dead zone time


Output Terminal
Fig.6-15 Schematic Diagram of Forward/Reverse Rotation ON
Dead-zone Time
Factory Time
F7.13 Reverse control default value 0
Fig.6-16 Schematic Diagram for FDT Level
Setup range 0 Actived
1 Disabled Frequency arrival Factory
F7.19 default value
2.00Hz
detection amplitude
when the parameter is set as 0:Reverse rotation running
Setup range 0.0Hz~the maximum frequency F0.11
actived
when the parameter is set as 1:Reverse rotation running When the output frequency of the inverter reaches the setup
disabled frequency value , this function can be used to adjust the
The parameter is enabled for all command sources . detection amplitude , it is shown as the following figure .

Setup frequency lower Output frequency


Factory
F7.14 than frequency lower default value
1
limit action
Setup range 0 Run with frequency lower limit Setup
frequency Detected Amplitude
1 stop
2 Running with zero velocity

It is used to select the running status of the inverter when the Time
setup frequency is lower than the frequency lower limit .
Output Terminal
In order to avoid the motor always running with low velocity,
this function can be used to stop . ON

Frequency detection Factory Time


F7.15 default value
50.00Hz
value ( FDT1 level )
Fig.6-17 Schematic Diagram for Detection Amplitude
Setup range 0.0Hz~the maximum frequency F0.11
Frequency detection Factory
F7.16 hysteresis default value 2.00Hz
( FDT1 hysteresis )
Setup range 0.0Hz~the maximum frequency F0.11
Frequency detection Factory
F7.17 default value
50.00Hz
value ( FDT2 level )
Setup range 0.0Hz~the maximum frequency F0.11

60
Chapter 6 Parameter Description

Group F8 Fault and Protection F8.07


Restart waiting time Factory
1.0S
after power-off default value
Setup range 0.1~10.0s
F8.00 Inverter overload Factory
default value 110%
pre-warning When restart after power-off is enabled ,inverter is on the
Setup range 50~200% running state before power cut. Then the inverter will start
automatically after the setup waiting time (it is set by F8.07)
Inverter overload Factory
F8.01 pre-warning delayed time default value 2.0S when power-on .During the restart waiting time ,the inverter
won’t start, even though there inputs run command, if there
Setup range 0.0~20.0s inputs stop command , it will finish the restart waiting state .
The reference for this value is the inverter rated current .
F8.08 Fault automatic Factory
When the inverter detects that the output current exceeds default value 0
reset times
the corresponding current of parameter F8.00 continuously,
Setup range 0~3
it outputs pre-warning signal from OC or relay, after the
delayed time of F8.01. When the inverter selects fault automatical reset , it is used to set
Overload 、Overheat Factory
0
the times of automatical reset .If the value is exceeded , the
F8.02 default value
protective action mode inverter will stop because of failure and wait for maintenance .
Setup range 0 inverter locks output
Fault automatic reset Factory
1 limitative current running(alarm) F8.09 default value 1.0S
interval time
Setup range 0.1~100.0s
The parameter set the inverter protective action mode when it
is overload or overheat. The waiting time of the inverter from the fault alarm to automatical
0:The inverter locks output immediately . When it is overload reset .
or overheat, the inverter locks output and the motor coasts to Factory
stop . F8.10 First time fault type default value
1:Limitative current running (alarm). When it is overload Factory
F8.11 Second time fault type
or overheat , the inverter is running in a limitative current mode, default value
and the inverter might reduce the output frequency to decrease Factory
F8.12 Third time fault type
the load current at this time. default value

Motor overload Factory


Fault meaning Fault code
F8.03 100%
protection codfficient default value 0:no fault --
Setup range 30.0~100.0% 1:Inverter unit protection E.1
2:Acceleration over current E.OC1
The value is equal to motor rated current/inverter rated current . 3:Deceleration over current E.OC2
When the inverter output current exceeds F8.03 multiply the 4:Constant speed over E.OC3
inverter rated output current for a certain time , the inverter current
5:Acceleration over voltage E.OU1
reports motor overload fault . 6:Deceleration over voltage E.OU2
Stall protection Factory 7:Constant speed over E.OU3
F8.04 coefficient over current default value 150% voltage
Setup range 110~200% 8:Stop over voltage E.OU4
9:Running under voltage E. LU
Select the protection point for the stall over current function. 10:Inverter overload E.OL1
When the value is exceeded , the inverter starts executing the 11:Motor overload E.OL2
protection function for stall over current . 12:Phase loss output E. LF
Stall protection Factory
13:Inverter overheat E. OH
F8.05 coefficient over current default value 130% 14:External equipment fault E. EF
15:Communication fault E. CE
Setup range 120~150%
16:Output grounding E. GF
Select the protection point for the stall over voltage function. 17:CPU interference E.2
When the value is exceeded , the inverter starts executing the 18:Current detect fault E.3
protection function for stall over voltage . 19:EEPROM read-write fault E.4
20:Phase loss input E.5
Restart setup after Factory 21:PID feedback
F8.06 default value
0 E.6
power-off disconnection
Setup range 0 no action 22:Reserved E.7
1 action 23:Reserved E.8

61
Chapter 6 Parameter Description

F8.13 Output frequency 5:Max{AI1,AI2}


on fault Display the state parameter 6:Pulse setup(DI)
Output current upon fault for the latest time . 7:Communication setup
F8.14
on fault The first part of LED:
F8.15 Bus voltage on fault Terminal status expression PID reference source
Module temperature for fault. 0:panel potentiometer
F8.16
on fault Refer to the details in FV.15 1:PID digital reference (F9.02)
F8.17 Terminal state . 2:AI1
on fault 3:AI2
4:Pulse setup(DI)
5:Communication setup

The third part of LED: PID action direction


Group F9 PID Function Positive action: When the feedback signal is higher than the
PID reference , the output frequency of the
PID function summarize
inverter should be reduced to balance the PID . Such as the
PID control is a common method of process control . It adjusts tension PID control of winding.
the output frequency through proportional , integral and The second part of LED: PID feedback source
differential calculations of the difference between the This parameter is used to select the PID feedback channel .
reference signal of the controlled quantity and the feedback When using the sensor with voltage output ,you need to modify
signal , and thus to stabilize the controlled quantity at the the voltage loss of the longer signal cable. It can be realized
target quality . through setting the minimum/maximum input of AI1 and AI2
PID reference signal :It is the signal that corresponding in Group F3 .
to control target of the controlled quantity. The first part of LED: PID reference source
PID feedback signal :It is the signal that measured by sensor This parameter decides the target quantity reference channel
and corresponding to the actual value of the controlled quantity, of the process PID .
it varies with process load and indicates the actual state during PID reference has two expression modes:
the control process.
The differences between the actual status of the controlled quantity 1:PID reference source selection: when the value is 0 or 2 or
and the control target will be reflected by the differences between 3 or 4 , PID setup value adopts percentage expression that
PID feedback and the reference signal . control target is relative to PID range , 100% PID setup
According to different symbols, PID controller rises or reduces corresponding to100% feedback signal of controlled system ,
output frequency accordingly so as to achieve the autocontrol PID is not necessary at that moment . No matter how much the
propose. range is , the system operates according to the relative value
The built-in PID controller inverter is applicable to process (0 to 100%) . Once setting the PID range , you can directly
control such as fluid control , pressure control ,temperature observed PID setup and the feedback corresponding signal
control and so on . actual value through the operation panel display parameter .
Prompt : When client needs to use the PID controller function ,
2:When PID reference source selects 1 or 5 , or PID second
he should set the frequency source selection parameter as PID
digital reference enabled , PID setup value adopts absolute value
enabled at first, which means F0.03 (F0.04)=7 .
expression that control target is relative to PID range , the control
Factory target value of controlled quantity is directly endued with
F9.00 PID control mode setup default value
001 parameter F9.02 and F9.03 at this moment .
Setup range The third part ot LED: When PID setup value is equal to the range , it is corresponding
PID action direction to100% feedback signal of controlled system , here PID range is
0:positive action necessary, for it is the value which is the percentage relationship
1:reverse action of both setup value and range that takes part in PID calculation.
The second part of LED: It means : PID setup = PID digital setup value / range *100%
PID feedback source The value corresponds to PID feedback percentage .
0:AI1
1:AI2 3:The above explanation is applcable to PID feedback of
2:AI1+AI2 communication setup .
3:AI1-AI2
4:Min{AI1,AI2}

62
Chapter 6 Parameter Description

PID reference Factory


F9.07 Factory
F9.01 default value 1000 Integration time I default value
2.0S
feedback range
Setup range 0~9999 Setup range 0.1~100.0s 100.0s : close I
PID reference feedback range is a nondimensional unit , it is used Proportional gain P:
to display the PID reference and feedback . It decides the adjustment intensity of the whole PID regulator . The
Factory higher the P is , the more powerful the adjustment intensity is .
F9.02 PID digital reference default value
500 When this parameter is 100 , it indicates the deviation between
Setup range 0 ~ F9.01 PID feedback quantity and the reference quantity is 100% , the
PID regulator regards the adjustment amplitude appointed by
PID digital reference is one of the PID reference channel. Refer the output frequency as the maximum frequency (the integral and
to explanation about the second expression mode of PID differential functions are neglected) .
reference for its meaning.
Integration time I:
F9.03 PID second digital Factory
500 It decides the speed of PID regulator adjusting the deviation
reference default value between the PID feedback quantity and the reference quantity .
Setup range 0 ~ F9.01 Integration time is the time within which the integration regulator
(the proportional and differential functions are neglected) performs
PID second digital reference is one of the PID reference channel.
continuous adjustment and the adjustment quantity reaches the
Refer to explanation about the second expression mode of PID
maximum frequency when the deviation between the PID feedback
reference for its meaning.
quantity and reference quantity is 100% .The shorter the integration
PID second digital reference is a makeup of the default PID
time is, the more powerful the adjustment intensity is .
reference source .
The external terminal is set as 25 by Group F3 parameter ,when
Factory
the terminal enabled ,PID setup value will be switched from F9.08 Differential time D default value
0.0s
the PID reference channel value selected in the first part of
Setup range 0.0~ 10.00s 0.0s : close D
F9.00 into the value of F9.03.
Factory
F9.09 Differential amplitude default value 5.0%
Factory
F9.04 Deviation limit default value
0.0%
Setup range 0.0~ 100.0%
Setup range 0.0~50.0%
Differential time D:
Factory
F9.05 Reserved function 0 It decides the intensity of PID regulator adjusting the change rate
default value
of deviation between the PID feedback quantity and the reference
Deviation limit :It means that PID system output value corresponding quantity .Differential time is the time within which if the feedback
to the biggest deviation allowed by close loop reference. When the PID quantity changes 100% , the adjustment quantity reaches the
feedback deviation is within this range , the PID stops adjustment . It is maximum frequency (proportional and integral functions are
shown as the follows . Setting the function code in reason can improve neglected) . The longer the differential time is , the more powerful
the precision and stability of PID system . the adjustment intensity is .
Factory
Feedback quantity F9.10 PID preset frequency default value
0.00Hz

Reference Deviation limit Setup range 0.0Hz~the maximum frequency


PID preset frequency Factory
F9.11 default value 0.0s
keep time
Setup range 0.0~3600.0S
Output frequency Time
In some applications, if process adjustment is set by optimum ,it will
delay the time to reach the required process state .In this kind of
application, you'd better make sure the output frequency that the
inverter inquired the motor to reach before start the process adjustment.
Time It can be realized by setting parameter F9.10. In this operational mode,
Fig.6-18 Corresponding Relationship between Deviation if running command is input, the inverter will make response according
Limit and Output Frequency to the acceleration/deceleration time at the open loop . Only when the
output frequency reached the setup PID preset frequency and it kept
Factory
F9.06 Proportional gain P default value 20.0% running at the frequency point for a period of time, will it run in term of
Setup range the characteristics of close loop .(The PID preset frequency could set by
0~100.0% 0.0% : close P
corresponding frequency of normally run of speed. This could be more
easy to meet the process condition).

63
Chapter 6 Parameter Description

Output frequency
PID feedback Factory
F9.16 disconnection default value 00
preset frequency detection
The second part of LED:action mode

Setup range
0:enter PID feedback disconnetcion
fault state(display E.6)
1:stop in term of F5.05 setup
preset frequency keep time stop mode
Time 2:keep current running frequency
The first part of LED:detection mode
Fig. 6-19 Schematic Diagram for PID Preset Frequency 0:no detection
Prompt :If close loop preset frequency function is not inquired 1:detection in term of PID
, you can set the preset frequency and its holding time to zero . feedback signal
2:detect in term of disconnection
proximity switch signal
Factory
F9.12 Sleeping frequency default value 0.0Hz
F9.17 PID feedback Factory
0.0%
Setup range 0.0Hz~the maximum frequency disconnection result default value
Factory
F9.13 Sleeping protract 60.0s Setup range 0.0~50.0%
default value
PID feedback
Setup range 0.0 ~ 3600s disconnection and
Factory
F9.18 default value 2.0s
When output frequency is lower than F9.12, it will enter the judgement delay
status of sleeping and coast to stop after F9.13 setup time. Setup range 0~20.0s
By selecting the output terminal function as 20, the output
terminal enabled at sleeping status. In this condition, the output There are two disconnection detection modes for selection:
terminal can drive small sleeping pump. For details, please refer When the first part of F9.16 is set as 1, PID feedback detects
to parameters from F4.00 to F4.02 . disconnection , F9.17 is the threshold , when the feedback is
Factory lower than the threshold, it may be in disconnection state .
F9.14 Awkening threshold default value 0.0%
When the first part of F9.16 is set as 2 , the disconnnection
Setup range 0.0~100.0% detection proximity switch signal detects disconnection , there
Factory needs to set the corresponding parameter of input terminal as
F9.15 Awakening protract 0.5s
default value 30 before use .
Setup range 0.0~60.0s Procedure deals with disconnection adjustment :
After the inverter starts , it starts to detect disconnection ,
Awakening threshold is the corresponding percentage of PID when disconnection signal (terminal/PID feedback) enabled
setup. In sleeping state , when PID feedback lower than PID and the duration reaches F9.18 (disconnection adjustment
setup value * F9.14, the inverter restarts after the time of F9.15. protract) , the inverter is in the status of disconnection and
PID feedback it deals with this in term of F9.16 setup action mode.
Awakening protract
parameter F9.15

Reserved function Factory


F9.19 default value
-
Awakening threshold
parameter F9.14 Factory
F9.20 Reserved function default value
-
Time
Factory
F9.21 Reserved function default value
-
PID output (output frequency)

Td=sleeping protract ,parameter F9.13 The precision after Factory


F9.22 default value 0
PID range radix point
Setup range 0~3
Sleeping frequency
parameter F9.12
Time
stop start

Fig. 6-20 Schematic Diagram for PID Sleeping /Awakening

64
Chapter 6 Parameter Description

Group FA Swing Frequency ,Fixed Length and Count


Setup frequency(Hz)
Frequency amplitude
Aw=Fset×FA.01
Frequency upper limit FH
+Aw
Cetnter frequency Fset
Frequency lower limit FL
-Aw
Textile kick frequency
=AW×FA.02

Triangular wave Time (t)


Accelerate by Decelerate by
acceleration time
=FA.03×FA.04 deceleration time

Frequency cycle FA.03


Running command
Stop command
Fig.6-21 Schematic Diagram for Swing Frequency

The swing frequency function is applicable to the textile and The parameter is used to determine the values of swing
chemical fiber fields and the applications where traversing and amplitude and kick frequency .
winding functions are required . Swing amplitude AW (variable swing amplitude) =
The swing frequency function means that the output frequency frequency source F0.07 x swing amplitude FA.01
of the inverter swings up and down with the setup frequency Swing amplitude AW (fixed swing amplitude) = upper
(frequency command is selected by F0.07) as the center . The frequency F0.11x swing amplitude FA.01
trace of running frequency at the time axis is shown as the Prompt:the swing frequency is limited by the frequency
figure above , in which the swing amplitude is set by FA.01 upper limit and frequency lower limit .If the setting is
and FA.02 . inappropriate , it works abnormally .
Swing amplitude Factory Kick frequency = swing amplitude AW x kick frequency
FA.00 00
setup mode default value amplitude FA.02
Setup range The second part of LED: swing If the swing amplitude relative to the central frequency is
frequency function enabled selected , the kick frequency is a variable value .
0:disabled 1:enabled If the swing amplitude relative to the upper limit frequency
The first part of LED:swing amplitude is selected , the kick frequency is a fixed value .
benchmark
0:relative to the central frequency Factory
FA.03 Swing frequency cycle default value 10.0S
1:relative to upper limit frequency
Setup range 0.1~3000.0s
The second part of LED: whether the Selection of swing
frequency function enabled Time constant of Factory
FA.04 default value 50.0%
triangular wave boost
The first part of LED:It is used to determine the swing
amplitude benchmark . Setup range 0.1~100.0%
0: Relative to the central frequency , and it is a variable swing
amplitude system . The swing amplitude varies with the central Swing frequency : I t refers to the time of a complete cycle of swing
frequency (setup frequency) . frequency .
1:Relative to the maximum frequency (F0.11) , and it is fixed FA.04 Time constant of triangular wave boost is relative to
swing amplitude system . The swing amplitude is fixed . FA.03 swing frequency cycle .
Triangular wave boost time = FA.03 x FA.04(unit : s)
Swing frequency Factory
FA.01 default value 0.0% Triangular wave falling time = FA.03 x(1- FA.04)(unit : s)
amplitude
Setup range 0.0~100.0%

FA.02 Kick frequency Factory


0.0%
amplitude default value
Setup range 0.0~50.0%

65
Chapter 6 Parameter Description

Factory The function is shown as the following figure:


FA.05 Setup length default value 1.000km 1 2 3 4 5 6 7 8
Counting Pulse X5
Setup range 0~65.535km
Setting Count 0 C1
Factory
FA.06 Designed length default value
1.000km
Designated 0 C2
Count
Setup range 0~65.535km
Number of pulses Factory Fig. 6-22 Schematic Diagram for Setup Counting Value
FA.07 default value 100.0 Reference and Designated Counting Value Reference
each meter
Setup range 0.1~6553.5 Counter control as one of the exact stop modes , when it arrivals
The setup (designed)length ,actual length and number of the setup length , the inverter stops automatically .
pulse each meter are mainly used for fixed length control . For detail setting ,refer to the parameter description of FA.11 .
For the image parameter FV.19 of FA.05 and FA.06 , their
Internal timing setup Factory
meanings are the same , just one method added to easy FA.10 default value 24.000h
running time
parameter modification and viewing. (Please refer to the Setup range 0.0~65.535 h
description of FA.11 exact stop mode .)
The length is calculated via the pulse signal input by the X6 For image parameter FV.21 of FA.10 , its meaning is the same
input terminal , and it needs to set the corresponding input , just one method added to easy parameter modification and
terminal to length count input terminal . viewing. (Please refer to the description of FA.11 exact stop
Actual length =length count input pulse numbers/number mode .)
of pulse each meter When actual running time FV.20 exceeds the setup running
When the actual length FV.18 exceeds the setup length FA.05 , time FA.10 , the output terminal “Setup running time arrival
the output terminal “Length arrival terminal” will output ON terminal” will output ON signal (refer to Group F4 function
signal (refer to Group F4 function code). code).
Fixed length control as one of the exact stop modes, when it Timing stop control as one of the exact stop modes , when it
arrivals the setup length, the inverter stops automatically. arrivals the setup length , the inverter stops automatically .
For detail setting, refer to the parameter description of FA.11 . For detail setting, refer to the parameter description of FA.11 .
Factory Factory
FA.08 Setup counting value default value
1000 FA.11 Exact stop mode setup 0
default value
Setup range 1~9999 Setup range 0 disabled
Designated counting Factory 1 setup counting value arrival
FA.09 default value
1000
value 2 setup length arrival
Setup range 1~9999 3 setup running time arrival

Actual counting value FV.16 is calculated via the pulse signal Exact stop mode: In term of several control
input by the X6 input terminal , and it needs to set the X6 produce quantity which is in common use to realize inverter
terminal to count input terminal . automatical stopping , and you can use operation panel to
For image parameter FV.17 of FA.08 , its meaning is the same replace counter , length controller , timing which are widely
, just one method added to easy parameter modification and used in machine facilities .
viewing. (Please refer to the description of FA.11 exact stop The operation methods of exact stop:
mode .) 1:data display and modification
When the actual counting value reaches the setup counting value If the parameter is set in reason , the inverter can display and
, the output terminal will output signal of the setup counting value. modify the data just like operating the counter ,the length
The counter will stop counting . controller and the timing .
When the actual counting value reaches the designated counting Firstly, set the corresponding parameter of exact stop as
value, the output terminal will output signal of the designated enabled by setting parameter F6.01 to F6.04.
counting value . The counter will continue counting till the e.g.: set F6.02 = 96 to make the setup length and the actual
“setup counting value” is reached . length enabled .
In the monitor mode of the state parameter, you can switch
The designated counting value FA.09 should not exceed the
display content via shift key . When it switches into
setup counting value FA.08 .
display actual length , you can modify it via Increase key
/Decrease key of the operation panel, exit it by pressing
FUNC key or ENTER key. The actual length value will

66
Chapter 6 Parameter Description

increase unceasingly, on base of modified value, along with Factory


the signal input. FB.00 MS speed 0 default value
0.0Hz
When it switches into display setup length , you can modify Setup range 0.00~upper limit frequency F0.11
the setup length via Increase key/Decrease key of operation
Factory
panel , exit it by pressing FUNC key or ENTER key. The FB.01 MS speed 1 default value 0.0Hz
difference between FUNC key and ENTER key is described
as follows : By pressing ENTER key, the modified content will Setup range 0.00~upper limit frequency F0.11
be saved to EEPROM so that it is still active when power-on at Factory
FB.02 MS speed 2 default value 0.0Hz
the next time , while by pressing FUNC key, the modification of
setup length only enabled at this time . Setup range 0.00~upper limit frequency F0.11
The above examples are also applicable to the modification of Factory
FB.03 MS speed 3 default value 0.0Hz
counter and timing data .
2:process data reset Setup range 0.00~upper limit frequency F0.11
The process data contains actual counting value , actual length Factory
FB.04 MS speed 4 0.0Hz
and actual running time. Through setting corresponding default value
parameters, the reset of them can be realized by external Setup range 0.00~upper limit frequency F0.11
terminals (setting Group F3 parameter ) or S key (setting F6.00) .
Factory
FB.05 MS speed 5 default value 0.0Hz
3:process data memory when power-off
When power-off, the inverter will save the process data, Setup range 0.00~upper limit frequency F0.11
which contains actual counting value , actual length and
Factory
actual running time, to EEPROM , and the data will FB.06 MS speed 6 default value 0.0Hz
recover to the value as before when power-on again so
Setup range 0.00~upper limit frequency F0.11
that it can produce continuously.
Factory
An example for exact stop action mode FB.07 MS speed 7 default value 0.0Hz
(set the counting value as N).
N-1 N N+1 Setup range 0.00~upper limit frequency F0.11
Counting pulse X6 1 2 Factory
FB.08 MS speed 8 default value 0.0Hz
Running command
Setup range 0.00~upper limit frequency F0.11
Stop command Factory
FB.09 MS speed 9 default value 0.0Hz
Fig. 6-23 Schematic Diagram for Exact Stop
Setup range 0.00~upper limit frequency F0.11
Control Mode
Factory
FB.10 MS speed 10 default value 0.0Hz

Setup range 0.00~upper limit frequency F0.11


Group FB MS Speed Function and FB.11 MS speed 11
Factory
0.0Hz
default value
Simple PLC Function
Setup range 0.00~upper limit frequency F0.11
Simple PLC function is to perform automatic control on the MS Factory
FB.12 MS speed 12 default value 0.0Hz
frequency logic through a built-in programmable controller
(PLC) of the inverter . It can set running time , running direction Setup range 0.00~upper limit frequency F0.11
and running frequency so as to meet the process requirements . Factory
FB.13 MS speed 13 default value 0.0Hz
The series of inverter can implement 16-segment variable
control and it has four types of acceleration/deceleration time Setup range 0.00~upper limit frequency F0.11
for selection . Factory
FB.14 MS speed 14 default value 0.0Hz
When the setup PLC completes one cycle , the multifunctional
output terminal can output an ON signal. Setup range 0.00~upper limit frequency F0.11
Refer to F4.00 to F4.02 for details . Factory
FB.15 MS speed 15 default value
0.0Hz
When the frequency source selections F0.07 , F0.03 and F0.04
are determined as MS speed running mode , FB.00 to FB.15 Setup range 0.00~upper limit frequency F0.11
should be set to determine its characteristics .

67
Chapter 6 Parameter Description

When the frequency source selections F0.07 , F0.03 and F0.04 2:Constant circulation
are determined as PLC running mode , FB.00 to FB.15,FB.16, The inverter will automatically start next one cycle upon
FB.17 and FB.18 to FB.41should be set to determine its the completion of one cycle , and will not stop until stop
characteristics . command is given .
f6 f6
Factory f2 f2
FB.16 PLC running mode 00 f7 f7
default value
f1 f5 f1 f5 d1
Setup range The second part of LED:PLC
f1 d1d2
running time unit selection f3 f3
0:second 1:hour
f4 f4
The first part of LED:PLC action
mode T1 T2 T3 T4 T5 T6 T7 T1 T2 T3 T4 T5 T6 T7 T1
0:Stop upon the completion of
one-time running First time cycle Second time cycle
1:Keep final value upon
the completion of one-time running RUN
2:Constant circulation command
STOP
command
The second part of LED:PLC running time unit selection
It is used to define every segment running time unit of Fig. 6-26 Constant circulation
the sixteen segments program .
The first part of LED: PLC action mode FB.17 PLC power-failure Factory
0
memory selection default value
0:Stop upon completion of one-time running Setup range 0 power failure without memory
The inverter will automatically stop upon completing one
1 power failure with memory
single cycle , and will not restart until another running
command is given . PLC power failure with memory means the memory of running
f6 phase and frequency of PLC before power failure.
f2 d7
a6 f7
a2
d3 f5 d7
a1 f1 FB.18
Factory
0.0s
a5 Phase 0 running time default value
a3 f3 d5
a4
f4 As for the above parameters, refer to
T1 T2 T3 T4 T5 T6 T7 the description of parameter table .

RUN command

PLC phase
completion Factory
PLC FB.41 Phase 14 /15 running 0000
mode default value
circulation
completion
Fig. 6-24 Stop Upon the Completion of one-time Running Group FC Communication Parameter
1:Keep final value upon the completion of one-time running For details, please refer to chapter 7.
The inverter will automatically keep the running frequency and
direction of last one segment upon completing one single cycle .
Group FD Particular Function
f6
f2 d7 Factory
a6 f7 FD.00 Droop control default value 0.0Hz
a2
d3 f5
a1 f1 Setup range 0.00Hz~10.00Hz
a5
a3 f3 d5
a4
f4 When several inverters drive the same load , different velocity
T4 T7
leads to the unbalanced load distribution, thereby, inverter with
T1 T2 T3 T5 T6
higher speed has to carry heavier load . The droop control
characteristics can change the speed droop with the addition of
RUN command load to balance the load distribution . The parameter is used to
Fig. 6-25 Keep Final Value Upon the Completion adjust the frequency change value of the inverter with droop
of one-time Running velocity .

68
Chapter 6 Parameter Description

Automatic energy Factory Factory


FD.01 0 FD.08 Inner fan control default value
0
conservation running default value
Setup range 0:no action 1:action Setup range 0 automatic
when select automatic energy conservation 1 constant open
running , the inverter will be able to adjust
the output in term of different load and 0:automatic
make the motor work in a high efficiency Inner fan switch on-off depends on the environmental temperature
state all the times . and inverter’s working state .
1:constant open
Inner fan opens all the times when power-on .
Simple servo function Factory
FD.02 default value 10
mode selection FD.09 User password Factory 0
Setup range The second part of LED: default value
the precision after FA.07 radix point Setup range 0~9999
0~3 Factory
FD.10 Parameter initialization default 0
The first part of LED: value
simple servo mode selection Setup range 0 no operation
0:disabled 1:enabled 1 Restore factory default setup value
2 Clear the fault record
Simple servo mode:
It calculates the needed speed curve in term of the setup length, 1:The inverter restores all the parameters except the parameters
the actual length and the current velocity automatically and in Group F1 to the factory default ones .
arrives the setup length in the shortest time accurately without 2:The inverter clears the recent fault records .
PLC and speed crawl phase.
Factory
FD.03 Relay break protract default value 0.0s
Setup range 0~1000.0s
Factory
FD.04 Pulse input filter times default value 4
Setup range 1~10
Input phase loss Factory
FD.05 protection selection default value 1
Setup range 0:disabled 1:enabled
EH640A3.7G/5.5P and thereinafter
level models haven’t this function
even though the value is set as one .
EH623A1.5G/2.2P and thereinafter
level models haven’t this function
even though the value is set as one .
Output phase loss Factory
FD.06 protection selection default value 1
Setup range 0:disabled 1:enabled

MS 0 frequency Factory
FD.07 default value 0
source selection
Setup range 0 FB.00
1 panel potentiometer
2 Digital setup by UP and DW
adjustment
(panel or external terminal )
3 AI1
4 AI2
5 Pulse reference (DI)

69
Chapter 6 Parameter Description

Group FV Status Parameter


Modif-
Function
code Name Setup range Minimum unit Factory default
value ication
F V.0 0 Output frequency 0.0Hz~upper limit frequency 0.01Hz *
F V.0 1 Setup frequency 0.0Hz~upper limit frequency 0.01Hz *
(flashes)
F V.0 2 Output current 0.1~1000.0A 0.01A *
F V.0 3 Running rev 0~9999rpm 1r/min *
F V.0 4 Setup rev (flashes) 0~9999rpm 1r/min *
F V.0 5 Running load speed 0.001~9999 0.01m/S *
F V.0 6 Setup load speed 0.001~9999 0.01m/S *
(flashes)
F V.0 7 Output voltage 0~rated voltage 1V *
F V.0 8 Bus voltage 1V *
F V.0 9 Input AC voltage 1V *
F V.10 AI1 0~10.00V 0.01V *
F V.
11 AI2 0~10.00V Note:when current input, 0.01V *
1V corresponding to 2mA
F V.
12 Pulse reference (DI) 0~50.00kHz 0.001kHz *
F V.
13 PID setup (Flashes) 0.1% *
F V.
14 PID feedback 0.1% *
F V.
15 Terminal status refer to the following detailed explanation *
F V.16 Actual counting value 0~setup counting value 1 0 ○
FV 1 7 Setup counting value 1~9999 1 1000 ○
. (flashes)
F V.18 Actual length 0.0~65.535km 0.001km 0.0km ○
F V.19 Setup length (flashes) 0.0~65.535km 0.001km 1.000km ○
F V.2 0 Actual running time 0.0~65.535h 0.001h ○
F V.2 1 Setup running time 0.0~65.535h 0.001h 24.00h ○
(flashes)
F V.2 2 AO1 output 0~10.00V Note:when current output, 0.01V *
1V corresponding to 2mA
F V.2 3 AO2 output 0~10.00V/0~50.00kHz 0.01V/0.001kHz *

F V.2 4 Radiator temperature 0. 1 C *
F V.2 5 Total running time total running time after leave factory 1h *

FV status parameter is used to display the current state of inverter , there are two methods to view it. As for details, please refer
to the method of viewing status parameter in 4.3 section .
FV.16 to FV.21, the control parameter of exact stop, can be modified on-line. As for the modification and setting, refer to the
parameter description of FA.11 .

70
Chapter 7 SD100 Communication Protocol and Description of Communication

Chapter 7 SD100 Communication Protocol


and Description of Communication
Communication protocol of SD100 is completely compatible with standard communication protocol of Modbus, meanwhile ,
according to the applied requests from client, the protocol added accumulation、 check mode and complex command mode to
enrich the programme choice of client.

7.1 SD100 serial communication protocol


In the SD100 series inverters , we will provide RS485 communication interface (when the interface of the host computer
is RS232, you can choose and buy RS485/232 adapter of our computer to transform signal at the same time ). User may realize
centralized control (set inverter running command , function code parameter , read the work status and fault information of
inverter ) by PC or PLC to adapt specific required usage.

1. Protocol contents
The serial communication protocol defines the transmission information and use format in the series communication.
It includes host-polling (or broadcasting) format , host coding method and the content are function code of action,
transferring data and error checking. The response of slave adopts the same structure , and it includes action affirmance,
data returning and error checking. If slave made mistakes while it is receiving the information or cannot finish the action
demanded by the host, it will send one fault signal to the host as a response.
When the host computer adapts broadcast address , all slave computers receive the data from the host computer, but no
response will made to host computer .

2. Application Mode
Inverter will be connected into a “Single-host Multi-slave”PC/PLC control net with RS485 bus .

3. Bus Structure
(1)Interface Mode
RS485 hardware interface
(2)Transmission Mode
Asynchronous serial and half-duplex transmission mode. Just one can send the data and the other receives the
data between the host and the slave at the same time. In the series asynchronous communication , the data is sent out
frame by frame in the form of message .
(3)Topological Structure
Single host computer multi-slave computer system . The setup range of slave address is1to 247, zero is broadcast
communication address. The address of the slave in the network must be exclusive.
4. Protocol Specification
SD100 series inverter communication protocol is a kind of serial host-slave communication protocol. In the network ,
only one equipment, the host, can build a protocol , (Named as "Inquiry/Command"). Other equipments , slaves, response
"Inquiry/Command" of the host only by providing the data or take the action according to "Inquiry/Command" of the host.
Here , the host is a Personnel Computer, Industrial Machine or Programmable logical controller , and the slave is inverter.
Host not only can communicate with certain slave separately, but also can send the broadcast information to all the slaves.
For the single inquired "Inquiry/Command" of the host, all the slaves should return a signal(a response) ; for the broadcast
information provided by the host, slaves need not to feedback a response.
5. Communication Structure
The Modbus protocol data format of SD100 series inverter is as following :
By using RTU mode, there are at least 3.5-byte startup interval time between data frames .The first field transferred
is equipment address , the character that can be used is 0 to 9 and A to F of hex .The net equipment senses the network bus
and the pause interval time continuously. When receiving the first field (means address message ) , every equipment is
decoding to judge whether the message is sent to it. When the last character is transmitted, there is a similar 3.5-byte
interval time to demarcate that the frame is finished.

71
Chapter 7 SD100 Communication Protocol and Description of Communication

And then a new message will startup after that time . The whole message frame must be transferred as a continuous
data stream. If there is pause time exceeds 1.5-byte internal time before the frame finished , the receive equipment will
refresh the non-integrated message and assume the next byte to be a address field of the new message. Similarly, a new
message starts with the former one in less than 3.5-byte internal time, the receive equipment will reckon it as the
continuation of the former, which will lead to errors because the value cannot be correct in the last checking field.
RTU frame format:
Frame START 3.5-byte internal time
Slave ADR add:1~247
CMD 03:read slave parameter; 06:write slave parameter
08:complex command(refers to page 76:Supplement)

DATA(N-1) Data content:


DATA(N-2) function code parameter address , function code
parameter number , function code parameter value
……
and so on .
DATA0
CRC low-order (accumulate sum high-order)
Select check mode by the second part of FC.01
CRC high-order(accumulate sum low-order)
END 3.5-byte internal time

CMD and DATA


CMD:03H,read N-word (at most 5-word) RTU Slave responding frame
eg: The startup add F002 of the inverter, whose slave
ADR 01H
address is 01, can read two value continuously.
CMD 03H
RTU Host command frame Byte number 04H
ADR 01H Data high-order
00H
(Add. F002H)
CMD 03H
Data low-order
00H
Startup Add. high-order F0H (Add. F002H)
Startup Add. low-order 02H Data high-order
00H
(Add. F003H)
Data number high-order 00H
Data low-order
00H
Data number low-order 02H (Add. F003H)
CRC low-order 56H CRC low-order FAH
CRC high-order CBH CRC high-order 33H
CMD:06H,write a word eg: Write the 5000(1388H) in F00B Add of the inverter ,whose slave Add is 02H.
Host command frame Slave responding frame
ADR 02H ADR 02H
CMD 06H CMD 06H
Data Add. high-order F0H Data add. high-order F0H
Data Add. low-order 0BH Data add. low-order 0BH
Data high-order 13H Data high-order 13H
Data data low-order 88H Data low-order 88H
CRC low-order C6H CRC low-order C6H
CRC high-order 6DH CRC high-order 6DH

72
Chapter 7 SD100 Communication Protocol and Description of Communication

Check Mode ——CRC check mode:CRC(Cyclical Redundancy Check):


By using RTU frame format , the message contains error detect field that bases on CRC method . CRC field detects
the whole message data. It is two bytes and includes 16-byte binary value, it is calculated by transmission equipment and then
added to the message, the receive equipment calculates CRC over again after receiving the message and compares it to the
received CRC value, if the two value is not the same, it indicates that the transmission is wrong.
CRC saves 0xFFFF to CRC register at first, and then deals with the continuous 8-bit byte of the message and the current
value of the register by transferring one process. Only 8-bit data of every character is valid for CRC, the start bit、 the stop bit
and the odd-even check bit are all invalid. During the CRC process : every 8-bit character is single exclusive or (XOR) with
the CRC register data , the result moves to the lowest valid bit , the highest valid bit is filled with 0. LSB is distilled and
detected , if LSB is 1, the CRC register is single exclusive with preset value, if LSB is 0, nothing happens. The whole process
needs to repeat for 8 times. When the last bit finished, the next 8-bit byte character is single exclusive with the CRC register
current value. The ultima CRC register value is the value since all the byte of the message has been performed .

The process of CRC calculation is as follows:


1.One 16-bit register value is set to FFFF (hex), named CRC register.
2.The first 8-bit character of data is exclusive with the low 8 bits of the 16 bits CRC register, and the result is saved to
CRC register.
3.CRC register moves one bit toward right (LSB),MSB is fulled with zero, move LSB out and check it.
4.When LSB is 0:repeat the third step;
When LSB is 1:CRC register and preset value:A001H(1010 0000 0000 0001B)perform exclusive operation .
5.Repeat the third step and the fourth step until the 8th shift finished. At this time, one 8-bit data is finished.
6.Repeat the second and the fifth step until all data is finished.
7.The final CRC data is CRC value .
Note: When CRC added to the message, low byte prior to high byte.

CRC simple function is shown as following:


unsigned int crc_dhk_yalue(unsigned char*data_value,unsignde char length)
{
unsigned int crc_value=0xFFFF;
int i;
while(length- -)
{
crc_value^=*data_value++;
for(i=0;i<8;i++);
{
if(crc_value&0x0001)

{
crc_value=(crc_value>>1)^0xa001;
}
else
{
crc_value=crc_value>>1;
}
}
}
return(crc_value);
}

73
Chapter 7 SD100 Communication Protocol and Description of Communication

The definition of Communication parameter add.:


This part is the content of communication, it is used to control the running of inverter and inverter status and the
correlative parameter setting .
Read-write function code parameter:
Add.rule:
Use the function code group number and sequence number to express the rule:
high-order:F0~FD
low-order:00~FF
e.g.:F3.12, the Add is expressed as F30C;

Note:
Some parameters can only be read but cannot be modified ,some parameters cannot be modified when the inverter is
in running status; when modify it ,you should notice the setup range ,unit and correlative description of parameters .
In addition , since EEPROM is saved frequently , its life will be reduced, thus, some function code needn't to be saved
and you just need to modify the RAM value in the communication mode. To realize the function , you need to change the
high-order F of function code address into 0.
Correlative function code address is expressed as following :
high-order:00~0D
low-order:00~FF
e.g.:function code F3.12 is not saved to EEPROM , only to modify RAM, the Add. is expressed as 030C.

Monitor parameter Group FV:


Add. Coding Description
1000H FV.00 Output frequency
1001H FV.01 Setup frequency(read or write, write may change the setup value of communication setting)
1002H FV.02 Output current
1003H FV.03 Running rotation speed
l l l
l l l
l l l
100DH FV.13 PID setup (read or write, write may change the PID setup value of communication setting)
100EH FV.14 PID feedback(read or write, write may change the PID feedback value of communication setting)
l l l
l l l
1019H FV.25 Total running time

Control command input into the inverter:(only-write) Read the status of the inverter:(only-read)
CMD Add. Data Add. Data
2000H 0001:Forward rotation running 3000H 0001:Forward rotation running
0002:Inverse rotation running 0002:Inverse rotation running
0003:Forward rotation Jog 0003:Forward rotation Jog running
0004:Inverse rotation Jog 0004:Inverse rotation Jog running
0005:coast stop 0005:DC brake
0006:deceleration stop 0006:inverter fault
0007:fault reset 0007:stop

74
Chapter 7 SD100 Communication Protocol and Description of Communication

Fault description (SD100 current fault information):

Fault Add. information


8000H 0000H:no fault(- -)
0001H:Inverter unit protection(E.1)
0002H:Acceleration over current(E.OC1)
0003H:Deceleration over current(E.OC2)
0004H:Constant speed over current(E.OC3)
0005H:Acceleration over voltage(E.OU1)
0006H:Deceleration over voltage(E.OU2)
0007H:Constant speed over voltage(E.OU3)
0008H:Stop over voltage(E.OU4)
0009H:Running under voltage(E.LU)
000AH:Inverter overload(E.OL1)
000BH:Motor overload(E.OL2)
000CH:Phase loss output(E.LF)
000DH:Inverter overheat(E.OH)
000EH:External equipment fault(E.EF)
000FH:Communication fault(E.CE)
0010H:Output grounding(E.GF)
0011H:CPU interference(E.2)
0012H:Current detect fault(E.3)

Disposal for exceptional case :


The host is looking forward to a normal response when it sends every inquiry to slave, except the broadcast. For host
inquiry, it might have one of the following four cases :
1:When slave receives inquiry normally and there is no error, it will return a normal response .
2:When slave does not receive inquiry due to communication error, it will not return any response. The host will deal
with the inquiry as overtime at finally.
3:When slave receives inquiry but meets communication error( odd and even check or CRC ), it will not return any
response too. The host will deal with the inquiry as overtime at finally.
4:When slave receives inquiry and there is no communication error, but it can’t carry out( for example: To read a
nonexistent register), the slave will return to the exceptional case to response and impart the error characters of the
host. The response for the exceptional case has other two fields to distinguish from the normal response .

Command field:Slave answers it with the primary inquired CMD when it response s normal. Generally, The highest
symbol bit (MSB) of CMD is zero (means the value is lower than 80H ) . When the exceptional case responses, the slave
will set the MSB of CMD to 1, thus to make the CMD value higher than 80H and the normal response value. In this case ,
the host can identify exceptional case response and check the content of data field at the same time.

Data field:In the normal response , the data contains data, which is given for demand, or Statistic value. When
exceptional case responses , the slave will return a exceptional case code in the data field . It can show how the exceptional
case happens to the slave. The following figure is an example that exceptional case responds to the host inquiry.

75
Chapter 7 SD100 Communication Protocol and Description of Communication

Host inquiry Slave responding

ADR 02H ADR 02H


CMD 06H CMD 86H
Register Add. high-order F0H Execptional code 03H
Register Add. low-order 00H CRC low-order F2H
Register number high-order 00H CRC high-order 61H
Register number low-order 00H
CRC low-order BAH
CRC high-order F9H

Note:Since F0.00 parameter is only-read parameter , the modification of response parameter disabled .
SD100 adapts the exceptional code
Code Exceptional case description
01H lawless function code
02H lawless data address
03H lawless data value
reasons:
Over the limited value
Write the only-read parameter
Forbid parameter writing in running state
The slave is busy, i t is mainly occur when the data is saved to
EEPROM

6. Group FC communication parameter description


Factory
FC.00 Baud rate default value 3
0 1200bps
1 2400bps

Setup range 2 4800bps


3 9600bps
4 19200bps
5 38400bps
The parameter is used to set the transmission velocity of the data between host and inverter. Please pay attention to this, the
setup baud rate of both host and inverter must be the same, or else, the communication can not be carried out. The higher the
baud rate is, the faster the commnication speed is .
Factory
FC.01 Data format default value 0
0 No check:data format〈8,N,2〉 Note:2 stop bits
The first part of LED
Setup range

(byte check mode) 1 Even check:data check〈8,E,1〉 1 stop bit


2 Odd check:data format〈8,0,1〉 1 stop bit
The second part of LED 0 CRC16
(frame check mode) 1 Accumulate sum(16 bit)

76
Chapter 7 SD100 Communication Protocol and Description of Communication

The setup data format of both host and inverter must be the same, or else, the communication can not be carried out.
As for users whose programmable check mode is accumulate sum , the communication protocol of Sinovo company is
compatible with this mode, it is realized by setting the second part of FC.01 to 1.
In the mode , the forenamed check data CRC low-order/high-order will be replaced by accumulate sum high-order/low-order.

Factory
FC.02 Local Add. default value 1
Setup range 0~247,0 is broadcast address, others are slaver address

When local address is zero , it indicates that the local computer as the host sends synchronous command and frequency signal
to all guests with broadcast address. On condition that the baud rate is coincide with the data format, guests accept the
command and execute it .
When local address is zero , it can realize broadcast functional and the command is enabled to all slaves.
1 ~ 247: slave address
Local address is unique( except broadcast address ), this is the foundation that to realize the point to point communication
between host and inverter .

FC.03 Delayed-acknowledge Factory


default value 2ms
Setup range 0~20ms

Delayed-acknowledge: It means the mid-internal time between the time spent by inverter to receive data completely and the
time It uses to send data to host. If the time is less than the system process time, then the benchmark of delayed-acknowledge
is system process time; if the time is more than the system process time , after the system disposed the data, it still needs to
delay to send data to host until the delayed-acknowledge time is out.

Factory
FC.04 Communication overtime time default value 0.0s
Setup range 0.0s(disabled),0.1~60.0s

When the function code is set to 0.0s, the communication overtime time parameter disabled.
When the function code is active , if the communication internal time between this communication and the next exceeds the communication
overtime time, the system will deal with it in term of FC.05 setup mode about communication overtime action selection.
Generally speaking, the parameter is disabled. In continuous communication system, you can monitor the case by setting
the second parameter.

FC.05 Communication overtime action selection Factory


default value 0
0 stop
Setup range 1 keep current setup frequency
2 stop and come forth communication fault(E.CE)

7. Communication function parameter description


Factory
F0.02 Command source selection default value 0
Setup range 0~4 3/4communication command channel enabled

Factory
F0.03 Main Frequency source X selection default value 0
Setup range 0~8 8:communication reference
Factory
F0.04 Auxiliary Frquency sourcy Y selection default value 2
Setup range 0~8 8:communication reference

77
Chapter 7 SD100 Communication Protocol and Description of Communication

8. Common communication command examples


Note: The following slave computer response is used as example to help user understanding protocol, but it might have
some differences with the actual response.

A. CRC check mode


Read :
Startup Add. Startup Add. Register Register CRC CRC
ADR CMD number number
high-order low-order high-order low-order low-order high-order
Inquire No.1 slave
computer output 01 03 10 00 00 01 80 CA
frequency:
Inquire No.1 slave
01 03 30 00 00 01 8B 0A
computer state:

Write :
Register Register Register Register CRC CRC
ADR CMD Add. Add. data data
high-order low-order high-order low-order low-order high-order
Send forward
rotation command to 01 06 20 00 00 01 43 CA
No.1 slave computer:

Send deceleration
stop to No.1 slave 01 06 20 00 00 06 02 08
computer:

All slaves’ computer


communication
references are 00 06 10 01 0B B8 DA 59
modified to 30.00Hz

Broadcast Forward
00 06 20 00 00 01 42 1B
running command

Broadcast
deceleration 00 06 20 00 00 06 03 D9
stop command

Broadcast fault 00 06 20 00 00 07 C2 19
reset command

B. Acceleration sum check mode


You can realize the accumulate sum check mode by setting the second part of FC.01 to 1.
In the mode , the forenamed check data CRC low-order/high-order will be replaced by the accumulate sum
high-order/low-order.

Read :
Startup Add. Startup Add. Register Register Accumulate Accumulate
ADR CMD number number sum sum
high-order low-order high-order low-order high-order low-order
Inquire No.1 slave
computer output 01 03 10 00 00 01 00 15
frequency:
Inquire No.1 slave 01 03 30 00 00 01 00 35
computer state:

78
Chapter 7 SD100 Communication Protocol and Description of Communication

Write :
Register Register Register Register CRC CRC
ADR CMD Add. Add. data data
high-order low-order high-order low-order low-order high-order
Send forward
rotation command to 01 06 20 00 00 01 00 28
No.1 slave computer:

Send deceleration
stop to No.1 slave 01 06 20 00 00 06 00 2D
computer:

All slaves’ computer


communication
00 06 10 01 0B B8 00 DA
references are
modified to 30.00Hz

Broadcast Forward
00 06 20 00 00 01 00 27
running command

Broadcast
deceleration 00 06 20 00 00 06 00 2C
stop command

Broadcast fault
00 06 20 00 00 07 00 2D
reset command

9. Supplement
As for the actual applied demand of inverter, SD100 provides a special communication protocol command, it is a
complex command mode that makes Read compatible with Write at the same time. The protocol check mode of complex
command has two choices as other command.

RTU frame format:

Frame START 3.5-byte internal time


Slave ADR add:1~247
CMD 08:complex CMD
Host send: Slave respond: For details about running command set out by
CMD data high-order status data high-order
the host and setup running frequency, the status
Host send: Slave respond:
CMD data low-order status data low-order of inverter responds by the slave and current
Host send: Slave respond: running frequency, please refer to the
setup frequency high-order setup frequency high-order explanation of page 72.
Host send: Slave respond:
setup frequency low-order setup frequency low-order
CRC low-order (accumulate sum high-order) Select check mode by the
CRC high-order(accumulate sum low-order) second part of FC.01

END 3.5-byte internal time

79
Chapter 7 SD100 Communication Protocol and Description of Communication

The followings take the accumulate sum check mode as an example to explain complex command
protocol.
Note: The following slave computer response is used as example to help user understanding protocol, but it might have
some differences with the actual response.
Host send:
Command Command Setup Setup Accumulate Accumulate
ADR CMD data data frequency frequency sum sum
high-order low-order high-order low-order high-order low-order

01 08 00 01 0B B8 00 CD

Send FWD running command to No.1 slave and set running frequency to 30.00Hz

Slave respond:
Status Status Running Running Accumulate Accumulate
ADR CMD data data frequency frequency sum sum
high-order low-order high-order low-order high-order low-order

01 08 00 01 09 C4 00 D7

No.1 slave responds to the host: the inverter is FWD running at present and the actual running
frequency is 25.00Hz
Host send:
Command Command Setup Setup Accumulate Accumulate
ADR CMD data data frequency frequency sum sum
high-order low-order high-order low-order high-order low-order

01 08 00 06 00 00 00 0F

Send deceleration stop command to No.1 slave and set running frequency to 0.00Hz

Slave respond:
Status Status Running Running Accumulate Accumulate
ADR CMD data data frequency frequency sum sum
high-order low-order high-order low-order high-order low-order

01 08 00 01 0B B8 00 CD

No.1 slave responds to the host: the inverter is FWD running at present and the actual running
frequency is 30.00Hz

80
Chapter 7 SD100 Communication Protocol and Description of Communication

7.2 Description of Communication Card

Communication card of SHENZHEN SINOVO ELECTRIC THECHNOLOGIES CO.,LTD is specially designed for the SD100
series inverter to provide long-distance serial port communication function .

NOTE: For the SD300 , SD80 series andSD100-4T- 11G/15P above power level inverters of our company, the
communication correlative hardware interface is provided by special communication CPU, please give a clear indication
while ordering when you need it.

Instruction for using


1. Model: RS-485
2. Terminal Connection
The physical structure and connecting mode are shown as the following figure. Installation should be conducted when
the inverter is completely power-off. Well aligned the communication card with the interface of the control board of the
inverter. In order to prevent the communication signal from interfering by external interferences, it is recommended that the
communication connection use the twisted-pair cables and avoid using parallel cables as much as possible .

If it can't communicate normally by adopting the wiring mentioned above, you can try to adopt the following methods :

1 Let the PLC (or host computer) power supply separately or insulate the power;

2 Use the magnetic ring on the communication cable , you can properly decrease the carrier wave frequency of inverter if the
condition allowed.

Communication card

RS485
interface

SD100 main
control board

81
Chapter 8 Troubleshooting and Countermeasures

Chapter 8 Troubleshooting and Countermeasures


8.1 Fault Alarm and Countermeasures
Inverters of our company has 22 pieces of warning information and protection function. In case of abnormal fault, the
protection function will be invoked , the inverter will stop output , and the faulty relay contact of the inverter will start , the
fault code will be displayed on the display panel of the inverter . Before consulting the service department , the user can perform
self-check according to the prompts of this chapter , analyze the reason and find out the solution . If the fault is caused by
the reasons described in the dotted frame , please consult the agent or our company directly .

Inverter Unit Protection

E.1

Check if there is contactor or Yes


other switch parts between inverter Remove
and motor the parts

No

Check if the output loop of the Yes Perform


inverter is grounding or short circuited troubleshooting

No

Whether the cable connecting Yes


Install a reactor
the motor with the inverter is too or output filter
long
No
Yes Check if the air duct is
Whether the module is over heat blocked and if the fan is in
normal status , and resolve
the existing problems .
No

Check if the cable connections Yes Insert all the connecting


inside the inverter are loosen cables properly
Ask for technical support
No

If it works normally after replacing Yes The main control


the main control board board is faulty

No
If it works normally after replacing Yes
The drive board
the drive board is faulty
No
Yes
If it works normally after replacing The inverter
the inverter module module is damaged

82
Chapter 8 Troubleshooting and Countermeasures

Acceleration over current

E. OC 1

Check if the output loop of the Yes


inverter is grounding or short circuited Perform troubleshooting

No
Yes
Whether the acceleration time is too short Prolong the acceleration time

No

Whether the manual boost torque No Adjust the manual boost


or V/F curve is proper torque or V/F curve

Yes
Yes
Whether the voltage is too low Adjust the voltage
to normal range
No

Yes Select start upon rotational


Whether the rotating motor is started velocity follow-up or start
upon motor shutdown
No
Whether the load is added suddenly Yes Remove the
during the acceleration added load

No
The inverter model
is rather small

Deceleration over current

E. OC 2

Check if the output loop of the Yes


inverter is grounding or short circuited Perform troubleshooting

No
Yes
Whether the decelerated time is too short Prolong the deceleration time

No
Yes Adjust the voltage
Whether the voltage is too low
to normal range

No

Whether the load is added suddenly Yes Remove the


during the acceleration added load

No

Whether the brake unit and brake Yes Install the brake unit
resistor are installed and brake resistor

Yes

Ask for technical support

83
Chapter 8 Troubleshooting and Countermeasures

Constant speed over current

E. O C 3

Check if the output loop of the Yes Perform troubleshooting ,


inverter is short circuited or has and install output reactor
leakage current if the cable is too long

No

Whether the load is added suddenly Yes


Remove the added load
during the running
No

Yes
Whether the inverter load can be lightened Lighten the load

No
The inverter model
is rather small

Acceleration over voltage

E. OU1

Yes Adjust the voltage


If the input voltage is too high
to normal range

No
If there are external forces Yes
driving the motor to run during the Remove the external forces
acceleration process .

No

Ask for technical support

Deceleration over voltage

E. OU2

Yes Adjust the voltage


Whether the input voltage is too high
to normal range
No

Whether there are external forces Yes Remove the external


driving the motor to run during the forces or install brake
deceleration process . unit and resistor
No
Yes Prolong the deceleration
Whether the deceleration time is too short time or install brake unit
and resistor
No

Whether the brake unit and resistor No Install the brake


are installed unit and resistor

Ask for technical support

84
Chapter 8 Troubleshooting and Countermeasures

Constant over voltage

E. O U3

Yes Adjust the voltage


Whether the input voltage is too high
to normal range
No

Whether there are external forces Yes


Remove the external
driving the motor to run during the forces or install brake
running process unit and resistor

No

Ask for technical support

Stop over voltage

E. O U 4

Yes Adjust the voltage


Whether the input voltage is too high to normal range
No

Ask for technical support

Running under voltage

E.LU

Yes
Whether there is transient power failure Inverter reset

No

Detect if the voltage at the input No Adjust electrical source or remove


end of the inverter is within the range external power supply loop fault
Maintainer reference specified by the specifications
No

Measure if the DC bus voltage is normal

No

Check Whether the rectifier bridge No


Replace the broken rectifier
Yes and buffer resistor are normal bridge or buffer resistor

Yes
No
Check Whether the main control Replace the
board is normal control board

Yes
No Replace the
Check Whether the drive board is normal
drive board

85
Chapter 8 Troubleshooting and Countermeasures

Motor overload
Inverter overload
E. O L2
E. OL1

Whether the motor overload protection No


Set it properly
parameter F8.03 is set properly

Yes

Whether the load is too heavy or Yes Reduce the load and
check the motor and
the motor does not rotate the machine
No
Yes Adjust the input
Whether the voltage of power net is too low voltage within the
allowable range

No
Yes Prolong the
Whether the deceleration time is too short
deceleration time

No

Whether the manual boost torque or No Adjust the manual boost


V/F curve is proper torque or V/F curve

Yes

The inverter
model is small

Phase loss at the output side

E.LF

Check Whether the cable connecting the No


inverter to the motor is normal Perform troubleshooting

Yes

Check Whether the three-phase output Yes Check if the three-phase


of the running inverter without motor winding of the motor is
is balanced normal and remove the fault
Ask for technical support
No

Check Whether the main control No Replace the main


board is normal control board

Yes
No Replace the
Check Whether the drive board is normal
drive board

Yes
No Replace the
Check Whether the module is normal
module

86
Chapter 8 Troubleshooting and Countermeasures

Inverter overheat
E. O H

Yes Reduce the ambient


Whether the ambient temperature is too high
temperature
No
Yes
Whether the air duct is blocked Clean the air duct
No
Yes
Whether the fan is broken Replace the fan
Ask for technical support
No

Check Whether the main control No Replace the main


board is normal control board
Yes
No Replace the
Check Whether the drive board is normal
drive board
Yes
Whether the thermistor of the module Yes Replace the
is broken thermistor
No
Yes Replace the
Whether the inverter module is broken
inverter module

External equipment fault

E.EF

Whether it inputs external fault signal Yes Check and remove


via the multifunctional terminal X the external fault

Communications fault

E.CE

No Check the host computer


Whether the host computer is working cable connection
Yes
Whether the RS485 communication No Check the communication
cable connection is normal cable
Yes
No
Whether the baud rate is setting correctly Set the baud
rate correctly
Yes
Whether the communication parameter No
Modify the communication
FC.03 and FC.04 are setting correctly parameter
Yes
Whether the carrier wave frequency Yes Reduce the carrier
F2.12 setup is too high wave frequency
No
Whether it is satisfy with the control Yes Modify the communication
need when communication parameter parameter
FC.05 isn’t set as 2
No

Ask for technical support

87
Chapter 8 Troubleshooting and Countermeasures

Output grounding

E.GF

Yes Replace cable


Check Whether the output is short circuited
Ask for technical support or motor

No

Replace the drive board

CPU interference

E.2
Ask for technical support

Whether it works normally after Yes The main control


replacing the main control board board is faulty

Current detect fault

E.3
Ask for technical support

Whether it works normally after Yes


The main control
replacing the main control board board is faulty

No

Check Whether the sensor and connect No Replace the


is normal sensor or the
connections

Yes
No Replace the
Check Whether the drive board is normal
drive board

EEPROM read-write fault

E.4
Ask for technical support

Whether it works normally after Yes The main control


replacing the main control board board is faulty

88
Chapter 8 Troubleshooting and Countermeasures

Phase loss at the input side


E.5

Check and resolve the problems in the


Check Whether three-phase input No external lines to ensure that the three
Ask for technical support power supply is normal -phase power input to the inverter is
normal

Yes
Check Whether the main control No Replace the
main control
board is normal board

Yes
No Replace the
Check Whether the drive board is normal
drive board

8.2 Common fault and resolution

During the using process of inverter, you may encounter 3)Check the rectifier whether it is punctured , if it is ,please
the following faults. Please conduct simple fault analysis by ask for technical support .
referring to the methods below: 4、The motor does not rotate upon inverter running :
1、No display upon power-on: 1)Whether it has balanceable three-phase output among U
1)Use multimeter to measure whether the input power is and V and W, if it has, there is something wrong with the motor
consistent with the rated voltage circuit or it is damaged or the motor blocked for mechanical
of inverter. If the power is faulty, please perform it . reasons. Please remove it.
2)Check whether the rectifier is good, if it is damaged 2)There is output but it is not balanceable , the reason
, please ask for technical support. might be the drive or module of inverter is damaged .
3)Check whether the start resister is good, if it is good Please ask for technical supply .
, the fault might be in switching power supply ,please 3)If there is no output voltage , the reason might be the
ask for technical support. drive board or output module is damaged. Please ask for
2、The operation panel displays the words “CE”upon technical supply .
power-on: 5、The inverter displays normally upon power-on , but
If the communication between keyboard and main control board the circuit breaker starts aside upon running :
has something wrong , you need to check whether the keyboard or 1)Check whether there is
main control board or it's connection is normal . double phase short circuit or grounding between the output
3、The circuit breaker starts aside after power-on: modules. If there is, please ask for technical supply.
1)Check whether the earth terminal E of inverter is grounding 2)Check whether there is grounding or short circuit
reliably and perform the problem . things between the motor cables, remove it if there is.
3)If the trip happens every once in a while and the distance
2)Check whether there is grounding or short circuited
between motor and inverter is too long, then you may consider
things between the input power, please remove it if there is.
to install an AC output reactor.

89
Warranty Agreement
1. The warranty period of the product is 18 months (refer to the bar code on the equipment body). During the
warranty period , if the product fails or it is damaged under the condition of normal use by following the
instruction, our company will be responsible for free maintenance .
2. Within the warranty period , maintenance will be charged for the damages caused by the following reasons :
a. The damage caused by improper use or repair/modification without prior permission ;
b. The damage caused by fire , flood , abnormal voltage , other natural disasters and second disaster ;
c. The hardware damage caused by artificial falling or transportation after purchase.
d. The damage caused by the improper operation ;
e. The damage or failure caused by the trouble out of the equipment (e.g. : External device)
3. If there is any failure or damage to the product , please fill in the information of the Product Warranty Card in
details correctly.
4. The maintenance fee is charged according to the newly adjusted Maintenance Price List of our company .
5. In general , the warranty card will not be re-issued. Please keep the card and present it to the maintenance
personnel when asking for maintenance .
6. If there is any problem during the service , please contact the agent of our company or our company directly .
7. The interpretation of this agreement shall reside with SHENZHEN SINOVO ELECTRIC TECHNOLOGIES CO.,LTD.

SHENZHEN SINOVO ELECTRIC TECHNOLOGY CO.,LTD.


Service Department
Add.:3rd Floor,No.B Building ,Huafeng Industrial Zone , Gushu Hangcheng Street , Xixiang Town, Bao'an District,
Shenzhen City,China
Tel:0755-29784870 Sell Service Cen4ter:0755-29784875
Fax:0755-29784873 P.C.:518000

SHENZHEN SINOVO ELECTRIC TECHNOLO GY CO.,LTD.

90
Product Warranty Card

Add. of corporation:

Customer Name of corporation: Contact person:


information

P.C.: Tel.:

Product model:

Product Body bar code:


information

Name of agent:

(maintenance time and content):

Failure
information

Maintenance personnel:

91