TECHNICAL MANUAL

MANUAL
GMS8 33-3/8" Gas Furnace Units
80% AFUE, Single Stage,
Multi-Speed, Upflow Horizontal
• Refer to Service Manual RS6612006 for troubleshooting information.
• Refer to the appropriate Parts Catalog for part number information.
• Model numbers listed on page 3.

This manual is to be used by qualified, professionally trained HVAC technicians


only. Goodman does not assume any responsibility for property damage or RT6621031r2
personal injury due to improper service procedures performed by an unqualified November 2013
person.

Copyright © 2013 Goodman Manufacturing Company, L.P.


PRODUCT IDENTIFICATION
The model and manufacturing number are used for positive identification of component parts used in manufacturing.
Please use these numbers when requesting service or parts information.

G M S 8 040 3 A X A A

PRODUCT
TYPE: FURNACE MAJOR REVISION
G: Goodman TYPE
S: Single-Stage/ A: Initial Release
Multi-Speed CABINET
WIDTH
A: 14"
B: 17-1/2"
C: 21"
D: 24-1/2" MINOR REVISION
A: Initial Release

SUPPLY TYPE
M: Upflow/Horizontal NOMINAL INPUT
040: 40,000 Btuh
060: 60,000 Btuh
080: 80,000 Btuh ADDITIONAL
100: 100,000 Btuh AIRFLOW FEATURES
120: 120,000 Btuh CAPABILITY N: Natural Gas
140: 140,000 Btuh 3: 1200 X: Low NOx
AFUE
4: 1600
8: 80%
5: 2000

HIGH VOLTAGE!
WARNING Disconnect ALL power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal
injury or death.

WARNING Goodman will not be responsible Installation and repair of this unit
WARNING
for any injury or property damage should be performed ONLY by
arising from improper service or service procedures. If individuals meeting the requirements of an "entry level
you install or perform service on this unit, you assume technician" as specified by the Air-Conditioning, Heating,
responsibility for any personal injury or property damage and Refrigeration Institute (AHRI). Attempting to install or
which may result. Many jurisdictions require a license to repair this unit without such background may result in
install or service heating and air conditioning equipment. product damage, personal injury or death.

2
PRODUCT IDENTIFICATION
The model and manufacturing number are used for positive identification of component parts used in manufacturing.
Please use these numbers when requesting service or parts information.

GMS80403A*BB GMS81405DNCC
GMS80603A*BB
GMS80604B*BB
GMS80804B*BB
GMS80805C*BB
GMS81005C*BB
GMS81205D*BA

*These models available in Natural Gas and Low NOx.

The United States Environmental Protection Agency (“EPA”) has issued various regulations re-
WARNING garding the introduction and disposal of refrigerants introduced into this unit. Failure to follow
these regulations may harm the environment and can lead to the imposition of substantial fines.
These regulations may vary by jurisdiction. Should questions arise, contact your local EPA office.

Do not connect or use any device To prevent the risk of property


WARNING that is not design certified by Good- WARNING
damage, personal injury, or death,
man for use with this unit. Serious do not store combustible materials or use gasoline or
property damage, personal injury, reduced unit perfor- other flammable liquids or vapors in the vicinity of this
mance and/or hazardous conditions may result from the appliance.
use of such non-approved devices.

3
PRODUCT DESIGN
General Operation NFPA 54/ANSI Z223.1 - latest edition. In Canada, the fur-
The GMS8 furnaces are equipped with an electronic ignition naces must be vented in accordance with the National Stan-
device used to light the burners and an induced draft blower dard of Canada, CAN/CSA B149.1 and CAN/CSA B149.2 -
to exhaust combustion products. latest editions and amendments.
An interlock switch prevents furnace operation if the inner
NOTE: The vertical height of the Category I venting system
blower door is not in place. Keep the blower access door in
must be at least as great as the horizontal length of the
place except for inspection and maintenance. (See illustra-
venting system.
tion on pages 5 and 6.)
This furnace is also equipped with a self-diagnosing elec- Accessibility Clearances (Minimum)
tronic control module. In the event a furnace component is Unobstructed front clearanace of 24" for servicing is rec-
not operating properly, the control module LED will flash on ommended.
and off in a factory-programmed sequence, depending on
the problem encountered. This light can be viewed through MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS - INCHES
the observation window in the blower access door. Refer to
Vent
the Troubleshooting Chart for further explanation of the LED Sides Rear Front* Top
SW B
codes and Abnormal Operation - Integrated Ignition Control
1 0 3 6 1 1
section in the Service Instructions for an explanation of the
possible problem. * 24" clearnace for serviceability recommended.
** Single Wall Vent (SW) to be used only as a conncetor.
The rated heating capacity of the furnace should be greater Refer to the venting tables outlined in the Installation Manual for
than or equal to the total heat loss of the area to be heated. additional venting requirements.

The total heat loss should be calculated by an approved Note: In all cases accessibility clearance shall take prece-
method or in accordance with “ASHRAE Guide” or “Manual dence over clearances from the enclosure where accessibil-
J-Load Calculations” published by the Air Conditioning Con- ity clearances are greater. All dimensions are given in inches.
tractors of America.
*Obtain from: American National Standards Institute 1430 High Altitude Derate
Broadway New York, NY 10018
IMPORTANT NOTE: The furnace as shipped requires no
change to run between 0 - 5500 feet. Do not attempt to
Location Considerations increase the firing rate by changing orifices or increasing
• The furnace should be as centralized as is practical the manifold pressure below 5500 feet. This can cause poor
with respect to the air distribution system. combustion and equipment failure.
• Do not install the furnace directly on carpeting, tile, or High altitude installations above 5500 feet may require both
combustible material other than wood flooring. a pressure switch and an orifice change. These changes
are necessary to compensate for the natural reduction in
• When installed in a residential garage, the furnace
the density of both the gas fuel and the combustion air at
must be positioned so the burners and ignition source
higher altitude.
are located not less than 18 inches (457 mm) above
the floor and protected from physical damage by ve- For installations above 5500 feet, please refer to your dis-
hicles. tributor for required kit(s). Contact the distributor for a tabu-
lar listing of appropriate manufacturer’s kits for propane gas
Notes:
and/or high altitude installations. The indicated kits must be
used to insure safe and proper furnace operation. All conver-
WARNING sions must be performed by a qualified installer, or service
agency.
TO PREVENT POSSIBLE PERSONAL INJURY OR DEATH DUE TO ASPHYXIATION,
THIS FURNACE MUST BE CATEGORY I VENTED. DO NOT VENT USING
CATEGORY III VENTING.

Category I Venting is venting at a non-positive pressure. A


furnace vented as Category I is considered a fan-assisted
appliance and the vent system does not have to be “gas
tight.” NOTE: Single stage gas furnaces with induced draft
blowers draw products of combustion through a heat ex-
changer allowing, in some instances, common venting with
natural draft appliances (i.e. water heaters). All installations
must be vented in accordance with National Fuel Gas Code

4
COMPONENT IDENTIFICATION

1 Tubular Heat Exchanger

2 Pressure Switch

3 Flue Pipe Connection

4 Induced Draft Blower


?

5 Gas Line
Entrance

6 Gas Valve
7 Rollout Limit
8 Junction Box

9 Wiring Harness
Grommet
Gas Manifold
Gas Line Entrance
(Alternate)
Inshot Burner

Transformer
Circulator Blower
Blower Door
Interlock Switch
Note: Primary Limit Not Shown

Integrated Control Module

Upflow/Horizontal

1 Tubular Heat Exchanger 9 Wiring Harness Grommet


2 Pressure Switch 10 Gas Manifold
3 Flue Pipe Connection 11 Inshot Burner
4 Induced Draft Blower 12 Transformer
5 Gas Line Entrance 13 Integrated Control Module
6 Gas Valve 14 Blower Door Interlock Swtich
7 Rollout Limit 15 Circulator Blower
8 Junction Box 16 Gas Line Entrance (Alternate)
5
PRODUCT DIMENSIONS
GMS8
Alt. Gas Inlet

Alt. Gas Inlet

High Voltage Inlet Alt. High Voltage

Low Voltage
Alt. LowVoltage

M ODEL A B

GMS80403A***
14 12 - 1/2
GMS80603A***

GMS80604B***
17 - 1/2 16
GMS80804B***

GMS80805C***
21 19 - 1/2
GMS81005C***
GMS81205D***
24 - 1/2 23
GM S81405DN**

6
GMS8[040-100]BB
GMS81205D*BA
PRODUCT DIMENSIONS GMS81405DNCC

P re ssure S w itch Trip P oints

Trip Point ID Blow er


ID Blow er Pressure
Model
Pressure Sw itch
Sw itch Part #

GM S80403A*BB -0.70 B1370158

GM S80603A*BB -0.75 B1370179

GM S80604B*BB -0.75 B1370179

GM S80804B*BB -0.70 B1370158

GM S80805C*BB -0.75 B1370179

GM S81005C*BB -0.70 B1370158

GM S81205D*BA -0.80 0130F00042

GMS81405DNCC -0.80 0130F00042

For installations in Canada, the GMS furnaces are certifed only to 4,500 ft.
* Negative pressure readings are in inches of water column (*w.c.)

P RIM ARY LIM IT


Pa r t Num ber 20162901 20 1 6 2 9 0 4 2 0 1 62 9 0 3
Open Se tting (°F) 210 150 160
GM S8 0 40 3 A* BB 1 --- ---
GM S8 0 60 3 A* BB --- 1 ---
GM S8 0 60 4 B* BB --- 1 ---
GM S8 0 80 4 B* BB --- 1 ---
GM S8 0 80 5 C* BB --- --- 1
GM S8 1 00 5 C* BB --- 1 ---
GM S8 1 20 5 D* BA --- --- 1
GMS 81 4 0 5 DNCC --- --- 1

AUXILIARY LIM IT S W ITCHES


ROLLOUT LIM IT SW ITCHES
Pa r t Num be r 0 1 3 0 F00 0 3 8
Pa rt Num be r 1 0 1 2 3 5 29
Ope n Se tting (°F) 120
Ope n Se tting (°F) 300
GM S80403A*BB 1
GM S 80 4 0 3 A*BB 2
GM S80603A*BB 1
GM S 80 6 0 3 A*BB 2
GM S80604B*BB 1
GM S 80 6 0 4 B*BB 2
GM S80804B*BB 1
GM S 80 8 0 4 B*BB 2
GM S80805C*BB 1
GM S 80 8 0 5 C*BB 2
GM S81005C*BB 1
GM S 81 0 0 5 C*BB 2
GM S 81 2 0 5 D*BA 2 GM S81205D*BA 1

GM S8 1 4 0 5 DNCC 2 GMS 8 14 0 5 DNCC 1

7
PRODUCT DESIGN
Thermostats:
It is recommended that a single-stage heat, non-power robbing thermostat be used. Refer to the product marketing
literature for a complete list of thermostats offered.

THERMOSTATS

Thermostat Man/Auto Programmable Cool Heat Batt. Powered Batt. Bkup

1213406* Man. Or Auto Yes 2 3 No No

1213407 Man. Changeover Yes 2 2 Yes Yes

1213411 Man. Changeover No 2 2 Yes No

*1213406 is the recommended model for the G*S* furnaces when used with a heat pump in a fossil fuel application.
It is NOT for use with the G*S8 as a sole heating source. 1213406 thermstats are 24V powered with battery
Filters: backup.

Filters are required with this furnace and must be provided by the installer. The filters used must comply with UL900 or
CAN/ULCS111 standards. Installing this furnace without filters will void the unit warranty

Upflow Filters

SIDE RETURN BOTTOM RETURN


Cabinet Nominal Approx. Cabinet Nominal Approx.
Width Filter Size Flow Area Width Filter Size Flow Area
(in.) (in.) (in2) (in.) (in.) (in2)
All 16 x 25 x 1 400 17-1/2 14 x 25 x 1 350
21 16 x 25 x 1 400
24-1/2 20 x 25 x 1 500

Refer to Minimum Filter Area tables to determine filter area requirement. NOTE: Filters can also be installed elsewhere in
the duct system such as a central return.

MINIMUM FILTER SIZES for DISPOSABLE FI LTERS


FURNACE I NPUT FILTER SIZE
40M 320 in 2
60M 483 in 2
80M 640 in 2
2
100M 800 in
2
120M 738 in
2
140M 738 in
DISPOSABLE NOMINAL 300 F.M. FACE VELOCITY

8
GMS8[040-100]BB
GMS81205D*BA
FURNACE SPECIFICATIONS GMS81405DNCC

GMS81405DNCC
GMS80403A*BB

GMS80603A*BB

GMS80604B*BB

GMS80804B*BB

GMS80805C*BB

GMS81005C*BB

GMS81205D*BA
M O DEL

Btuh Input (US) High Fire 40,000 60,000 60,000 80,000 80,000 100,000 120,000 140,000
O utput (US) High Fire 32,000 48,000 48,000 64,000 64,000 80,000 96,000 112,000
A.F.U.E. 80% 80% 80% 80% 80% 80% 80% 80%
Rated External Static (" w.c.) .20 - .50 .20 - .50 .20 - .50 .20 - .50 .20 - .50 .20 - .50 .20 - .50 .20 - .50
Tem perature Rise (°F) 25 - 55 25 -55 20 - 50 35 - 65 35 - 65 35 - 65 40 - 70 40 - 70
High Stage Pressure Sw itch
-0.70 -0.75 -0.75 -0.70 -0.75 -0.70 -0.80 -0.80
Trip Point (" w .c .)
Blow er W heel (D" x W ") 10 X 6 10 x 6 10 x 8 10X8 10x10 10X10 11x10 11x10
Blow er Horsepow er 1/3 1/3 1/2 1/2 1/2 1/2 3/4 3/4
Blow er Speeds 4 4 4 4 4 4 4 4
Max C FM @ 0.5 E.S.P. 1298 1157 1883 1725 1960 1974 2131 2131
Power Supply 115-60-1 115-60-1 115-60-1 115-60-1 115-60-1 115-60-1 115-60-1 115-60-1
(1)
Minim um C ircuit Am pacity (MCA) 8.5 8.5 12.9 12.9 12.9 12.9 15.2 14.7
(2)
Maxim um O vercurrent Devic e 15 15 15 15 15 15 15 15
Transform er (VA) 40 40 40 40 40 40 40 40
Heat Anticipator (Am ps) 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7
Prim ary Lim it Setting (°F) 210° 150° 150° 150° 160° 150° 160° 160°
Auxiliary Lim it Setting (°F) 120° 120° 120° 120° 120° 120° 120° 120°
Rollout Lim it Setting (°F) 300° 300° 300° 300° 300° 300° 300° 300°
Gas Supply Pressure
7 / 11 7 / 11 7 / 11 7 / 11 7 / 11 7 / 11 7 / 11 7 / 11
(Natural/Propane) (" w.c.)
Manifold Pressure
3.5 / 10 3.5 / 10 3.5 / 10 3.5 / 10 3.5 / 10 3.5 / 10 3.5 / 10 3.5 / 10
(Natural/Propane) High Stage (" w.c.)
O rifice Size (Natural/Propane) #45 / #55 #45 / #55 #45 / #55 #45 / #55 #45 / #55 #45 / #55 #45 / #55 #43 / #55
Num ber of Burners 2 3 3 4 4 5 6 6
(3 )
Vent Connector D iam eter (inc hes) 4 4 4 4 4 4 4 4
Shipping W eight (lbs.) 84 88 98 106 114 118 130 130

(1)
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
(2)
Maximum Overcurrent Protection Device: May use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
(3)
See Installation Instructions for appropriate vent diameter, length and number of elbows.

1. These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation.
2. For elevations above 2000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level. The furnace must not be derated, orifice
changes should only be made if necessary for altitude.
3. The total heat loss from the structure as expressed in TOTAL BTU/HR must be calculated by the manufactures method in accordance with the
"A.S.H.R.A.E. GUIDE" or "MANUAL J-LOAD CALCULATIONS" published by the AIR CONDITIONING CONTRACTORS OF AMERICA. The total
heat loss calculated should be equal to or less than the heating capacity. Output based on D.O.E. test procedures, steady state efficiency times
output.
4. Minimum Circuit Ampacity calculated as: (1.25 x Circulator Blower Amps) + I.D. Blower Amps.

Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial plate for the most up-to-date general and electrical information.
9
GMS8[040-100]BB
GMS81205D*BA
BLOWER PERFORMANCE SPECIFICATIONS GMS81405DNCC
(CFM & Te m pe ra ture Rise vs. Ex te rna l S ta tic P re ssure )

Model Ton s AC EXTER N AL STATIC PR ESSUR E (Inches Water C olum n )


Motor
at 0 .5 " 0.1 0 .2 0.3 0.4 0 .5 0 .6 0 .7 0.8
Heating Speed Spe ed
A s Shipped ESP C FM R ISE C FM R ISE C FM R ISE CFM R ISE C FM R ISE C FM CFM CFM
H IGH 3 .0 1 52 1 ---- 146 6 ---- 14 14 ---- 1 37 3 ---- 129 8 ---- 12 43 1 164 1 07 5
*MS8 04 03A*BB MED 2 .5 1 16 0 26 116 0 26 11 32 26 1 12 1 26 108 2 27 10 42 99 7 9 25
(MED IUM) MED -L O 2 .0 9 61 31 9 55 31 94 8 31 9 32 32 9 13 33 88 2 82 1 8 03
L OW 1 .5 7 81 38 7 85 38 78 1 38 7 73 38 7 61 32 74 5 71 6 6 68
H IGH 3 .0 1 42 2 31 135 2 33 13 07 34 1 19 7 37 115 7 38 10 92 1 075 9 83
*MS8 06 03A*BB MED 2 .5 1 09 8 40 108 1 41 10 51 42 1 03 9 43 102 1 44 98 3 92 4 8 68
(MED IUM) MED -L O 2 .0 9 19 48 9 13 49 89 2 50 8 47 ---- 8 29 ---- 81 8 79 2 7 28
L OW 1 .5 7 58 ---- 7 41 ---- 74 1 ---- 7 33 ---- 6 99 ---- 67 7 64 9 6 26
H IGH 4 .0 2 13 4 21 210 0 21 20 42 22 1 97 5 23 188 3 24 17 86 1 700 1 60 1
*MS80 60 4B*BB MED 3 .5 1 66 8 27 166 3 27 16 56 27 1 64 5 27 161 6 28 15 49 1 492 1 39 1
(MED IUM) MED -L O 3 .0 1 41 9 31 142 6 31 14 26 31 1 43 2 31 141 9 31 13 78 1 328 1 26 1
L OW 2 .5 1 13 4 39 114 5 39 11 66 38 1 17 1 38 116 0 38 11 44 1 111 1 07 1
H IGH 4 .0 2 05 1 ---- 198 3 ---- 18 95 ---- 1 81 2 ---- 172 5 ---- 16 27 1 530 1 43 9
*MS80 80 4B*BB MED 3 .5 1 73 6 ---- 170 8 35 16 52 36 1 61 1 37 154 0 38 14 75 1 394 1 30 7
(MED IUM) MED -L O 3 .0 1 69 3 35 166 8 36 14 59 41 1 42 9 41 138 9 43 13 39 1 274 1 20 4
L OW 2 .5 1 20 0 49 118 5 50 11 80 50 1 17 3 51 115 8 51 11 25 1 125 1 08 0
H IGH 5 .0 2 29 0 ---- 222 9 ---- 21 55 ---- 2 04 7 ---- 196 0 ---- 18 37 1 712 1 58 4
*MS80 80 5C *BB MED 4 .0 1 85 2 ---- 182 0 ---- 17 77 ---- 1 71 9 --- 164 1 36 15 67 1 469 1 38 2
(MED IUM) MED -L O 3 .5 1 61 5 37 159 2 37 15 56 38 1 51 6 39 147 0 40 14 05 1 346 1 23 5
L OW 3 .0 1 29 0 46 128 5 46 12 65 47 1 23 5 48 121 4 49 11 74 1 044 9 04
H IGH 5 .0 2 32 3 ---- 222 5 ---- 21 20 35 2 04 0 36 197 4 38 18 01 1 688 1 57 7
*MS81 00 5C *BB MED 4 .0 1 85 8 40 184 7 40 17 99 41 1 74 4 42 167 4 44 15 77 1 493 1 39 9
(MED IUM) MED -L O 3 .5 1 59 6 46 158 7 47 15 71 47 1 55 2 48 149 3 50 13 97 1 326 1 21 7
L OW 3 .0 1 29 1 57 127 2 58 12 61 59 1 25 7 59 120 5 61 11 68 1 118 1 06 0
H IGH 5 .0 2 46 9 ---- 238 9 ---- 23 00 ---- 2 22 3 40 213 1 42 20 27 1 902 1 78 6
*MS81 20 5D *BA MED 4 .0 1 57 5 56 155 8 57 15 45 58 1 51 3 59 150 0 59 14 19 1 354 1 27 1
(MED IUM) MED -L O 3 .5 1 40 2 63 138 0 64 13 43 66 1 31 9 67 129 6 69 12 45 1 183 1 10 6
L OW 3 .0 1 20 0 ---- 118 6 ---- 11 61 ---- 1 12 7 ---- 108 2 ---- 10 42 99 5 9 26
H IGH 5 .0 2 46 9 42 238 9 43 23 00 45 2 22 3 47 213 1 49 20 27 1 902 1 78 6
GMS81 40 5D N CC MED 4 .0 1 57 5 66 155 8 67 15 45 67 1 51 3 69 150 0 69 14 19 1 354 1 27 1
(MED IUM) MED -L O 3 .5 1 40 2 ---- 138 0 ---- 13 43 ---- 1 31 9 ---- 129 6 ---- 12 45 1 183 1 10 6
L OW 3 .0 1 20 0 ---- 118 6 ---- 11 61 ---- 1 12 7 ---- 108 2 ---- 10 42 99 5 9 26

NOTES:
• CFM in chart is without filter(s). Filters do not ship with this furnace, but must be provided by the installer.
• All furnaces ship as hig-speed cooling. Installer must adjust blower cooling speed as needed.
• For most jobs, about 400 CFM per ton when cooling is desirable
• INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATING PLATE.
• The chart is for information only. For satisfactory operation, external static pressure must not exceed values shown on the rating plate. The shaded area insicated
ranges in excess of maximum static pressure allowed when heating.
• The dashed (---) areas indicate a temperature rise not recommended for this model.
• At higher altitudes, a properly de-rated unit will have approximatley the same temperature rise at a particular CFM, while ESP at the CFM will be lower.

10
BTU OUTPUT vs TEMPERATURE RISE CHART

100

600 CFM
90
700

80 800

900

70 1000
1100
1200
60
1400

1600
50
1800
2000

TEMPERATURE RISE
40 2200
2400 CFM
BLOWER PERFORMANCE SPECIFICATIONS

30
FORMULAS
BTU OUTPUT = CFM x 1.08 x RISE
20 BTU OUTPUT
RISE =

10
30 40 50 60 70 80 90 100 110 120 130 140 150

11
OUTPUT BTU/HR x 1000
WIRING DIAGRAMS GMS8

WARNING:DISCONNECT POWER BEFORE HUMIDIFIER INTEGRATED


SERVICING.WIRING TO UNIT MUST BE CONTROL MODULE
PROPERLY POLARIZED AND GROUNDED. XFMR (6) GND
24 VAC
HUMIDIFIER GND (8)
C2 GAS
C G R W Y MVC (9) VALVE

M1
MV (12)
DIAGNOSTIC C ID BLOWER
FUSE LED AUXILIARY PRESSURE
LIMIT CONTROLS SWITCH
OR

24V THERMOSTAT CONNECTIONS


G PS (10) C NO

3 2 1 TO PSO (4)
Y
MICRO HLI (7)
6 5 4 YL
W
HLO (1)
9 8 7 RD
AUTO RESET
12 11 10 YL PRIMARY
R
LIMIT
BL

BR RO2 (11)
CONTROL
AUXILI ARY
INTEGRATED LIMITS RO1 (5)
CONTROL MODULE

11 5 VAC NEUTRAL
RD

MANUAL RESET ROLLOUT


LIMIT CONTROL(S)
(SINGLE CONTROL ON SOME MODELS)
XFMR (3)
24 VAC
GR

40 VA
RD

2 BR TRANSFORMER
1

OR
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.

XFMR-H 115 VAC XFMR-N

YL
FLAME SENSOR
WH
BL
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS

YL
PU

FP (2)
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO

RD

HOT SURFACE
IGNITER
WH
BK

IGN IGN-N

OR (MED LOW)

INTEGRATED CONTROL MODULE


115 VAC HOT AND PARK TERMINALS
PU

BK

INTEGRATED CONTROL MODULE


LINE-H XFMR-H HEAT-H COOL-H

BL (MED)
RD (LOW)

BK (HI)
WH (N)

ID
BLWR
IND IND-N

COOL-H
OR

CICULATOR BLOWER

24V BK CO
OL
BR

BK
WH

CIRCULATOR
115V BLWR
CIR-N
YL

BR

XFMR
BR

AT
RD

WH HE
CAP
YL

HEAT-H
WH

15 PIN PLUG
GR

ON SOME MODELS
WH

BLOWER COMPARTMENT LINE-H LINE-N

BURNER COMPARTMENT JUNCTION BOX

24 VAC DOOR
DOOR SWITCH
BK

HUMIDIFIER SWI TCH


SWITCH LOCATED IN BLOWER
COMPARTMENT ON SOME MODELS NO C
YL
WARNING:
OR

RD RD
DISCONNECT POWER DISCONNECT
PRESSURE YL BEFORE SERVICING.
SWITCH
WH

PRIMARY LIMIT
BK

WIRING TO UNIT
MUST BE
PROPERLY
POLARIZED
WH AND GROUNDED.
WH

BK L GND N
BR TO 115VAC/1 Ø /60 HZ POWER SUPPLY WITH
HIGH VOLTAGE!

BL OVERCURRENT PROTECTION DEVICE


OR
BK
JUNCTION
WH BOX
HOT M1 C2
SURFACE FLAME LINE-N
IGNITER SENSOR
GAS VALVE GND
LINE H
PU
INDUCED DRAFT
BLOWER
TO 115 VAC/ 1/60HZ
PU PU POWER SUPPLY WITH
OVERCURRENT PROTECTION
DEVICE
ROLLOUT LIMITS
(SINGLE CONTROL ON SOME MODELS)

0 STEADY ON = NORMAL OPERATION LOW VOLTAGE (24V) EQUIPMENT GND


OFF = CONTROL FAILURE
LOW VOLTAGE FIELD FIELD GND
1 1 FLASH = SYSTEM LOCKOUT (RETRIES/RECYCLES EXCEEDED)
HI VOLTAGE (115V)
2 2 FLASHES = PRESSURE SWITCH STUCK CLOSED FIELD SPLICE
3 3 FLASHES = PRESSURE SWITCH STUCK OPEN HI VOLTAGE FIELD
SWITCH (TEMP.)
4 4 FLASHES = OPEN HIGH LIMIT JUNCTION
5 5 FLASHES = FLAME SENSE WITHOUT GAS VALVE IGNITER
TERMINAL
6 6 FLASHES = OPEN ROLLOUT SWITCH (PRESS.)
INTERNAL TO
7 7 FLASHES = LOW FLAME SIGNAL INTEGRATED CONTROL OVERCURRENT
C RAPID FLASHES = REVERSED 115 VAC POLARITY/VERIFY GND PLUG CONNECTION PROT. DEVICE

PK PINK NOTES:
COLOR CODES:
1. SET HEAT ANTICIPATOR ON ROOM THERMOSTAT AT 0.7 AMPS.
YL YELLOW BR BROWN 2. MANUFACTURER'S SPECIFIED REPLACEMENT PARTS MUST BE USED W HEN SERVICING.
OR ORANGE W H WHITE 3. IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE MUST BE
PU PURPLE BL BLUE REPLACED, IT MUST BE REPLACED W ITH W IRING MATERIAL HAVING A TEMPERATURE
RATING OF AT LEAST 105 C. USE COPPER CONDUCTORS ONLY.
GR GREEN GY GRAY
4. BLOWER SPEEDS MUST BE ADJUSTED BY INSTALLER TO MATCH THE INSTALLATION
BK BLACK RD RED REQUIREMENTS SO AS TO PROVIDE THE CORRECT HEATING TEMPERATURE RISE AND THE
CORRECT COOLING CFM. (SEE SPEC SHEET FOR AIR FLOW CHART)
5. UNIT MUST BE PERMANENTLY GROUNDED AND CONFORM TO N.E.C. AND LOCAL CODES.

0140F00119-C

Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
12
SCHEMATICS GMS8
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.

CIRCULATOR
BLOWER
INDUCER

CIR
HEAT COOL PARK PARK NEU IND
R
K2
RO2 ROLLOUT
K3 RO1 SWITCH
TH
K1
XFMR
HOT
24 VAC

.0005 XFMR
NEU COMPRESSOR
FACTORY TR CONTACTOR
3M K8 COIL R
JUMPER C
K5
FACTORY Y
JUMPER Y
G G
W W
FP IGN GND MV MV PS HLO HLI PSO
THERMOSTAT
FLAME
SENSOR
PROBE
GAS HIGH AUX
IGNITOR VALVE LIMIT LIMIT

PRESSURE
SWITCH

TYPICAL SCHEMATIC
GMS8 * MODEL FURNACES
WR 50T55-289 INTEGRATED IGNITION CONTROL

This schematic is for reference only. Not all wiring is as shown above. Always refer to the appropriate wiring diagram for the unit being serviced.

13