* Excluding under-pressure testing, IP56 with under-pressure, Inverter has internal mechanism that prevent under-pressure inside the cabinet.
Rev-No. Description and Date of Revision Prepared by Vinya Vibhuti Doc No.
2 Rev01 Date: 19-02-2019 Approved by Prasanna Kumar L 3AYN1973XXX-HAX
Customer Title Dept. EPSO-Solar
L&T INVERTER DATASHEET Sheet A4
Project Lang. English
To be confirmed INABB-SOLAR Page 1 of 2
INVERTER GENERAL TECHNICAL PARAMETERS
F CABINET DATA
1 Inverter Dimension (W/H/D) in mm 3180 / 2443 / 1522
2 Total Weight [kg] 3850 kg approx.
G ENVIRONMENT LIMIT
1 Ambient Temperature Range (Nominal Rating) -20 ...+50 DegC
2 Maximum Ambient Temperature (Operational) +60 DegC
3 Relative Humidity 5 ... 100%, Non Condensing
4 Nominal Altitude 1000 meter above Sea Level
5 Maximum Altitude (with power derating) 4000 meter above Sea Level
6 Maximum Noise Level ** < 88 dB(A) at one meter
** At partial power, typically less than 75 dbA
H USER INTERFACE AND COMMUNICATIONS
1 Local User Interface ABB Control Panel ( LCD Display with Keypad)
2 Fieldbus connectivity +K475, Ethernet Adapter (Modbus TCp/IP, 2 - port)
3 Emergency stop switch Yes
4 Display of Alarm and Fault Display is available
5 Display of AC and DC Parameter Display is available
5 Display of Energy Generation Display is available
I CABLE TERMINATION
1 Cable Entry/Exit Bottom Entry with undrilled gland plates, Al 5mm
2 AC Termination Busbar Details 160 X 10, Tinned Al Busbar with M12 holes for termination
3 DC Termination Busbar Details 30 X 10, Tinned Cu Busbar with M8 holes for termination
1Cx6Rx540sqmm(cable size not to exceed 67 mm in dia.) Al cable/XLPE per
Recommended AC Cable Termination phase or 1Cx9Rx300sqmm (cable size not to exceed 35 mm in dia.) Al
4 cable/XLPE per phase
5 Recommended DC Cable Termination Calculated based on DC inputs
6 Recommended Earthing Cable Termination 300 sq. mm
J Grid Monitoring
1 Grid Reconnection Delay Programmable up to 300 s, Default Value ( 60 s)
2 Remote Start and Stop Yes, Provision available
3 Power Factor Control Yes, Provision available
4 DC Current Injection As per CEA
Grid Monitoring, Anti-islanding, Under/Over voltage and frequency protection, LVRT/HVRT Support, Reactive Power Compensation, Night time Reactive
Power Support, Insulation Monitoring, Over temperature protection, DC Reverse Polarity, Over Current Protection.
L Applicable Standards
IEC Conformity: IEC61000-6-2, EN55011, IEC61727, IEC62116, IEC61683, IEC60068-2, BS-EN 60529, IEC62910, IEC 62109
Other: BDEW,
Rev-No. Revision Description & Date Prepared by Vinya Vibhuti Doc No.
2 Rev01 Date: 19-02-2019 Approved by Prasanna Kumar L 3AYN1973XXX-HAX
Customer Title Dept. EPPE
L&T INVERTER DATASHEET Sheet A4
Project Lang. English
To be confirmed INABB-SOLAR Page 2 of 2