INVERTER GENERAL TECHNICAL PARAMETERS
A TOTAL INVERTER QUANTITY TO BE CONFIRMED
B INVERTER DATA
PVS980
58
1 Product Model
2091 kVA
L
2 Inverter Type (Monolithic / Modular) Modular
3 Switching Element and Technology PWM Controlled IGBT based Three Level Inverter
4 Number of IGBT Module (Stack) in Inverter 2 X R35i Module
5 MPPT Tracker - Master slave/ Multi MPPT MPPT single
6 No. of MPPT Trackers/Controller 1
7 Degree of Protection IP 56/66 *
C INPUT VARIABLES
1 Max. allowed PV field power 3346 kWp
2 Max. DC Power/Nominal AC Power ratio 160%
3 DC Voltage range MPP(Udc,mpp) at 35°C 978 - 1500 V
4 DC Voltage range MPP(Udc,mpp) at 50°C 978 - 1100 V
5 Max. Permissible DC voltage(Umax (DC)) 1500 Vdc
6 Max. Permissible DC current (Ipc max) 2400 A
7 Number of DC inputs 12H382 - 12 DC inputs
8 DC Input (String/Zone) Current Monitoring G417 - String Monitoring
9 DC Side grounding Negative grounding
10 DC Side Fuses 400 A
14 DC Surge Arresters Type 1+2, F300
D OUTPUT VARIABLES
1 Nominal AC voltage(UN (AC)) 690 V ± 10%
2 Type of Phase Connection 3 Phase, 3 Wire , IT type
3 Nominal AC current (IN (AC)) 1750 A
4 Maximum AC current (IMAX (AC)) 1925 A
5 Output Frequency 50Hz (± 10%)
6 Power factor range (cos phi) .8 lag to .8 lead
7 Distribution Network type 3 Phase, IT (floating) networks
8 Total Harmonic Distortion, Current < 3% at nominal load (under ideal conditions)
9 Nominal Rating 2091 kVA at 50°C
10 Maximum Rating 2300 kVA at 35°C
11 Disconnection from Grid +F296 , Controllable and Motorised MCCB with LS-I protection
12 AC Surge Arrester Type 1+2, F263
13 Connection Method Bottom Connected Cables (Standard)
E POWER CONSUMPTION & EFFICIENCY
1 Maximum efficiency(Without Aux. power consumption) 98.8%
2 Euro efficiency(Without Aux. power consumption) 98.6%
3 CEC efficiency (With Aux Power Included) 98.5%
4 Own Power consumption (Operation) < 2500 W
5 Own Power consumption (Standby/Night Time) 235 W
6 Auxiliary Power Supply +G415, Internal Auxiliary Power(4kVA)

* Excluding under-pressure testing, IP56 with under-pressure, Inverter has internal mechanism that prevent under-pressure inside the cabinet.

Rev-No. Description and Date of Revision Prepared by Vinya Vibhuti Doc No.
2 Rev01 Date: 19-02-2019 Approved by Prasanna Kumar L 3AYN1973XXX-HAX
Customer Title Dept. EPSO-Solar
L&T INVERTER DATASHEET Sheet A4
Project Lang. English
To be confirmed INABB-SOLAR Page 1 of 2
INVERTER GENERAL TECHNICAL PARAMETERS
F CABINET DATA
1 Inverter Dimension (W/H/D) in mm 3180 / 2443 / 1522
2 Total Weight [kg] 3850 kg approx.

G ENVIRONMENT LIMIT
1 Ambient Temperature Range (Nominal Rating) -20 ...+50 DegC
2 Maximum Ambient Temperature (Operational) +60 DegC
3 Relative Humidity 5 ... 100%, Non Condensing
4 Nominal Altitude 1000 meter above Sea Level
5 Maximum Altitude (with power derating) 4000 meter above Sea Level
6 Maximum Noise Level ** < 88 dB(A) at one meter
** At partial power, typically less than 75 dbA
H USER INTERFACE AND COMMUNICATIONS
1 Local User Interface ABB Control Panel ( LCD Display with Keypad)
2 Fieldbus connectivity +K475, Ethernet Adapter (Modbus TCp/IP, 2 - port)
3 Emergency stop switch Yes
4 Display of Alarm and Fault Display is available
5 Display of AC and DC Parameter Display is available
5 Display of Energy Generation Display is available

I CABLE TERMINATION
1 Cable Entry/Exit Bottom Entry with undrilled gland plates, Al 5mm
2 AC Termination Busbar Details 160 X 10, Tinned Al Busbar with M12 holes for termination
3 DC Termination Busbar Details 30 X 10, Tinned Cu Busbar with M8 holes for termination
1Cx6Rx540sqmm(cable size not to exceed 67 mm in dia.) Al cable/XLPE per
Recommended AC Cable Termination phase or 1Cx9Rx300sqmm (cable size not to exceed 35 mm in dia.) Al
4 cable/XLPE per phase
5 Recommended DC Cable Termination Calculated based on DC inputs
6 Recommended Earthing Cable Termination 300 sq. mm

J Grid Monitoring
1 Grid Reconnection Delay Programmable up to 300 s, Default Value ( 60 s)
2 Remote Start and Stop Yes, Provision available
3 Power Factor Control Yes, Provision available
4 DC Current Injection As per CEA

K GRID SUPPORT AND GRID FUNCTION

Grid Monitoring, Anti-islanding, Under/Over voltage and frequency protection, LVRT/HVRT Support, Reactive Power Compensation, Night time Reactive
Power Support, Insulation Monitoring, Over temperature protection, DC Reverse Polarity, Over Current Protection.

L Applicable Standards
IEC Conformity: IEC61000-6-2, EN55011, IEC61727, IEC62116, IEC61683, IEC60068-2, BS-EN 60529, IEC62910, IEC 62109
Other: BDEW,

Other Additional Option Codes : P928

Rev-No. Revision Description & Date Prepared by Vinya Vibhuti Doc No.
2 Rev01 Date: 19-02-2019 Approved by Prasanna Kumar L 3AYN1973XXX-HAX
Customer Title Dept. EPPE
L&T INVERTER DATASHEET Sheet A4
Project Lang. English
To be confirmed INABB-SOLAR Page 2 of 2