PROJECT DESCRIPTION

THIS ROOF MOUNTED PHOTOVOLTAIC (PV) SYSTEM IS TO BE INSTALLED AT THE SINGLE-FAMILY DWELLING IN PHOENIX, ARIZONA.
THE ENERGY PRODUCED BY THE PV SYSTEM SHALL BE INTERCONNECTED WITH THE UTILITY GRID THROUGH THE EXISTING ON-SITE ELECTRICAL EQUIPMENT VIA
A BACK-FED BREAKER IN THE MAIN SERVICE PANEL. THIS PROJECT DOES NOT INCLUDE STORAGE BATTERIES.

SHEET INDEX SCOPE OF WORK CONSTRUCTION NOTES


T1.0 COVER (20) PV AC MODULES (TOTAL: 351 SQ. FT.) 1.) CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS PRIOR TO
A1.0 SITE PLAN (28) ATTACHMENT POINTS @ 72" O.C. MAX. INITIATING CONSTRUCTION.
2.) CONTRACTOR SHALL REVIEW ALL MANUFACTURER INSTALLATION
A1.1 ROOF #1: PV LAYOUT (2) AC DISCONNECTS, 240 VAC, NEMA 3R DOCUMENTS PRIOR TO INITIATING CONSTRUCTION.
A2.0 MOUNTING & RACKING METHOD (1) AC COMBINER BOX, 240 VAC, NEMA 3R 3.) ALL EQUIPMENT SHALL BE LISTED BY U.L. (OR EQUAL) AND LISTED FOR
E1.0 ELECTRICAL DIAGRAM (1) PV METER, 240 VAC, NEMA 3R ITS SPECIFIC APPLICATION.
4.) ALL EQUIPMENT SHALL BE RATED FOR THE ENVIRONMENT IN WHICH IT AC Modules Project:
E1.1 ELECTRICAL CALCULATIONS (1) PV MONITOR, 240 VAC, NEMA 1 IS INSTALLED.
E2.0 SAFETY PLACARDS 5.) ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE
PHOENIX, AZ 85027
D1.0 PV AC MODULE DATA SHEET MANUFACTURER'S INSTALLATION INSTRUCTIONS.
6.) ACCESS TO ELECTRICAL COMPONENTS OVER 150 VOLTS TO GROUND
D2.0 RACKING DATA SHEET SHALL BE RESTRICTED TO QUALIFIED PERSONNEL. Project Details:
D3.0 ATTACHMENT DATA SHEET SITE SPECIFICATIONS 7.) ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600 VOLTS AND 6.90 kWstc, 6.40 kW AC
90°C WET ENVIRONMENT, UNLESS OTHERWISE NOTED. AHJ: PHOENIX, CITY OF
D4.0 GROUNDING DATA SHEET OCCUPANCY CATEGORY: II 8.) WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS ARE
D5.0 MAIN PANEL DATA SHEET DESIGN WIND SPEED: 110 MPH NOT SPECIFIED, CONTRACTOR SHALL SIZE THEM ACCORDING TO Engineering Approval:
EXPOSURE CATEGORY: C APPLICABLE CODES.
9.) PV MODULE FRAMES SHALL BE BONDED TO RACKING RAIL OR BARE
GROUND SNOW LOAD: 0 PSF COPPER G.E.C. PER THE MODULE MANUFACTURER'S LISTED INSTRUCTION
PARTS LIST SHEET.
10.) PV MODULE RACKING RAIL SHALL BE BONDED TO BARE COPPER
Quantity Name G.E.C. VIA WEEB LUG, ILSCO GBL-4DBT LAY-IN LUG, OR EQUIVLENT LISTED
12 Sunpower End Clamp LUG.
GOVERNING CODES 11.) GROUNDING ELECTRODE CONDUCTOR (G.E.C.) SHALL BE CONTINUOUS
20 PV AC Module 2011 NEC (AS AMENDED BY CITY) AND/OR IRREVERSIBLY SPLICED/WELDED.
12.) ALL JUNCTION BOXES, COMBINER BOXES, AND DISCONNECTS SHALL
28 Unirac Cone Flashing 2012 INTERNATIONAL BUILDING CODE BE INSTALLED IN AN ACCESSIBLE LOCATION.
28 Unirac Standoff
2012 INTERNATIONAL RESIDENTIAL CODE 13.) ROOF ACCESS POINTS SHALL BE AT A STRONG POINT ON THE
2012 INTERNATIONAL FIRE CODE BUILDING AND NOT REQUIRE THE PLACEMENT OF LADDERS OVER EXTERIOR REVISIONS
DESCRIPTION DATE REV
28 Unirac L-Foot 2012 INTERNATIONAL GREEN CONSTRUCTION CODE WALL OPENINGS.
ORIGINAL 10/25/2017 A
14.) WORKING SPACE AROUND ELECTRIAL EQUPMENT SHALL COMPLY WITH
34 Sunpower Mid Clamp UNDERWRITERS LABORATORIES (UL) STANDARDS NEC 110.26
OSHA 29 CFR 1910.269
56 5/16" Lag Screw
140 Feet of Sunpower Invisimount Rail

Sheet Title:

Sheet Number:
T1.0
Sheet Size:
ANSI B - 17" x 11"
DESIGN & DRAFTING BY:
ANDREW DOBBINS

Reviewed & Approved by:


EH
N

PV AZIMUTH
FENCE

180°

MAIN SERVICE PANEL


AC Modules Project:
UTILITY METER
AC COMBINER BOX
PHOENIX, AZ 85027
PV SYSTEM AC DISCONNECT
36" RIDGE CLEARANCE Project Details:
HVAC (TYP.) 6.90 kWstc, 6.40 kW AC
AHJ: PHOENIX, CITY OF
GATE JUNCTION BOX
BRANCH #1 (10) Engineering Approval:

BRANCH #2 (10)

PV SYSTEM UTILITY
36" ACCESS PATHWAYS DISCONNECT SWITCH
19° PITCH (V.I.F.) PV PRODUCTION UTILITY METER
3/4" EMT

ROOF ACCESS POINT


REVISIONS
DESCRIPTION DATE REV
ORIGINAL 10/25/2017 A

TO BE TRIMMED OR
UTILITY HAS 24-HR UNRESTRICTED REMOVED AS NECESSARY
ACCESS TO ALL PHOTOVOLTAIC SYSTEM
COMPONENTS LOCATED AT THE
SERVICE ENTRANCE. Sheet Title:
PROPERTY LINE
WORKSPACE IN FRONT OF THE AC
ELECTRICAL SYSTEM COMPONENTS SHALL BE IN
Sheet Number:
ACCORDANCE WITH APS & NEC REQUIREMENTS.
FOR APS REQUIREMENTS, REFERENCE SECTION DRIVEWAY A1.0
300 OF THE APS ESRM & SECTION 8.2 OF THE APS Sheet Size:
INTERCONNECTION REQUIREMENTS. ANSI B - 17" x 11"
DESIGN & DRAFTING BY:
REFERENCE SECTION 301.15 OF THE ANDREW DOBBINS
APS ESRM FOR ELECTRIC METER SEPARATION
BETWEEN WATER & GAS.

6 ft 12 ft 24 ft GOLDENVIEW DRIVE Reviewed & Approved by:


SCALE: 1" = 12' EH
N
LEGEND
FLASHING RAFTER/TRUSS PV MODULE VENT CHIMNEY SKYLIGHT

PV AZIMUTH
180°

28'-1"
2'
TYP.
6' MAX. AC Modules Project:
RIDGE
PHOENIX, AZ 85027

3' MIN. Project Details:


6.90 kWstc, 6.40 kW AC
AHJ: PHOENIX, CITY OF

Engineering Approval:

3' MIN.

19° PITCH (V.I.F.)


3' MIN.
REVISIONS
DESCRIPTION DATE REV
ORIGINAL 10/25/2017 A

Sheet Title:

Sheet Number:
A1.1
EAVE Sheet Size:
ANSI B - 17" x 11"
DESIGN & DRAFTING BY:
21'-1" ANDREW DOBBINS

2 ft 4 ft 8 ft

SCALE: 1" = 4' Reviewed & Approved by:


EH
AC Modules Project:

PHOENIX, AZ 85027

Project Details:
6.90 kWstc, 6.40 kW AC
AHJ: PHOENIX, CITY OF

Engineering Approval:

STRUCTURAL CALCULATIONS
QT Y WEIGHT EA. TOTAL
PV MODULE 20 x 41.0 LBS = 820 LBS
RACKING RAIL 140 x 1.30 LB/FT = 182 LBS
ATTACHMENT 28 x 4.0 LBS = 112 LBS
TOTAL WEIGHT: 1114 LBS 2
ARRAY AREA: 351 SQ. FT. -
REVISIONS
DEAD LOAD: 3.2 PSF 8 in 16 in 32 in
DESCRIPTION DATE REV

MOUNTING PLAN VIEW ORIGINAL 10/25/2017 A


POINT LOAD: 39.8 LBS 1
SCALE: 1" = 16"

Sheet Title:

Sheet Number:
A2.0
Sheet Size:
ANSI B - 17" x 11"
DESIGN & DRAFTING BY:
ANDREW DOBBINS

MOUNTING METHOD MOUNTING DETAIL


2 3
SCALE: 1" = 12" SCALE: 1" = 6"
6 in 12 in 24 in 3 in 6 in 12 in Reviewed & Approved by:
EH
Array Configuration PV Module Specifications Inverter Specifications 120% Rule Calculation per NEC 705.12(D)(2)
Array Power (kWstc): 6.90 Model Number: SUNPOWER SPR-X21-345-C-AC Model Number: SUNPOWER SPR-X21-345-C-AC Ma i n Bus ba r Rati ng: 200 Amps
Micro-Inverter Quantity: 20 Weight: 41.0 lbs Power Rating: 320 W AC Ma i n Servi ce Brea ker Rati ng: 100 Amps
Branch Circuit Quantity: 2 Dimensions: 61.4 x 41.2 x 1.8 inches Nominal Voltage: 240 Volts AC PV Ba ckfeedi ng Current: 33.3 Amps
Length of Branch #1: 10 Power @ STC: 345 Watts Max Output Current: 1.33 Amps MAIN MAX PV
BUSBAR x 120% - =
Length of Branch #2: 10 Voc: 68.2 Volts DC CEC Weighted Efficiency: 96.0% BREAKER BREAKER
Total Module Quantity: 20 Vmp: 57.3 Volts DC Maximum # of Modules 240 - 100 = 140
12
Isc: 6.39 Amps per Branch:
AC System Summary Imp: 6.02 Amps Maximum DC Voltage: 80 Volts DC
Sys tem Vol ta ge: 240 VAC Voc Temp Coeff: -0.27 %/°C
690.8(A) Ma x Current: 26.6 Amps
AC Modules Project:
690.8(B) Ma x Current: 33.3 Amps

NOTE: THE CONDUCTORS BETWEEN ALL ROOF MOUNTED CONDUIT PHOENIX, AZ 85027
THE AC DISCONNECT AND THE PV MUST BE MOUNTED A MINIMUM
BREAKER MUST BE A MINIMUM OF 1/2" ABOVE THE ROOF. 3 5 6 8 Project Details:
OF 4' IN LENGTH. MAIN SERVICE PANEL 6.90 kWstc, 6.40 kW AC
240 VAC, 200 A, 1-PH. AHJ: PHOENIX, CITY OF
AC1 CONDUCTORS NOT LOCATED
UTILITY METER
ALL WIRE TERMINALS SHALL BE RATED UNDERNEATH MODULES MUST BE PROTECTED BY 3/4" EMT. Engineering Approval:
MINIMUM 75° C. 100 A / 2P
TO UTILITY GRID
TO EXISTING LOADS
3 7
2 3 2 3 9
AC COMBINER BOX
PV SYSTEM PV PRODUCTION PV SYSTEM UTILITY
AC DISCONNECT UTILITY METER DISCONNECT SWITCH

4 35 A / 2P
JUNCTION BOX
PV AC MODULES AC3 AC3 AC3 AC3
20 A / 2P
(1) BRANCH OF
REVISIONS
(10) PV AC MODULES DESCRIPTION DATE REV
AC1
ORIGINAL 10/25/2017 A

PV AC MODULES
20 A / 2P
(1) BRANCH OF
(10) PV AC MODULES
AC1 AC2
Sheet Title:

NOTE: THE CONDUCTORS BETWEEN THE AC DISCONNECT


NOTE: AC1 CONDUCTORS NOT LOCATED UNDERNEATH Sheet Number:
AND THE PV BREAKER MUST BE A MINIMUM OF 4' IN LENGTH.
MODULES MUST BE PROTECTED BY 3/4" EMT.
WIRE AN D CON DUIT SCHEDUL E
PV System Maximum Voltage Calculation per NEC 690.7(A) Sheet Size:
Local Record Low Temp: -3 °C Data Source: PHOENIX SKY HARBOR INTL AP TAG
C ON D CON D CON D GN D GN D GN D CON DUIT CON DU IT ES T. ANSI B - 17" x 11"
QTY S IZE TYP E QTY S IZE TYP E S IZE TYP E DIS T.
25°C - Voc Voc Ma x # of Temperature DESIGN & DRAFTING BY:
Voc Temp
Coeffi ci ent
x Record + 1 = Correcti on Correcti on x Voc x Modul es = Corrected Open AC1 2 AWG #12 THWN-2 1 AWG #8 THWN-2 N/A N/A 20 ANDREW DOBBINS
Low Temp. Fa ctor Factor i n Seri es Ci rcui t Vol tage AC2 4 AWG #10 THWN-2 1 AWG #8 THWN-2 3/4" EMT 50
0.27%/°C x 28°C +1 = 1.076 1.076 x 68.2 x 1 = 73.4 Volts DC AC3 3 AWG #8 THWN-2 1 AWG #8 THWN-2 3/4" EMT 30
CONDUCTOR SPECIFICATIONS REQUIRED CONDUCTOR AMPACITY AMPACITY CHECK #1 CONDUCTOR TEMPERATURE DERATING CONDUIT FILL DERATING CORRECTED AMPACITY CALCULATION AMPACITY CHECK #2 VOLTAGE DROP
CIRCUIT AMPACITY @ CONT. INVERTER # OF MICRO- REQUIRED LOCAL 2% HEIGHT TEMP. ADDER AMPACITY # OF AMPACITY CONDUIT DERATED REQUIRED DERATED ESTIMATED
TAG CIRCUIT ORIGIN TEMP. TRADE REQUIRED CONDUCTOR OPERATING CONDUCTOR TEMP VOLTAGE
DESTINATION MATERIAL RATING 30°C PER OPERATION x OUTPUT x INVERTERS = AMPACITY < CIRCUIT ENVIRONMENT HIGH ABOVE PER CORRECTION UNGROUNDED CORRECTION x DERATE x FILL = CONDUCTOR AMPACITY < CONDUCTOR ONE-WAY
SIZE AMPACITY AMPACITY TEMP (°C) AMPACITY DROP
310.15(B)(16) 690.8(B)(1) CURRENT (A) IN PARALLEL 690.8(B)(1) TEMP AVG. ROOF (in) 310.15(B)(3)(c) 310.15(B)(2)(a ) CONDUCTORS 310.15(B)(3)(a ) DERATE AMPACITY 690.8(B)(2) AMPACITY DISTANCE
AC1 MICRO-INVERTER JUNCTION BOX COPPER 90°C AWG #12 30 Amps 1.25 x 1.33 x 10 = 16.6 Amps 16.6 Amps < 30.0 Amps ROOFTOP, FREE AIR 43 - N/A 43 0.87 N/A 1.00 30 x 0.87 x 1.00 = 26.1 Amps 13.3 Amps < 26.1 Amps 20 ft 0.44% Reviewed & Approved by:
AC2 JUNCTION BOX AC COMBINER BOX COPPER 90°C AWG #10 40 Amps 1.25 x 1.33 x 10 = 16.6 Amps 16.6 Amps < 40.0 Amps ROOFTOP, IN CONDUIT 43 1 22 65 0.65 4 0.80 40 x 0.65 x 0.80 = 20.8 Amps 13.3 Amps < 20.8 Amps 50 ft 0.67%
AC3 AC COMBINER BOX PV BREAKER COPPER 75°C AWG #8 50 Amps 1.25 x 1.33 x 20 = 33.3 Amps 33.3 Amps < 50.0 Amps EXT. BLDG. WALL (+15°C) 43 - N/A 58 0.58 2 1.00 50 x 0.58 x 1.00 = 29 Amps 26.6 Amps < 29.0 Amps 30 ft 0.52% EH
= EQUIP. GROUNDING CONDUCTOR = CIRCUIT CONDUCTOR = FUSE = CIRCUIT BREAKER (N) = NEW EQUIP. (E) = EXISTING EQUIP. L1 = LINE 1 (BLACK) L2 = LINE 2 (RED) N = NEUTRAL (WHITE) G = GROUND (GREEN) = POSITIVE (RED) = NEGATIVE (BLACK)

120% Rule Calculation per NEC 705.12(D)(2) WIRE AND CON DUIT SCHEDUL E
Ma in Bus ba r Ra ti ng: 200 Amps CON D CON D CON D GN D GN D GN D CON DUIT CON DUIT ES T.
TAG
Mai n Service Brea ker Ra ti ng: 100 Amps QTY S IZE TYP E QTY S IZE TYP E S IZE TYP E DIS T.

PV Ba ckfeedi ng Current: 33.3 Amps AC1 2 AWG #12 THWN-2 1 AWG #8 THWN-2 N/A N/A 20
MAIN MAX PV AC2 4 AWG #10 THWN-2 1 AWG #8 THWN-2 3/4" EMT 50
BUSBAR x 120% - =
BREAKER BREAKER AC3 3 AWG #8 THWN-2 1 AWG #8 THWN-2 3/4" EMT 30
240 - 100 = 140 Array Configuration
ON ROOFTOP BLDG EXTERIOR WALL, INSIDE FENCE
Array Power (kWstc): 6.90 AC Modules Project:
3 7
(N) AC COMBINER BOX Micro-Inverter Quantity: 20
PHOENIX, AZ 85027
SQ D HOM612L100RB
(OR EQUIVALENT)
Branch Circuit Quantity: 2
SUNPOWER
240 VAC, 100 A Length of Branch #1: 10 Project Details:
NEMA 3R, UL LISTED 6.90 kWstc, 6.40 kW AC
AC PV MODULE 4
(N) JUNCTION BOX L1
Length of Branch #2: 10 AHJ: PHOENIX, CITY OF
NEMA 4X, UL LISTED L2 TO PV SYSTEM Total Module Quantity: 20
Engineering Approval:
L1 L1 N AC DISCONNECT
L2 L2 20 A G AC System Summary
10 2 1 AC1 L1
AC3 Sys tem Vol tage: 240 VAC
G L2
690.8(A) Ma x Current: 26.6 Amps
BRANCH #1
690.8(B) Ma x Current: 33.3 Amps
20 A
L1 L1 L1

G G G L2 L2 L2 TO UTILITY GRID
BRANCH #2 10 2 1 AC1 G
G G (2) AWG #14 CU REVISIONS
AC2 G IN MIN. 1/2" EMT L1 L2 N
DESCRIPTION DATE REV
BRANCH N ORIGINAL 10/25/2017 A
LENGTH INDICATOR (E) BI-DIRECTIONAL
UTILITY METER
1-PHASE, 240 V
L1 L2 N
TO ETHERNET OR
CT SUNPOWER PV L1
(E) BONDING JUMPER
NOTE: THE CONDUCTORS BETWEEN PLC (POWER LINE LAN SUPERVISOR L2 PER NEC 250.92(A)(2)
COMMUNICATION)
THE AC DISCONNECT AND THE PV L1 L2 N SPLIT-CORE CT'S
Sheet Title:

CT
BREAKER MUST BE A MINIMUM BLDG EXTERIOR WALL, OUTSIDE FENCE (E) MAIN SERVICE DISCONNECT

CT
100 A, 240 V, 2-P
OF 4' IN LENGTH. (E) BUS BARS: 200 A
2 3 100 A
(N) PV PRODUCTION 2 3 9
(N) PV SYSTEM (N) PV BREAKER Sheet Number:
UTILITY METER (N) PV SYSTEM UTILITY
ALL WIRE TERMINALS SHALL BE RATED AC DISCONNECT SQ D CQRB100CP 20 A 35 A, 240 V, 2-P E1.0
SQ D DU222RB (OR EQUIVALENT)
DISCONNECT SWITCH L1 INSTALLED PER
MINIMUM 75° C. (OR EQUIVALENT) 240 VAC, 100 A SQ D DU222RB
L2 NEC 705.12(D)(7) Sheet Size:
240 VAC, 60 A 240 VAC, 60 A
NEMA 3R, UL LISTED
FORM 2S, RING TYPE
NEMA 3R, UL LISTED
ANSI B - 17" x 11"
NEMA 3R, UL LISTED 35 A 3 5 6 8
ALL ROOF MOUNTED CONDUIT L1 L1 L1 L1 L1 L1 L1 (E) MAIN SERVICE PANEL DESIGN & DRAFTING BY:
ANDREW DOBBINS
SCHNEIDER ELECTRIC
MUST BE MOUNTED A MINIMUM FROM AC L2 L2 L2 L2 L2 L2 L2
SC2040M200PS
COMBINER BOX N N N N N N
OF 1/2" ABOVE THE ROOF. G G G G G G 200 A, 240 VAC, 1-PH.

AC3 AC3 AC3 AC3 N G (E) GROUNDING


AC1 CONDUCTORS NOT LOCATED ELECTRODE SYSTEM
Reviewed & Approved by:
UNDERNEATH MODULES MUST BE PROTECTED BY 3/4" EMT. EH
Array Configuration PV Module Specifications Inverter Specifications
Array Power (kWstc): 6.90 Model Number: SUNPOWER SPR-X21-345-C-AC Model Number: SUNPOWER SPR-X21-345-C-AC
Micro-Inverter Quantity: 20 Weight: 41.0 lbs Power Rating: 320 W AC
Branch Circuit Quantity: 2 Dimensions: 61.4 x 41.2 x 1.8 inches Nominal Voltage: 240 Volts AC
Length of Branch #1: 10 Power @ STC: 345 Watts Max Output Current: 1.33 Amps
Length of Branch #2: 10 Voc: 68.2 Volts DC CEC Weighted Efficiency: 96.0%
Total Module Quantity: 20 Vmp: 57.3 Volts DC Maximum # of Modules
12
Isc: 6.39 Amps per Branch: AC Modules Project:

AC System Summary Imp: 6.02 Amps Maximum DC Voltage: 80 Volts DC PHOENIX, AZ 85027

Sys tem Vol ta ge: 240 VAC Voc Temp Coeff: -0.27 %/°C 120% Rule Calculation per NEC 705.12(D)(2) Project Details:
6.90 kWstc, 6.40 kW AC
690.8(A) Ma x Current: 26.6 Amps Ma in Bus ba r Ra ting: 200 Amps AHJ: PHOENIX, CITY OF

690.8(B) Ma x Current: 33.3 Amps Ma in Service Brea ker Ra ting: 100 Amps Engineering Approval:

PV System Maximum Voltage Calculation per NEC 690.7(A) PV Ba ckfeedi ng Current: 33.3 Amps
Loca l Record Low Temp: -3 °C Da ta Source: PHOENIX SKY HARBOR INTL AP MAIN MAX PV
BUSBAR x 120% - =
25°C - Voc Voc Ma x # of Tempera ture
BREAKER BREAKER
Voc Temp
x Record + 1 = Correcti on Correcti on x Voc x Modules = Corrected Open 240 - 100 = 140
Coeffi ci ent
Low Temp. Fa ctor Fa ctor i n Series Ci rcuit Vol ta ge
REVISIONS
0.27%/°C x 28°C +1 = 1.076 1.076 x 68.2 x 1 = 73.4 Volts DC DESCRIPTION DATE REV
ORIGINAL 10/25/2017 A

Sheet Title:

Sheet Number:
E1.1
Sheet Size:

CONDUCTOR SPECIFICATIONS AMPACITY CHECK #1 AMPACITY CHECK #2 VOLTAGE DROP ANSI B - 17" x 11"
CIRCUIT AMPACITY @ REQUIRED REQUIRED DERATED ESTIMATED DESIGN & DRAFTING BY:
TAG CIRCUIT ORIGIN TEMP. TRADE CONDUCTOR VOLTAGE ANDREW DOBBINS
DESTINATION MATERIAL
RATING SIZE
30°C PER AMPACITY <
AMPACITY
AMPACITY < CONDUCTOR ONE-WAY
DROP
310.15(B)(16) 690.8(B)(1) 690.8(B)(2) AMPACITY DISTANCE
AC1 MICRO-INVERTER JUNCTION BOX COPPER 90°C AWG #12 30 Amps 16.6 Amps < 30.0 Amps 13.3 Amps < 26.1 Amps 20 ft 0.44%
AC2 JUNCTION BOX AC COMBINER BOX COPPER 90°C AWG #10 40 Amps 16.6 Amps < 40.0 Amps 13.3 Amps < 20.8 Amps 50 ft 0.67%
Reviewed & Approved by:
AC3 AC COMBINER BOX PV BREAKER COPPER 75°C AWG #8 50 Amps 33.3 Amps < 50.0 Amps 26.6 Amps < 29.0 Amps 30 ft 0.52% EH
WARNING WARNING

REQ'D BY: NEC 690.5(C) REQ'D BY: NEC 690.13(B) REQ'D BY: NEC 690.17(E) REQ'D BY: NEC 690.31(G)(3) REQ'D BY: NEC 705.12(D)(3)
1 2 3 4 5
APPLY TO: APPLY TO: APPLY TO: APPLY TO: APPLY TO:
INVERTER(S), IF NOT APPLIED BY MFR AC DISCONNECT SWITCHES DISCONNECTS, FUSES, CIRCUIT BREAKERS JUNCTION BOXES, RACEWAYS, CABLE TRAYS, ANY/ALL ELECTRICAL PANELS
CONDUIT BODIES WITH AVAILABLE OPENINGS, CONNECTED TO MULTIPLE POWER SOURCES
EVERY 10', WITHIN 1' OF TURNS/PENETRATIONS

AC Modules Project:

WARNING AC DISCONNECT PHOENIX, AZ 85027


33
240
Project Details:
6.90 kWstc, 6.40 kW AC
AHJ: PHOENIX, CITY OF
REQ'D BY: NEC 705.12(D)(2)(3)(b) REQ'D BY: AHJ REQ'D BY: AHJ REQ'D BY: NEC 690.54
6 7 8 9
APPLY TO: APPLY TO: APPLY TO: APPLY TO:
PV BACKFED CIRCUIT BREAKER(S) PV SYSTEM UTILITY DISCONNECT SWITCH AC COMBINER BOX POINT OF INTERCONNECTION Engineering Approval:

Available Fault Current Calculation


Assu mp tions Utility Company: A PS
120/240V Single Phase Service Rating: 100 amperes
Copper Conductors in Metal Raceway Utility Sym m etrical Fault Cu rrent = 8,890 amperes
(Voltage Line-to-Line) E = 240 volts REVISIONS
DESCRIPTION DATE REV
ORIGINAL 10/25/2017 A
Phase Conductor = 8 AWG
Conductor L ength F rom PV Breaker Neutral Conductor = 8 AWG
to Utility PV Disconnect Te rm inations
sha ll n ot be less th an this length ------> (Conductor Length) L = 4 feet

(# of Conduc tors per phase) N = 1 Sheet Title:

(P hase conductor constant) C = 1,559


(Voltage line-to-line) V L-L = 240 Volts
'f ' factor = 2x Lx I f= 0.190 Sheet Number:

N x C x E L-N (Neutral conductor constant) C = 1,559 E2.0


(Voltage line-to-neutral) V L-N = 120 Volts Sheet Size:
f= 0.380 ANSI B - 17" x 11"
DESIGN & DRAFTING BY:
ANDREW DOBBINS
SIGNAGE REQUIREMENTS M ultiplier: M = 1 (Multiplier: Line-to-Line) ML-L = 0.840
1.) RED BACKGROUND 1+f (Multiplier: Line-to-Neutral) M L-N = 0.725
2.) WHITE LETTERING
3.) MIN. 3/8" LETTER HEIGHT
4.) ALL CAPITAL LETTERS Isca x M = fault current at terminals of utility PV disconnect L- L = 7,470 amperes
5.) ARIAL OR SIMILAR FONT Is ca x M = fault current at terminals of utility PV disconnect L- N = 9,662 amperes
6.) WEATHER RESISTANT Reviewed & Approved by:
MATERIAL, PER UL 969 SCALE: 1" = 4" EH
AC Modules Project:

PHOENIX, AZ 85027

Project Details:
6.90 kWstc, 6.40 kW AC
AHJ: PHOENIX, CITY OF

Engineering Approval:

REVISIONS
DESCRIPTION DATE REV
ORIGINAL 10/25/2017 A

Sheet Title:

Sheet Number:
D1.0
Sheet Size:
ANSI B - 17" x 11"
DESIGN & DRAFTING BY:
ANDREW DOBBINS

Reviewed & Approved by:


EH
AC Modules Project:

PHOENIX, AZ 85027

Project Details:
6.90 kWstc, 6.40 kW AC
AHJ: PHOENIX, CITY OF

Engineering Approval:

REVISIONS
DESCRIPTION DATE REV
ORIGINAL 10/25/2017 A

Sheet Title:

Sheet Number:
D2.0
Sheet Size:
ANSI B - 17" x 11"
DESIGN & DRAFTING BY:
ANDREW DOBBINS

Reviewed & Approved by:


EH
AC Modules Project:

PHOENIX, AZ 85027

Project Details:
6.90 kWstc, 6.40 kW AC
AHJ: PHOENIX, CITY OF

Engineering Approval:

REVISIONS
DESCRIPTION DATE REV
ORIGINAL 10/25/2017 A

Sheet Title:

Sheet Number:
D3.0
Sheet Size:
ANSI B - 17" x 11"
DESIGN & DRAFTING BY:
ANDREW DOBBINS

Reviewed & Approved by:


EH
AC Modules Project:

PHOENIX, AZ 85027

Project Details:
6.90 kWstc, 6.40 kW AC
AHJ: PHOENIX, CITY OF

Engineering Approval:

REVISIONS
DESCRIPTION DATE REV
ORIGINAL 10/25/2017 A

Sheet Title:

Sheet Number:
D4.0
Sheet Size:
ANSI B - 17" x 11"
DESIGN & DRAFTING BY:
ANDREW DOBBINS

Reviewed & Approved by:


EH
AC Modules Project:

PHOENIX, AZ 85027

Project Details:
6.90 kWstc, 6.40 kW AC
AHJ: PHOENIX, CITY OF

Engineering Approval:

REVISIONS
DESCRIPTION DATE REV
ORIGINAL 10/25/2017 A

Sheet Title:

Sheet Number:
D5.0
Sheet Size:
ANSI B - 17" x 11"
DESIGN & DRAFTING BY:
ANDREW DOBBINS

Reviewed & Approved by:


EH
CAUTION: ELECTRICAL POWER IS ALSO SUPPLIED FROM THIS SOURCE
WITH DISCONNECTS LOCATED AS SHOWN PER NEC 705.10

N
KEY:

1 MAIN ELECTRICAL SERVICE ENTRANCE


and
UTILITY REVENUE METER

2 PHOTOVOLTAIC SYSTEM UTILITY DISCONNECT SWITCH


and
DEDICATED PHOTOVOLTAIC SYSTEM KWH METER 1
3 PHOTOVOLTAIC SYSTEM AC COMBINER BOX 3
and
PHOTOVOLTAIC SYSTEM AC DISCONNECT SWITCH 2
4 SUNPOWER SPR-X21-345-C-AC, 345 WATT AC SOLAR MODULES
TOTAL QUANTITY: 20 (FLUSH MOUNTED, 19° PITCH)