Professional Documents
Culture Documents
G ENVIRONMENT LIMIT
1 Ambient Temperature Range (Nominal Rating) -20 ...+50 DegC
2 Maximum Ambient Temperature (Operational) +60 DegC
3 Relative Humidity 4 ... 100%, Non Condensing
4 Nominal Altitude 1000 meter above Sea Level
5 Maximum Altitude (with power derating) 4000 meter above Sea Level
6 Maximum Noise Level *** < 84 dB(A) at one meter
** *At partial power, typically less than 75 dbA
H USER INTERFACE AND COMMUNICATIONS
1 Local User Interface ABB Control Panel ( LCD Display with Keypad)
2 Fieldbus connectivity +K475, Ethernet Adapter (Modbus TCp/IP, Profinet; 2 - port)
3 Emergency stop switch Yes
4 Display of Alarm and Fault Display is available
5 Display of AC and DC Parameter Display is available
5 Display of Energy Generation Display is available
I TERMINATION DETAILS
1 Cable Entry/Exit Bottom Entry
2 Gland Plate Undrilled
3 AC Termination Busbar Details 160mm X20mm , Cu ; hole size : 14.5 mm(dia.)
4 DC Termination Busbar Details 40mm X 5mm, Tinned Aluminium; hole size : 13 mm(dia.) for 30 DC input
5 Recommended AC Cable Termination Bus duct
6 Recommended DC Cable Termination Calculated based on DC inputs
Ground Fault Monitoring, Grid Monitoring, Anti-Islanding, LVRT, DC Reverse Polarity, Reactive Power Compensation, Over voltage Protection, Over
Current Protection, Insulation Monitoring, Over temperature Protection
Rev-No. Revision Description & Date Prepared by Vinya Vibhuti Doc No.
0 Friday, May 10, 2019 Approved by Jayarama Shetty 3AYN197XXXX-HAX
Customer Title Dept. EPPE
L&T INVERTER DATASHEET Sheet A4
Project Lang. English
Raasi Green Project ABB INABB-SOLAR Page 2 of 2