ETA ENGlNEERlNG PRIVATE LIMITED

503-504, Prakash Deep Building, 7, Tolstoy Marg, New Delhi - 11OOOi


Ph. : 011-26451115/6/7/8,43743800, 41520840/43
Fax : 011-43743866,41520844
Email : etametro@vsnl.net

Ref: ETAllCMU9MWlBClSClKK/131
Date: August 29, 201 1

-
DGM BUSINESS DEVELOPMENT (POWER)
MIS CESC Limited
CESC House
Chowringhee Square
Kolkata - 700 0022
West Bengal

KIND ATTN: MR ADRlT PALCHOUDHURY

SUB: ICML 9MW SOLAR POWER PROJECT AT PRATAPGARH, DlST KUTCH,


GUJARAT - SUBMISSION OF DRAWING AND DOCUMENT FOR BASIC
DESIGN OF AIR CONDITIONING SYSTEM REGARDING SYSTEM
DESCRIPTION - BASIC DESIGN.

Dear Sir,

This is in reference to the subject project, we are pleased to attach herewith the
following Drawing and Documents your kind information.

SI. NO. Description of the Document Rev No.


1 BASIC DESIGN OF AIR CONDITIONING SYSTEMS 00

We hope the above is in line with your requirements and would request you to kindly
let us have your approval to enable us to proceed further.

Thanking you and assuring you of our best services at all times.
Yours faithfully
For ETA ENGINEERING PVT LTD

SAURABH CHAUHAN
GENERAL MANAGER

Encl: as above

Regd. Office : 5, Mocres Road, Chennai - 600 006 Tamil Nadu, India
Branches (Tel.) - Bangalore : 41802300, Chennai : 28297626, Hyderabad : 27763529/30, Mumbai : 67742700, Pune : 26051310, Kolkata : 24864329
lor-
T ~ u ~ T : . I c ~CBa . 3 1 M i m i n x

Li,"s*ed
SUBMISSION

PROJECT :9MWp GRID INTERACTIVE SOLAR PV


POWER PROJECT
CUSTOMER : INTEGRATED COAL MINING LIMITED -
GUJARAT
CONTRACTOR : ETA ENGINEERING PVT LTD
Submission Phase:

DRAWINGS 1 DOCUMENT

VENDOR & TECHNICAL SUBMITTAL

CONSTRUCTION DOCUMENTS

REPORTS

RECORDS

Submission Number: I First Second Third Fourth


Submission Contents:
S.no Description of the Document System Description Rev No
1. BASIC DESIGN OF AIR Basic Design 00
CONDITIONING SYSTEM
For Information For Approval As Built
ETA:
Prepared By Checked By Reviewed By Approved By
Nisheeth Ankita Kapil Kumar X s a y q b h Chauhan

ICML:

Details Name Designation Sign

Approved By

DOCUMENT TRANSMITTAL. REF. DOC Date


ETA-SOLAR-TRANS-66 29-Aug-2011
---
-----
---
-
-
-
- -
-
- --
-
- - -
- - -
- -
SYSTEM DESCRIPTION
(AC SYSTEM)

DESCRIPTION OF AIR CONDITIONING SYSTEM


OF POWER CONTRO UNIT(PCU) ROOM

AIR-CONDITIONING SYSTEM
The AC system for PCU(Power Control Unit) Room is using is called DX system. It
consist of Indoor HI-WALL split units & OUTDOOR split units.The indoor HI-WALL split
units is located inside the PCU room & OUTDOOR split units is located outside of PCU
room & interconnect with Refrigerant pipes.The indoor split units having filters & coil &
outdoor units having compressor, condenser & fan.The refrigerant copper pipes is
using for cool the air & its supply in area.

One PCU room having two nos. of inverters with Heat exchanger with liquid cooled
components. The heat exchanger is installed outside the PCU room.The heat
exchanger is obsorbing the heat emit. from inverters by liquid cooled components. The
heat output of each inverters (without liquid cooled components) is upto 7000 w at
maximum power. For this project the inverters is with liquid cooled components so the
liquid cooled components is absorbing some heat & extra heat is emit. In the room. The
each heat exchanger is absorbing the 4.6 KW heat approximate & balance 2.4 KW heat
emit. In the room. So the heat considered for AC system heat load is 2.4 KW for each
---
--
---
-
-
- -- -
-
- --
- -
--
- -
-
- - - -
- -
- -
-
SYSTEM DESCRIPTION
lAC SYSTEM)

DESIGN PARAMETERS CONSIDERED

For PCU room the design parameters that related to general operation of the system
are following:-
Outdoor condition:-
55 deg C (DB)
3 0 d q C<WB)

Inside condition:-
35 deg C (DB)
25 deg C (WB)

Area of PCU room : 242.42 sq. Ft.


Ht. Of PCU room : 10 ft.
Occupancy : 2 Nos.
Lighting : 3.5 W/ sq. ft.
Heat output form each inverters : 2.4 KW

The above mentioned data is considered for Heat load of PCU (Power Control Unit)
room.