M ELECTRICAL SYMBOL LEGEND M

BASIC MATERIALS BASIC MATERIALS CONT. TELEPHONE/COMPUTER RACEWAY SYSTEM GENERAL NOTES:
SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION

1. LIGHT SWITCHES SHALL BE MOUNTED 48 INCHES ABOVE FINISHED FLOOR TO CENTER LINE OF A R C H I T E C T S I N C
Sa SINGLE POLE SWITCH AUTOMATIC TRANSFER SWITCH DEVICE, UNLESS OTHERWISE NOTED. License # AA C001863
(SUBSCRIPT INDICATES ITEM CONTROLLED)
S3 30AR NON-FUSED DISCONNECT SWITCH, SIZE & # OF POLES COMMUNICATIONS "INFORMATION OUTLET" MTD. AT
THREE-WAY SWITCH 1500 Jackson Street, Suite 200
NF RECEPTACLE HEIGHT UNLESS OTHERWISE NOTED. DIVISION
L NF DENOTES NON-FUSED RECEPTACLES SHALL BE LOCATED 18 INCHES ABOVE FINISHED FLOOR TO CENTER LINE OF L Fort Myers, Florida 33901
S4 FOUR-WAY SWITCH 16 CONTRACTOR TO PROVIDE 4" SQUARE WITH SINGLE GANG 2. DEVICE, UNLESS OTHERWISE NOTED. ABOVE-COUNTER RECEPTACLES SHALL BE MOUNTED Phone: 239-278-3838 Fax: 239-275-5356
AR DENOTES AMP RATING OF SWITCH RAISED MUD RING. CONTRACTOR TO STUB UP (2) 1"
SP SINGLE POLE SWITCH WITH PILOT LIGHT 6" ABOVE BACK SPLASH TO CENTERLINE OF DEVICE.
CONDUITS AT EACH LOCATION TO ABOVE CEILING AND TURN
SWP SINGLE POLE SWITCH WITH WEATHERPROOF COVER 30AR TO ACCESSIBLE CEILING SPACE. CONTRACTOR TO PROVIDE 949 Central Ave.
FUSED DISCONNECT BUSHING ON END OF CONDUIT AND PULLSTRING WITHIN. 3. EQUIPMENT SHALL BE OF MATERIALS SUITABLE FOR AND RATED FOR THE ENVIRONMENT IN Naples, Florida 34102
20AF
WHICH THEY ARE TO BE INSTALLED. Phone: 239-643-3103 Fax: 239-643-7435
SWPL SINGLE POLE SWITCH WITH WEATHERPROOF LOCKING COVER AR DENOTES AMP RATING OF SWITCH
MCP AF DENOTES AMP FUSE SIZE
SK SINGLE POLE KEY SWITCH SIZE TV TELEDATA/TV OUTLET - 4" SQUARE 2 GANG BOX WITH A. WORKING CLEARANCES FOR ELECTRICAL EQUIPMENT SHALL BE IN COMPLIANCE WITH Project:
# OF POLES (2) 1" CONDUITS PER ABOVE. 4.
NEC 110.

Lee County
S3K THREE-WAY KEY SWITCH 30/3 COMBINATION MAGNETIC MOTOR STARTER, SIZE & # OF POLES
0 3R
S4K FOUR-WAY KEY SWITCH 4'
3 POLE UNLESS OTHERWISE NOTED B. THE EXCLUSIVELY-DEDICATED SPACE EXTENDING FROM FLOOR TO STRUCTURAL

Justice Center
3'-6"

3'
ENCLOSURE NEMA RATING. TELEPHONE OUTLET FLOOR MOUNTED CEILING WITH A WIDTH AND DEPTH OF THE PANELBOARD OR SWITCHBOARD MUST BE
K SL SINGLE POLE SWITCH WITH SECURITY LOCKING KEY CLEAR OF ALL PIPING, DUCTS OR EQUIPMENT FOREIGN TO THE ELECTRICAL EQUIPMENT K
NEMA STARTER SIZE OR ARCHITECTURAL APPURTENANCES IN ACCORDANCE WITH NEC 408.

Second Floor
SLV
4'

LOW VOLTAGE SWITCH 3'-6"


BRANCH CIRCUIT PANELBOARD, UNDER 250 VOLTS,
3'
TTB
SURFACE MOUNTED TELEPHONE/COMPUTER TERMINAL BOARD
SF FAN SWITCH 4'
5. WHEN ELECTRICAL BOXES ARE LOCATED IN VERTICAL FIRE-RESISTIVE ASSEMBLIES,

Remodel Pod D
(CLASSIFIED AS FIRE/SMOKE AND SMOKE PARTITIONS), THEY SHALL BE INSTALLED
3'-6"

SM MANUAL MOTOR STARTER WITH OVERLOAD HEATERS 3'


BRANCH CIRCUIT PANELBOARD, UNDER 250 VOLTS,
FLUSH MOUNTED TTC WITHOUT AFFECTING THE FIRE CLASSIFICATION. ALL OF THE FOLLOWING CONDITIONS
SMP MANUAL MOTOR STARTER WITH OVERLOAD HEATERS AND PILOT LIGHT TELEPHONE TERMINAL CABINET SHALL BE MET:
BRANCH CIRCUIT PANELBOARD, OVER 250 VOLTS,
Part B
4'

3'-6"

SD DIMMER SWITCH
3'

SURFACE MOUNTED
(1500 WATTS UNLESS OTHERWISE INDICATED) T A. ALL ELECTRICAL BOXES SHALL BE METALLIC.
TELEPHONE SYSTEM RACEWAY Owner:
BRANCH CIRCUIT PANELBOARD, OVER 250 VOLTS,
J
DUPLEX RECEPTACLE
FLUSH MOUNTED B. BOX OPENING SHALL OCCUR ONLY ON ONE SIDE OF FRAMING SPACE. J Lee County Board
T
TWIST LOCK RECEPTACLE
BRANCH CIRCUIT CONDUIT CONCEALED ABOVE CEILING OR IN WALL.
CONDUIT SHALL INCLUDE PHASE, NEUTRAL AND GROUND CONDUCTORS
C. BOX OPENING SHALL NOT EXCEED 16 SQUARE INCHES. of Commissioners
SURGE PROTECTION TYPE (TVSS) AS REQUIRED FOR CIRCUITS (UNLESS OTHERWISE NOTED). D. ALL CLEARANCES BETWEEN OUTLET BOX AND GYPSUM BOARD SHALL BE
SP DUPLEX RECEPTACLE COMPLETELY FILLED WITH JOINT COMPOUND (OR OTHER APPROVED MATERIAL).

PEDESTAL MOUNTED RECEPTACLE


BRANCH CIRCUIT CONDUIT CONCEALED IN SLAB,
UNDERGROUND OR UNDER FLOOR. FIRE ALARM/DETECTION SYSTEM E. PROVIDE A WALL AROUND OUTLETS LARGER THAT 16 SQUARE INCHES. THE INTEGRITY Consultant:
OF THE WALL RATING SHALL BE MAINTAINED.
FLOOR OUTLET BOX AND DUPLEX RECEPTACLE BRANCH CIRCUIT CONDUIT EXPOSED 13099 S. Cleveland Ave.
SYMBOL DESCRIPTION
WITH APPROPRIATE FLANGE. F. THE TOTAL AGGREGATE SURFACE AREA OF THE BOXES SHALL NOT EXCEED 100 Suite 500
GROUND OR GROUND ROD AS NOTED Fort Myers, Florida 33907
SQUARE INCHES PER 100 SQUARE FEET. H
FLOOR OUTLET BOX WITH DUPLEX RECEPTACLE F MANUAL PULL STATION
H EM Phone: 239-275-4240
AND ONE COMBINATION W/ VOICE/DATA OUTLET EMERGENCY BRANCH CONDUIT G. OUTLET BOXES LOCATED ON OPPOSITE SIDES OF FIRE-RESISTIVE ASSEMBLIES Fax: 239-275-3511
CEILING SMOKE DETECTOR, PHOTO-ELECTRIC SHALL BE SEPARATED BY A MINIMUM HORIZONTAL DISTANCE OF 24 INCHES. www.tlc-engineers.com
FLOOR OUTLET BOX WITH TWO DUPLEX RECEPTACLES CONDUIT TURNING UP TYPE UNLESS OTHERWISE NOTED © Copyright 2014 TLC Engineering for Architecture, Inc.
UP H. OUTLET BOXES SHALL BE SECURELY FASTENED TO WALL FRAMING MEMBERS.
AND ONE COMBINATION W/ VOICE/DATA OUTLET E = ELEVATOR WITH RECALL CONTACTS EB #0000015 TLC NO: 714124
CONDUIT TURNING DOWN I = IONIZATION I. THE OPENING IN THE GYPSUM BOARD FACING SHALL BE CUT NOT TO EXCEED 1/8 INCH
FLOOR POKE THRU - WITH POWER AND TELECOMM DEVICES DN
BETWEEN THE EDGES OF THE OUTLET BOX AND THE EDGES OF THE OPENING.
CONDUIT STUB DUCT SMOKE DETECTOR Seal:
PP POWER POLE R = RETURN
6. ALL DEVICES SHALL BE MOUNTED VERTICAL, UNLESS OTHERWISE NOTED.
CONDUIT CONTINUED S = SUPPLY
DUPLEX RECEPTACLE WIRED TO COMPUTER PANEL FLEXIBLE CONDUIT 7. ALL RECEPTACLES SHALL BE MOUNTED SUCH THAT THE GROUND PIN IS MOUNTED DOWN.
R SUPERVISED CONTROL RELAY
G G
DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER EXISTING TO BE REMOVED
DUCT SMOKE REMOTE ALARM INDICATING LAMP,
R
EXISTING TO REMAIN W/ TEST SWITCH, WALL MOUNTED 72" AFF
DUPLEX SAFETY RECEPTACLE MOUNT
COVERPLATES WITH SPANNER HEAD SCREWS FUTURE RT REMOTE INDICATING LAMP FIRE ALARM WITH TEST SWITCH
NEW WALL MOUNTED 72" AFF
SIMPLEX RECEPTACLE (EWC DENOTES
EWC ELECTRIC WATER COOLER. COORDINATE WITH EWC
F COMBINATION AUDIBLE/VISUAL
INSTALLER FOR MOUNTING HEIGHT)
NOTIFICATION DEVICE
GFI RECEPTACLE. WP DENOTES WEATHERPROOF COVER.
F
WP SS FIRE ALARM SPEAKER - CEILING MOUNTED
COMPLIANCE STATEMENT F
Project Phase:
GFI RECEPTACLE MOUNTED ABOVE COUNTER
FS WALL MOUNTED SPEAKER WITH STROBE Design
TWO DUPLEX RECEPTACLES WITH COMMON COVER LIGHTING SS Development
FIRE ALARM SPEAKER - WALL MOUNTED
TWO DUPLEX RECEPTACLES WITH COMMON COVER
MOUNTED ABOVE COUNTER Project #: 0118.22
F FIRE ALARM SPEAKER WITH STROBE - CEILING MOUNTED
ISOLATED GROUND DUPLEX RECEPTACLE, FLUORESCENT STRIP FIXTURE Project Issued: xx/xx/14
IG (ORANGE DEVICE) VISUAL SIGNALING UNIT, WALL MOUNTED Sheet Issued:
A F
FIXTURE DESIGNATION (NO AUDIO DEVICE)
E
DUPLEX RECEPTACLE FLUORESCENT FIXTURE PLANS HAVE BEEN PREPARED IN COMPLIANCE E
NOTE: WITH THE 2010 FLORIDA BUILDING CODE AND No. Date Revision
P FIREMANS PHONE JACK
TICK MARKS SHOWN ON ANY DEVICE REPRESENTS RECEPTACLE CIRCUIT NUMBER 2 a LOWER CASE LETTER INDICATES CONTROL CIRCUIT SWITCH LEG
CONNECTED TO THE EMERGENCY CIRCUIT (RED DEVICE) TYPICAL
THE 2008 NATIONAL ELECTRICAL CODE.
FOR ANY DEVICE IN LEGEND FLUORESCENT FIXTURE SPRINKLER TAMPER
TS
DIAGONAL SHADING DENOTES EMERGENCY LIGHT FIXTURE. SWITCH CONNECTION
C CLOCK RECEPTACLE
FLUORESCENT WALL MOUNTED FIXTURE WITH WALL OUTLET BOX SPRINKLER WATERFLOW
FS
SPECIAL PURPOSE RECEPTACLE, RATING AS NOTED SWITCH CONNECTION
HID, FLUORESCENT, OR INCANDESCENT FIXTURE
LIGHTING CONTROL TIME CLOCK FP FIRE ALARM SYSTEM PRINTER
GND GROUND BAR ACCENT FLOOD LIGHTING - AIMING AS INDICATED
D ZAM ZONE ADDRESSABLE MODULE D
PLUG-IN STRIP WITH RECEPTACLES, 18" O.C. UNLESS EXIT LIGHT FIXTURE
OTHERWISE INDICATED DIRECTION ARROWS AS SHOWN
(SHADED QUADRANT INDICATES FACE(S) OF FIXTURE)
ELECTROMAGNETIC DOOR HOLD OPEN DEVICE
ELECTRICAL DRAWING INDEX
UNDER GROUND CONCRETE ENCASED DUCTBANK
WALL MOUNTED EXIT LIGHT FIXTURE
H
ELECTROMAGNETIC DOOR HOLD OPEN DEVICE
SHEET NUMBER SHEET NAME ISSUED
CONNECTION TO CLOSURE/ HOLDER
J JUNCTION BOX E0.01 LEGEND, GENERAL NOTES AND INDEX - ELECTRICAL
BATTERY PACK WITH TWIN HEADS
J JUNCTION BOX ELECTROMAGNETIC DOOR HOLD OPEN DEVICE E1.01 SECOND FLOOR POD D PLAN PHASE II - LIGHTING
H CONNECTION TO CLOSURE/ HOLDER INCLUDES DETECTOR
J JUNCTION BOX- WALL MOUNTED E1.02 SECOND FLOOR POD D PLAN PHASE II - POWER & SYSTEMS
J JUNCTION BOX- FURNITURE SYSTEM FEED H
CEILING HEAT DETECTOR 135° UNLESS OTHERWISE E2.01 DETAILS - ELECTRICAL
C INDICATED. C
CONDUIT SEAL-OFF FITTINGS
E2.02 DETAILS - ELECTRICAL
T BEAM DETECTOR - TRANSMITTER
SS
C3
SURGE SUPRESSOR
C3 = SERVICE ENTRANCE DEVICE
LIGHTING CONTROL R BEAM DETECTOR - RECEIVER
B3 = DISTRIBUTION BOARD DEVICE
A3 = PANELBOARD DEVICE FACP
FIRE ALARM CONTROL PANEL
SHUNT-TRIP BUTTON - FLUSH MOUNTED UNLESS OS WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR MOUNTED AT 90" A.F.F. Copyright © 2014. BSSW Architects, Inc.
ST FATC reserves copyright and other rights
OTHERWISE NOTED NEMA 3R FOR EXTERIOR LOCATIONS
FIRE ALARM TERMINAL CABINET restricting these documents to the original
OS CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR site or purpose for which they were
MAGNETIC MOTOR STARTER OR CONTACTOR prepared. Reproductions, changes or
B SIZE AS NOTED FAAP B assignments are prohibited.
FIRE ALARM ANNUNCIATOR PLAN - FLUSH MOUNTED
SO WALL MOUNTED PASSIVE INDRA-RED OCCUPANCY SENSOR WITH MANUAL OVERRIDE. Sheet Title:
EDH-X
LEGEND, GENERAL
MOUNT @ 48" A.F.F. FIRE ALARM SYSTEM CONDUIT AND WIRING
ELECTRIC DUCT HEATER F
Brett L. Sands, P.E.
ST WALL MOUNTED DIGITAL TIMER. `P' INDICATED WITH PILOT LIGHT Florida License #48477
5
4'
MOTOR CONNECTION, NUMBER DENOTES HORSEPOWER

VARIABLE FREQUENCY DRIVE


MOUNT @ 48" A.F.F.
E FIREMAN'S ELEVATOR WARNING LIGHT
NOTES AND INDEX -
ELECTRICAL
VFD 3'-6"

3'

PROVIDE ALL NECESSARY POWER PACKS AND RELAYS FOR A FULLY FUNCTIONAL SYSTEM
DDC DIRECT DIGITAL CONTROL PANEL

T TRANSFORMER Sheet No.


A A

Seal
E0.01
NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

C:\Users\mark.hauser\Documents\714124_LCJC 2ND FLR POD D PH II_CENTRAL_R14_mark.hauser.rvt 1/8/2015 8:01:36 AM


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

M
LIGHTING FIXTURE SCHEDULE M

Required Lamps
Lamp
Type Description Manufacturer Model Voltage Type Quantity Comments A R C H I T E C T S I N C
B RECESSED COMPACT FOURESCENT LIGHTOLIER PH60-132T-277 277 V 42WTT 1 LIMITS OF CONSTRUCTION License # AA C001863
DOWNLIGHT 6" DIA.
1500 Jackson Street, Suite 200
L B2 2x4 PRABOLIC W/18 CELL LIGHTOLIER 2LP3GS332-36AL-277-1/21-EB 277 V F32WT8 2 L Fort Myers, Florida 33901
SEMI-SPECULAR ALUMINUM LOUVER Phone: 239-278-3838 Fax: 239-275-5356

E2 2x2 PRABOLIC W/9 CELL LIGHTOLIER 2LP3GS332-36AL-277-1/21-EB 277 V F32WT8 2 949 Central Ave.
SEMI-SPECULAR ALUMINUM LOUVER POD B Naples, Florida 34102
Phone: 239-643-3103 Fax: 239-643-7435
X EXISTING TO BE REUSED 277 V CLEAN &
RE-LAMP EXISTING Project:

Lee County
CR
GENERAL LIGHTING NOTES :

K 1. ALL FLUORESCENT FIXTURES SHALL USE T8 LAMPS AND ELECTRONIC BALLASTS, UNLESS
OTHERWISE NOTED.
4. IF THERE IS A DISCREPANCY BETWEEN A FIXTURE DESCRIPTION AND GENERAL NOTES, AND
THE CATALOG NUMBER LISTED, THE FIXTURE DESCRIPTION AND GENERAL NOTES SHALL
K
Justice Center
2. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LOCATION OF LIGHT
5.
DICTATE.

ALL LIGHT FIXTURES SHALL BE SUPPORTED INDEPENDANT OF CEILING GRID.


Second Floor
Remodel Pod D
FIXTURES.

FIX
3. COORDINATE TYPE OF CEILING FOR EACH FIXTURE WITH ARCHITECTURAL REFLECTED

Part B
ACT
CEILING PLANS AND PROVIDE FIXTURE TRIM AS REQUIRED. 8' - 6" A.F.F.

Owner:

J J Lee County Board


LIMITS OF CONSTRUCTION
GENERAL NOTES: of Commissioners
1. ALL LIGHT FIXTURES SHALL BE CONNECTED TO EXISTING NORMAL POWER LIGHTING
CIRCUITS. `H3' UNLESS NOTED OTHERWISE. ALL LIGHT SWITCHES SHALL BE 277V RATED
U.N.O.
E2 E2 E2 E2 Consultant:
GWB 2. COORDINATE EXACT LOCATION OF EACH LIGHT FIXTURE WITH MECHANICAL PIPING,
B GWB 8' - 0" A.F.F. GWB CONDUIT, HVAC GRILLES, etc. FIELD ADJUST ANY LIGHT TO AVOID CONFLICT.
B 8' - 0" A.F.F.
B B B B 8' - 0" A.F.F. 13099 S. Cleveland Ave.
E2 E2 ACT Suite 500
8' - 6" A.F.F.
3. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT TYPE AND HEIGHT H
Fort Myers, Florida 33907
H B E2 E2 E2 OF CEILING IN EACH ROOM. COORDINATE WITH ARCHITECT/ENGINEER PRIOR TO Phone: 239-275-4240
B E2 E2 ROUGH-IN OF ANY FIXTURES. COORDINATE ALL CONTROL JOINTS LOCATIONS WITH Fax: 239-275-3511
ACT (Wood Look) LIGHT FIXTURES PRIOR TO ANY ROUGH-IN OF FIXTURES. www.tlc-engineers.com
E2
8' - 11 1/2" A.F.F. © Copyright 2014 TLC Engineering for Architecture, Inc.
E2 E2 4. ALL ELECTRICAL CONTROL DEVICES SHALL BE MOUNTED AT A HEIGHT THAT IS EB #0000015 TLC NO: 714124
B E2 E2 E2 E2
B GWB E2 ACCESSIBLE TO THE DISABLED IN ACCORDANCE WITH THE FLORIDA ACCESSIBILITY
E2
GWB ACT 8' - 6" A.F.F. CODE. REFER TO ELECTRICAL SHEET E000 FOR MOUNTING HEIGHTS OF ELECTRICAL
8' - 0" A.F.F. 8' - 6" A.F.F. CONTROL DEVICES. Seal:
E2 E2 E2
B
E2 E2 E2 5.
ACT (Wood Look) E2 PROVIDE CONDUIT AND WIRING AS REQUIRED TO MEET CIRCUITING SHOWN TO
8' - 11 1/2" A.F.F. E2 CONFORM TO NEC REQUIREMENTS. PROVIDE EQUIPMENT GROUND CONDUCTOR IN
B E2 GWB ALL RACEWAYS.
G 8' - 0" A.F.F. G
E2 E2 E2 E2
GWB 6. MULTIPLE LIGHT SWITCHES, AT THE SAME LOCATION, SHALL BE GANGED TOGETHER
8' - 0" A.F.F. E2 E2 UNDER ONE COVER PLATE. DIMMER SWITCHES SHALL BE INSTALLED IMMEDIATELY
CR
E2 BELOW SWITCH LOCATIONS.
B ACT (Wood Look)
E2 E2 E2 8' - 11 1/2" A.F.F.
GWB ACT (Wood Look)
8' - 0" A.F.F. 8' - 11 1/2" A.F.F. E2 E2 E2 GWB 7. CORRIDOR LIGHTING TO BE CONNECTED TO EXISTING CORRIDOR LIGHTING CIRCUITS.
B 8' - 0" A.F.F.
E2 E2
E2 GWB
E2 E2 E2 GWBE2
CR
GWB 8' - 0" A.F.F.
ACT (Wood Look) 8' - 6" A.F.F. DPS 8' - 0" A.F.F.
E2 8' - 11 1/2" A.F.F. X
F E2 E2 E2 E2
E2
DPS
GWB ACT # KEYNOTES: F
Project Phase:

Design
8' - 0" A.F.F. 8' - 6" A.F.F.
E2 1. SAME AS TYPE A, EXCEPT CIRCUIT IS FED FROM EMERGENCY
GWB 3
GWB E2 8' - 6" A.F.F. E2 E2 DISTRIBUTION TYPICAL.

Development
E2 E2 E2 GWB GWB
8' - 6" A.F.F.
8' - 0" A.F.F. 8' - 0" A.F.F. 2. SAME AS TYPE B, EXCEPT CIRCUIT IS FED FROM EMERGENCY
E2 E2
GWB DISTRIBUTION, TYPICAL.
E2 E2 E2 8' - 0" A.F.F. Project #: 0118.22
ACT (Wood E2 Look) E2
8' - 11 1/2" A.F.F. ACT (Wood Look) Project Issued: 07/01/13
E2 E2 8' - 11 1/2" A.F.F.
E2
ACT ACT Sheet Issued:
E2 E2 E2 8' - 11 1/2" A.F.F. 8' - 6" A.F.F.
E E
POD A
E2 E2 E2 E2 No. Date Revision
GWB
8' - 6" A.F.F. GWB E2 E2
E2 8' - 6" A.F.F. E2 E2
E2
ACT (Wood Look)
E2 E2 EXISTING
ACT APPROX LINE OF CONSTRUCTION
8' - 11 1/2" A.F.F. E2 E2 E2
8' - 11 1/2" A.F.F. EXISTING CLG TO REMAIN
E2 E2 E2 E2 E2
GWB
8' - 0" A.F.F. E2 E2 E2 E2
GWB
E2 8' - 6" A.F.F. GWB
7' - 6" A.F.F.
D E2 ACT (Wood Look)
E2 E2 E2 E2 E2 E2 D

M
E2 ACT

O
8' - 11 1/2" A.F.F. 8' - 0" A.F.F. B2
POD C

NR
ACT
ACT

O
E2 E2 8' - 0" A.F.F.
3 E2 E2

E
8' - 6" A.F.F.

ST
E2 E2 E2 B2

RE
E2 E2 X

ET
B E2 E2 E2
PS

GWB ACT
D

8' - 0" A.F.F. B2


POD B
8' - 0" A.F.F.
KITCHEN
B E2 E2 E2
E2 E2 E2
GWB B2
C B 8' - 0" A.F.F. C

GWB B2
8' - 6" A.F.F. E2 E2
CR

EXISTING ACT
LIMITS OF CONSTRUCTION
POD D POD A
8' - 11 1/2" A.F.F. Copyright © 2014. BSSW Architects, Inc.
reserves copyright and other rights
D2401.A-2 restricting these documents to the original
site or purpose for which they were
prepared. Reproductions, changes or
B B assignments are prohibited.
KEY PLAN Sheet Title:

CAFETERIA Brett L. Sands, P.E. SECOND FLOOR POD


Florida License #48477
D PLAN PHASE II -
LIGHTING
Sheet No.
A A
SECOND FLOOR POD D PLAN PHASE II - LIGHTING
E1.01
1
E1.01
1/8" = 1'-0"
Seal

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

C:\Users\mark.hauser\Documents\714124_LCJC 2ND FLR POD D PH II_CENTRAL_R14_mark.hauser.rvt 1/8/2015 8:01:34 AM


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

M M

A R C H I T E C T S I N C
License # AA C001863

1500 Jackson Street, Suite 200


L L Fort Myers, Florida 33901
Phone: 239-278-3838 Fax: 239-275-5356
F4
949 Central Ave.
Naples, Florida 34102
D
Phone: 239-643-3103 Fax: 239-643-7435
LIMITS OF CONSTRUCTION
Project:
D

ELEC/MECH
Lee County
K K
Justice Center
Second Floor
CR Remodel Pod D

D
PS
Part B
CR E-Filing
13 L4
±983 SF Owner:

D
PS
Lee County Board
L4
J J

D
PS
Chair Storage
12 CT CPT L4 L4 of Commissioners

FIX
±380 SF
L4
F2
Consultant:
L4 USB
2 ENLARGED ELEC/MECH ROOM POD D PLAN PHASE II F2
13099 S. Cleveland Ave.
Suite 500
E1.02 USB
1/4" = 1'-0"
UP H
Fort Myers, Florida 33907
H F2 Phone: 239-275-4240
AT 18" Fax: 239-275-3511
USB www.tlc-engineers.com
F USB FS AT 8'-0" © Copyright 2014 TLC Engineering for Architecture, Inc.
Seating Area 2
ETR
Vestibule LIMITS OF CONSTRUCTION 05 EB #0000015 TLC NO: 714124
Men's 10 ±416 SF
11 USB
2 Seal:
E1.02

USB
G G

USB

USB
ELEC/MECH
Women's
09

F F CR F
Project Phase:

Design

D
PS
ETR
"

D
18

Vestibule

PS
"
6
AT

8'-
AT

08
Jury Seating FS
01 Development
±Redundant CR

Room Project #: 0118.22


DPS

DPS
Project Issued: 07/16/13
Sheet Issued:
UP
"
18

"
6

Bailiff Queing
AT

8'-

E E
AT

Area No. Date Revision


FS
02
±353 SF
"
18

" 6
AT

8'-
AT

FS D

F4
D D

M
O
POD C
"
18

NR
"

F4
6
AT

8'-

O
AT

E
FS

ST
Seating Area 1

RE
ET
04
D
±3935 SF
F4
Break/Lounge
D
Jury Staff 15 POD B
C F4
06 C
±712 SF

USB
PS

Bailiff Queing
D
PS

POD D POD A
D

USB Area F4
03 Supervisor's
USB ±397 SF
Office
07 F4
D
GENERAL NOTES: # KEYNOTES: Copyright © 2014. BSSW Architects, Inc.
reserves copyright and other rights
restricting these documents to the original
F4
site or purpose for which they were
±160 SF 1. REFER TO MECHANICAL DRAWINGS FOR EXACT LOCATION OF ALL MECHANICAL 1. 3/4" C WITH (2) #12, (1) #12 GROUND. TERMINATE ON EXISTING prepared. Reproductions, changes or
B F4 20A/2P CIRCUIT BREAKER. B assignments are prohibited.
KEY PLAN
CR
EQUIPMENT.
2. REFER TO ELECTRICAL DETAIL DRAWINGS FOR MOUNTING HEIGHTS OF ALL WALL 2. NEW FIRE ALARM PULL STATION. Sheet Title:

LIMITS OF CONSTRUCTION
3.
MOUNTED ELECTRICAL DEVICES.
PROVIDE CONDUIT/WIRING AS REQUIRED TO MEET CIRCUITING SHOWN TO
3. CEILING MOUNTED SMOKE DETECTORS FOR SMOKE DOORS.
Brett L. Sands, P.E. SECOND FLOOR POD
Florida License #48477
D PLAN PHASE II -
CONFORM TO N.E.C. REQUIREMENTS. PROVIDE EQUIPMENT GROUND CONDUCTOR 4. MAGNETIC DOOR HOLD OPEN DEVICES.
IN ALL RACEWAYS.
5. LOCATION OF EXISTING PANELS.

POWER & SYSTEMS


4. ALL WIRING OVER 100' IN LENGTH SHALL BE #10 AWG.
6. LOCATION OF EXISITNG IDF.
5. ALL NEW FIRE ALARM DEVICES SHALL MATCH EXISTING (3RD FLOOR) TYPE AND BE
COMPATIBLE WITH EXISTING FIRE ALARM SYSTEM. "SIMPLEX - TRUE ALARM" 7. LOCATION OF EXISTING MECHANICAL ROOM.
DEVICE. Sheet No.
A A

E1.02
8. APPROXIMATE LOCATION OF NEW FIRE ALARM DUCT
1 SECOND FLOOR POD D PLAN PHASE II - POWER & SYSTEMS 6. ALL EXISTING CABLE RENDERED "ABANDONED" SHALL BE REMOVED ENTIRELY.
ANY CABLE LEFT IN PLACE (NOT USED) SHALL BE TAGGED WITH LABELS
DETECTORS FOR CONTROL ON NEW FIRE SMOKE DAMPERS.
COORDINATE LOCATION WITH MECHANICAL CONTRACTORS.
E1.02 INDICATING "FUTURE USE" WITH IDENTIFICATION AT BOTH ENDS.
1/8" = 1'-0"
Seal

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

C:\Users\mark.hauser\Documents\714124_LCJC 2ND FLR POD D PH II_CENTRAL_R14_mark.hauser.rvt 1/8/2015 8:01:26 AM


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

M M

1 PANEL "HPx"
WATT STOPPER WA-200 OR
3 APPROVED EQUIVALENT
A R C H I T E C T S I N C
License # AA C001863
BLUE
2 BLACK 1500 Jackson Street, Suite 200
HOT (BLACK) Fort Myers, Florida 33901
L L
BLACK Phone: 239-278-3838 Fax: 239-275-5356
LINE LOAD
277VAC,60Hz 949 Central Ave.
Naples, Florida 34102
GREEN Phone: 239-643-3103 Fax: 239-643-7435
GROUND
NEUTRAL (WHITE) WHITE Project:

PLAN SYMBOL = SO Lee County


K K
Justice Center
NOTES:
PANEL "HPx"
277V,
GROUND
NEUTRAL (WHT) LIGHTING
Second Floor
1
Remodel Pod D
WALL ASSEMBLY - THE 1, 2, 3, OR 4 HOUR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY HOT (BLK) LOAD
60HZ
SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL
U300 OR U400 SERIES WALL OR PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY.

2 CONDUIT - NOM 4" DIA OR SMALLER STEEL ELECTRICAL METALLIC TUBING. A MAX OF ONE CONDUIT IS Part B
PERMITTED IN THE FIRESTOP SYSTEM. CONDUIT TO BE INSTALLED NEAR CENTER OF STUD CAVITY THE NUMBER OF DEVICES POWERED FROM A Owner:
WIDTH AND TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY.
Lee County Board
SINGLE
J POWER PACK VARIES WITH THE TYPE OF DEVICE. J
A SEPARATE POWER PACK IS REQUIRED FOR EACH
of Commissioners
3 FILL VOID OR CAVITY MATERIAL - CAULK FILL MATERIAL BEARING THE UL CLASSIFICATION MARKING
CIRCUIT BEING CONTROLLED.
INSTALLED TO COMPLETELY FILL ANNULAR SPACE BETWEEN PIPE OR CONDUIT AND GYPSUM
WALLBOARD AND WITH A MIN 1/4" DIAM BEAD OF CAULK APPLIED TO PERIMETER OF CONDUIT AT ITS
TYPICAL OVERRIDE SWITCH
EGRESS FROM THE WALL. CAULK INSTALLED SYMMETRICALLY ON BOTH SIDES OF WALL ASSEMBLY. POWER PACK
THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE HOURLY FIRE RATING OF CONTACTS
THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS SHOWN IN THE FOLLOWING TABLE. THE HOURLY T REDRATED FOR 20 AMPS. Consultant:
RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE OF THE CONDUIT AND THE RED
HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS TABULATED BELOW: 13099 S. Cleveland Ave.
BLACK RED 24 VDC Suite 500
BLACK COMMON
WHITE BLUE CONTROL Fort Myers, Florida 33907
H
H CONTROL (BLUE) TO 24 VDC Phone: 239-275-4240
MAX CONDUIT ANNULAR SPACE, F RATING, HR. T RATING, HR. (RED) Fax: 239-275-3511
DIAM, IN. IN. POWER PACK CLOSES OSP CONTACTS. www.tlc-engineers.com
© Copyright 2014 TLC Engineering for Architecture, Inc.
1 0 TO 3/16 1 OR 2 0, 1 OR 2 EB #0000015 TLC NO: 714124
1 1/4 TO 1/2 3 OR 4 3 OR 4
4 0 TO 1-1/2 1 OR 2 0
6 1/4 TO 1/2 3 OR 4 0 PLAN SYMBOL = OS CEILING MOUNTED
DUAL TECHNOLOGY
Seal:
12 3/16 TO 3/8 1 OR 2 0 OCCUPANCY SENSOR

G G

CONDUIT PENETRATION OF FIREWALL 3 TYPICAL OCCUPANCY SENSOR WIRING DIAGRAM 1


UL SYSTEM NO. W-L-1001 No Scale

F F
Project Phase:

Design
Development
CENTERED BETWEEN
DOOR & CEILING
CLOCK OUTLET FIRE HORN (OR CHIME) &
(COORDINATE WITH
WALL MOUNTED LIGHT FIXTURES LIGHT 80" AFF Project #:
AS NOTED ON PLANS h EXIT ARCHITECT)
Project Issued:
0118.22
07/16/13
TELEVISION
BOTTOM TV Sheet Issued:
OUTLET
OF DEVICE
E h E
No. Date Revision

CENTERED OVER DOOR RT REMOTE TEST VOLUME CONTROL VC


(WHERE APPLICABLE) 80"
PANELBOARD
90"
DUPLEX h
RECEPTACLE W
h TELE. OUTLET

h FA PULL F
D D
6" AFC SWITCH STATION 54"

48" DUPLEX
78" MAX. RECEPTACLE
TO TOP DEVICE
1
36" TELE. OUTLET
COMPUTER
AFF OUTLET

h
18"
C AFF C

1 42" A.F.F. W/ 36" COUNTER, FINISHED FLOOR


39" A.F.F. W/ 30" COUNTER, SPECIAL POWER OUTLET
48" A.F.F. WITHOUT COUNTER
OR AS NOTED ON PLANS
Copyright © 2014. BSSW Architects, Inc.
reserves copyright and other rights
restricting these documents to the original
site or purpose for which they were
prepared. Reproductions, changes or
B B assignments are prohibited.

Sheet Title:

MOUNTING HEIGHTS Brett L. Sands, P.E. DETAILS - ELECTRICAL


No Scale
2 Florida License #48477

Sheet No.
A A

Seal
E2.01
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

C:\Users\mark.hauser\Documents\714124_LCJC 2ND FLR POD D PH II_CENTRAL_R14_mark.hauser.rvt 1/8/2015 8:01:19 AM


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

M M

A R C H I T E C T S I N C
License # AA C001863

1500 Jackson Street, Suite 200


L L Fort Myers, Florida 33901
Phone: 239-278-3838 Fax: 239-275-5356

DAMMING 949 Central Ave.


MATERIAL WALL OR FLOOR Naples, Florida 34102
Phone: 239-643-3103 Fax: 239-643-7435
3M #CP-25 FIRE
BARRIER CAULK Project:
CONDUIT BUSHING
Lee County
OR EQUIVALENT
ON EACH END OF SEAL BOTH ENDS OF
PIPE CLAMP CONDUIT SLEEVE AFTER WIRE

Justice Center

~
INSTALLATION
K EACH SIDE K

CABLING
Second Floor
ACCESSIBLE CEILING
Remodel Pod D
Part B
8" KINDORF SECTION Owner:

J
EACH SIDE
J Lee County Board
of Commissioners
NOTE: CONTRACTOR SHALL RESTORE THE INTEGRITY OF RATED WALLS PENETRATED PER SPECIFICATIONS.
1" CONCELED CONDUIT ANY NEW PENETRATIONS SHALL FOLLOW THIS GUIDELINE.

DOUBLE GANG WALL BOX


Consultant:

IF ADDITIONAL SLEEVES ARE NEEDED OR REQUESTED USE FOLLOWING 13099 S. Cleveland Ave.
WALL SLEEVE SIZING TABLE EQUIVALENT TO CAT. 5 CABLES Suite 500
FACEPLATE ADJUST COUNT BASED ON CABLE SIZES Fort Myers, Florida 33907
H
H Phone: 239-275-4240
# OF CABLES SLEEVE SIZE Fax: 239-275-3511
www.tlc-engineers.com
1-8 1" © Copyright 2014 TLC Engineering for Architecture, Inc.
9-14 1 1/4"
EB #0000015 TLC NO: 714124
15-18 1 1/2"
19-26 2"
FLOOR SLAB Seal:
27-40 2 1/2"
41-60 3"
UNLESS OTHERWISE NOTED ON DRAWINGS

G G

TYPICAL FLUSH OUTLET DETAIL 3 HORIZONTAL/VERTICAL PENETRATION DETAIL 1


No Scale No Scale

F F
Project Phase:

Design
Development
IDF# - PP #-PORT#
Project #: 0118.22
Project Issued: 07/16/13
Sheet Issued:
(1) 4PR UTP CAT-
6
E CABLE FROM IDF E
No. Date Revision

(1) RJ45 CAT-6 JACK


MODULE
OR-63750030

SINGLE GANG PP #-PORT#


FACEPLATE
FRAME OR-40300549
D D
CONCRETE ANCHOR
ROOF DECK BAR JOIST
OUTLET DESIGNATOR SELF ADHESIVE LABELS
CLAMP
IDF # : IDF WHERE OUTLET IS CONNECTED TO
PP # : PATCH PANEL IN IDF
PORT #: PORT # ON PATCH PANEL
CAT 6 UTP CABLE

CADDY CABLE CAT-6 J-HOOKS

C C

FOR THE OTHER JACK COUNT IN OUTLET


PROVIDE AS FOLLOWS
# OF RJ45 CAT-6 JACKS # OF UTP CAT-6
# OF JACKS FACE PLATE
OR-63750030 CABLES FROM IDF
F2 OR-40300548 2 2
Copyright © 2014. BSSW Architects, Inc.
F3 OR-40300547 3 3
reserves copyright and other rights
F4 OR-40300546 4 4 restricting these documents to the original
F6 OR-40300545 6 6 site or purpose for which they were
prepared. Reproductions, changes or
B B assignments are prohibited.

Sheet Title:

Brett L. Sands, P.E. DETAILS - ELECTRICAL


CABLE HANGERS 4 TYPICAL DATA OUTLET 2
Florida License #48477
No Scale No Scale

Sheet No.
A A

Seal
E2.02
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

C:\Users\mark.hauser\Documents\714124_LCJC 2ND FLR POD D PH II_CENTRAL_R14_mark.hauser.rvt 1/8/2015 8:01:18 AM


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

M M
SCOPE OF WORK 61G15 FAC COMPLIANCE NOTES FIRE PROTECTION LEGEND GENERAL NOTES
SYMBOL DESCRIPTION
SCOPE OF WORK: THE SPRINKLER CONTRACTOR SHALL RELOCATE EXISTING SPRINKLER HEADS TO ACCOMMODATE (2) ACCEPTANCE TEST CRITERIA IDENTIFIED. 1. FIRE PROTECTION SYSTEM TO COMPLY WITH NFPA 13, 14, 20, 24 AND ALL APPLICABLE STATE
FOR NEW WALL AND CEILING LAYOUT. CONTRACTOR SHALL PROVIDE HYDRAULIC CALCULATION TO VERIFY THAT THE THE ACCEPTANCE TESTING FOR ABOVE GROUND WET-PIPE FIRE SPRINKLER SYSTEM AND ALL RELATED OR - CONTROL VALVE W/TAMPER SWITCH CODES.
SPRINKLER SYSTEM WILL FUNCTION PROPERLY WITH THE NEW SPRINKLER HEAD LAYOUT/ PROVIDE ALL NEW PIPING, COMPONENTS SHALL CONSIST OF ALL APPLICABLE ITEMS SHOWN ON FORMS: NFPA 13, 2002, CHAPTER 16, FIGURE A R C H I T E C T S I N C
FITTINGS AND SPRINKLER HEADS FOR NEW LAYOUT. CONTRACTOR SHALL COORDINATE DOWN-TIME WITH OWNER AND 16.1, CONTRACTOR'S MATERIAL AND TEST CERTIFICATE FOR ABOVEGROUND PIPING, AND NFPA 13, 2002 EDITION, - CHECK VALVE 2. FINAL INSPECTION AND APPROVAL BY LOCAL FIRE MARSHAL AND ARCHITECT/ENGINEER.
THE LOCAL AHJ. CHAPTER 10, FIGURE 10.10.1, CONTRACTOR'S MATERIAL AND TEST CERTIFICATE FOR UNDERGROUND PIPING. NFPA 13,
License # AA C001863
- FLOW SWITCH
2002 “ INSTALLATION OF SPRINKLER SYSTEMS” AND NFPA 24, “INSTALLATION OF PRIVATE FIRE SERVICE MAINS 3. SPRINKLER SHOP DRAWINGS AND MATERIAL SUBMITTALS SHALL BE SUBMITTED TO THE
AND THEIR APPURTENANCES” REQUIREMENTS ARE APPLICABLE IN THEIR ENTIRETY RELATING TO DESIGN, 1500 Jackson Street, Suite 200
FDC - FIRE DEPARTMENT CONNECTION ARCHITECT/ENGINEER AND STATE FIRE MARSHAL AND SHALL BE APPROVED PRIOR TO ANY
L INSTALLATION AND ACCEPTANCE TESTING CRITERIA. L Fort Myers, Florida 33901
PIV - POST INDICATOR VALVE W/TAMPER SWITCH INSTALLATION. Phone: 239-278-3838 Fax: 239-275-5356
(3) STRUCTURAL SUPPORT AND STRUCTURAL OPENINGS REQUIRED BY THE FIRE PROTECTION SYSTEM ARE SHOWN ON
FVC - FIRE VALVE CABINET 4. PIPE ROUTING SHOWN IS SCHEMATIC ONLY. IT IS THE RESPONSIBILITY OF THIS CONTRACTOR 949 Central Ave.
THE DOCUMENTS THE EXISTING STRUCTURAL SUPPORT SYSTEM FOR THIS BUILDING HAS BEEN DESIGNED BY A STATE
OF FLORIDA LICENSED STRUCTURAL ENGINEER IN ACCORDANCE WITH THE FLORIDA ADMINISTRATIVE CODE. NO
TO PROVIDE ANY ADDITIONAL OFFSETS REQUIRED FOR PROPER INSTALLATION AND Naples, Florida 34102
FDV - STANDPIPE WITH FIRE DEPARTMENT VALVE COORDINATION WITH OTHER TRADES.
ADDITIONAL DEAD LOADS ARE REQUIRED FOR THE MODIFICATION OF THIS STANDPIPE SYSTEM. Phone: 239-643-3103 Fax: 239-643-7435
- SPRINKLER AND DRAIN RISER
B) APPLICABLE NFPA STANDARD TO BE APPLIED 5. PIPING IN AREAS WITH EXPOSED STRUCTURE SHALL BE INSTALLED AS HIGH AS POSSIBLE TO
NFPA 13, AND FLORIDA FIRE PREVENTION CODE LATEST EDITION. - BACKFLOW PREVENTOR W/TAMPER SWITCHES Project:
ALLOW THE OWNER MAXIMUM USE OF THE SPACE.

Lee County
(A) POINT OF SERVICE
- ROOF MANIFOLD
THE POINT OF SERVICE IS AN EXISTING 8" SPRINKLER MAIN THAT BEGINS AT THE NEW BACKFLOW THAT 6. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR CEILING DESCRIPTIONS AND
IS LOCATED APPROX. 30' FROM THE BUILDING SPRINKLER RISER. - HYDRAULIC REFERENCE NODE HEIGHTS.
K
(C) CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR AREA
- NEW SPRINKLER PIPING 7. SPRINKLERS ARE TO BE COORDINATED WITH ALL DIFFUSERS, SPEAKERS, LIGHTING FIXTURES
K
Justice Center
Second Floor
F.C. - FLUSHING CONNECTION AND CEILING SYSTEMS. SPACING OF SPRINKLERS SHALL BE IN ACCORDANCE WITH NFPA 13
LIGHT HAZARD: OPEN OFFICE SPACE, RESTROOMS AND CONFERENCE ROOMS AND THE LISTING OF THE SPRINKLER.
ORDINARY HAZARD GROUP 1: STORAGE AREAS, MECHANICAL ROOMS, MATERIAL STORAGE AND - EXISTING \" UPRIGHT SPRINKLER
CONCRETE FASTENER
(U.L. LISTED OR F.M. APPROVED)
ELECTRICAL ROOMS - EXISTING \" RECESSED SPRINKLER
- EXISTING \" CONCEALED SPRINKLER
8. SPRINKLER LOCATIONS SHALL BE CENTERED IN THE TILE. PROVIDE ARMOVER OR SWING JOINT
AS REQUIRED. Remodel Pod D
(D) DESIGN APPROACH:
LIGHT HAZARD : - EXISTING CONTROL VALVE W/TAMPER SWITCH
9. SPRINKLERS IN AREAS WITH EXPOSED STRUCTURE (OBSTRUCTED CONSTRUCTION) SHALL BE
INSTALLED WITH DEFLECTOR 1" BELOW THE BOTTOM OF THE BEAM (MAXIMUM 22" BELOW
Part B
SPRINKLER SYSTEM TO BE ATTACHED AND SUPPLIED FROM SPRINKLER RISER STANDPIPE. SYSTEM SHALL
ALL THREAD ROD ROOF DECK). EXPOSED BAR JOISTS THAT HAVE SPRAY-ON FIRE PROOFING THAT MAKES THE Owner:
BE EXTENDED INTO ENTIRE BUILDING IN ACCORDANCE WITH NFPA-13. U.L, LIGHT HAZARD. LISTED AND - EXISTING SPRINKLER PIPING
J APPROVED UPRIGHTS & PENDANTS (5.6 K-FACTOR) SPRINKLER HEADS TO BE USED. HEADS SHALL BE
- EXISTING SPRINKLER PIPING TO BE REMOVED
JOIST SOLID SHALL BE TREATED LIKE A BEAM WITH THE SPRINKLERS 1" BELOW THE BOTTOM
OF THE FIRE PROOFING. J Lee County Board
RATED AT 155 DEGREES. MAX. SPRINKLER HEAD SPACING SHALL NOT EXCEED 225 SQ FT WITH A .10
DENSITY. SPRINKLER CONTRACTOR SHALL PROVIDE HYDRAULIC CALCULATION. 1500 SQ. FT. SHALL BE - CONNECT TO EXISTING
10. SLEEVE AND/OR FIRESTOP ALL PENETRATIONS THROUGH RATED WALLS, CEILINGS, AND FLOORS
of Commissioners
USED WHEN PERFORMING HYDRAULIC CALCULATION
- DEMOLISH TO POINT INDICATED WITH U/L LISTED ASSEMBLIES. FIRESTOP ASSEMBLIES SHALL BE EQUAL OR EXCEED THE
ORDINARY HAZARD GROUP 1 : RATING OF THE WALL, CEILING OR FLOOR. SEE ARCHITECTURAL DRAWINGS FOR FINAL FINISHES.
1 - REVISION REFERENCE
SPRINKLER SYSTEM TO BE ATTACHED AND SUPPLIED FROM SPRINKLER RISER STANDPIPE. SYSTEM SHALL
BE EXTENDED INTO ENTIRE BUILDING IN ACCORDANCE WITH NFPA-13. U.L, ORDINARY HAZARD. LISTED AND 1
11. PROVIDE ACCESS PANELS TO ALL VALVES ABOVE NON-ACCESSIBLE CEILINGS AND CHASES. Consultant:
- DETAIL REFERENCE: TOP-DETAIL#,
APPROVED UPRIGHTS & PENDANTS (5.6 K-FACTOR) SPRINKLER HEADS TO BE USED. HEADS SHALL BE FP-1 BOTTOM-DRAWING# SHOWN ON 13099 S. Cleveland Ave.
RATED AT 155 DEGREES. MAX. SPRINKLER HEAD SPACING SHALL NOT EXCEED 130 SQ FT WITH A .15 12. PROVIDE A PERMANENTLY ATTACHED NAME TAG TO THE RISER STATING THE REQUIRED DESIGN
CRITERIA FOR EACH HYDRAULICALLY-DESIGNED SYSTEM. Suite 500
DENSITY SPRINKLER CONTRACTOR SHALL PROVIDE HYDRAULIC CALCULATION. 1500 SQ FT SHALL BE
USED WHEN PERFORMING HYDRAULIC CALCULATIONS . NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT H
Fort Myers, Florida 33907
H PIPE HANGER RING 13. PROVIDE SPRINKLERS UNDERNEATH ALL EXPOSED DUCTWORK WHICH IS OVER 48" WIDE AND Phone: 239-275-4240
Fax: 239-275-3511
(U.L. LISTED OR F.M. APPROVED) (F) FLOW TEST DATA: SPRINKLER CONTRACTOR SHALL PROVIDE A CURRENT FLOW TEST
THAT SHALL BE INCLUDED WITH SHOP DRAWING SUBMITTAL. FIRE SPRINKLER LEGEND SPACE HEADS AROUND ALL OBSTRUCTIONS IN ACCORDANCE WITH NFPA 13. HEADS UNDER
DUCTS ARE NOT INDICATED ON THE DRAWINGS BUT ARE REQUIRED AND SHALL BE PROVIDED
IN ACCORDANCE WITH NFPA 13. SPRINKLER LOCATIONS UNDER DUCTWORK AND AROUND
www.tlc-engineers.com
© Copyright 2014 TLC Engineering for Architecture, Inc.

MODEL PLATE OBSTRUCTIONS SHALL BE GOVERNED BY FINAL INSTALLED LOCATIONS. EB #0000015 TLC NO: 714124
(G) VALVING AND ALARM REQUIREMENTS TO MINIMIZE POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED SYMBOL ORF TEMP RESPONSE K-FAC FINISH STYLE MFG.
FLOW OF WATER
14. PROVIDE SPRINKLER GUARDS ON ALL HEADS IN ELECTRIC ROOMS, TELEPHONE ROOMS, Seal:
5.6" 135° QUICK 5.5 CHROME F4FR CONCEALED CHROME RELIABLE
THE EXISTING FIRE SPRINKLER RISER FOR THIS BUILDING IS EQUIPPED WITH A WATER FLOW SWITCH WITH A LOCAL ELEVATOR ROOMS, ELEVATOR SHAFTS AND ON ANY HEADS LESS THAN 7'-0" ABOVE THE
ALARM AND OFF-SITE MONITORING. 5.6" 155° QUICK 5.62 BRASS F1FR UPRIGHT NONE RELIABLE
FLOOR.
5.6" 155° QUICK 5.62 BRASS F1FR UPRIGHT HD/GD RELIABLE
(I) BACKFLOW PREVENTION AND METERING SPECIFICATIONS: 15. IF SYSTEM PRESSURE EXCEEDS 100 PSI, ALL HANGERS ON END HEADS IN PENDANT POSITION
G G
SHALL BE WITHIN 12" OF END OF LINE IN ACCORDANCE WITH NFPA 13.
THE BACKFLOW PREVENTION DEVICE ASSEMBLY AND METERING EQUIPMENT ARE EXISTING AND MEET THE
REQUIREMENTS OF THE LOCAL WATER PURVEYOR. THE MAX. PRESSURE LOSS SHALL NOT EXCEED -8 P.S.I, @
1000 GPM
APPLICABLE CODES AND STANDARDS 16. COORDINATE PIPING WITH ALL ELECTRICAL EQUIPMENT (PANELS, TRANSFORMERS, ETC.) PRIOR
TO ANY INSTALLATION. DO NOT ROUTE ANY PIPING OVER ANY ELECTRICAL PANELS UNDER ANY
FLORIDA BUILDING CODE 2010 EDITION CIRCUMSTANCES. ANY PIPING RUN OVER ELECTRICAL SHALL BE REROUTED AT NO ADDITIONAL
(J) QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD AND INTERIOR FIRE PROTECTION FLORIDA FIRE PREVENTION CODE 2010 EDITION COST.
COMPONENTS FLORIDA ADMINISTRATION CODE 61G15 FAC
HANGER - CONCRETE 2 ALL NEW YARD AND INTERIOR FIRE PROTECTION EQUIPMENT SHALL BE UL LISTED AND FM APPROVED. NFPA 13, 2007 EDITION
NFPA 14, 2007 EDITION
17. SPRINKLERS IN ELEVATOR SHAFTS AND EQUIPMENT ROOMS ARE TO BE INTERMEDIATE
TEMPERATURE 200°F SPRINKLERS PER NFPA 13.
No Scale

F FP - FIRE PROTECTION DRAWING LIST F


Project Phase:
SHEET NUMBER SHEET NAME ISSUED Design
FP0.01 LEGEND, NOTES, INDEX & 61G15 FAC - FIRE PROTECTION
1" SYSTEM
TEE OR ELBOW
FP1.01 SECOND FLOOR POD D PLAN PHASE II - FIRE PROTECTION Development
Project #: 0118.22
Project Issued: 07/29/13
Sheet Issued:

E E
No. Date Revision

BRANCH LINE
1" NPT MALE
D COUPLING D
INLET MAX. REDUCER
ADJUSTMENT
1" NIPPLE

4 7/8" ± 3/4"
FACE OF FITTING
TO FACE OF 1" 90° ELL 1" 90° ELL
CEILING DIMENSION

1" DROP
C REDUCER C
CEILING

SPRINKLER HEAD
Copyright © 2014. BSSW Architects, Inc.
reserves copyright and other rights
restricting these documents to the original
site or purpose for which they were
3/16" prepared. Reproductions, changes or
B MAX. COVER B assignments are prohibited.
ADJUSTMENT
Sheet Title:

Lawrin T. Ellis, P.E. LEGEND, NOTES,


Florida License #66383
SPRINKLER HEAD DETAIL 3 SWING JOINT 1 INDEX & 61G15 FAC -
No Scale No Scale FIRE PROTECTION
Sheet No.
A A

Seal
FP0.01
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

C:\Users\mark.hauser\Documents\714124_LCJC 2ND FLR POD D PH II_CENTRAL_R14_mark.hauser.rvt 1/8/2015 8:01:17 AM


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

M M

A R C H I T E C T S I N C
License # AA C001863
LIMITS OF CONSTRUCTION
1500 Jackson Street, Suite 200
L L Fort Myers, Florida 33901
Phone: 239-278-3838 Fax: 239-275-5356

949 Central Ave.


Naples, Florida 34102
Phone: 239-643-3103 Fax: 239-643-7435

Project:

Lee County
K K
Justice Center
Second Floor
Remodel Pod D
ACT
8' - 6" A.F.F.
Part B
Owner:

J J Lee County Board


LIMITS OF CONSTRUCTION of Commissioners

Consultant:
GWB 13099 S. Cleveland Ave.
GWB 8' - 0" A.F.F. GWB
8' - 0" A.F.F. 8' - 0" A.F.F. Suite 500
ACT
8' - 6" A.F.F. H
Fort Myers, Florida 33907
H Phone: 239-275-4240
Fax: 239-275-3511
www.tlc-engineers.com
ACT (Wood Look) © Copyright 2014 TLC Engineering for Architecture, Inc.
8' - 11 1/2" A.F.F. EB #0000015 TLC NO: 714124
OPEN OFFICE AREA

GWB
GWB ACT 8' - 6" A.F.F. Seal:
8' - 0" A.F.F. 8' - 6" A.F.F.

ACT (Wood Look)


G
8' - 11 1/2" A.F.F. G
GWB
8' - 0" A.F.F.
LIGHT HAZARD GWB LIGHT HAZARD
8' - 0" A.F.F.
ACT (Wood Look)
ACT (Wood Look) 8' - 11 1/2" A.F.F.
GWB NEW UPRIGHT
8' - 0" A.F.F. 8' - 11 1/2" A.F.F. GWB
SPRINKLER HEAD
LOCATION TYP. 8' - 0" A.F.F.

GWB
GWB GWB 8' - 0" A.F.F.
ACT (Wood Look) 8' - 6" A.F.F. 8' - 0" A.F.F.
F 8' - 11 1/2" A.F.F. F
Project Phase:

Design
GWB ACT
8' - 0" A.F.F. 8' - 6" A.F.F.
GWB
GWB
8' - 6" A.F.F.
8' - 6" A.F.F.
GWB
8' - 0" A.F.F.
GWB
8' - 0" A.F.F.
Development
GWB Project #: 0118.22
ACT (Wood Look) 8' - 0" A.F.F. Project Issued: 07/29/13
8' - 11 1/2" A.F.F. ACT (Wood Look) Sheet Issued:
8' - 11 1/2" A.F.F. ACT ACT
8' - 11 1/2" A.F.F. 8' - 6" A.F.F.
E E
No. Date Revision
GWB
8' - 6" A.F.F. OPEN OFFICEGWB
AREA
8' - 6" A.F.F.
NEW UPRIGHT
ACT (Wood Look) SPRINKLER HEAD
8' - 11 1/2" A.F.F. ACT LOCATION TYP.
8' - 11 1/2" A.F.F.

GWB
8' - 0" A.F.F.
GWB
8' - 6" A.F.F. GWB
D 7' - 6" A.F.F. D
LIGHT HAZARD LIGHT HAZARD

M
O
ACT (Wood Look) ACT
POD C

NR
8' - 11 1/2" A.F.F. 8' - 0" A.F.F.

O
ACT
ACT

E
8' - 0" A.F.F.

ST
8' - 6" A.F.F.

RE
ET
GWB ACT
8' - 0" A.F.F.
NEW UPRIGHT
8' - 0" A.F.F.
POD B
C GWB SPRINKLER HEAD C
8' - 0" A.F.F. LOCATION TYP.

GWB
8' - 6" A.F.F.

LIMITS OF CONSTRUCTION POD D POD A


ACT Copyright © 2014. BSSW Architects, Inc.
8' - 11 1/2" A.F.F. reserves copyright and other rights
restricting these documents to the original
D2401.A-2 site or purpose for which they were
prepared. Reproductions, changes or
B B assignments are prohibited.

KEY PLAN Sheet Title:

Lawrin T. Ellis, P.E. SECOND FLOOR POD


Florida License #66383
D PLAN PHASE II -
FIRE PROTECTION
Sheet No.
A A

1
FP1.01
SECOND FLOOR POD D PLAN PHASE II - FIRE PROTECTION
1/8" = 1'-0"
Seal
FP1.01
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

C:\Users\mark.hauser\Documents\714124_LCJC 2ND FLR POD D PH II_CENTRAL_R14_mark.hauser.rvt 1/8/2015 8:01:15 AM


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

M
MECHANICAL SYMBOL LEGEND MECHANICAL ABBREVIATIONS PLUMBING GENERAL NOTES HVAC GENERAL NOTES M
SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION
1. FIELD VERIFY EXISTING INSTALLATIONS. MODIFY EXISTING PLUMBING SYSTEMS, WHICH ARE TO 1. CONNECTION TO EQUIPMENT SHALL BE VERIFIED WITH MANUFACTURER'S CERTIFIED
REMAIN ACTIVE, TO FACILITATE RECONNECTION AND EXTENSION OF THE NEW WORK. DRAWINGS. TRANSITIONS TO ALL EQUIPMENT SHALL BE VERIFIED AND PROVIDED
-CEILING DIFFUSER, ROUND NECK AFD -ADJUSTABLE FREQUENCY DRIVE LD -LINEAR DIFFUSER FOR EQUIPMENT FURNISHED.
(CEILING DIFFUSERS ARE 4-WAY THROW UNO) -FLEXIBLE DUCT 2. NOTIFY OWNER AT LEAST 24 HOURS PRIOR TO INTERRUPTING EXISTING SERVICE. SCHEDULE
AFF -ABOVE FINISHED FLOOR MBH -THOUSAND BTUs PER HOUR DISCONNECTION AND TIE-INS TO MINIMIZE DISRUPTION OF SERVICES. SERVICES ARE NOT TO BE 2. DIMENSIONS SHALL BE FIELD-VERIFIED AND COORDINATED PRIOR TO PROCUREMENT OR
AFR -ABOVE FINISHED ROOF MCA -MINIMUM CIRCUIT AMPS LEFT DISRUPTED DURING NON-NORMAL CONTRACTOR WORKING HOURS. FABRICATION. COORDINATE THE WORK WITH OTHER TRADES INVOLVED. FIELD MODIFICATIONS A R C H I T E C T S I N C
-REVISION REFERENCE -TRANSITION, CONCENTRIC SUCH AS OFFSETS IN PIPING OR DUCTWORK (INCLUDING DIVIDED DUCTWORK) NEEDED DUE TO
1 AHU -AIR HANDLING UNIT MOCP -MAXIMUM OVER CURRENT PROTECTION 3. PIPE ROUTING SHOWN IS SCHEMATIC AND IS NOT INTENDED TO INDICATE EXACT ROUTING AND OBSTRUCTIONS OR INTERFERENCES SHALL BE PROVIDED AT NO ADDITIONAL COST. FOR PROJECTS License # AA C001863
1 AP -ACCESS PANEL ANY ADDITIONAL OFFSETS AND FITTINGS REQUIRED FOR PROPER INSTALLATION AND TO INVOLVING RENOVATION, COORDINATE NEW WORK WITH EXISTING ELEMENTS SUCH AS THE
-DETAIL REFERENCE: TOP-DETAIL#, MOD -MOTOR OPERATED CONTROL DAMPER (MOD) 1500 Jackson Street, Suite 200
MAINTAIN CLEARANCES. VERIFY STRUCTURAL, MECHANICAL AND ELECTRICAL INSTALLATIONS BUILDING STRUCTURE AND ARCHITECTURAL FEATURES, SPRINKLER PIPING, LIGHTS, PLUMBING, AND
M-1 BOTTOM-DRAWING# SHOWN ON -TRANSITION, ECCENTRIC BOP Fort Myers, Florida 33901
L -BOTTOM OF PIPE NC -NORMALLY CLOSED AND OTHER POTENTIAL OBSTRUCTIONS AND ROUTE PIPING TO AVOID INTERFERENCES. ELECTRICAL CONDUIT. L
Phone: 239-278-3838 Fax: 239-275-5356
T -THERMOSTAT/TEMPERATURE SENSOR BHP -BRAKE HORSEPOWER NO 4. CONCEAL PIPING ABOVE CEILINGS, WITHIN WALLS OR CHASES EXCEPT IN MECHANICAL ROOMS 3. DUCT CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE
-NORMALLY OPEN
10x8 8Ø -TRANSITION, SQUARE TO ROUND BTU -BRITISH THERMAL UNIT OR AS SPECIFICALLY NOTED. PROVIDE ACCESS PANELS FOR ALL VALVES CONCEALED IN SMACNA HVAC DUCT CONSTRUCTION STANDARD. 949 Central Ave.
-DUCT SMOKE DETECTOR NTS -NOT TO SCALE WALLS OR ABOVE NON-ACCESSABLE CEILINGS. Naples, Florida 34102
h -CENTER LINE OA 4. SEE SPECIFICATIONS FOR GAUGES, THICKNESS, BRACING, REQUIREMENTS, ETC., OF DUCTWORK. Phone: 239-643-3103 Fax: 239-643-7435
-OUTSIDE AIR
-CONNECT TO EXISTING c 5. SLEEVE AND FIRE STOP PENETRATIONS OF RATED WALLS, FLOORS, CEILINGS AND ROOFS.
-SQUARE THROAT TEE -CFM (CUBIC FEET PER MINUTE) OAL -OUTSIDE AIR LOUVER FLASH AND COUNTERFLASH ROOF PENETRATIONS. 5. PROVIDE AIR TURNING VANES IN ALL 90 DEGREE RECTANGULAR DUCT ELBOWS.
Project:
-DEMOLISH TO POINT INDICATED CD -CEILING DIFFUSER PRV -PRESSURE REDUCING VALVE

Lee County
6. WHEN BEAM SLEEVE PENETRATIONS ARE NECESSARY, COORDINATE PENETRATIONS WITH ALL 6. DUCT SIZES AND ALL OPENINGS THROUGH BUILDING CONSTRUCTION SHALL SUIT EQUIPMENT
CT -COOLING TOWER PRS TRADES, THE ARCHITECT AND THE STRUCTURAL ENGINEER. FURNISHED.
1 -SHEET NOTE CALLOUT -PRESSURE REDUCING STATION
CV -CONSTANT AIR VOLUME

Justice Center
PSI -POUNDS PER SQUARE INCH 7. SEE ARCHITECTURAL DRAWINGS FOR FIXTURE LOCATIONS AND MOUNTING HEIGHTS. 7. COORDINATE DIFFUSER, GRILLE AND REGISTER LOCATIONS WITH ARCHITECTURAL
K P -CHANGE IN PRESSURE ALL EXPOSED PIPE AND FITTINGS IN FINISHED AREAS SHALL BE CHROME PLATED. REFLECTED CEILING PLANS AND EQUIPMENT OF ALL TRADES. K
PSIG -PSI GAUGE
-SQUARE THROAT ELBOW

Second Floor
T -CHANGE IN TEMPERATURE PTAC 8. PROVIDE CLEANOUTS IN ACCORDANCE WITH APPROPRIATE CODES AND REGULATIONS. 8. LOCATE THERMOSTATS, TEMPERATURE SENSORS, HUMIDISTATS, AND HUMIDITY SENSORS AT 48"
W/TURNING VANES -RECTANGLE-TO-ROUND TAKE-OFF -PACKAGED TERMINAL AIR CONDITIONER
CFM ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE. COORDINATE LOCATIONS WITH OTHER
-CUBIC FEET PER MINUTE PVC -POLYVINYL CHLORIDE PIPE 10. COORDINATE PIPING WITH ALL ELECTRICAL EQUIPMENT(PANELS, TRANSFORMERS, ETC.) PRIOR EQUIPMENT, FURNITURE, AND DOOR SWINGS.

-RADIUS ELBOW -STANDARD BRANCH TAKE-OFF


CU
DDC
-CONDENSING UNIT
-DIRECT DIGITAL CONTROLS
RA
RHC
-RETURN AIR
-REHEAT COIL
TO ANY INSTALLATION. DO NOT ROUTE ANY PIPING OVER ANY ELECTRICAL PANELS UNDER ANY
CIRCUMSTANCES. ANY PIPING RUN OVER PANELS SHALL BE REROUTED AT NO ADDITIONAL COST. 9. ALL EQUIPMENT, DUCTWORK, ETC., SHALL BE SUPPORTED AS DETAILED AND/OR SPECIFIED. PROVIDE
ADDITIONAL SUPPORTS AS REQUIRED TO PROVIDE A VIBRATION-FREE, RIGID INSTALLATION.
Remodel Pod D
-SPIN-IN TAKE-OFF
DN
EAT
-DOWN RHP -ROOFTOP HEAT PUMP 10. ALL DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS. Part B
-ENTERING AIR TEMPERATURE RPM
-RECTANGULAR/ROUND BRANCH TAKE-OFF -REVOLUTIONS PER MINUTE
11. DAMPERS AND INSIDES OF DUCTS VISIBLE THROUGH GRILLES, REGISTERS AND DIFFUSERS SHALL BE Owner:

Lee County Board


ESP -EXTERNAL STATIC PRESSURE
OR ROUND/ROUND BRANCH TAKE-OFF RS/L -REFRIGERANT SUCTION & LIQUID LINES PAINTED FLAT BLACK.
J J
EWT -ENTERING WATER TEMPERATURE
of Commissioners
RTU -ROOFTOP AIR HANDLING UNIT 12. REFER TO TYPICAL DETAILS FOR PIPING AND INSTALLATION OF EQUIPMENT.
FCU -FAN COIL UNIT SA -SUPPLY AIR
-FIRE DAMPER 13. ACCESS PANELS IN DUCTWORK AND CEILINGS SHALL BE PROVIDED WHERE REQUIRED FOR
(WITH ACCESS PANEL) FD -FIRE DAMPER SP -STATIC PRESSURE OPERATION, BALANCING OR MAINTENANCE OF ALL MECHANICAL EQUIPMENT.
F/S FF -FINAL FILTERS TAD -TRANSFER AIR DUCT
14. ALL DUCTWORK AND PIPING IS SHOWN SCHEMATICALLY. PROVIDE ALL TRANSITIONS, TURNING
-FIRE & SMOKE DAMPER FLA TSP Consultant:
-FULL LOAD AMPS -TOTAL STATIC PRESSURE VANES, ELBOWS, FITTINGS, ETC., TO ALLOW SMOOTH FLOWS. ALL SPLIT DUCT FITTINGS SHALL
(WITH ACCESS PANEL)
TRANSITION TO FULL SIZE OF THE SUM OF BOTH BRANCHES, UPSTREAM OF SPLIT.
FPM -FEET PER MINUTE UNO -UNLESS NOTED OTHERWISE 13099 S. Cleveland Ave.
15. VERIFY FINISH WITH ARCHITECT PRIOR TO PURCHASING GRILLES, REGISTERS, DIFFUSERS, LOUVERS Suite 500
GPM -GALLONS PER MINUTE V/PH -VOLTS/PHASE
AND OTHER AIR DISTRIBUTION DEVICES. H
Fort Myers, Florida 33907
-MANUAL BALANCING DAMPER KW
H -KILOWATT VAV -VARIABLE AIR VOLUME Phone: 239-275-4240
16. PROVIDE FLEXIBLE DUCT CONNECTIONS ON ALL DUCTWORK CONNECTING TO EACH FAN, AIR Fax: 239-275-3511
LAT -LEAVING AIR TEMPERATURE VFD HANDLING UNITS, AND FAN COIL UNITS. www.tlc-engineers.com
UC

-UNDERCUT DOOR -VARIABLE FREQUENCY DRIVE


LWT -LEAVING WATER TEMPERATURE © Copyright 2014 TLC Engineering for Architecture, Inc.
17. PROVIDE TRANSITIONS AT DIFFUSER NECKS AS REQUIRED TO MATCH SIZES OF FLEX DUCTS TO BE
EB #0000015 TLC NO: 714124
CONNECTED.
24x12 -NEW DUCTWORK, FIRST DIMENSION IS SIDE SHOWN
18. INTERRUPTIONS TO EXISTING SERVICES SHALL BE SCHEDULED FOR TIMES OTHER THAN NORMAL
OPERATING HOURS (SUCH AS NIGHTS AND WEEKENDS). SUCH INTERRUPTIONS TO SERVICES SHALL Seal:
24x12 -EXISTING DUCTWORK TO REMAIN NOT BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER'S REPRESENTATIVE AND
PROPER COORDINATION WITH OTHER TRADES. PRE-WORK SHALL BE PERFORMED TO MAKE THE
24x12 -EXISTING DUCTWORK TO BE REMOVED SHUTDOWN PERIOD AS BRIEF AS POSSIBLE.

G 24x12 19. ALL EQUIPMENT, DUCTWORK, ETC., TO BE REMOVED SHALL REMAIN PROPERTY OF THE OWNER OR G
-DUCT ELBOW, POSITIVE PRESSURE (SUPPLY), FIRST DISPOSED OF LEGALLY, AS DIRECTED BY OWNER.
DIMENSION INDICATES SIDE TO WHICH ARROW IS
UP W/IN FLOOR POINTING 20. MAINTAIN CLEARANCE OF A MINIMUM OF 6" BETWEEN DUCTWORK, PIPING, EQUIPMENT, ETC., AND ALL
DOWN
FIRE RATED AND FIRE/SMOKE RATED PARTITIONS, TO ALLOW FOR INSPECTIONS OF RATED WALLS.
-DUCT ELBOW, NEGATIVE PRESSURE, RETURN
21. DUCT RUNOUTS TO DIFFUSERS SHALL MATCH THE SIZE OF THE DIFFUSER NECK.

-DUCT ELBOW UP THROUGH ROOF OR SLAB ABOVE 22. SLEEVE AND SEAL ALL PIPING PENETRATIONS THROUGH BUILDING PARTITIONS.

23. PIPING, DUCTWORK, LEAK PROTECTION APPARATUS, OR OTHER EQUIPMENT FOREIGN TO ELECTRICAL
SWITCHBOARDS, PANELBOARDS, DISTRIBUTION BOARDS, OR MOTOR CONTROL CENTERS SHALL NOT
-VOLUME WITH ELECTRIC HEAT BE INSTALLED WITHIN THE REQUIRED SPACE FOR WORKING CLEARANCES OR DEDICATED SPACES OF
F THE ELECTRICAL EQUIPMENT, EXTENDING IN FRONT OF AND FROM FLOOR TO STRUCTURAL CEILING F
Project Phase:

Design
WITH A WIDTH AND DEPTH OF THE ELECTRICAL EQUIPMENT IN ACCORDANCE WITH NEC-110.26.

Development
Project #: 0118.22
Project Issued: 07/10/13
Sheet Issued:

E MECHANICAL PIPING SYMBOL LEGEND E


No. Date Revision

SYMBOL DESCRIPTION

- DOMESTIC COLD WATER


- ABOVE GROUND SANITARY
- SANITARY VENT

D
- BALL VALVE
HVAC EQUIPMENT TAGS MECHANICAL DRAWING INDEX D
-VALVE ON RISER Sheet Number Sheet Name Issued
TAG
-CAP M0.01 LEGEND, GENERAL NOTES AND INDEX - MECHANICAL
A 200 -AIR DISTRIBUTION DEVICE M1.01 SECOND FLOOR POD D PLAN PHASE II - MECHANICAL
-CONNECTION, BOTTOM
CFM
M3.01 MECHANICAL DETAILS AND SCHEDULES
-CONNECTION, TOP
M6.01 MECHANICAL SPECIFICATIONS
-COUPLING
AHU NUMBER
-ELBOW, 90°
C AHU-1 -AIR HANDLING UNIT C
-ELBOW, 45°

Copyright © 2014. BSSW Architects, Inc.


reserves copyright and other rights
restricting these documents to the original
site or purpose for which they were
prepared. Reproductions, changes or
B B assignments are prohibited.

Sheet Title:

Lawrin T. Ellis, P.E. LEGEND, GENERAL


Florida License #66383
NOTES AND INDEX -
MECHANICAL
Sheet No.
A A

Seal
M0.01
1 2 3 4
NOTE: SOME SYMBOLS SHOWN5ON THIS LEGEND MAY NOT PERTAIN
6 TO THIS PROJECT 7 8 9 10 11 12 13 14 15 16

C:\Users\mark.hauser\Documents\714124_LCJC 2ND FLR POD D PH II_CENTRAL_R14_mark.hauser.rvt 1/8/2015 8:01:09 AM


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

M M

A R C H I T E C T S I N C
LIMITS OF CONSTRUCTION License # AA C001863

1500 Jackson Street, Suite 200


L L Fort Myers, Florida 33901
Phone: 239-278-3838 Fax: 239-275-5356

949 Central Ave.


Naples, Florida 34102
Phone: 239-643-3103 Fax: 239-643-7435

Project:

E-Filing Lee County


Justice Center
13
K K
±983 SF

Chair Storage
Second Floor
12
±380 SF
CT CPT
Remodel Pod D
Part B
Owner:

J J Lee County Board


LIMITS OF CONSTRUCTION
UP of Commissioners

Seating Area 2
Vestibule 05 Consultant:
Men's 10 ±416 SF 13099 S. Cleveland Ave.
11 EX. 66X12 RA
Suite 500
H
Fort Myers, Florida 33907
H Phone: 239-275-4240
Fax: 239-275-3511
www.tlc-engineers.com
© Copyright 2014 TLC Engineering for Architecture, Inc.
EB #0000015 TLC NO: 714124

Seal:

Women's
G 09 G

Vestibule
08
Jury Seating
01
±Redundant
Room

F EX. 44X14 SA EX. 48X14 SA F


UP Project Phase:
Bailiff Queing
Design
EX. 40X14 SA

Area
02
±353 SF Development
Project #: 0118.22
Project Issued: 07/11/13
Sheet Issued:

E E
No. Date Revision
EX. 30X14 SA

Seating Area 1
04
±3935 SF
D Break/Lounge D

M
O
Jury Staff 15
POD C

NR
06

O
E
±712 SF

ST
RE
ET
EX. 18X10 SA

Bailiff Queing
Area
03
±397 SF
Supervisor's
Office POD B
C 24X12 TAD 07 C
±160 SF

POD D POD A
Copyright © 2014. BSSW Architects, Inc.
reserves copyright and other rights
restricting these documents to the original
LIMITS OF CONSTRUCTION site or purpose for which they were
prepared. Reproductions, changes or
B B assignments are prohibited.
KEY PLAN Sheet Title:

Lawrin T. Ellis, P.E. SECOND FLOOR POD


Florida License #66383
D PLAN PHASE II -
MECHANICAL
Sheet No.
A A

1
M1.01
SECOND FLOOR POD D PLAN PHASE II - MECHANICAL
1/8" = 1'-0"
Seal
M1.01
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

C:\Users\mark.hauser\Documents\714124_LCJC 2ND FLR POD D PH II_CENTRAL_R14_mark.hauser.rvt 1/8/2015 8:01:07 AM


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

PLUMBING FIXTURE SCHEDULE


FIXTURE TRIM
M FLOW RATE / M
MARK TYPE MANUFACTURER MODEL MANUFACTURER MODEL FLUSH RATE SPECIFICATIONS / ACCESSORIES
EWC-1 ELECTRIC WATER COOLER ELKAY EMABFTL(VR) DUAL HEIGHT ADA DRINKING FOUNTAIN WITH STAINLESS STEEL BASIN AND PANELS, MECHANICALLY
(ACCESSIBLE) 8SC ACTIVATED FRONT AND SIDE PUSHBARS . ELECTRICAL CHARACTERISTICS: 115V AC, 370W, 60 HZ, SINGLE
PHASE.
A R C H I T E C T S I N C
License # AA C001863
AIR DISTRIBUTION SCHEDULE
1500 Jackson Street, Suite 200
L CFM L Fort Myers, Florida 33901
MARK NECK SIZE FACE SIZE DESCRIPTION Phone: 239-278-3838 Fax: 239-275-5356
MIN MAX LENGTH
949 Central Ave.
A 0 110 6Ø 24x24 SUPPLY DIFFUSER
Naples, Florida 34102
REUSE SALVAGED SUPPLY LOUVER
115 250 8Ø 24x24 Phone: 239-643-3103 Fax: 239-643-7435
COLOR: WHITE
24X24 MODULE SIZE
Project:
B 0 500 N/A 24x24 RETURN GRILLE
TITUS 350RL
COLOR: WHITE Lee County
K
NOTES:

1. SELECT UNDAMAGED DEVICES FROM THOSE REMOVED DURING DEMOLITION. THROUGHLY CLEAN EACH UNIT BEFORE INSTALLATION.
K
Justice Center
Second Floor
EXISTING VAV UNIT SCHEDULE
Remodel Pod D
Nominal Design Air Min. Air Heating Air Static Part B
Mark Inlet Size Flow Flow Flow Pressure Owner:

J
VAV 232C 0' - 6" 360 CFM 225 CFM 225 CFM 0.25 in-wg J Lee County Board
VAV 234C 0' - 6" 360 CFM 225 CFM 225 CFM 0.25 in-wg
of Commissioners

Consultant:

13099 S. Cleveland Ave.


Suite 500
H
Fort Myers, Florida 33907
H Phone: 239-275-4240
Fax: 239-275-3511
www.tlc-engineers.com
© Copyright 2014 TLC Engineering for Architecture, Inc.
EB #0000015 TLC NO: 714124

Seal:

G G

F RETAINING ANGLES 1-1/2"x 1-1/2"x 1/8" MIN. ALL F


SIDES (SEE NOTE #2) Project Phase:

Design
FIRE RESISTIVE MATERIAL (TYP.)

MANUFACTURER OR FIELD FABRICATED


STEEL SLEEVE 16 GA. MIN.
Development
CAULKING (TYP. OF 2) Project #: 0118.22
NOTE #5
Project Issued: 07/12/13
DUCT MOUNTED SMOKE DETECTOR
TO BE INSTALLED WITHIN 5'-0" OF EXTENDED OPERATOR Sheet Issued:
165°F FUSIBLE LINK
DAMPER PER MANUFACTURER'S SPIN-IN FITTING ON BALANCE DAMPER
E RECOMMENDATIONS, WITH NO AIR W/VOLUME E
WRAPPED SHEET METAL DUCT INLETS OR OUTLETS BETWEEN THE No. Date Revision
CONTROL DAMPER (INSUL.
DETECTOR AND THE DAMPER. PER SPEC.) DRAW BAND
U.L. (555S) LABELED FIRE/SMOKE DAMPER,
SECURE TO SLEEVE

NOTE #1
CLEARANCE 1/8" PER LINEAR FOOT
BOTH DIMENSIONS. FLEXIBLE DUCT MAX.
PLAIN "S" SLIP (TYP.) BREAK-AWAY 8'-0" IN LENGTH 1. Wall Assembly — The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be
CONNECTION FULLY EXTENDED. constructed of the materials and in the manner specified in the individual U400 or V400
DUCT WRAP W/VAPOR BARRIER Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the
D (TYP.) 1A following construction features: D
CLOSURE TAPE A A. Studs — Wall framing may consist of steel channel studs. Steel studs to be min 3-1/2 in.
MOUNTING ANGLE 1" MIN. 6" MAX. 3A 3A
OVERLAP ALL SIDES. 2 (89 mm) wide and spaced max 24 in. (610 mm) OC. Additional steel studs shall be used to
METAL STUD CONSTRUCTION completely frame the opening.
B. Wallboard, Gypsum* — Thickness, type, number of layers and fasteners as required in
the individual Wall and Partition Design. Max size of opening is 9,800 in2 (6.32 m2) with a
NOTES: max dimension of 100 in. (254 cm).
The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall
1. PROVIDE ACCESS DOOR & LABEL ON SIDE OR BOTTOM OF DUCT AS FOLLOWS: assembly in which it is installed.
DUCT WIDTH DOOR SIZE 2. Steel Duct — Nom 96 by 96 in. (244 by 244 cm, or smaller) galv steel duct to be installed
DRAW BAND within the opening. The duct shall be constructed and reinforced in accordance with
10" THRU 12" 8"X8"
14" THRU 20" 12"X12" SMACNA construction standards and provided with 2 in. (51 mm) standing seams. The
22" AND ABOVE 18"X18" BLANK-OFF PLATES annular space between the duct and the periphery of opening shall be a min 1 in.(25 mm) to
C WHERE REQUIRED DIFFUSER NECK (INSUL. PER SPEC.) a max 2 in. (51 mm) with the exception that the standing seams which shall be installed at C
2. 1-1/2" x 1-1/2" x 1/8" RETAINING ANGLES SHALL LAP STRUCTURAL OPENING 1" MIN. & COVER CORNERS OF OPENINGS. ANGLES ATTACH TO SLEEVE point contact to the framing of the opening. Duct to be rigidly supported on both sides of
CEILING TEE DIFFUSER CONE (INSUL. PER SPEC.) A 3B 3B 1B opening.
ONLY AND MUST NOT BE ATTACHED TO EACH OTHER AT CORNERS OR TO WALL.
The hourly T Rating of the firestop system is 0 hr except that when the thickness of the steel
3. ALL ATTACHMENTS PER MANUFACTURER'S APPROVED INSTALLATION INSTRUCTION. SECTION A-A duct is 18 ga, the T Rating is ¾ hr.
3. Firestop System — The firestop system shall consist of the following.
4. VERTICAL POSITION SHOWN. HORIZONTAL INSTALLATION SIMILAR. A. Fill, Void or Cavity Material* - Intumescent Caulk or Sealant — Min 5/8 in. (16 mm)
thickness of caulk applied within annulus, flush with both surfaces of wall assembly.
5. ACTUATOR TO BE MOUNTED ON OUTSIDE OF DAMPER SLEEVE ON ACCESIBLE SIDE. ACTUATOR SHALL NOT INTERFERE WITH "S" JOINT. ACTUATOR B. Steel Retaining Angles — Min 16 gauge galv steel angles sized to lap duct a min of 2 in. Copyright © 2014. BSSW Architects, Inc.
ASSEMBLY TO BE U.L. LABELED. (51 mm) and lap wall surface a min of 1 in. (25 mm). Angles attached to the duct on both reserves copyright and other rights
sides of wall with No. 10 (or larger) steel sheet metal screws 1 in. (25 mm) from each end, restricting these documents to the original
and 6 in. (152 mm) OC. On the opposite side of wall, the screw pattern to be staggered. site or purpose for which they were
6. VERIFY THAT ACCESS IS PROVIDED ON THE ACTUATOR SIDE OF THE WALL/FLOOR SO THAT THE LINK MAY BE SERVICED WITH THE DAMPER IN prepared. Reproductions, changes or
LIGHT *Bearing the UL Classification Mark
B CLOSED POSITION. B assignments are prohibited.

Sheet Title:

FIRE & SMOKE DAMPER INSTALLATION DIFFUSER MOUNTING 1 HOUR WALL - DUCT PENETRATION DETAIL Lawrin T. Ellis, P.E. MECHANICAL DETAILS
3 2 1 Florida License #66383
No Scale No Scale No Scale
AND SCHEDULES

Sheet No.
A A

Seal
M3.01
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

C:\Users\mark.hauser\Documents\714124_LCJC 2ND FLR POD D PH II_CENTRAL_R14_mark.hauser.rvt 1/8/2015 8:01:02 AM


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

HVAC SPECIFICATIONS: HVAC SPECIFICATIONS: (CONT.) FIRE PROTECTION SPECIFICATIONS: PLUMBING SPECIFICATIONS:
1.00 - GENERAL PROVISIONS 1.00 - GENERAL PROVISIONS
2.7 SHEET METAL DUCT INSULATION 1.00 - GENERAL PROVISIONS
M M
1.1 SUMMARY A. ALL PRODUCTS, INCLUDING VAPOR BARRIERS AND ADHESIVES, SHALL CONFORM TO NFPA
A. PROVIDE ALL LABOR AND MATERIALS NECESSARY FOR COMPLETE AND OPERATIONAL 90A. FOR ALL PRODUCTS, THE FLAME SPREAD RATING SHALL NOT EXCEED 25 AND THE SMOKE 1.1 PROVIDE ALL LABOR, MATERIAL AND EQUIPMENT FOR A COMPLETE AND PROPERLY 1.1 PROVIDE ALL LABOR, MATERIAL AND EQUIPMENT FOR A COMPLETE AND PROPERLY
HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS. DEVELOPED RATING SHALL NOT EXCEED 50. OPERATING FIRE PROTECTION SYSTEM. OPERATING PLUMBING SYSTEM.

1.2 EXAMINATION OF DOCUMENTS B. DUCT INSULATION SHALL BE A MINIMUM 1-INCH THICK, 1-1/2 LB. DENSITY FIBERGLASS 1.2 CODES AND STANDARDS: THE FIRE SPRINKLER PROTECTION SYSTEMS INSTALLATION, 1.2 CODES AND STANDARDS: ALL PLUMBING WORK SHALL BE IN STRICT COMPLIANCE WITH
A. THE INTENT OF THE DRAWINGS AND SPECIFICATIONS IS TO ESTABLISH TYPE AND QUALITY OF BLANKET; MAXIMUM THERMAL CONDUCTIVITY OF 0.31 BTUH/°F/SQ.FT. AT 75 DEG F WITH FACTORY FLUSHING AND TESTING SHALL COMPLY WITH THE REQUIREMENTS OF NFPA 13 AND 24, 2007 THE FLORIDA PLUMBING CODE 2010 AND ALL LOCAL CODES HAVING JURISDICTION.
MATERIALS, SIZES AND CAPACITIES OF COMPONENTS, AND A GENERAL LAYOUT AND LOCATION APPLIED REINFORCED-FOIL-KRAFT FACING. SEAL ALL JOINTS AND SEAMS USING NYLON FINISH AND ALL LOCAL CODES HAVING JURISDICTION.
1.3 ALL PLUMBING WORK SHALL BE DONE IN A NEAT AND WORKMANLIKE MANNER.
OF COMPONENTS THAT COMPRISE THE HVAC SYSTEMS. FABRIC AND MASTIC. A R C H I T E C T S I N C
1.3 PIPE THREAD PATTERN: ALL THREADS SHALL BE IN ACCORDANCE WITH LOCAL FIRE
B. CONTRACTOR SHALL PROVIDE IN HIS BID: C. DUCT INSULATION MASTIC SHALL BE LOW ODOR, FIRE AND VAPOR RETARDANT, WITH DEPARTMENT SPECIFICATIONS AND NFPA 1963, 1998 REVISION. 1.4 CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS AND FEES, ETC., REQUIRED License # AA C001863
1. ALL LABOR, TOOLS, MATERIALS, PLANT, TRANSPORTATION, TAXES, RELATED ITEMS, ETC., PERMEANCE NOT EXCEEDING 0.08 PERMS INACCORDANCE WITH ASTM E96. MASTIC COATING FOR THE EXECUTION OF THIS WORK.
ESSENTIAL FOR INSTALLATION AND OPERATION OF THE WORK. SHALL BE NONFLAMMABLE IN BOTH WET AND DRY STATES. 1.4 UL/FM APPROVAL: ALL EQUIPMENT, VALVES, COUPLINGS, HANGERS AND DEVICES SHALL 1500 Jackson Street, Suite 200
1.5 CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL OTHER TRADES BEFORE Fort Myers, Florida 33901
L 2. ALL SYSTEMS SHALL BE COMPLETE AND LEFT IN OPERATING CONDITION. BE APPROVED BY UNDERWRITERS' LABORATORY (UL) OR FACTORY MUTUAL (FM) FOR L
D. DUCT INSULATION ADHESIVE SHALL ADHERE FIBERGLASS BLANKET TO METAL DUCTWORK. USE IN FIRE PROTECTION SERVICE. FABRICATION OR INSTALLATION. OFFSETS AND/OR TRANSITIONS REQUIRED SHALL BE Phone: 239-278-3838 Fax: 239-275-5356
1.3 WARRANTY WHERE DUCT WIDTH IS 24-INCHES OR GREATER, THE INSULATION SHALL BE ADDITIONALLY PROVIDED WITHOUT ADDITIONAL COST. CONTRACTOR SHALL COORDINATE AND INSTALL
A. ALL PRODUCTS AND WORKMANSHIP SHALL BE WARRANTED FOR A MINIMUM OF (1) ONE YEAR SECURED TO THE BOTTOM OF THE DUCT USING MECHANICAL FASTENERS SPACED 1-FOOT ON 1.5 LICENSURE: THE FIRE PROTECTION SYSTEMS SHALL BE INSTALLED BY A STATE OF HIS WORK IN A TIMELY MANNER TO PREVENT DELAYS IN THE CONSTRUCTION.
949 Central Ave.
FROM DATE OF SUBSTANTIAL COMPLETION. CENTER TO PREVENT SAGGING OF THE INSULATION. FLORIDA CERTIFIED FIRE PROTECTION CONTRACTOR. Naples, Florida 34102
1.6 CONTRACTOR SHALL BE RESPONSIBLE TO REPAIR OR REPLACE DAMAGED EQUIPMENT
AND/OR MATERIAL. Phone: 239-643-3103 Fax: 239-643-7435
1.4 CODES AND STANDARDS 2.8 COMBINATION FIRE AND SMOKE DAMPERS 1.6 ALL FIRE PROTECTION WORK SHALL BE DONE IN A NEAT AND WORKMAN-LIKE MANNER.
A. FURNISH AND INSTALL HVAC SYSTEMS TO MEET ALL CURRENT REQUIREMENTS OF THE A. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE PRODUCTS BY
1.7 PROVIDE ALL MATERIALS REQUIRED TO PROPERLY SUPPORT ALL PIPING AND Project:
FLORIDA BUILDING CODE 2010, THE FLORIDA MECHANICAL CODE 2010, AND ALL LOCAL CODES THE FOLLOWING: 1.7 CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS AND FEES, ETC., REQUIRED
EQUIPMENT. PIPE HANGERS SHALL BE ADJUSTABLE TYPE AND BE SPACED IN

Lee County
HAVING JURISDICTION.. 1. AIR BALANCE INC.; A DIVISION OF MESTEK, INC. FOR THE EXECUTION OF THIS WORK.
2. CESCO PRODUCTS; A DIVISION OF MESTEK, INC. ACCORDANCE WITH THE STANDARD PLUMBING CODE. PROVIDED PLASTIC COATED RING
1.5 PERMITS AND INSPECTIONS 3. GREENHECK FAN CORPORATION. 1.8 CONTRACTOR SHALL COORDINATE WORK WITH OTHER TRADES BEFORE ON HANGERS FOR COPPER PIPING TO PROVIDE DIELECTRIC ISOLATION.

Justice Center
A. SECURE AND PAY FOR ALL PERMITS AND LICENSES BEFORE ACTUAL WORK IS STARTED AND 4. NAILOR INDUSTRIES INC. FABRICATION OR INSTALLATION. OFFSETS AND/OR TRANSITIONS REQUIRED SHALL BE
K OBSERVE ANY REQUIREMENT STIPULATED THEREON. 5. POTTORFF. PROVIDED WITHOUT ADDITIONAL COST. CONTRACTOR SHALL COORDINATE AND INSTALL 1.8 PROVIDE DIELECTRIC UNIONS OR FLANGES BETWEEN COPPER AND STEEL PIPING AND K
6. RUSKIN COMPANY. WORK IN A TIMELY MANNER TO PREVENT DELAYS IN THE CONSTRUCTION. BETWEEN BRASSWARE AND STEEL. DO NOT USE STEEL AND COPPER PIPING IN THE
SAME SYSTEM WITHOUT SUCH ISOLATION.
Second Floor
B. THE INSTALLATION SHALL BE MADE IN A NEAT AND WORKMANLIKE MANNER BY PERSONNEL
LICENSED AND SKILLED IN THE TRADE. THE WORK WILL BE INSPECTED BY AN AGENT OF THE B. TYPE: DYNAMIC; RATED AND LABELED ACCORDING TO UL 555 AND UL 555S BY AN NRTL. 1.9 CONTRACTOR SHALL BE RESPONSIBLE TO REPAIR OR REPLACE DAMAGED EQUIPMENT
GOVERNMENTAL AUTHORITY HAVING JURISDICTION. AND/OR MATERIAL. 1.9 PROVIDE REDUCING FITTINGS (REDUCING BUSHINGS SHALL NOT BE USED) WHERE

Remodel Pod D
C. CLOSING RATING IN DUCTS UP TO 4-INCH WG (1-KPA) STATIC PRESSURE CLASS AND MINIMUM CHANGES IN PIPE SIZES OCCUR.
1.6 CUTTING AND PATCHING 2000-FPM (10-M/S) VELOCITY. 1.10 PIPING SHOP DRAWINGS: SUBMIT 1/8" SCALE PIPING SHOP DRAWINGS. SHOP DRAWINGS
A. PROVIDE ALL NECESSARY CUTTING AND PATCHING REQUIRED IN CONNECTION WITH SHALL INCLUDE SPRINKLER PIPING CUT LENGTHS, OFFSETS, FITTINGS AND DEVICES, 1.10 THIS CONTRACTOR SHALL SUPPLY AND INSTALL ALL SERVICES THROUGHOUT THE

Part B
MECHANICAL WORK. D. FIRE RATING: 1-1/2 HOURS. ELEVATIONS, HANGER LOCATIONS, SPRINKLER HEAD COUNT BY TYPE, ELEVATION REMODELED PORITION OF THE BUILDING AND MAKE CONNECTION TO NEAREST UTILITIES.
SECTIONS AND OTHER INSTALLATION INFORMATION. SUBMIT HYDRAULIC CALCULATIONS CONTRACTOR SHALL SUPPLY AND INSTALL FIXTURES, FITTINGS, VALVING AND
1.7 SUBMITTALS E. FRAME: HAT-SHAPED, 0.094-INCH- (2.4-MM-) THICK, GALVANIZED SHEET STEEL, WITH PROVING THE VIABILITY OF THE MOST HYDRAULICALLY-REMOTE AREAS OF THE PROJECT. TRIM AND MAKE READY FOR USE ALL FIXTURES, EQUIPMENT, ETC.
Owner:
A. FINAL REVIEW OF EQUIPMENT AND MATERIALS WILL BE BASED ON THE MANUFACTURER'S MECHANICALLY ATTACHED CORNERS AND MOUNTING FLANGE. INDICATE HYDRAULIC REFERENCE POINTS AND SUBMIT COMPUTER ANALYZED NODAL
Lee County Board
CATALOG CUTS, BROCHURES AND PERFORMANCE DATA. FOUR (4) SETS OF EACH ITEM SHALL CALCULATIONS IN BOTH TABULAR AND GRAPHICAL FORMATS. HYDRAULIC IMBALANCE 1.11 SEE ARCHITECTURAL DRAWINGS FOR FIXTURE LOCATIONS AND MOUNTING HEIGHTS.
J J
BE SUBMITTED FOR REVIEW. F. HEAT-RESPONSIVE DEVICE: REPLACEABLE, 165 DEG F (74 DEG C) RATED, FUSIBLE LINKS. SHALL NOT EXCEED 0.01 GPM AT ANY NODE, AND WATER VELOCITY SHALL NOT EXCEED
of Commissioners
1. AIR GRILLES, REGISTERS, AND DIFFUSERS 20 FEET PER SECOND. DEMONSTRATE COMPLIANCE WITH THE REQUIREMENTS OF NFPA- 2.00 - BASIC MATERIALS AND METHODS
2. DAMPERS G. HEAT-RESPONSIVE DEVICE: ELECTRIC RESETTABLE DEVICE AND SWITCH PACKAGE, FACTORY 13 REGARDING DENSITY, AREA OF APPLICATION, SELECTION OF HYDRAULICALLY-REMOTE
3. DUCT MATERIAL INSTALLED, 250 DEG F (121 DEG C) RATED. AREAS, AND MAXIMUM COVERAGE PER SPRINKLER. 2.1 ABOVEGROUND WATER PIPE AND FITTINGS - TYPE "L" COPPER.
4. DUCT INSULATION
H. SMOKE DETECTOR: INTEGRAL, FACTORY WIRED FOR SINGLE-POINT CONNECTION. 1.11 COORDINATE ALL PIPE ROUTING WITH ALL OTHER TRADES PRIOR TO INSTALLATION. 2.2 PROVIDE UNIONS OR FLANGES IN ALL DOMESTIC WATER SERVICE LINES AT EACH PIECE
1.8 CLEANING ROUTE ALL PIPING TO AVOID DUCTWORK, PIPING, AND BUILDING STRUCTURE. OF EQUIPMENT, SPECIALTY VALVES OR AT OTHER LOCATIONS REQUIRED FOR READY
A. CLEAR AWAY ALL DEBRIS, SURPLUS MATERIALS, ETC., (AND DISPOSE BY LEGAL I. BLADES: ROLL-FORMED, HORIZONTAL, OVERLAPPING, 0.063-INCH- (1.6-MM-) THICK, GALVANIZED DISCONNECT. Consultant:
PROCEDURE) RESULTING FROM WORK AND OPERATIONS, LEAVING THE JOB AND EQUIPMENT SHEET STEEL.
PROVIDED UNDER CONTRACT IN A CLEAN AND FIRST-CLASS CONDITION. 2.00 - BASIC MATERIALS AND METHODS 2.3 WATER HAMMER ARRESTORS SHALL BE INSTALLED AT THE LOCATIONS ON THE PLANS 13099 S. Cleveland Ave.
J. LEAKAGE: CLASS II. AND IN ACCORDANCE WITH PDI STANDARD WH-201. PRODUCTS SHALL BE EQUAL TO Suite 500
1.9 RECORD DOCUMENTS THOSE MANUFACTURED BY PRECISION PLUMBING PRODUCTS OR SIOUX CHIEF. Fort Myers, Florida 33907
H
H A. PROVIDE "AS-BUILT" DRAWINGS INCLUDING DUCT SYSTEMS ROUTING, AND INSTALLED K. RATED PRESSURE AND VELOCITY TO EXCEED DESIGN AIRFLOW CONDITIONS. 2.1 GENERAL: ONLY THE FOLLOWING MATERIALS DESIGNED FOR 175 PSIG CWP SHALL BE Phone: 239-275-4240
ACCESSORIES AND DEVICES. USED FOR FIRE PROTECTION PIPING UNLESS SPECIFICALLY INDICATED OTHERWISE. ALL 2.4 VALVES: PROVIDE VALVES TO ISOLATE EACH RISER, BRANCH LINE AND PIECE OF
Fax: 239-275-3511
L. MOUNTING SLEEVE: FACTORY-INSTALLED, 0.05-INCH- (1.3-MM-) THICK, GALVANIZED SHEET PIPING MATERIALS SHALL HAVE A CORROSION RESISTANCE RATING (CCR) OF 1.0 OR EQUIPMENT.
www.tlc-engineers.com
1.10 CONTRACTOR QUALIFICATIONS STEEL; LENGTH TO SUIT WALL OR FLOOR APPLICATION. GREATER. © Copyright 2014 TLC Engineering for Architecture, Inc.
A. CONTRACTOR SHALL PROVIDE QUALIFIED EXPERIENCE INSTALLING AND SERVICING 2.5 ABOVEGROUND SANITARY WASTE, SANITARY VENT AND STORM PIPING - SERVICE WEIGHT
CAST IRON WITH NO-HUB COUPLINGS - ("HUSKEY 4000" OR "CLAMPALL" ONLY). EB #0000015 TLC NO: 714124
COMMERCIAL HVAC EQUIPMENT FOR A MINIMUM OF 5 YEARS. M. MASTER CONTROL PANEL FOR USE IN DYNAMIC SMOKE-MANAGEMENT SYSTEMS. 2.2 PIPE: 2 INCH OR SMALLER PIPE, AND ALL THREADED PIPING SHALL BE BLACK STEEL,
SCHEDULE 40, ASTM A-53. 2-1/2 INCH AND LARGER PIPE MAY BE BLACK STEEL, SCHEDULE
B. CONTRACTOR SHALL BE RESPONSIBLE TO COVER THE SERVICE FEES FOR ANY AND ALL N. DAMPER MOTORS: TWO-POSITION ACTION. 10, ASTM A-135. 2.6 ABOVEGROUND SANITARY WASTE ARMS - SERVICE WEIGHT CAST IRON WITH NO-HUB
SUBSEQUENT SITE VISITS NECESSARY TO ENSURE THAT EQUIPMENT IS INSTALLED AND COUPLINGS OR DWV COPPER. Seal:
OPERATING PROPERLY. CONTRACTOR'S WORK SHALL NOT BE CONSIDERED COMPLETE UNTIL O. COMPLY WITH NEMA DESIGNATION, TEMPERATURE RATING, SERVICE FACTOR, ENCLOSURE 2.3 FITTINGS: SCHEDULE 40 BLACK STEEL PIPE SHALL BE JOINED BY MECHANICAL
TEST AND BALANCE REPORT INDICATES THAT THE EQUIPMENT COMPONENTS ARE PROPERLY TYPE, AND EFFICIENCY REQUIREMENTS FOR MOTORS SPECIFIED IN SECTION 230513 "COMMON COUPLINGS, THREADED OR WELDED FITTINGS; SCHEDULE 10 BLACK STEEL PIPE SHALL 2.7 INSTALL GRAVITY LINES SLOPED AT 1/8" PER FOOT FOR PIPE 3" AND LARGER AND 1/4" PER
INSTALLED AND OPERATING PER DESIGN DOCUMENTS AND MANUFACTURER'S WRITTEN MOTOR REQUIREMENTS FOR HVAC EQUIPMENT." BE JOINED BY ROLLED GROOVE COUPLINGS OR WELDED FITTINGS ONLY. WELDED FOOT FOR PIPE SMALLER THAT 3". VERIFY INVERT ELEVATION WITH SITE PIPING PRIOR TO
INSTALLATION RECOMMENDATIONS. 1. MOTOR SIZES: MINIMUM SIZE AS INDICATED. IF NOT INDICATED, LARGE ENOUGH SO DRIVEN BRANCH CONNECTIONS WHICH ARE AT LEAST 2 NOMINAL PIPE SIZES SMALLER THAN THE ANY PIPE BEING INSTALLED.
G LOAD WILL NOT REQUIRE MOTOR TO OPERATE IN SERVICE FACTOR RANGE ABOVE 1.0. MAINS ARE PERMITTED. THREADED FITTINGS ARE ACCEPTABLE ONLY FOR PIPING 2 INCHES G
2.00 - PRODUCTS 2. CONTROLLERS, ELECTRICAL DEVICES, AND WIRING: COMPLY WITH REQUIREMENTS FOR AND SMALLER. 3.00 - PLUMBING FIXTURES AND TRIM
ELECTRICAL DEVICES AND CONNECTIONS SPECIFIED IN SECTION 230900 "INSTRUMENTATION
2.1 METAL DUCTWORK AND CONTROL FOR HVAC." 2.4 HANGERS: ALL HANGER SPACING SHALL COMPLY WITH THE REQUIREMENTS OF NFPA-13. 3.1 ALL PLUMBING FIXTURES SHALL BE "FIRST QUALITY" AS DEFINED AND SET FORTH IN
A. MATERIALS: UNLESS NOTED OTHERWISE, ALL DUCTWORK SHALL BE GALVANIZED SHEET 3. PERMANENT-SPLIT-CAPACITOR OR SHADED-POLE MOTORS: WITH OIL-IMMERSED AND COMMERCIAL STANDARD CS77-28 AS PROMULGATED BY THE U.S. DEPARTMENT OF
METAL. FIBERGLASS DUCT BOARD SHALL BE PROHIBITED. SEALED GEAR TRAINS. 2.5 SPRINKLER HEAD LOCATION: INSTALL SPRINKLER HEADS IN THE CENTER OF THE CEILING COMMERCE.
1. GALVANIZED SHEET STEEL: LOCK-FORMING QUALITY, ASTM A527, COATING DESIGNATION G 4. SPRING-RETURN MOTORS: EQUIP WITH AN INTEGRAL SPIRAL-SPRING MECHANISM WHERE TILES FOR SUSPENDED CEILING APPLICATIONS.
90. INDICATED. ENCLOSE ENTIRE SPRING MECHANISM IN A REMOVABLE HOUSING DESIGNED FOR 3.2 FIXTURES AND FITTINGS PROPOSED SHALL BE FROM ONE MANUFACTURER AND OF
SERVICE OR ADJUSTMENTS. SIZE FOR RUNNING TORQUE RATING OF 150 IN. X LBF (17 N X M) 2.6 SPRINKLER CAGE GUARD: PROVIDE HEAD GUARDS ON ALL HEADS IN ELECTRICAL ROOMS SIMILAR CHARACTER IN ANY ROOM OR LOCATION. ESCUTCHEONS, HANDLES, ETC., ON
B. SEALING MATERIALS AND BREAKAWAY TORQUE RATING OF 150 IN. X LBF (17 N X M). AND ON ALL HEADS LESS THAN 7'-0" ABOVE FINISHED FLOOR. THE DIFFERENT FIXTURES SHALL BE OF THE SAME DESIGN.
1. JOINT AND SEAM SEALANT: ONE-PART, NONSAG, SOLVENT-RELEASE-CURING, 5. OUTDOOR MOTORS AND MOTORS IN OUTDOOR-AIR INTAKES: EQUIP WITH O-RING GASKETS
POLYMERIZED BUTYL SEALANT COMPLYING WITH FS TT-S-001657, TYPE I; FORMULATED DESIGNED TO MAKE MOTORS WEATHERPROOF. EQUIP MOTORS WITH INTERNAL HEATERS TO 2.7 GAUGES: PROVIDE GAUGES AND GAUGE VALVES AS REQUIRED BY NFPA 13. GAUGE 3.3 PROVIDE FIXTURE CARRIERS AS RECOMMENDED BY FIXTURE MANUFACTURER AND/OR
WITH A MINIMUM OF 75 PERCENT SOLIDS. TAPING IS NOT PERMITTED. SEALANT IS NOT TO PERMIT NORMAL OPERATION AT MINUS 40 DEG F (MINUS 40 DEG C). SCALE SHALL BE 0-300 PSI UNLESS OTHERWISE INDICATED. CONSTRUCTION METHOD.
F BE VISIBLE. 6. NONSPRING-RETURN MOTORS: FOR DAMPERS LARGER THAN 25 SQ. FT. (2.3 SQ. M), SIZE F
3.4 PROVIDE ACCESS PANELS TO ALL VALVES WITHIN CHASES OR ABOVE NON-ACCESSIBLE Project Phase:

Design
MOTOR FOR RUNNING TORQUE RATING OF 150 IN. X LBF (17 N X M) AND BREAKAWAY TORQUE 2.8 ACCESS PANELS: PROVIDE ACCESS PANELS TO ALL VALVES WITHIN CHASES OR ABOVE
C. HANGERS AND SUPPORTS RATING OF 300 IN. X LBF (34 N X M). NON-ACCESSIBLE CEILINGS. REFER TO ARCHITECTURAL DRAWINGS FOR CEILING TYPES. CEILINGS. REFER TO ARCHITECTURAL DRAWINGS FOR CEILING TYPES.
1. BUILDING ATTACHMENTS: PROVIDE INSERTS AS APPROPRIATE FOR BUILDING MATERIALS. 7. ELECTRICAL CONNECTION: 115 V, SINGLE PHASE, 60 HZ.

Development
2. HANGERS: GALVANIZED SHEET STEEL. CONFORM WITH TABLE 4-1 IN SMACNA HVAC DUCT 2.9 HYDROSTATIC TESTS: ABOVE GROUND AND BELOW GROUND PIPING SYSTEMS SHALL BE 4.00 - VALVES AND COCKS
CONSTRUCTION STANDARDS, CURRENT EDITION, FOR SHEET STEEL WIDTH AND GAGE. P. ACCESSORIES: HYDROSTATICALLY TESTED AT NOT LESS THAN 200 PSI PRESSURE, OR AT 50 PSI IN
3. DUCT ATTACHMENTS: SHEET METAL SCREWS, BLIND RIVETS, OR SELF-TAPPING METAL 1. AUXILIARY SWITCHES FOR SIGNALING OR POSITION INDICATION. EXCESS OF THE MAXIMUM PRESSURE, WHICHEVER IS GREATER, FOR A PERIOD OF 2 4.1 VALVES 2" AND SMALLER SHALL BE BALL VALVES, 150 PSI SWP, 400 PSI WOG. STANDARD
PORT BALL, BRONZE TRIM, CAST BRONZE BODY, CHROMIUM-PLATED BRASS BALL,
SCREWS; COMPATIBLE WITH DUCT MATERIALS. 2. TEST AND RESET SWITCHES, DAMPER MOUNTED. HOURS. THE TEST PRESSURE SHALL BE READ FROM A GAUGE LOCATED AT THE LOW Project #: 0118.22
ELEVATION POINT OF THE INDIVIDUAL SYSTEM OR PORTION OF THE SYSTEM BEING BRONZE NON-BLOWOUT STEM, TEFLON SEAT, DOUBLE O-RING STEM SEALS, ZINC-COATED
STEEL HANDLE WITH PLASTIC COATED HAND GRIP, 90 DEGREE OPERATION FROM FULL Project Issued: 07/16/13
D. DUCT FABRICATION: CONSTRUCT IN ACCORDANCE WITH SMACNA REQUIREMENTS. 3.1 METAL DUCTWORK AND INSULATION TESTED. THE SPRINKLER PIPING SHALL NOT HAVE LEAKAGE EXCEEDING THE AMOUNTS
A. GENERAL: SELECT DUCTWORK ACCORDING TO THE FOLLOWING APPLICATIONS: SPECIFIED IN NFPA 24. LEAKAGE QUANTITIES SHALL BE DETERMINED BY PUMPING AT THE OPEN TO TIGHT SHUT-OFF - STOCKHAM S214-BR-T-T, STOCKHAM S216-BR-T-S OR EQUAL. Sheet Issued:
E. DUCTWORK SHALL COMPLY WITH THE FOLLOWING MINIMUM PRESSURE REQUIREMENTS: 1. CONCEALED SUPPLY AND RETURN AIR: GALVANIZED SHEET METAL, EXTERNALLY SPECIFIED TEST PRESSURE FROM A CALIBRATED CONTAINER. REPAIR LEAKING JOINTS
1. SUPPLY DUCTWORK FROM TERMINAL UNIT TO AIR DEVICE: 2 INCH W.G. INSULATED AND RETEST AS NECESSARY UNTIL ALL SYSTEMS HAVE BEEN TESTED. TEST THE PIPING 5.00 - STERILIZATION
E E
2. EXHAUST AIR DUCTWORK: -1 INCH W.G. 2. CONCEALED SUPPLY RUNOUTS: UL181 FLEXIBLE DUCTWORK BETWEEN THE CHECK VALVE IN THE FIRE DEPARTMENT INLET PIPE AND THE OUTSIDE No. Date Revision
3. SUPPLY AIR THE FIRST 10 FEET OF RETURN AIR DUCTS EXPOSED IN FINISHED AREAS: CONNECTION THE SAME AS THE BALANCE OF THE SYSTEM. 5.1 DOMESTIC WATER PIPING SHALL BE THOROUGHLY FLUSHED OUT AND STERILIZED IN
F. ALL LONGITUDINAL SEAMS SHALL COMPLY WITH SMACNA. SEAMS SHALL BE SELECTED GALVANIZED SHEET METAL READY FOR PAINT,INTERNALLY LINED. ACCORDANCE WITH THE STANDARD PLUMBING CODE.
BASED ON THE SPECIFIED PRESSURE CLASSIFICATION. THE INSIDE FACING OF ALL
LONGITUDINAL SEAMS ANDTRANSVERSE JOINTS SHALL BE FLAT AND SMOOTH. SEALANT B. SEAM AND JOINT SEALING 3.00 - FIRE PROTECTION PRODUCTS AND ACCESSORIES
SHALL BE APPLIED OVER THE CONTINUOUS LENGTH OF ALL SEAMS. 1. SEAL ALL TRANSVERSE JOINTS AND LONGITUDINAL SEAMS.

2.2 DUCT ACCESSORIES C. HANGING AND SUPPORTING 3.1 QUICK-RESPONSE UPRIGHT SPRINKLERS: SPRINKLER HEADS SHALL BE MANUFACTURED
A. FLEXIBLE DUCTS 1. INSTALL METAL DUCT WITH SUPPORT SYSTEMS INDICATED IN SMACNA HVAC DUCT WITH UPRIGHT DEFLECTORS FOR INSTALLATION ABOVE THE BRANCH LINE WITH BRASS
1. GENERAL: COMPLY WITH UL 181, CLASS 1. CONSTRUCTION STANDARDS. FINISH - CENTRAL GB-QR OR VIKING MICROFAST MODEL M.
2. FLEXIBLE DUCTS - INSULATED: FACTORY-FABRICATED, INSULATED, ROUND DUCT, WITH AN
OUTER JACKET ENCLOSING 1-INCH-THICK, GLASS FIBER INSULATION AROUND A CONTINUOUS D. CLEANING 3.2 QUICK RESPONSE SEMI-RECESSED SPRINKLERS: SPRINKLER HEADS SHALL BE
D INNER LINER. 1. REMOVE DUST AND DEBRIS FROM INSIDE DUCTS AND FITTINGS. MANUFACTURED WITH PENDANT DEFLECTOR FOR INSTALLATION BELOW THE BRANCH D
a. REINFORCEMENT: STEEL-WIRE HELIX ENCAPSULATED IN THE INNER LINER. 2. CLEAN EXTERIOR OF INSULATION TO REMOVE DUST AND DIRT. LINE WITH CHROME-PLATED FINISH - CENTRAL GB-QR OR VIKING MICROFAST MODEL M
b. OUTER JACKET: GLASS-REINFORCED, REINFORCED METALIZED POLYESTER JACKET. WITH MODEL F-1 ESCUTCHEON.
c. INNER LINER: POLYETHYLENE FILM. 3.2 TESTING, ADJUSTING, AND BALANCING HVAC SYSTEMS
3. FLEXIBLE DUCT CLAMPS: NYLON BAND INSTALLED WITH USE OF TENSION CLAMPING TOOL. A. SUMMARY:
1. TEST, ADJUST, AND BALANCE THE AIR SYSTEMS.
2.3 AIR INLETS AND OUTLETS 2. VERIFY TEMPERATURE CONTROL SYSTEM OPERATION.
A. GENERAL: EXCEPT AS OTHERWISE INDICATED, PROVIDE MANUFACTURER'S STANDARD 3. PROVIDE COPY OF BALANCE REPORT TO OWNER AND ARCHITECT.
CEILING AIR DIFFUSERS WHERE SHOWN; OF SIZE, SHAPE, CAPACITY AND TYPE INDICATED;
CONSTRUCTED OF MATERIALS AND COMPONENTS AS INDICATED, AND AS REQUIRED FOR
COMPLETE INSTALLATION. PROVIDE CEILING AIR DIFFUSERS THAT HAVE, AS MINIMUM,
TEMPERATURE AND VELOCITY TRAVERSES, THROW AND DROP, AND NOISE CRITERIA RATINGS
FOR EACH SIZE DEVICE AS LISTED INMANUFACTURER'S CURRENT DATA. PROVIDE DIFFUSERS
C WITH BORDER STYLES THAT ARE COMPATIBLEWITH ADJACENT CEILING SYSTEMS, AND THAT C
ARE SPECIFICALLY MANUFACTURED TO FIT INTO CEILINGMODULE WITH ACCURATE FIT AND
ADEQUATE SUPPORT. PROVIDE CEILING DIFFUSERS OF TYPE, CAPACITY, AND WITH
ACCESSORIES AND FINISHES AS LISTED ON DIFFUSER SCHEDULE.

B. MANUFACTURER: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE DIFFUSERS OF


ONE OF THE FOLLOWING OR AS APPROVED:
1. PRICE INDUSTRIES
2. KRUEGER MFG. CO. Copyright © 2014. BSSW Architects, Inc.
3. TITUS PRODUCTS DIV.; PHILIPS INDUSTRIES, INC. reserves copyright and other rights
restricting these documents to the original
2.4 DAMPERS site or purpose for which they were
A. STANDARD VOLUME CONTROL DAMPERS: SINGLE BLADE DESIGN, STANDARD LEAKAGE prepared. Reproductions, changes or
B B assignments are prohibited.
RATING, SUITABLE FOR HORIZONTAL OR VERTICAL APPLICATIONS. PROVIDE FACTORY
FABRICATED VOLUME CONTROL DAMPERS COMPLETE WITH REQUIRED HARDWARE AND Sheet Title:
ACCESSORIES. PROVIDE BOWDEN CABLE CONTROLLER, CONCEALED CEILING INSTALLATION,
AS REQUIRED.
Lawrin T. Ellis, P.E. MECHANICAL
Florida License #66383
SPECIFICATIONS
2.5 HANGERS AND SUPPORTS
A. BUILDING ATTACHMENTS: PROVIDE BEAM CLAMPS, INSERTS, AND SUPPORTS AS
APPROPRIATE FOR BUILDING MATERIALS.

Sheet No.
A A

Seal
M6.01
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

C:\Users\mark.hauser\Documents\714124_LCJC 2ND FLR POD D PH II_CENTRAL_R14_mark.hauser.rvt 1/8/2015 8:01:01 AM


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

M M

A R C H I T E C T S I N C
License # AA C001863

1500 Jackson Street, Suite 200


L L Fort Myers, Florida 33901
DAMMING Phone: 239-278-3838 Fax: 239-275-5356
MATERIAL WALL OR FLOOR
949 Central Ave.
3M #CP-25 FIRE Naples, Florida 34102
Phone: 239-643-3103 Fax: 239-643-7435
BARRIER CAULK
OR EQUIVALENT CONDUIT BUSHING
Project:
ON EACH END OF SEAL BOTH ENDS OF SLEEVE

PUBLIC
AFTER WIRE INSTALLATION
PIPE CLAMP CONDUIT

~
EACH SIDE

K CABLING K
DEFENDER'S
OFFICE - 5TH
ACCESSIBLE CEILING
FLOOR
8" KINDORF SECTION
EACH SIDE
Owner:

J CONCRETE ANCHOR J Lee County Board


NOTE: CONTRACTOR SHALL RESTORE THE INTEGRITY OF RATED WALLS PENETRATED PER SPECIFICATIONS. ROOF DECK
ANY NEW PENETRATIONS SHALL FOLLOW THIS GUIDELINE. 1" CONCELED CONDUIT
BAR JOIST
of County
CLAMP
DOUBLE GANG WALL BOX Commissioners
IF ADDITIONAL SLEEVES ARE NEEDED OR REQUESTED USE FOLLOWING CAT 6 UTP CABLE Consultant:
WALL SLEEVE SIZING TABLE EQUIVALENT TO CAT. 5 CABLES
ADJUST COUNT BASED ON CABLE SIZES
FACEPLATE 13099 S. Cleveland Ave.
CADDY CABLE CAT-6 J-HOOKS Suite 500
# OF CABLES SLEEVE SIZE
H
Fort Myers, Florida 33907
H Phone: 239-275-4240
1-8 1"
Fax: 239-275-3511
9-14 1 1/4" www.tlc-engineers.com
15-18 1 1/2" © Copyright 2014 TLC Engineering for Architecture, Inc.
19-26 2" EB #0000015 TLC NO: 714125
FLOOR SLAB
27-40 2 1/2"
41-60 3" Seal:
UNLESS OTHERWISE NOTED ON DRAWINGS

G G

HORIZONTAL/VERTICAL PENETRATION DETAIL 1 TYPICAL FLUSH OUTLET DETAIL 2 CABLE HANGERS 3


No Scale No Scale No Scale

PROVIDE 1" CONDUIT


F F
Project Phase:

Construction
Documents
Project #: 0118.22
STRUCTURE
Project Issued: 11/05/14
TO MAIN SERVICE GROUND Sheet Issued:

GROUND CONDUCTORS PROVIDE SINGLE GANG FACE


E E
QTY. AS REQUIRED PLATE No. Date Revision
EXTRON CPM101

2" INSULATED STANDOFF


PROVIDE HDMI J-HOOKS POWER OUTLET
GROUND LUG CONNECTOR REFER TO ELEC.
EXTRON IN9467
DRAWINGS

PROVIDE COMPOSITE VIDEO CEILING


CONNECTOR
EXTRON IN9382
D D
FACEPLATE WITH GROMMET
2" PROVIDE S-VIDEO
COPPER GROUND BAR CONNECTOR VOICE-DATA OUTLET
EXTRON IN9381-SE1

1/8" PROVIDE VGA


CONNECTOR
EXTRON IN9362
12"
C C

4" X 4" ELECTRICAL BACK


BOX
OWNER PROVIDED PROJECTOR
WITH SINGLE DEVICE PLATE Copyright © 2014. BSSW Architects, Inc.
reserves copyright and other rights
restricting these documents to the original
site or purpose for which they were
CONTRACTOR TO PROVIDE ALL CABLING AND
B
AV TERMINATIONS B
prepared. Reproductions, changes or
assignments are prohibited.
FROM A/V OUTLET TO CEILING MOUNTED PROJECTOR.
Sheet Title:

COMMUNICATIONS GROUND BAR 4 A/V PLATE DETAIL 5 PROJECTOR MOUNTING 6 Brett L. Sands, P.E. TECHNOLOGY
No Scale Florida License #48477
DETAILS
No Scale No Scale

Sheet No.
A A

Seal
T202
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

C:\Users\mark.hauser\Documents\714125_LCJC ANNEX 5TH FL_MEP CENTRAL_R14_mark.hauser.rvt 1/8/2015 8:09:19 AM


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

M
ELECTRICAL SYMBOL LEGEND M

BASIC MATERIALS BASIC MATERIALS CONT. TELEPHONE/COMPUTER RACEWAY SYSTEM GENERAL NOTES:
SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION
Sa SINGLE POLE SWITCH AUTOMATIC TRANSFER SWITCH A R C H I T E C T S I N C
1. LIGHT SWITCHES SHALL BE MOUNTED 48 INCHES ABOVE FINISHED FLOOR TO CENTER LINE OF DEVICE,
(SUBSCRIPT INDICATES ITEM CONTROLLED) UNLESS OTHERWISE NOTED. License # AA C001863
S3 THREE-WAY SWITCH 30AR NON-FUSED DISCONNECT SWITCH, SIZE & # OF POLES COMMUNICATIONS "INFORMATION OUTLET" MTD. AT RECEPTACLE
NF NF DENOTES NON-FUSED HEIGHT UNLESS OTHERWISE NOTED. DIVISION 16 CONTRACTOR 1500 Jackson Street, Suite 200
S4 FOUR-WAY SWITCH TO PROVIDE 4" SQUARE WITH SINGLE GANG RAISED MUD RING. 2. RECEPTACLES SHALL BE LOCATED 18 INCHES ABOVE FINISHED FLOOR TO CENTER LINE OF DEVICE, Fort Myers, Florida 33901
L AR DENOTES AMP RATING OF SWITCH L
SP SINGLE POLE SWITCH WITH PILOT LIGHT CONTRACTOR TO STUB UP (2) 1" CONDUITS AT EACH LOCATION UNLESS OTHERWISE NOTED. ABOVE-COUNTER RECEPTACLES SHALL BE MOUNTED 6" ABOVE BACK Phone: 239-278-3838 Fax: 239-275-5356
TO SPLASH TO CENTERLINE OF DEVICE.
SWP SINGLE POLE SWITCH WITH WEATHERPROOF COVER 30AR ABOVE CEILING AND TURN TO ACCESSIBLE CEILING SPACE.
FUSED DISCONNECT 949 Central Ave.
20AF CONTRACTOR TO PROVIDE BUSHING ON END OF CONDUIT AND 3. EQUIPMENT SHALL BE OF MATERIALS SUITABLE FOR AND RATED FOR THE ENVIRONMENT IN WHICH
SWPL SINGLE POLE SWITCH WITH WEATHERPROOF LOCKING COVER AR DENOTES AMP RATING OF SWITCH Naples, Florida 34102
PULLSTRING WITHIN. THEY ARE TO BE INSTALLED.
MCP Phone: 239-643-3103 Fax: 239-643-7435
AF DENOTES AMP FUSE SIZE
SK SINGLE POLE KEY SWITCH SIZE
# OF POLES TV TELEDATA/TV OUTLET - 4" SQUARE 2 GANG BOX 4. A. WORKING CLEARANCES FOR ELECTRICAL EQUIPMENT SHALL BE IN COMPLIANCE WITH NEC 110.
S3K WITH Project:
THREE-WAY KEY SWITCH 30/3 COMBINATION MAGNETIC MOTOR STARTER, SIZE & # OF POLES
(2) 1" CONDUITS PER ABOVE.
0 3R
S4K
SL
FOUR-WAY KEY SWITCH

SINGLE POLE SWITCH WITH SECURITY LOCKING KEY


3 POLE UNLESS OTHERWISE NOTED
ENCLOSURE NEMA RATING. TELEPHONE OUTLET FLOOR MOUNTED
B. THE EXCLUSIVELY-DEDICATED SPACE EXTENDING FROM FLOOR TO STRUCTURAL CEILING WITH
A WIDTH AND DEPTH OF THE PANELBOARD OR SWITCHBOARD MUST BE CLEAR OF ALL PIPING,
DUCTS OR EQUIPMENT FOREIGN TO THE ELECTRICAL EQUIPMENT OR ARCHITECTURAL
PUBLIC
DEFENDER'S
NEMA STARTER SIZE
K APPURTENANCES IN ACCORDANCE WITH NEC 408. K
SLV LOW VOLTAGE SWITCH BRANCH CIRCUIT PANELBOARD, UNDER 250 VOLTS, TTB

OFFICE - 5TH
SF FAN SWITCH SURFACE MOUNTED TELEPHONE/COMPUTER TERMINAL BOARD
5. WHEN ELECTRICAL BOXES ARE LOCATED IN VERTICAL FIRE-RESISTIVE ASSEMBLIES,
SM MANUAL MOTOR STARTER WITH OVERLOAD HEATERS BRANCH CIRCUIT PANELBOARD, UNDER 250 VOLTS, (CLASSIFIED AS FIRE/SMOKE AND SMOKE PARTITIONS), THEY SHALL BE INSTALLED WITHOUT
TTC AFFECTING THE FIRE CLASSIFICATION. ALL OF THE FOLLOWING CONDITIONS SHALL BE MET:
FLOOR
FLUSH MOUNTED
SMP MANUAL MOTOR STARTER WITH OVERLOAD HEATERS AND PILOT LIGHT TELEPHONE TERMINAL CABINET
BRANCH CIRCUIT PANELBOARD, OVER 250 VOLTS,
SD DIMMER SWITCH SURFACE MOUNTED
(1500 WATTS UNLESS OTHERWISE INDICATED) T A. ALL ELECTRICAL BOXES SHALL BE METALLIC.
BRANCH CIRCUIT PANELBOARD, OVER 250 VOLTS, TELEPHONE SYSTEM RACEWAY
DUPLEX RECEPTACLE
FLUSH MOUNTED B. BOX OPENING SHALL OCCUR ONLY ON ONE SIDE OF FRAMING SPACE. Owner:

J T
TWIST LOCK RECEPTACLE BRANCH CIRCUIT CONDUIT CONCEALED ABOVE CEILING OR IN WALL.
CONDUIT C. BOX OPENING SHALL NOT EXCEED 16 SQUARE INCHES. J Lee County Board
SP
SURGE PROTECTION TYPE (TVSS)
DUPLEX RECEPTACLE
SHALL INCLUDE PHASE, NEUTRAL AND GROUND CONDUCTORS AS
REQUIRED D. ALL CLEARANCES BETWEEN OUTLET BOX AND GYPSUM BOARD SHALL BE COMPLETELY of County
Commissioners
FOR CIRCUITS (UNLESS OTHERWISE NOTED). FILLED WITH JOINT COMPOUND (OR OTHER APPROVED MATERIAL).
BRANCH CIRCUIT CONDUIT CONCEALED IN SLAB,
PEDESTAL MOUNTED RECEPTACLE UNDERGROUND OR UNDER FLOOR. FIRE ALARM/DETECTION SYSTEM E. PROVIDE A WALL AROUND OUTLETS LARGER THAT 16 SQUARE INCHES. THE INTEGRITY OF THE
WALL RATING SHALL BE MAINTAINED.
FLOOR OUTLET BOX AND DUPLEX RECEPTACLE BRANCH CIRCUIT CONDUIT EXPOSED Consultant:
WITH APPROPRIATE FLANGE.
SYMBOL DESCRIPTION
GROUND OR GROUND ROD AS NOTED F. THE TOTAL AGGREGATE SURFACE AREA OF THE BOXES SHALL NOT EXCEED 100 SQUARE
INCHES PER 100 SQUARE FEET. 13099 S. Cleveland Ave.
FLOOR OUTLET BOX WITH DUPLEX RECEPTACLE F MANUAL PULL STATION Suite 500
EM EMERGENCY BRANCH CONDUIT G. OUTLET BOXES LOCATED ON OPPOSITE SIDES OF FIRE-RESISTIVE ASSEMBLIES SHALL BE
AND ONE COMBINATION W/ VOICE/DATA OUTLET
H
Fort Myers, Florida 33907
CEILING SMOKE DETECTOR, PHOTO-ELECTRIC SEPARATED BY A MINIMUM HORIZONTAL DISTANCE OF 24 INCHES.
H Phone: 239-275-4240
FLOOR OUTLET BOX WITH TWO DUPLEX RECEPTACLES CONDUIT TURNING UP TYPE UNLESS OTHERWISE NOTED Fax: 239-275-3511
UP H. OUTLET BOXES SHALL BE SECURELY FASTENED TO WALL FRAMING MEMBERS.
AND ONE COMBINATION W/ VOICE/DATA OUTLET E = ELEVATOR WITH RECALL CONTACTS www.tlc-engineers.com
CONDUIT TURNING DOWN I = IONIZATION I. THE OPENING IN THE GYPSUM BOARD FACING SHALL BE CUT NOT TO EXCEED 1/8 INCH © Copyright 2014 TLC Engineering for Architecture, Inc.
FLOOR POKE THRU - WITH POWER AND TELECOMM DEVICES DN
BETWEEN THE EDGES OF THE OUTLET BOX AND THE EDGES OF THE OPENING. EB #0000015 TLC NO: 714125
CONDUIT STUB DUCT SMOKE DETECTOR
PP POWER POLE R = RETURN
6. ALL DEVICES SHALL BE MOUNTED VERTICAL, UNLESS OTHERWISE NOTED.
CONDUIT CONTINUED S = SUPPLY Seal:
DUPLEX RECEPTACLE WIRED TO COMPUTER PANEL FLEXIBLE CONDUIT 7. ALL RECEPTACLES SHALL BE MOUNTED SUCH THAT THE GROUND PIN IS MOUNTED DOWN.
R SUPERVISED CONTROL RELAY

DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER EXISTING TO BE REMOVED


DUCT SMOKE REMOTE ALARM INDICATING LAMP,
R (N) = NEW EQUIPMENT)
G EXISTING TO REMAIN W/ TEST SWITCH, WALL MOUNTED 72" AFF G
DUPLEX SAFETY RECEPTACLE MOUNT (E) = EXISTING TO REMAIN)

*
COVERPLATES WITH SPANNER HEAD SCREWS
EXISTING AFFECTED BY THIS PROJECT RT REMOTE INDICATING LAMP FIRE ALARM WITH TEST SWITCH (R) = EXISTING TO BE REMOVED)
WALL MOUNTED 72" AFF
SIMPLEX RECEPTACLE (EWC DENOTES FUTURE (ER) = EXISTING TO BE RELOCATED)
EWC ELECTRIC WATER COOLER. COORDINATE WITH EWC
INSTALLER FOR MOUNTING HEIGHT) NEW F COMBINATION AUDIBLE/VISUAL
NOTIFICATION DEVICE
GFI RECEPTACLE. WP DENOTES WEATHERPROOF COVER.
WP SS FIRE ALARM SPEAKER - CEILING MOUNTED

GFI RECEPTACLE MOUNTED ABOVE COUNTER


COMPLIANCE STATEMENT
F FS WALL MOUNTED SPEAKER WITH STROBE F
TWO DUPLEX RECEPTACLES WITH COMMON COVER LIGHTING WORK ON THESE PLANS HAS BEEN PREPARED IN ACCORDANCE WITH THE Project Phase:

TWO DUPLEX RECEPTACLES WITH COMMON COVER


SS FIRE ALARM SPEAKER - WALL MOUNTED
2008 NATIONAL ELECTRICAL CODE, AS WELLS AS THE 2010 FLORIDA
BUILDING CODE WITH AMENDMENTS. Construction
Documents
MOUNTED ABOVE COUNTER
F FIRE ALARM SPEAKER WITH STROBE - CEILING MOUNTED
ISOLATED GROUND DUPLEX RECEPTACLE, FLUORESCENT STRIP FIXTURE
IG (ORANGE DEVICE) VISUAL SIGNALING UNIT, WALL MOUNTED
F Project #: 0118.22
FIXTURE DESIGNATION A (NO AUDIO DEVICE)
DUPLEX RECEPTACLE FLUORESCENT FIXTURE Project Issued: XX/XX/14
NOTE:
P FIREMANS PHONE JACK Sheet Issued:
TICK MARKS SHOWN ON ANY DEVICE REPRESENTS RECEPTACLE CIRCUIT NUMBER 2 a LOWER CASE LETTER INDICATES CONTROL CIRCUIT SWITCH LEG
CONNECTED TO THE EMERGENCY CIRCUIT (RED DEVICE) TYPICAL
E FOR FLUORESCENT FIXTURE SPRINKLER TAMPER E
TS No. Date Revision
ANY DEVICE IN LEGEND DIAGONAL SHADING DENOTES EMERGENCY LIGHT FIXTURE. SWITCH CONNECTION
C CLOCK RECEPTACLE
FLUORESCENT WALL MOUNTED FIXTURE WITH WALL OUTLET BOX SPRINKLER WATERFLOW
FS
SPECIAL PURPOSE RECEPTACLE, RATING AS NOTED SWITCH CONNECTION
HID, FLUORESCENT, OR INCANDESCENT FIXTURE
LIGHTING CONTROL TIME CLOCK FP FIRE ALARM SYSTEM PRINTER
GND GROUND BAR ACCENT FLOOD LIGHTING - AIMING AS INDICATED
ZAM ZONE ADDRESSABLE MODULE
PLUG-IN STRIP WITH RECEPTACLES, 18" O.C. UNLESS EXIT LIGHT FIXTURE
OTHERWISE INDICATED DIRECTION ARROWS AS SHOWN ELECTROMAGNETIC DOOR HOLD OPEN DEVICE
(SHADED QUADRANT INDICATES FACE(S) OF FIXTURE)
D UNDER GROUND CONCRETE ENCASED DUCTBANK D
WALL MOUNTED EXIT LIGHT FIXTURE ELECTROMAGNETIC DOOR HOLD OPEN DEVICE
H CONNECTION TO CLOSURE/ HOLDER
J JUNCTION BOX
BATTERY PACK WITH TWIN HEADS
J JUNCTION BOX ELECTROMAGNETIC DOOR HOLD OPEN DEVICE
H CONNECTION TO CLOSURE/ HOLDER INCLUDES DETECTOR
J JUNCTION BOX- WALL MOUNTED
CEILING HEAT DETECTOR 135° UNLESS OTHERWISE
J JUNCTION BOX- FURNITURE SYSTEM FEED H
INDICATED.
CONDUIT SEAL-OFF FITTINGS
T BEAM DETECTOR - TRANSMITTER
SS SURGE SUPRESSOR
C
C3
C3 = SERVICE ENTRANCE DEVICE LIGHTING CONTROL R BEAM DETECTOR - RECEIVER C
B3 = DISTRIBUTION BOARD DEVICE
A3 = PANELBOARD DEVICE FACP
FIRE ALARM CONTROL PANEL
ST SHUNT-TRIP BUTTON - FLUSH MOUNTED UNLESS OS WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR MOUNTED AT 90" A.F.F.
OTHERWISE NOTED NEMA 3R FOR EXTERIOR LOCATIONS FATC
FIRE ALARM TERMINAL CABINET
MAGNETIC MOTOR STARTER OR CONTACTOR OS CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR
SIZE AS NOTED FAAP FIRE ALARM ANNUNCIATOR PLAN - FLUSH MOUNTED Copyright © 2014. BSSW Architects, Inc.
SO WALL MOUNTED PASSIVE INDRA-RED OCCUPANCY SENSOR WITH MANUAL OVERRIDE. reserves copyright and other rights
EDH-X restricting these documents to the original
MOUNT @ 48" A.F.F. FIRE ALARM SYSTEM CONDUIT AND WIRING site or purpose for which they were
ELECTRIC DUCT HEATER F
prepared. Reproductions, changes or
B ST WALL MOUNTED DIGITAL TIMER. `P' INDICATED WITH PILOT LIGHT B assignments are prohibited.
5 MOTOR CONNECTION, NUMBER DENOTES HORSEPOWER E FIREMAN'S ELEVATOR WARNING LIGHT
MOUNT @ 48" A.F.F. Sheet Title:
VFD

DDC
VARIABLE FREQUENCY DRIVE

DIRECT DIGITAL CONTROL PANEL


PROVIDE ALL NECESSARY POWER PACKS AND RELAYS FOR A FULLY FUNCTIONAL SYSTEM Brett L. Sands, P.E. ELECTRICAL SYMBOL
Florida License #48477
T TRANSFORMER LEGEND, GENERAL
NOTES & INDEX
Sheet No.
A A
NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT.

Seal
E001
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

C:\Users\mark.hauser\Documents\714125_LCJC ANNEX 5TH FL_MEP CENTRAL_R14_mark.hauser.rvt 1/8/2015 8:10:43 AM


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

M # KEYNOTES: M

1. EXISTING STAIRWELL. NO DEMOLITION REQUIRED.

2. EXISTING ELEVATOR CORE. NO CHANGES REQUIRED.

3. THE EXTENT OF THE DEMOLITION WITHIN THIS EXISTING ELECTRICAL ROOM, IS CONFINED
TO ANY WORK ASSOCIATED WITH THE REMOVAL OF THE EXISTING CONDUIT AND WIRING A R C H I T E C T S I N C
WHICH IS TO BE ABANDONED (EITHER HIGH VOLTAGE. LOW VOLTAGE, OR STRUCTURED License # AA C001863
CABLING). NOTE: ONLY THE CONDUIT AND CABLING ASSOCIATED WITH THE ABANDONED
SYSTEMS IS TO BE REMOVED. THERE ARE EXISTING SYSTEMS BOTH LIFE SAFETY AND FOR 1500 Jackson Street, Suite 200
L OTHER TENANTS WHICH MUST REMAIN IN SERVICE. DEMOLITION IN THIS AREA TO BE VERY L Fort Myers, Florida 33901
SELECTIVE. Phone: 239-278-3838 Fax: 239-275-5356

4. DEMOLITION WITHIN THIS SPACE IS CALLED OUT ON THE POWER AND SYSTEMS FLOOR 949 Central Ave.
PLAN, AND IS RELATED TO THE RELOCATION/UPGRADE OF ELECTRICAL SERVICE TO THE Naples, Florida 34102
NEW AIR HANDLER. Phone: 239-643-3103 Fax: 239-643-7435
D101
5. DEMOLITION WITHIN THIS SPACE IS SELECTIVE AND LIMITED TO THE REPLACEMENT OF Project:
TYP.
SOME OF THE EXISTING LIGHT FIXTURES AND THE RELOCATION OF ROOM LIGHTING
CONTROL.
PUBLIC
DEFENDER'S
6. DEMOLITION WITHIN THIS SPACE IS SELECTIVE AND LIMITED REMOVAL OF SOME EXISTING
K WALLS AND CEILINGS. COORDINATE IN FIELD. K

D103
7. UNLESS SPECIFICALLY NOTED OTHERWISE IN #1 - #6 ABOVE, ALL OTHER DEVICES AND
CABLING WHICH SERVES THIS FLOOR ARE TO BE REMOVED. ALL CABLING AND CONDUIT OFFICE - 5TH
NOT SCHEDULED TO BE RE-USED, IS TO BE REMOVED ALL THE WAY BACK TO THE
TYP.
EXISTING PANELBOARD OR TERMINAL CABINET FROM WHICH IT ORIGINATED. IF CONDUIT
AND CABLING RUNNING THROUGH THE THIRD FLOOR IS SERVING OTHER AREAS OF THE
FLOOR
BUILDING, CONTRACTOR SHALL RE-ROUTE SAID CONDUIT AND CABLING TO MAINTAIN
EXISTING SYSTEMS WHICH SERVE OTHER FLOORS, ESPECIALLY LIFE SAFETY SYSTEMS.
Owner:

J
PEDESTRIAN BRIDGE
J Lee County Board
D110
D111
BELOW
of County
Commissioners
Consultant:

13099 S. Cleveland Ave.


Suite 500
H
Fort Myers, Florida 33907
H Phone: 239-275-4240
Fax: 239-275-3511
D111 www.tlc-engineers.com
© Copyright 2014 TLC Engineering for Architecture, Inc.
EB #0000015 TLC NO: 714125

Seal:
D105 D102
D104
TYP.
D102
G D102 G

D102
STAIR No. 1 STAIR No. 2
D102
D110

D102
D102
D102

D107
F D109 F
Project Phase:
D107
D109 D102
D107
D109
D102
Construction
D102
Documents
D102 Project #: 0118.22
Project Issued: 11/05/14
D102
Sheet Issued:

E E
No. Date Revision
D105

D104
TYP.

D111

D D

D106 TYP.
D108 TYP.

C C

Copyright © 2014. BSSW Architects, Inc.


reserves copyright and other rights
restricting these documents to the original
site or purpose for which they were
prepared. Reproductions, changes or
B B assignments are prohibited.

Sheet Title:

Brett L. Sands, P.E. 5TH FLOOR


Florida License #48477
DEMOLITION PLAN -
ELECTRICAL
Sheet No.
A A

1
E101
5TH FLOOR - DEMOLITION - ELECTRICAL E101
1/8" = 1'-0" Seal

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

C:\Users\mark.hauser\Documents\714125_LCJC ANNEX 5TH FL_MEP CENTRAL_R14_mark.hauser.rvt 1/8/2015 8:10:43 AM


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 8.9 9 10 GENERAL NOTES:


M M
1. ALL LIGHT FIXTURES SHALL BE CIRCUITED TO EXISTING PANEL `H3' UNLESS NOTED
OTHERWISE. ALL LIGHT SWITCHES SHALL BE 277V RATED U.O.N.

2. COORDINATE EXACT LOCATION OF EACH LIGHT FIXTURE WITH MECHANICAL PIPING,


CONDUIT, HVAC GRILLES, etc. FIELD ADJUST ANY LIGHT TO AVOID CONFLICT.

3. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT TYPE AND HEIGHT
OF CEILING IN EACH ROOM. COORDINATE WITH ARCHITECT/ENGINEER PRIOR TO A R C H I T E C T S I N C
ROUGH-IN OF ANY FIXTURES. COORDINATE ALL CONTROL JOINTS LOCATIONS WITH
LIGHT FIXTURES PRIOR TO ANY ROUGH-IN OF FIXTURES.
License # AA C001863

1500 Jackson Street, Suite 200


L
A 4. ALL ELECTRICAL CONTROL DEVICES SHALL BE MOUNTED AT A HEIGHT THAT IS
ACCESSIBLE TO THE DISABLED IN ACCORDANCE WITH THE FLORIDA ACCESSIBILITY L Fort Myers, Florida 33901
CODE. REFER TO ELECTRICAL SHEET E000 FOR MOUNTING HEIGHTS OF ELECTRICAL Phone: 239-278-3838 Fax: 239-275-5356
CONTROL DEVICES.
949 Central Ave.
5. PROVIDE CONDUIT AND WIRING AS REQUIRED TO MEET CIRCUITING SHOWN TO
B2 Naples, Florida 34102
B2 B2 B2 B2 B2 CONFORM TO NEC REQUIREMENTS. PROVIDE EQUIPMENT GROUND CONDUCTOR IN
ALL RACEWAYS. Phone: 239-643-3103 Fax: 239-643-7435
B2 E2
E2 B2 6. MULTIPLE LIGHT SWITCHES, AT THE SAME LOCATION, SHALL BE GANGED TOGETHER Project:
UNDER ONE COVER PLATE. DIMMER SWITCHES SHALL BE INSTALLED IMMEDIATELY

PUBLIC
E2 BELOW SWITCH LOCATIONS.
E2
B
B2
DEFENDER'S
B2 E2 B2 E2
K K
B2
# KEYNOTES:
OFFICE - 5TH
B2
1. EXISTING AREA LIGHTING TO REMAIN. (NO WORK)
N1 N1
E2 E2

FLOOR
2. EXISTING ELECTRICAL ROOM. PANEL LOCATIONS ARE SHOWN IN THE ROOM
B2 C ENLARGEMENT ON E102.
B2 3. ALL CORRIDOR AND OPEN OFFICE AREA FIXTURES TO BE WIRED THRU LIGHTING
B2 CONTACTOR CONTROLLED BY BUILDING EMS SYSTEM. PROVIDE OVER-RIDE
B2 E2 E2 SWITCHES IN LOCATIONS NOTED. SEE PANEL SCHEDULES AND DETAIL DRAWINGS
FOR MORE INFORMATION. SHADED FIXTURES ARE ON EMERGENCY LIGHTING
B2 CIRCUITS. PROVIDE "EM" BYPASS RELAY FOR SWITCH OVERRIDE IN EMERGENCY MODE Owner:

J
B2
E2
N1 N1
E2 D
DURING POWER LOSS.
J Lee County Board
B2 4. PROVIDE SEPARATE SLIDER DIMMER(S) AS INDICATED. DIMMERS TO BE SIZED
B2
E2 E2
APPROPRIATELY FOR LOAD SERVED. COLOR TO MATCH OTHER DEVICES. MOUNT
DIMMERS IN SEPARATE BOXES TO ACCOMMODATE HEAT.
of County
5. NEW BATHROOM LIGHTING TO REPLACE EXISTING AS INDICATED. CONNECT TO
CIRCUITS INDICATED AND SWITCH AS SHOWN.
Commissioners
B2 B2 B2
B2 6. ALL DOWNLIGHTS SHOWN ON THIS PLAN ARE TO BE TYPE "D" UNLESS NOTED
E2 E2 OTHERWISE. SEE FIXTURE SCHEDULE ON DRAWING `E301'. Consultant:
B2
B2 7. ALL EXIT LIGHT FIXTURES SHOWN ON THIS PLAN ARE TO BE CIRCUITED TO PANEL 13099 S. Cleveland Ave.
`HE3-4'.
Suite 500
B2 B2 B2 B2 B2 B2 8. EXISTING BATHROOM SCONCES TO REMAIN, CLEAN & RELAMP FIXTURES. CONNECT TO Fort Myers, Florida 33907
B2 CIRCUITS INDICATED AND SWITCH AS SHOWN. H
H B2 E2 E2 Phone: 239-275-4240
B2 B2
Fax: 239-275-3511
B2 B2 B2 B2 B2 B2 B2 www.tlc-engineers.com
B2
E © Copyright 2014 TLC Engineering for Architecture, Inc.
B2 B2 B2 EB #0000015 TLC NO: 714125
B2 E2 E2
B2
B2 Seal:
B2 B2 B2 B2 B2 B2 B2 B2 B2
B2
E2 E2 B2

E2 B2 E.5
G B2 E2 G
N1
OPEN TO
B2 E2 ABOVE E2 B2
B2 B2 B2
N1 N1 N1

B2 B2 B2 B2
B2 B2
B2 E2 N1 N1 N1 E2
E2 B2
OPEN TO OPEN TO
ABOVE EXISTING ABOVE
CEILING
TO REMAIN
F
F B2 E2 B2 B2 E2 B2 F
Project Phase:

Construction
B2
OPEN TO N1 N1 N1
B2 ABOVE
B2 B2
Documents
B2 B2
F.3
B2 E2 N1 N1 N1 E2 B2
B2
OPEN TO Project #: 0118.22
ABOVE OPEN TO N1 E2 B2 B2 Project Issued: 11/05/14
B2 ABOVE
B2 B2 Sheet Issued:
B2 B2 B2 E2 E2 B2

E F.7 E
No. Date Revision
E2 B2 B2 B2 B2 B2 B2 B2 B2 B2 B2 B2 E2
B2
B2

B2 B2 B2
E2 B2 B2 B2 B2 E2
B2
B2 G
B2
B2 B2 B2
B2 B2 B2 E2 B2
D E2 D
B2 B2 B2
B2 B2
B2 B2
E2 B2

B2
B2
G.8
E2 B2 B2 B2
B2
B2 B2 B2
E2
H
E2 B2 B2 B2 B2
C B2 B2 B2 C

E2 B2 B2 B2 B2
B2 B2

Copyright © 2014. BSSW Architects, Inc.


reserves copyright and other rights
restricting these documents to the original
site or purpose for which they were
prepared. Reproductions, changes or
B B assignments are prohibited.

Sheet Title:

Brett L. Sands, P.E. 5TH FLOOR PLAN -


Florida License #48477
LIGHTING
3.5 3.9 4.8 6.2 6.9 7.5
Sheet No.
A A

1
E102
5TH FLOOR - LIGHTING
1/8" = 1'-0" Seal
E102
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

C:\Users\mark.hauser\Documents\714125_LCJC ANNEX 5TH FL_MEP CENTRAL_R14_mark.hauser.rvt 1/8/2015 8:10:40 AM


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 8.9 9 10 GENERAL NOTES:


M M
1. REFER TO MECHANICAL DRAWINGS FOR EXACT LOCATION OF ALL MECHANICAL
EQUIPMENT.
2. REFER TO ELECTRICAL DETAIL DRAWINGS FOR MOUNTING HEIGHTS OF ALL WALL
MOUNTED ELECTRICAL DEVICES.
3. PROVIDE CONDUIT/WIRING AS REQUIRED TO MEET CIRCUITING SHOWN TO
CONFORM TO N.E.C. REQUIREMENTS. PROVIDE EQUIPMENT GROUND CONDUCTOR A R C H I T E C T S I N C
IN ALL RACEWAYS. License # AA C001863
4. ALL WIRING OVER 100' IN LENGTH SHALL BE #10 AWG.
1500 Jackson Street, Suite 200
A Fort Myers, Florida 33901
L 5. ALL NEW FIRE ALARM DEVICES SHALL MATCH EXISTING (3RD FLOOR) TYPE AND BE L
COMPATIBLE WITH EXISTING FIRE ALARM SYSTEM. "SIMPLEX - TRUE ALARM" Phone: 239-278-3838 Fax: 239-275-5356
DEVICE.
949 Central Ave.
ADP 14 BREAK ROOM ADP 13 6. ALL EXISTING CABLE RENDERED "ABANDONED" SHALL BE REMOVED ENTIRELY. ANY Naples, Florida 34102
CABLE LEFT IN PLACE (NOT USED) SHALL BE TAGGED WITH LABELS INDICATING Phone: 239-643-3103 Fax: 239-643-7435
72 35 47
"FUTURE USE" WITH IDENTIFICATION AT BOTH ENDS.
Project:

APD 15
ALIGN ALIGN B PUBLIC
DEFENDER'S
APD 12
K 70 K
44 # KEYNOTES:
APD 16
1. FLUSH, WALL MOUNTED J-BOX, FOR NORMAL POWER CONNECTION TO MODULAR OFFICE - 5TH
APD 11 FURNITURE.
73 J 64 C
2. FLUSH, WALL MOUNTED J-BOX, FOR VOICE/DATA CABLING. PROVIDE (1) 1" CONDUIT TO
FLOOR
ABOVE CEILING SPACE. PROVIDE BUSHING ON END OF CONDUIT WITH PULL STRING.

APD 10 3. FLUSH, WALL MOUNTED J-BOX, FOR VOICE/DATA CABLING CONNECTION TO MODULAR Owner:
APD 17
J 71
45
D
FURNITURE. PROVIDE (2) 1" CONDUITS TO ABOVE CEILING SPACE. PROVIDE BUSHING ON
END OF CONDUIT WITH PULL STRING. J Lee County Board
4. TELECOMM. SERVICES TO POKE-THRUS REQUIRES (2) 3/4" CONDUITS
of County
TRAINING
38
APD 9 5. 20A/125V. SIMPLEX OUTLET FOR COPIER/FAX UNIT, COORDINATE DEVICE
Commissioners
APD 18 STOR / EQUIP STOR/EQUIP 23 REQUIREMENTS WITH OWNER.
69 39 40 Consultant:
6. FURNITURE MOUNTED DEVICE. CIRCUIT AS INDICATED ON THIS PLAN. LOCATION AND
AMOUNT OF DEVICES SET BY SYSTEM FURNITURE SUPPLIER. COORDINATE FURNITURE 13099 S. Cleveland Ave.
WIRING ACCESS LOCATIONS WITH VENDOR PRIOR TO ROUGH-IN. Suite 500
APD 19 APD 8
H
Fort Myers, Florida 33907
68 INVEST. 2 INVEST. 3 INVEST. 4 INVEST. 5 INVEST. 6 INVEST. 7 INVEST. 8 INVEST. 9 22
H 7. SWITCH FOR MOTORIZED PROJECTION. VERIFY REQUIREMENTS WITH SUPPLIER/ Phone: 239-275-4240
43 34 33 36 61 41 60 63 INSTALLER. Fax: 239-275-3511
www.tlc-engineers.com
8.E COORDINATE LOCATION OF DETECTORS WITH OTHER CEILING DEVICES. © Copyright 2014 TLC Engineering for Architecture, Inc.
APD 20 APD7 EB #0000015 TLC NO: 714125
67 21 9. PROVIDE SINGLE GANG J-BOX WITH BLANK COVER PLATE AT 48" A.F.F. FOR FUTURE
SECURITY ACCESS CONTROL. (BY OTHERS) RUN 3/4"C IN WALL TO J-BOX ABOVE DOOR
HEADER. Seal:
ALIGN ALIGN ALIGN APD 6
10. PROVIDE FIRE ALARM RELAY TO INTERFACE WITH THE ACCESS CONTROL SYSTEM.
APD 21 20
COORDINATE LOCATION OF AND CONNECITON TO RELAY WITH THE SECURITY SYSTEM
66 E.5 SUPPLIER/INSTALLER. PROVIDE (4) 20A CIRCUITS FOR SECURITY EQUIP.
G J
J G
11. PROVIDE J-BOX RECESSED UNDER COUNTER FOR OVER RIDE BUTTON. RUN 3/4"C. BACK
INVEST. 1 TO ELECTRICAL ROOM.
MECH. MEN'S INVEST. 10
88 89 87 12. PROVIDE J-BOX RECESSED UNDER COUNTER FOR SECURITY ASSISTANCE
SS/10 91
APD 22 SS/9 APD 5
NOTIFICATION. RUN 3/4"C BACK TO ELECTRICAL ROOM.
65 SS/9 19
13. ALL EQUIPMENT, INCLUDING FIRE ALARM SYSTEM PANEL & TRANSFORMER
SUSPENDED FROM STRUCTURE OVERHEAD, IS EXISTING TO REMAIN U.O.N., SEE
DRAWING `E301' FOR PANEL INFORMATION.
ELEVATOR 14.
SS/11 PROVIDE CEILING RECEPTACLE AND J-BOX FOR TELECOM CONNECTION TO
LOBBY (E) WORKROOM
SS/8 F OVERHEAD PROJECTOR. COORDINATE ADDITIONAL A/V CONDUIT REQUIREMENTS
F 501E 24 WITH OWNER. F
SS/8 Project Phase:
ELEC.
Construction

J
APD 4 15. PROVIDE NEW 15KVA TRANSFORMER AND 120/208V PANEL `L3E'. SEE PANEL
ADP 23

J
92 SCHEDULES FOR MORE DETAILS.
F.3
Documents
58 WOMENS 18
WORKROOM J J J
29 90 16. OUTLETS MOUNTED LOW IN WALL BELOW GLAZING.
SS/12 IDE 17. J-BOXES ABOVE CEILING FOR VOICE, DATA AND POWER FEED INTO MODULAR Project #: 0118.22
94 JAN. FURNITURE VIA POWER POLE.
SS/6 SS/7 Project Issued: 11/05/14
APD 24 93 APD 3
SS/6 SS/7 Sheet Issued:
76 17

E ALIGN ALIGN
F.7 E
No. Date Revision

APD 25 APD 2
75 SS/2 16

J J
RECEPT. COPY/
PRINT/
2 WORK AREA SS/3 SS/4 SS/5 APD 1 G
ADP 26 CONF. ROOM

J
74
3 95

J
D Work Stations D
ADP 27
SS/1 501F
78 ADMIN.
15

G.8
ADMIN.
14
PUBLIC CONFERENCE CHIEF ASSIT.
DEFENDER ROOM PD ADMIN. ADMIN. H
4 6 7 12 13
C C

Copyright © 2014. BSSW Architects, Inc.


reserves copyright and other rights
restricting these documents to the original
site or purpose for which they were
prepared. Reproductions, changes or
B B assignments are prohibited.

Sheet Title:

Brett L. Sands, P.E. 5TH FLOOR PLAN -


Florida License #48477
POWER & SYSTEMS
3.5 3.9 4.8 6.2 6.9 7.5
Sheet No.
A A

1
E103
5TH FLOOR - POWER
1/8" = 1'-0" Seal
E103
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

C:\Users\mark.hauser\Documents\714125_LCJC ANNEX 5TH FL_MEP CENTRAL_R14_mark.hauser.rvt 1/8/2015 8:10:01 AM


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

M M

A R C H I T E C T S I N C
License # AA C001863

1 1500 Jackson Street, Suite 200


PANEL "HPx" Fort Myers, Florida 33901
L L
WATT STOPPER WA-200 OR Phone: 239-278-3838 Fax: 239-275-5356
PROVIDE PLATES AND CONNECTORS AS REQUIRED FOR 3 APPROVED EQUIVALENT
DEVICES AS SHOWN ON FLOOR PLANS. COORDINATE PLATES 949 Central Ave.
WITH TELECOMM CONTRACTORS. Naples, Florida 34102
BLUE
PROVIDE DUPLEX RECEPTACLES AS SHOW ON FLOOR PLANS. REFER TO Phone: 239-643-3103 Fax: 239-643-7435
TECHNOLOGY DRAWINGS FOR TELECOMM REQUIREMENTS. PROVIDE 2 BLACK
HOT (BLACK)
WIREMOLD POKE THRU #6AT. Project:
BLACK
LINE
277VAC,60Hz
LOAD
PUBLIC
DEFENDER'S
GREEN
K GROUND K
NEUTRAL (WHITE) WHITE
OFFICE - 5TH
PLAN SYMBOL = SO
FLOOR
NOTES: GROUND
PANEL "HPx"
277V,
NEUTRAL (WHT) LIGHTING Owner:
1 WALL ASSEMBLY - THE 1, 2, 3, OR 4 HOUR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE LOAD
Lee County Board
60HZ HOT (BLK)
J CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES J
WALL OR PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY.
of County
CONDUIT - NOM 4" DIA OR SMALLER STEEL ELECTRICAL METALLIC TUBING. A MAX OF ONE CONDUIT IS
2 PERMITTED IN THE FIRESTOP SYSTEM. CONDUIT TO BE INSTALLED NEAR CENTER OF STUD CAVITY WIDTH AND THE NUMBER OF DEVICES POWERED FROM A SINGLE Commissioners
TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. POWER PACK VARIES WITH THE TYPE OF DEVICE.
A SEPERATE POWER PACK IS REQUIRED FOR EACH
FILL VOID OR CAVITY MATERIAL - CAULK FILL MATERIAL BEARING THE UL CLASSIFICATION MARKING INSTALLED CIRCUIT BEING CONTROLLED. Consultant:
3 TO COMPLETELY FILL ANNULAR SPACE BETWEEN PIPE OR CONDUIT AND GYPSUM WALLBOARD AND WITH A MIN 13099 S. Cleveland Ave.
1/4" DIAM BEAD OF CAULK APPLIED TO PERIMETER OF CONDUIT AT ITS EGRESS FROM THE WALL. CAULK Suite 500
TYPICAL OVERRIDE SWITCH
INSTALLED SYMMETRICALLY ON BOTH SIDES OF WALL ASSEMBLY. THE HOURLY F RATING OF THE FIRESTOP POWER PACK
SYSTEM IS DEPENDENT UPON THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS CONTACTS H
Fort Myers, Florida 33907
PROVIDE WIREMOLD
H SHOWN IN THE FOLLOWING TABLE. THE HOURLY T RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON RED RATED FOR 20 AMPS.
Phone: 239-275-4240
EVOLUTION SERIES
Fax: 239-275-3511
6AT THE TYPE OR SIZE OF THE CONDUIT AND THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS RED www.tlc-engineers.com
PLAN SYMBOL INSTALLED, AS TABULATED BELOW:
BLACK RED 24 VDC
BLACK COMMON
© Copyright 2014 TLC Engineering for Architecture, Inc.
WHITE BLUE CONTROL EB #0000015 TLC NO: 714125
CONTROL (BLUE) TO 24 VDC (RED)
MAX CONDUIT ANNULAR SPACE, F RATING, HR. T RATING, HR. CLOSES OSP CONTACTS.
DIAM, IN. IN. POWER PACK Seal:

1 0 TO 3/16 1 OR 2 0, 1 OR 2
1 1/4 TO 1/2 3 OR 4 3 OR 4
4 0 TO 1-1/2 1 OR 2 0
G 6 1/4 TO 1/2 3 OR 4 0 PLAN SYMBOL = OS CEILING MOUNTED
DUAL TECHNOLOGY
G
12 3/16 TO 3/8 1 OR 2 0 OCCUPANCY
SENSOR

FLOOR POKE THRU OUTLET 1 CONDUIT PENETRATION OF FIREWALL 2 TYPICAL OCCUPANCY SENSOR WIRING DIAGRAM 3
No Scale UL SYSTEM NO. W-L-1001 No Scale

F F
3/4" CONDUIT TO LOCAL 4 HR. OVER-RIDE Project Phase:
SWITCHES LOCATED AT MAIN ENTRIES.
REFER TO LIGHTING FLOOR PLAN
FOR EXACT LOCATION.
Construction
Documents
EMS PANEL Project #: 0118.22
PANEL `H3' CENTERED BETWEEN
Project Issued: 11/05/14
DOOR & CEILING
N CLOCK OUTLET FIRE HORN (OR CHIME) & Sheet Issued:
20A C (COORDINATE WITH
LIGHT 80" AFF
E
TYP.
2 TO CORRIDOR/OPEN OFFICE AREA LIGHTS
WALL MOUNTED LIGHT FIXTURES
AS NOTED ON PLANS CL EXIT ARCHITECT)
E
No. Date Revision
TELEVISION
4 TO CORRIDOR/OPEN OFFICE AREA LIGHTS BOTTOM TV
OUTLET
OF DEVICE
6 TO CORRIDOR/OPEN OFFICE AREA LIGHTS
CL
8 TO CORRIDOR/OPEN OFFICE AREA LIGHTS
SPARE
SPARE CENTERED OVER DOOR RT REMOTE TEST VOLUME CONTROL VC
(WHERE APPLICABLE) 80"
PANELBOARD
90"
600V RATED LIGHTING CONTACTOR "LC-1" N.O. 20A, 277V. CONTACTS, DUPLEX CL
277V RECEPTACLE
D W D
COIL. NEMA 1 ENCLOSURE SQ.'D' CLASS 8903 'LG1200-VO4'
CL TELE. OUTLET

CL FA PULL F
6" AFC SWITCH STATION 54"
3/4" CONDUIT TO LOCAL 4 HR. OVER-RIDE
SWITCHES LOCATED AT MAIN ENTRIES.
48" DUPLEX
REFER TO LIGHTING FLOOR PLAN
FOR EXACT LOCATION. 78" MAX. RECEPTACLE
TO TOP DEVICE
1
36" TELE. OUTLET
COMPUTER
EMS PANEL AFF OUTLET
C PANEL `HE3' C
CL
20A N 18"
C
TYP. AFF
2 TO CORRIDOR/OPEN OFFICE AREA LIGHTS
SPARE
1 42" A.F.F. W/ 36" COUNTER, FINISHED FLOOR
SPARE 39" A.F.F. W/ 30" COUNTER, SPECIAL POWER OUTLET
48" A.F.F. WITHOUT COUNTER Copyright © 2014. BSSW Architects, Inc.
SPARE reserves copyright and other rights
OR AS NOTED ON PLANS
restricting these documents to the original
site or purpose for which they were
600V RATED LIGHTING CONTACTOR "LC-2" N.O. 20A, 277V. CONTACTS, prepared. Reproductions, changes or
B B assignments are prohibited.
277V
COIL. NEMA 1 ENCLOSURE SQ.'D' CLASS 8903 'LG1200-VO4' Sheet Title:

Brett L. Sands, P.E. ELECTRICAL DETAILS


Florida License #48477
CORRIDOR LIGHTING CONTROL DIAGRAM 4 MOUNTING HEIGHTS 5
No Scale No Scale

Sheet No.
A A

Seal
E201
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

C:\Users\mark.hauser\Documents\714125_LCJC ANNEX 5TH FL_MEP CENTRAL_R14_mark.hauser.rvt 1/8/2015 8:09:56 AM


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

M
FIRE PROTECTION LEGEND GENERAL NOTES M

APPLICABLE CODES AND STANDARDS SYMBOL DESCRIPTION 1. FIRE PROTECTION SYSTEM TO COMPLY WITH NFPA 13, 14, 20, 24 AND ALL APPLICABLE STATE CODES.
FIRE PROTECTION SYSTEM 2. FINAL INSPECTION AND APPROVAL BY LOCAL FIRE MARSHAL AND ARCHITECT/ENGINEER.
OR - CONTROL VALVE W/TAMPER SWITCH
- CHECK VALVE 3. SPRINKLER SHOP DRAWINGS AND MATERIAL SUBMITTALS SHALL BE SUBMITTED TO THE
FLORIDA ADMINISTRATIVE CODE 61G15 (2) (B) 1/06/05 A R C H I T E C T S I N C
ARCHITECT/ENGINEER AND STATE FIRE MARSHAL AND SHALL BE APPROVED PRIOR TO ANY
FLORIDA BUILDING CODE, 2007 EDITION - FLOW SWITCH License # AA C001863
INSTALLATION.
NFPA-13, 2007 EDITION
FDC - FIRE DEPARTMENT CONNECTION
NFPA-24, 2007 EDITION 1500 Jackson Street, Suite 200
4. PIPE ROUTING SHOWN IS SCHEMATIC ONLY. IT IS THE RESPONSIBILITY OF THIS CONTRACTOR TO
L PIV - POST INDICATOR VALVE W/TAMPER SWITCH L Fort Myers, Florida 33901
PROVIDE ANY ADDITIONAL OFFSETS REQUIRED FOR PROPER INSTALLATION AND COORDINATION WITH Phone: 239-278-3838 Fax: 239-275-5356
FVC - FIRE VALVE CABINET OTHER TRADES.

61G15 FAC COMPLIANCE NOTES FDV - STANDPIPE WITH FIRE DEPARTMENT VALVE
- SPRINKLER AND DRAIN RISER
5. PIPING IN AREAS WITH EXPOSED STRUCTURE SHALL BE INSTALLED AS HIGH AS POSSIBLE TO ALLOW THE
OWNER MAXIMUM USE OF THE SPACE.
949 Central Ave.
Naples, Florida 34102
Phone: 239-643-3103 Fax: 239-643-7435
- BACKFLOW PREVENTOR W/TAMPER SWITCHES 6. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR CEILING DESCRIPTIONS AND HEIGHTS.
61G15-32.003 Project:
- ROOF MANIFOLD

PUBLIC
7. SPRINKLERS ARE TO BE COORDINATED WITH ALL DIFFUSERS, SPEAKERS, LIGHTING FIXTURES AND
(2) ACCEPTANCE TEST CRITERIA - HYDRAULIC REFERENCE NODE CEILING SYSTEMS. SPACING OF SPRINKLERS SHALL BE IN ACCORDANCE WITH NFPA 13 AND THE LISTING
SHALL COMPLY WITH N.F.P.A. 13 2007 CHAPTER 16. SYSTEM ACCEPTANCE OF THE SPRINKLER.

DEFENDER'S
SECTION: - NEW SPRINKLER PIPING
K K
16.1 APPROVAL OF SPRINKLER SYSTEM. F.C. - FLUSHING CONNECTION 8. SPRINKLER LOCATIONS SHALL BE CENTERED IN THE TILE. PROVIDE ARMOVER OR SWING JOINT AS
16.2 ACCEPTANCE REQUIREMENTS.

OFFICE - 5TH
REQUIRED.
16.3 CIRCULATING CLOSED LOOP SYSTEM
16.4 INSTRUCTION 1 - REVISION REFERENCE
16.5 HYDRAULIC DESIGN INFORMATION SIGNS 9. SPRINKLERS IN AREAS WITH EXPOSED STRUCTURE (OBSTRUCTED CONSTRUCTION) SHALL BE INSTALLED

FLOOR
1 - DETAIL REFERENCE: TOP-DETAIL#, WITH DEFLECTOR 1" BELOW THE BOTTOM OF THE BEAM (MAXIMUM 22" BELOW ROOF DECK). EXPOSED
10.10.1 CONTRACTORS MATERIAL & TEST CERTIFICATE FOR UNDERGROUND
PIPING FP-1 BOTTOM-DRAWING# SHOWN ON BAR JOISTS THAT HAVE SPRAY-ON FIRE PROOFING THAT MAKES THE JOIST SOLID SHALL BE TREATED
LIKE A BEAM WITH THE SPRINKLERS 1" BELOW THE BOTTOM OF THE FIRE PROOFING.

(5) STRUCTURAL SUPPORT COORDINATION: NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT 10. SLEEVE AND/OR FIRESTOP ALL PENETRATIONS THROUGH RATED WALLS, CEILINGS, AND FLOORS WITH
THIS IS AN EXISTING STRUCTURE THERE ARE NO ADDITIONAL LIVE AND DEAD LOADS THAT ARE REQUIRED FOR THE U/L LISTED ASSEMBLIES. FIRESTOP ASSEMBLIES SHALL BE EQUAL OR EXCEED THE RATING OF THE WALL, Owner:

Lee County Board


MODIFICATION OF THE EXISTING SPRINKLER SYSTEM. CEILING OR FLOOR. SEE ARCHITECTURAL DRAWINGS FOR FINAL FINISHES.
J J
61G15-32.004 (2)
11. PROVIDE ACCESS PANELS TO ALL VALVES ABOVE NON-ACCESSIBLE CEILINGS AND CHASES.
of County
(A) POINT OF SERVICE:
THE POINT OF SERVICE IS A EXISTING 6" FIRE MAIN THE ENTERS THE BUILDING. THERE IS AN EXISTING
12. PROVIDE A PERMANENTLY ATTACHED NAME TAG TO THE RISER STATING THE REQUIRED DESIGN
CRITERIA FOR EACH HYDRAULICALLY-DESIGNED SYSTEM.
Commissioners
ELECTRIC
FIRE PUMP. THIS WILL REMAIN ACTIVE THOUGHT OUT THE RENOVATION. 13. PROVIDE SPRINKLERS UNDERNEATH ALL EXPOSED DUCTWORK WHICH IS OVER 48" WIDE AND SPACE Consultant:
(C) CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR AREA: HEADS AROUND ALL OBSTRUCTIONS IN ACCORDANCE WITH NFPA 13. HEADS UNDER DUCTS ARE NOT
LIGHT HAZARD: RESTROOMS, OFFICE AREAS, CONFRENCE ROOMS, BREAK ROOMS AND SMALL CLOSTES INDICATED ON THE DRAWINGS BUT ARE REQUIRED AND SHALL BE PROVIDED IN ACCORDANCE WITH 13099 S. Cleveland Ave.
ORDINARY HAZARD GROUP 1: MECHANICAL ROOMS AND ELECTRICAL ROOMS NFPA 13. SPRINKLER LOCATIONS UNDER DUCTWORK AND AROUND OBSTRUCTIONS SHALL BE GOVERNED Suite 500
BY FINAL INSTALLED LOCATIONS.
H
Fort Myers, Florida 33907
LIGHT HAZARD : Phone: 239-275-4240
H
SPRINKLER SYSTEM TO BE ATTACHED AND SUPPLIED FROM SPRINKLER RISER STANDPIPE. SYSTEM SHALL BE EXTENDED Fax: 239-275-3511
INTO ENTIRE BUILDING IN ACCORDANCE WITH NFPA-13. U.L, LIGHT HAZARD. LISTED AND APPROVED UPRIGHTS & PENDANTS 14. PROVIDE SPRINKLER GUARDS ON ALL HEADS IN ELECTRIC ROOMS, TELEPHONE ROOMS, ELEVATOR www.tlc-engineers.com
(5.6 K-FACTOR) SPRINKLER HEADS TO BE USED. HEADS SHALL BE RATED AT 155 DEGREES. MAX. SPRINKLER HEAD SPACING ROOMS, ELEVATOR SHAFTS AND ON ANY HEADS LESS THAN 7'-0" ABOVE THE FLOOR. © Copyright 2014 TLC Engineering for Architecture, Inc.
SHALL NOT EXCEED 225 SQ FT WITH A .10 DENSITY SPRINKLER CONTRACTOR SHALL PROVIDE HYDRAULIC CALCULATION. 1500
EB #0000015 TLC NO: 714125
SQ FT SHALL BE USED WHEN PERFORMING HYDRAULIC CALCULATIONS. PROVIDE INTERMEDIATE TEMP SPRINKLER HEADS IN 15. IF SYSTEM PRESSURE EXCEEDS 100 PSI, ALL HANGERS ON END HEADS IN PENDANT POSITION SHALL BE
ATTIC AREA. WITHIN 12" OF END OF LINE IN ACCORDANCE WITH NFPA 13.
ORDINARY HAZARD GROUP 1 : Seal:
SPRINKLER SYSTEM TO BE ATTACHED AND SUPPLIED FROM SPRINKLER RISER STANDPIPE. SYSTEM SHALL BE EXTENDED 16. COORDINATE PIPING WITH ALL ELECTRICAL EQUIPMENT (PANELS, TRANSFORMERS, ETC.) PRIOR TO ANY
INTO ENTIRE BUILDING IN ACCORDANCE WITH NFPA-13. U.L, LIGHT HAZARD. LISTED AND APPROVED UPRIGHTS & PENDANTS INSTALLATION. DO NOT ROUTE ANY PIPING OVER ANY ELECTRICAL PANELS UNDER ANY
(5.6 K-FACTOR) SPRINKLER HEADS TO BE USED. HEADS SHALL BE RATED AT 155 DEGREES. MAX. SPRINKLER HEAD SPACING CIRCUMSTANCES. ANY PIPING RUN OVER ELECTRICAL SHALL BE REROUTED AT NO ADDITIONAL COST.
SHALL NOT EXCEED 130 SQ FT WITH A .15 DENSITY SPRINKLER CONTRACTOR SHALL PROVIDE HYDRAULIC CALCULATION. 1500
G 17. WET BULK SUPPLY MAINS AND HOSE SUPPLY MAINS EXPOSED TO THE WEATHER SHALL BE INSULATED G
SQ FT SHALL BE USED WHEN PERFORMING HYDRAULIC CALCULATIONS.
AND PROVIDED WITH AN ALUMINUM JACKET.

(F) FLOW TEST DATA:


THE SPRINKLER CONTRACTOR SHALL PROVIDE A CURRENT FIRE FLOW TEST AT THE TIME OF SHOP DRAWING
SUBMITTAL. HYDRAULIC CALCULATIONS SHALL ALSO BE PERFORMED BY THE CONTRACTOR DEMONSTRATING
THAT
THERE IS ADEQUATE AMOUNT OF FIRE FLOW FOR THE NEWLY RENOVATED FLOOR.

(G) VALVING AND ALARM REQUIREMENTS TO MINIMIZE POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF WATER:
THE EXISTING FIRE SPRINKLER RISER IS EQUIPPED WITH A WATER FLOW SWITCH WITH A LOCAL ALARM AND OFF-
F SITE F
Project Phase:

Construction
MONITORING. THE BACKFLOW PREVENTION DEVICE IS EXISTING.
(H) MICROBIAL INDUCED CORROSION (MIC):
THE LOCAL WATER PURVEYOR, LEE COUNTY PUBLIC UTILITIES, ACKNOWLEDGES THAT THE WATER SERVICE
PROVIDED MEETS OR EXCEEDS STATE AND FEDERAL CORROSION WATER CONTROL QUALITY PARAMETERS.
ADDITIONALLY, THE PURVEYOR ACKNOWLEDGES THAT NO SPECIFIC TESTING GUIDELINES FOR MIC PRESENTLY
Documents
EXIST. AS SUCH THE INSTALLING FIRE SPRINKLER CONTRACTOR SHALL MAKE PIPE AND FITTING SELECTIONS Project #: 0118.22
BASED ON THIS INFORMATION AND IN ACCORDANCE WITH NFPA 13, (2002 EDITION), CHAPTER 8, SUBSECTION
8.15.3.2.2; CHAPTER 15, SUBSECTION 15.1.5; AND ANNEX A, SUBSECTION A.15.1.5. Project Issued: 11/05/14
Sheet Issued:

E (I) BACKFLOW PREVENTION AND METERING SPECIFICATIONS: E


No. Date Revision
IS EXISTING AND SHALL REMAIN.

(J) QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD AND INTERIOR FIRE PROTECTION COMPONENTS:
ALL NEW YARD AND INTERIOR FIRE PROTECTION EQUIPMENT SHALL BE UL LISTED AND FM APPROVED.
SCOPE OF WORK: THIS BUILDING HAS WITH A EXISTING SPRINKLER AND STANDPIPE SYSTEM PER NFPA 13 AND 14. THE
SPRINKLER SYSTEM SHALL BE MODIFIED ON THE 3RD FLOOR TO ACCOMMODATE THE NEW WALLS AND CEILINGS. THE
SYSTEM SHALL BE HYDRAULICALLY CALCULATED BY THE SPRINKLER CONTRACTOR. SHOP DRAWING ARE REQUIRED TO
BE APPROVED PRIOR TO INSTALLING BY THE OWNER, AHJ, ARCHITECT AND THE ENGINEERS. UPON COMPELLATION THE
SYSTEM SHALL BE HYDROSTATICALLY TESTED PER THE LOCAL AHJ.
D D

C C

Copyright © 2014. BSSW Architects, Inc.


reserves copyright and other rights
restricting these documents to the original
site or purpose for which they were
prepared. Reproductions, changes or
B B assignments are prohibited.

Sheet Title:

Lawrin T. Ellis, P.E. FIRE PROTECTION


Florida License #66383
SYMBOL LEGEND,
GENERAL NOTES &
A A INDEX
Sheet No.

Seal
F001
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

C:\Users\mark.hauser\Documents\714125_LCJC ANNEX 5TH FL_MEP CENTRAL_R14_mark.hauser.rvt 1/8/2015 8:09:55 AM


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

M
HVAC SYMBOL LEGEND HVAC ABBREVATIONS GENERAL NOTES M
SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION
1. CONNECTION TO EQUIPMENT SHALL BE VERIFIED WITH MANUFACTURER'S CERTIFIED
AFD -ADJUSTABLE FREQUENCY DRIVE MCA -MINIMUM CIRCUIT AMPS
-EXHAUST DUCT UP THROUGH SLAB W/FAN UP DN DRAWINGS. TRANSITIONS TO ALL EQUIPMENT SHALL BE VERIFIED AND PROVIDED FOR
ON ROOF ABOVE -FIRE DAMPER AFF -ABOVE FINISHED FLOOR MOCP -MAXIMUM OVER CURRENT PROTECTION EQUIPMENT FURNISHED.
-CHANGE OF ELEVATION
(WITH ACCESS PANEL)
AFR -ABOVE FINISHED ROOF MOD -MOTOR OPERATED CONTROL DAMPER (MOD) 2. DIMENSIONS SHALL BE FIELD-VERIFIED AND COORDINATED PRIOR TO PROCUREMENT OR
-EXHAUST FAN ON ROOF W/DUCT DOWN -FLEXIBLE DUCT FABRICATION. COORDINATE THE WORK WITH OTHER TRADES INVOLVED. FIELD
A R C H I T E C T S I N C
AHU -AIR HANDLING UNIT
THROUGH ROOF -FIRE & SMOKE DAMPER NC -NORMALLY CLOSED MODIFICATIONS SUCH AS OFFSETS IN PIPING OR DUCTWORK (INCLUDING DIVIDED License # AA C001863
(WITH ACCESS PANEL) AP -ACCESS PANEL DUCTWORK) NEEDED DUE TO OBSTRUCTIONS OR INTERFERENCES SHALL BE PROVIDED AT
-TRANSITION, CONCENTRIC NO -NORMALLY OPEN
-OUTSIDE AIR DUCT UP THROUGH SLAB W/FAN
BOP -BOTTOM OF PIPE NO ADDITIONAL COST. FOR PROJECTS INVOLVING RENOVATION, COORDINATE NEW WORK 1500 Jackson Street, Suite 200
L ON ROOF ABOVE NTS -NOT TO SCALE WITH EXISTING ELEMENTS SUCH AS THE BUILDING STRUCTURE AND ARCHITECTURAL L Fort Myers, Florida 33901
-EXISTING FIRE DAMPER TO REMAIN -TRANSITION, ECCENTRIC BHP -BRAKE HORSEPOWER FEATURES, SPRINKLER PIPING, LIGHTS, PLUMBING, AND ELECTRICAL CONDUIT. Phone: 239-278-3838 Fax: 239-275-5356
OA -OUTSIDE AIR
-OUTSIDE AIR FAN ON ROOF W/DUCT DOWN
BTU -BRITISH THERMAL UNIT
THROUGH ROOF 10x8 8 -TRANSITION, SQUARE TO ROUND OAL -OUTSIDE AIR LOUVER 949 Central Ave.
-EXISTING FIRE & SMOKE DAMPER TO REMAIN
h -CENTER LINE
3. Naples, Florida 34102
PRV -PRESSURE REDUCING VALVE DUCT CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE
Phone: 239-643-3103 Fax: 239-643-7435
-SQUARE THROAT ELBOW c -CFM (CUBIC FEET PER MINUTE) SMACNA HVAC DUCT CONSTRUCTION STANDARD.
-CEILING DIFFUSER, ROUND NECK PRS -PRESSURE REDUCING STATION
(CEILING DIFFUSERS ARE 4-WAY THROW UNO)
W/TURNING VANES
SA-1 -SOUND ATTENUATOR CD -CEILING DIFFUSER 4. SEE SPECIFICATIONS FOR GAUGES, THICKNESS, BRACING, REQUIREMENTS, ETC., OF Project:
PSI -POUNDS PER SQUARE INCH
DUCTWORK.

PUBLIC
CT -COOLING TOWER
PSIG -PSI GAUGE
-ROUND DIFFUSER -MOTOR OPERATED CONTROL DAMPER (MOD) CV -CONSTANT AIR VOLUME 5. PROVIDE AIR TURNING VANES IN ALL LOW PRESSURE 90 DEGREE RECTANGULAR
-RADIUS ELBOW PTAC -PACKAGED TERMINAL AIR CONDITIONER DUCT ELBOWS.
K
-CEILING RETURN
M

FM -AIR FLOW MEASURING STATION


CFM
CU
-CUBIC FEET PER MINUTE
-CONDENSING UNIT
PVC -POLYVINYL CHLORIDE PIPE
6. DUCT SIZES AND ALL OPENINGS THROUGH BUILDING CONSTRUCTION SHALL SUIT
K
DEFENDER'S
RA -RETURN AIR EQUIPMENT FURNISHED.
-CEILING EXHAUST
-RECTANGULAR/ROUND BRANCH TAKE-OFF
OR ROUND/ROUND BRANCH TAKE-OFF
DDC -DIRECT DIGITAL CONTROLS
RHC -REHEAT COIL 7. COORDINATE DIFFUSER, GRILLE AND REGISTER LOCATIONS WITH ARCHITECTURAL OFFICE - 5TH
DN -DOWN
FLOOR
-MANUAL BALANCING DAMPER RHP -ROOFTOP HEAT PUMP REFLECTED CEILING PLANS AND EQUIPMENT OF ALL TRADES.
-CEILING DIFFUSER, RECTANGULAR OR
EAT -ENTERING AIR TEMPERATURE RPM -REVOLUTIONS PER MINUTE
SQUARE NECK (CEILING DIFFUSERS -DOOR GRILLE 8. LOCATE TEMPERATURE SENSORS, HUMIDITY SENSORS AND CARBON DIOXIDE SENSORS AT 48"
ARE 4-WAY THROW UNO) -SQUARE THROAT TEE ESP -EXTERNAL STATIC PRESSURE ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE. COORDINATE LOCATIONS WITH OTHER
RS/L -REFRIGERANT SUCTION & LIQUID LINES
EQUIPMENT, FURNITURE, AND DOOR SWINGS.
EWT -ENTERING WATER TEMPERATURE RTU -ROOFTOP AIR HANDLING UNIT
-SUPPLY REGISTER OR GRILLE 9. ALL EQUIPMENT, DUCTWORK, ETC., SHALL BE SUPPORTED AS DETAILED AND/OR Owner:
FCU -FAN COIL UNIT

UC
(VERTICAL MOUNT, SIDEWALL) -UNDERCUT DOOR SA -SUPPLY AIR
J FD -FIRE DAMPER SP -STATIC PRESSURE
SPECIFIED. PROVIDE ADDITIONAL SUPPORTS AS REQUIRED TO PROVIDE A
VIBRATION-FREE, RIGID INSTALLATION. J Lee County Board
-RETURN/EXHAUST REGISTER OR GRILLE
(VERTICAL MOUNT, SIDEWALL)
-ACCESS DOORS, VERTICAL OR HORIZONTAL
12x8 -RADIUS TEE FF -FINAL FILTERS
TSP -TOTAL STATIC PRESSURE 10. ALL DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS. of County
FLA -FULL LOAD AMPS UNO -UNLESS NOTED OTHERWISE 11. DAMPERS AND INSIDES OF DUCTS VISIBLE THROUGH GRILLES, REGISTERS AND Commissioners
1 -REVISION REFERENCE -STAINLESS STEEL DUCTWORK FPM -FEET PER MINUTE DIFFUSERS SHALL BE PAINTED FLAT BLACK.
V/PH -VOLTS/PHASE
1 -DETAIL REFERENCE: TOP - DETAIL#; -RECTANGLE-TO-ROUND TAKE-OFF GPM -GALLONS PER MINUTE 12. REFER TO TYPICAL DETAILS FOR PIPING, DUCTWORK AND INSTALLATION OF EQUIPMENT. Consultant:
-FLEXIBLE CONNECTION VAV -VARIABLE AIR VOLUME
M-1 BOTTOM - DRAWING# SHOWN ON
KW -KILOWATT 13. TRAPPED CONDENSATE DRAINS FROM ALL MECHANICAL EQUIPMENT SHALL BE 13099 S. Cleveland Ave.
VFD -VARIABLE FREQUENCY DRIVE
T -THERMOSTAT/TEMPERATURE SENSOR 12x8 LAT -LEAVING AIR TEMPERATURE PROVIDED FOR PROPER DRAINAGE TO SUIT EQUIPMENT FURNISHED. Suite 500
-FLAT OVAL DUCT -STANDARD BRANCH TAKE-OFF P -CHANGE IN PRESSURE
-LEAVING WATER TEMPERATURE 14. ACCESS PANELS IN DUCTWORK AND CEILINGS SHALL BE PROVIDED WHERE H
Fort Myers, Florida 33907
H -HUMIDISTAT/HUMIDITY SENSOR LWT
H 24x12 T -CHANGE IN TEMPERATURE REQUIRED FOR OPERATION, BALANCING OR MAINTENANCE OF ALL MECHANICAL Phone: 239-275-4240
-NEW DUCTWORK, FIRST DIMENSION IS SIDE SHOWN
-SPIN-IN TAKE-OFF LD -LINEAR DIFFUSER EQUIPMENT. Fax: 239-275-3511
-DUCT SMOKE DETECTOR www.tlc-engineers.com
24x12 -EXISTING DUCTWORK TO REMAIN MBH -THOUSAND BTUs PER HOUR © Copyright 2014 TLC Engineering for Architecture, Inc.
15. ALL DUCTWORK AND PIPING IS SHOWN SCHEMATICALLY. PROVIDE ALL TRANSITIONS,
-CONNECT TO EXISTING
TURNING VANES, ELBOWS, FITTINGS, ETC., TO ALLOW SMOOTH FLOWS. ALL SPLIT DUCT EB #0000015 TLC NO: 714125
24x12 -EXISTING DUCTWORK TO BE REMOVED FITTINGS SHALL TRANSITION TO FULL SIZE OF THE SUM OF BOTH BRANCHES, UPSTREAM
-DEMOLISH TO POINT INDICATED OF SPLIT.
Seal:
M -MOTORIZED CONTROL DAMPER 16. VERIFY FINISH WITH ARCHITECT PRIOR TO PURCHASING GRILLES, REGISTERS,
-DUCT ELBOW, POSITIVE PRESSURE (SUPPLY)
TS -TEMPERATURE SENSOR DOWN UP W/IN FLOOR HVAC EQUIPMENT TAGS 17.
DIFFUSERS, LOUVERS AND OTHER AIR DISTRIBUTION DEVICES.

PROVIDE FLEXIBLE DUCT CONNECTIONS ON ALL DUCTWORK CONNECTING TO EACH FAN,


P -PRESSURE SENSOR -DUCT ELBOW, EXHAUST AIR HANDLING UNITS, AND FAN COIL UNITS.
G G
-BACKDRAFT DAMPER TAG
BD 18. PROVIDE TRANSITIONS AT DIFFUSER NECKS AS REQUIRED TO MATCH SIZES OF
-DUCT ELBOW, NEGATIVE PRESSURE, RETURN FLEX DUCTS TO BE CONNECTED.
0 -NEUTRAL RELATIVE PRESSURE A 200 -AIR DISTRIBUTION DEVICE
19. INTERRUPTIONS TO EXISTING SERVICES SHALL BE SCHEDULED FOR TIMES OTHER THAN
+ -POSITIVE RELATIVE PRESSURE -DUCT ELBOW UP THROUGH ROOF OR SLAB ABOVE CFM NORMAL OPERATING HOURS (SUCH AS NIGHTS AND WEEKENDS). SUCH INTERRUPTIONS
TO SERVICES SHALL NOT BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE
_ -NEGATIVE RELATIVE PRESSURE -RECTANGULAR DUCT SECTION UP, POSITIVE PRESSURE, OWNER'S REPRESENTATIVE AND PROPER COORDINATION WITH OTHER TRADES.
SUPPLY OR OUTSIDE AIR AHU NUMBER PRE-WORK SHALL BE PERFORMED TO MAKE THE SHUTDOWN PERIOD AS BRIEF AS
1 -SHEET NOTE CALLOUT POSSIBLE.
-RECTANGULAR DUCT SECTION UP,
-SHEET NOTE CALLOUT
NEGATIVE PRESSURE, RETURN AHU-1 -AIR HANDLING UNIT
1 20. ALL EQUIPMENT, DUCTWORK, ETC., TO BE REMOVED SHALL REMAIN PROPERTY OF
F F
-RECTANGULAR DUCT SECTION UP, EXHAUST THE OWNER OR DISPOSED OF LEGALLY, AS DIRECTED BY OWNER. Project Phase:
1 -SHEET NOTE CALLOUT
-ROUND DUCT SECTION UP
21. MAINTAIN CLEARANCE OF A MINIMUM OF 6" BETWEEN DUCTWORK, PIPING,
EQUIPMENT, ETC., AND ALL FIRE RATED AND FIRE/SMOKE RATED PARTITIONS,
Construction
Documents
-CEILING MOUNTED ACCESS DOOR VARIABLE/CONSTANT AIR VOLUME TERMINAL UNITS TO ALLOW FOR INSPECTIONS OF RATED WALLS.
-FLAT OVAL DUCT SECTION UP
TERMINAL UNIT TYPE FLOOR NUMBER
22. DUCT RUNOUTS TO DIFFUSERS SHALL MATCH THE SIZE OF THE DIFFUSER NECK.
VAV - VARIABLE TERMINAL UNIT Project #: 0118.22
TERMINAL NUMBER 23. WATER PRESSURE DROPS THROUGH COIL CONTROL VALVES SHALL NOT EXCEED Project Issued: 11/05/14
5 PSI.
VAV-3-1 Sheet Issued:
24. UNLESS OTHERWISE NOTED, ALL EQUIPMENT AND VALVE DRAINS SHALL BE
E INDEPENDENTLY PIPED FULL SIZE TO THE NEAREST PLUMBING DRAIN. E
No. Date Revision
IAQ - VENTILATION DESIGN CRITERIA
HVAC PIPING SYMBOL LEGEND ASHRAE 62-2004 FLORIDA MECHANICAL CODE
25. SLEEVE AND SEAL ALL PIPING PENETRATIONS THROUGH BUILDING PARTITIONS.
PROVIDE MANUAL AIR VENTS AT ALL HIGH POINTS IN CHILLED WATER AND HOT
WATER PIPING.
SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION PEOPLE AREA OA EXHAUST PEOPLE EXHAUST
AREA OA
26. THIS HVAC SYSTEM IS DESIGNED AS A PLENUM RETURN SYSTEM.
OA RATE, RATE AIR RATE, OA RATE, RATE AIR RATE,
CWS -CONDENSER WATER SUPPLY -FLOW DIRECTION
EQUIP. AREA SERVED CFM/PERS CFM/SQ FT CFM/FIXTURE CFM/PERS CFM/SQ FT CFM/FIXTURE
- P-TRAP
CWR -CONDENSER WATER RETURN -GATE VALVE
OFFICE 5 0.06 0 20 0 0
MV
CHWS -CHILLED WATER SUPPLY -BALL VALVE -MANUAL VENT CONFERENCE/MEETING RM. 5 0.06 0 20 0 0
CORRIDOR 0 0.06 0 0 0.05 0
D CHWR -CHILLED WATER RETURN -CALIBRATING BALANCING VALVE D
LOBBIES 5 0.06 0 15 0 0
CD -CONDENSATE -BUTTERFLY VALVE BREAK ROOMS 5 0.06 0 0 0
-PRESSURE GAUGE 0
-GAS COCK STORAGE ROOM 0 0.12 0 0 0.15 0
CR -CONDENSATE RETURN FM -FLOW METER
TOILET - PUBLIC 0 0 50 0 0 20
PC -PUMPED CONDENSATE -UNION -WATER METER WAITING/RECEPTION 5 0.06 0 15 0 0
M
HWR -HOT WATER RETURN -STRAINER NOTES:
-INLINE PUMP
HWS -HOT WATER SUPPLY -CONTROL VALVE 1. VENTILATION IS CALCULATED IN ACCORDANCE WITH THE VENTILATION RATE PROCEDURE PER ASHRAE
-INLINE PUMP
S STANDARD 62.1-2007, IN COMPLIANCE WITH THE 2007 FLORIDA BUILDING CODE, MECHANICAL, CHAPTER 4,
HPS -HIGH PRESSURE STEAM SUPPLY -SOLENOID VALVE -CAP SECTION 403.4.
C C
MPS -MEDIUM PRESSURE STEAM SUPPLY -PSI REG.
-CONNECTION, BOTTOM 2. ACTUAL OCCUPANCY FOR OFFICES, CONFERENCE ROOMS, WAITING ROOMS AND BREAK ROOMS ARE BASED ON
LPS -LOW PRESSURE STEAM SUPPLY -CHECK VALVE SEATING PROVIDED WITHIN EACH SPACE.
-CONNECTION, TOP
HPR -HIGH PRESSURE STEAM RETURN -FLOW SWITCH 3. MAXIMUM OUTSIDE AIRFLOW RATES ARE CALCULATED PER THE TABLE ABOVE.
-COUPLING
MPR -MEDIUM PRESSURE STEAM RETURN -SLOPE DIRECTION (DOWN)
-ELBOW, 90° 4. EXHAUST AIRFLOWS FOR FIXTURES ARE BASED ON CONTINUOUS VENTILATION RATES. EXHAUST SYSTEMS FOR
LPR -LOW PRESSURE STEAM RETURN -FLEX CONNECTION THESE SPACES ARE DESIGNED TO OPERATE CONTINUOUSLY.
-ELBOW, 45° Copyright © 2014. BSSW Architects, Inc.
reserves copyright and other rights
RL -REFRIGERANT LIQUID -O.S.&Y. GATE VALVE 5. OUTSIDE AIR QUANTITIES ARE BASED ON 30% OUTDOOR AIR AT THE restricting these documents to the original
-ELBOW, TURNED DOWN site or purpose for which they were
ROOFTOP PACKAGED UNITS.
RS -REFRIGERANT SUCTION -STEAM TRAP prepared. Reproductions, changes or
B -ELBOW, TURNED UP B assignments are prohibited.
-THREE-WAY CONTROL VALVE
Sheet Title:
-TEE, OUTLET DOWN

-THERMOMETER -TEE, OUTLET UP COMPLIANCE STATEMENT Lawrin T. Ellis, P.E. HVAC SYMBOL
Florida License #66383
LEGEND, GENERAL
D D
-TWO-WAY CHECK VALVE -45° PIPE RISE (R) / DROP (D)

-RELIEF VALVE -PIPE ANCHORS


-CONCENTRIC REDUCER
THESE PLANS HAVE BEEN PREPARED IN COMPLIANCE WITH
THE 2007 FLORIDA BUILDING CODE AND THE 2007 FLORIDA
NOTES & INDEX
-VALVE ON RISER
-ECCENTRIC REDUCER MECHANICAL CODE. Sheet No.
A A
NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT

Seal
M001
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

C:\Users\mark.hauser\Documents\714125_LCJC ANNEX 5TH FL_MEP CENTRAL_R14_mark.hauser.rvt 1/8/2015 8:09:46 AM


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

M KEYNOTES: M

1 EXISTING AHU TO BE REMOVED. INSTALL NEW ISOLATION


VALVES WITH BLIND FLANGES AT RISER.

2 EXISTING SUPPLY AIR DUCTWORK TO BE REMOVED (TYPICAL).

3 EXISTING VAV BOXES TO BE REMOVED. REMOVE ALL ASSOCIATED A R C H I T E C T S I N C


DUCTWORK, PIPING, WIRING AND CONTROLS. License # AA C001863
4 LINEAR SUPPLY/RETURN DIFFUSER TO BE REMOVED. 1500 Jackson Street, Suite 200
L L Fort Myers, Florida 33901
5 LINEAR SUPPLY/RETURN/EXHAUST DIFFUSER TO BE REMOVED. Phone: 239-278-3838 Fax: 239-275-5356

6 EXHAUST DUCT AND GRILLE TO BE REMOVED. 949 Central Ave.


Naples, Florida 34102
7 EXISTING 4" CONCRETE PAD TO BE REMOVED. Phone: 239-643-3103 Fax: 239-643-7435
D101
TYP. 8 DUCT SIZES ARE SHOWN FOR REFERENCE ONLY. Project:

PUBLIC
K
DEMOLITION NOTES K
DEFENDER'S
D103
TYP.
1 THE CONTRACTOR SHALL PROVIDE PROTECTION FOR ALL PARTS OF THE BUILDING.
ITS CONTENTS AND OCCUPANTS WHEREVER WORK UNDER THIS CONTRACT IS PERFORMED.
OFFICE - 5TH
2 DEMOLITION SHALL INCLUDE REMOVAL OF EXISTING BUILDING CONSTRUCTION TO
EXTENT REQUIRED TO PERFORM CONSTRUCTION ACTIVITIES INDICATED.
FLOOR
3 THE DEMOLITION PROCEDURES SHALL PROVIDE FOR SAFE CONDUCT OF THE WORK,
PROTECTION OF PERSONNEL, CAREFUL REMOVAL AND DISPOSITION OF MATERIALS
SPECIFIED TO BE SALVAGED, PROTECTION OF PROPERTY TO REMAIN UNDISTURBED, Owner:

Lee County Board


COORDINATION WITH OTHER WORK IN PROGRESS, AND TIMELY DISCONNECTION OF
J PEDESTRIAN BRIDGE UTILITY SERVICES. J
BELOW

of County
D110
D111 4 EXISTING WORK TO REMAIN SHALL BE PROTECTED FROM DAMAGE. WORK DAMAGED
BY THE CONTRACTOR SHALL BE REPAIRED TO MATCH EXISTING WORK OR WORK
INSTALLED UNDER THIS CONTRACT DEPENDING ON CONTRACT REQUIREMENTS. Commissioners
5 EXISTING WORK SHALL BE CUT, DRILLED, ALTERED, REMOVED OR TEMPORARILY
REMOVED AND REPLACED FOR PERFORMANCE OF WORK UNDER THE CONTRACT. Consultant:
WORK REPLACED SHALL MATCH SIMILAR EXISTING WORK. STRUCTURAL MEMBERS OF
CONCRETE OR STRUCTURAL STEEL SHALL NOT BE CUT OR ALTERED, EXCEPT AS SHOWN 13099 S. Cleveland Ave.
WITHOUT AUTHORIZATION OF THE OWNER. WORK REMAINING IN PLACE DAMAGED Suite 500
OR DEFACED DURING THIS CONTRACT SHALL BE RESTORED TO THE CONDITION AT Fort Myers, Florida 33907
TIME OF AWARD OF CONTRACT. CUT, ALTER, REMOVE OR TEMPORARILY REMOVE H
H AND REPLACE EXISTING WORK FOR THE INSTALLATION OF MECHANICAL, PLUMBING Phone: 239-275-4240
D111 AND ELECTRICAL WORK AND OTHER CONSTRUCTION. Fax: 239-275-3511
www.tlc-engineers.com
PROPERLY REMOVE AND DISPOSE OF ALL EXISTING FIXTURES AS REQUIRED © Copyright 2014 TLC Engineering for Architecture, Inc.
6
TO ACCOMODATE NEW PLAN. REFER TO THE ARCHITECTURAL DEMOLITION PLANS. EB #0000015 TLC NO: 714125
CONSULT WITH THE OWNER AND OBTAIN OWNERS APPROVAL PRIOR TO
DISPOSAL OF REMOVED MATERIAL.
Seal:
D105 D102 7 UNLESS INDICATED OTHERWISE, ALL EXISTING MECHANICAL EQUIPMENT, DUCTWORK, PIPING,
D104 WIRING, HANGERS AND SUPPORTS SHALL BE REMOVED BACK TO BELOW SLAB, ABOVE
TYP. CEILING, OR WITHIN WALL CAVITIES AS INDICATED ON THE DRAWINGS.
D102 REFER TO THE ARCHITECTURAL DEMOLITION PLANS.
D102 CONSULT WITH THE OWNER AND OBTAIN OWNERS APPROVAL PRIOR TO DISPOSAL
G OF REMOVED MATERIAL. G
D102
STAIR No. 1 STAIR No. 2 8 THE EXISTING EQUIPMENT INDICATED ON THESE DRAWINGS REPRESENTS A BEST FAITH EFFORT BY THE
D102 ENGINEER TO DEMONSTRATE THE CONDITIONS UNDER WHICH THE WORK IS TO BE EXECUTED. THE
D110
CONTRACTOR SHALL VISIT SITE AND REVIEW EXISTING CONDITIONS TO THE DEGREE AND EXTENT
D102 NECESSARY TO PREPARE A PROPER AND ADEQUATE BID FOR THE WORK INDICATED. SUBMISSION OF
D102 A BID WILL BE INTERPRETED AS MEANING THE CONTRACTOR HAS REVIEWED EXISTING CONDITIONS AND
D102 UNDERSTANDS THE DIFFICULTIES AND CHALLENGES UNDER WHICH THE WORK IS TO BE ACCOMPLISHED.

D107
D109
F F
D107 D107 D102 Project Phase:
D109 D102 D109
Construction
Documents
D102

D102
Project #: 0118.22
D102 Project Issued: 11/05/14
Sheet Issued:

E E
No. Date Revision
D105

D104
TYP.

D111

D D

D106 TYP.
D108 TYP.

C C

Copyright © 2014. BSSW Architects, Inc.


reserves copyright and other rights
restricting these documents to the original
site or purpose for which they were
prepared. Reproductions, changes or
B B assignments are prohibited.

Sheet Title:

Lawrin T. Ellis, P.E. 5TH FLOOR


Florida License #66383
DEMOLITION PLAN -
HVAC
Sheet No.
A A

1
M101
5TH FLOOR - DUCTWORK - DEMOLITION M101
1/8" = 1'-0" Seal

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

C:\Users\mark.hauser\Documents\714125_LCJC ANNEX 5TH FL_MEP CENTRAL_R14_mark.hauser.rvt 1/8/2015 8:09:44 AM


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

M M

A R C H I T E C T S I N C
License # AA C001863
PRESSURE GAUGE & COCK (TYP.)
1500 Jackson Street, Suite 200
L TWO WAY CONTROL VALVE L Fort Myers, Florida 33901
MANUAL AIR VENT W/AUTO Phone: 239-278-3838 Fax: 239-275-5356
AUTOMATIC FLOW CONTROL SHUT-OFF COCK
DEVICE PRESET BY MANUF. 949 Central Ave.
COIL
W/ P & T TEST PORTS, Naples, Florida 34102
STRAINER, AND DRAIN. Phone: 239-643-3103 Fax: 239-643-7435
(PRE-MANUF. SINGLE
ASSEMBLY ACCEPTABLE) STRAIGHT SECTION OF METAL INLET DUCT IN SIZE Project:
BALANCING DAMPER EQUAL TO INLET COLLAR. MIN. LENGTH SHALL
SHEET METAL DUCT WITH
INTERIOR DUCT LINING
RETURN BE 4 TIMES DUCT DIAMETER
INLET COLLAR, ROUND OR OVAL.
PUBLIC
K
SEE SCHEDULE FOR SIZES
AIRFLOW SENSOR
K
DEFENDER'S
12" MINIMUM OR AS
INDICATED PER SPEC.
SUPPLY
OFFICE - 5TH
SHUT-OFF VALVE (TYP.)
SUPPORT STRAP HANGERS, SECURE
FLOOR
P/T TEST PORTS TO STRUCTURE. (TYP. OF 4)
STRAINER W / BLOWDOWN
Owner:

Lee County Board


AIR FLOW
J UNION (TYP.) J
2'-0" MINIMUM
FLEX. CONNECTION (TYP.)
of County
THERMOMETER W/SEPARABLE WELL (TYP.)
Commissioners
PRESSURE INDEPENDENT
CONTROLS PACKAGE
RETURN REGISTER (SEE PLAN DRWGS.
NOTES: 1. PROVIDE (4 x DIA.) OF STRAIGHT PIPE ON BOTH SIDES OF
FOR TYPE AND SIZE) Consultant:
BALANCING VALVE ELECTRIC HEATER AND CONTROL
2. ALL COMPONENTS FULL LINE SIZE UNLESS NOTED OTHERWISE BOX. MAINTAIN NECESSARY SHEET METAL DUCTWORK W/ 13099 S. Cleveland Ave.
CLEARANCE FOR SERVICE EXTERNAL INSULATION Suite 500
3. LOCATE UNIONS TO ALLOW FOR COIL PULL
H
Fort Myers, Florida 33907
H Phone: 239-275-4240
Fax: 239-275-3511
www.tlc-engineers.com
© Copyright 2014 TLC Engineering for Architecture, Inc.
EB #0000015 TLC NO: 714125

Seal:

G G
TYPICAL RETURN AIR BOOT 3 2-WAY COIL PIPING DIAGRAM 2 VARIABLE VOLUME TERMINAL W/ELECTRIC HEAT 1
No Scale No Scale No Scale

SEE SPECS FOR ROD SIZES


F F
Project Phase:
AIRFLOW RECTANGULAR MEDIUM
PRESSURE DUCT Construction
45 DEGREE CONNECTION
Documents
45 DEGREE BOOT TO ROUND OR RECTANGULAR Project #: 0118.22
TAP, TYPICAL ANGULAR FITTING WITH
Project Issued: 11/05/14
SQUARE TO ROUND
TRANSITION Sheet Issued:
GALVANIZED SADDLE
MANUAL BALANCING
E DAMPER, TYPICAL 45 DEGREE ROUND E
No. Date Revision
ADJUSTABLE ELBOW
CLEVIS HANGER
ROUND DUCT RUNOUT
SIZES 2-1/2" UP TO 4" TO TERMINAL UNIT

PIPE HANGER
(SEE SPECS.) ROUND MEDIUM
AIRFLOW
PRESSURE DUCT

D D
PIPE SADDLE HAS FLARED
EDGES NOTCHED TO FIT
45 DEGREE DIVERGING
PIPE HANGER.
CORNERS ARE WYE FITTING
CLIPPED
45 DEGREE ROUND
ELBOW

ROUND DUCT RUNOUT


RADIUS ELBOWS MAY BE USED TO TERMINAL UNIT
IN LIEU OF SQUARE ELBOWS
C C
PIPE
SADDLE
FLARED EDGES (TYP.)
FLARED END

ALL INSULATION PASSES


LENGTH=TWICE THRU HANGER UNBROKEN
Copyright © 2014. BSSW Architects, Inc.
INSULATION O.D. SIZES UP TO 2" reserves copyright and other rights
restricting these documents to the original
site or purpose for which they were

B TYPICAL LOW PRESSURE DUCTWORK 6 INSULATED PIPE HANGER - INDOORS 5 MEDIUM PRESSURE DUCT BRANCH TAKE-OFF 4 B
prepared. Reproductions, changes or
assignments are prohibited.

No Scale No Scale No Scale Sheet Title:

Lawrin T. Ellis, P.E. HVAC DETAILS


Florida License #66383

Sheet No.
A A

Seal
M201
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

C:\Users\mark.hauser\Documents\714125_LCJC ANNEX 5TH FL_MEP CENTRAL_R14_mark.hauser.rvt 1/8/2015 8:09:38 AM


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

M M

A R C H I T E C T S I N C
License # AA C001863

1500 Jackson Street, Suite 200


SUPPORT FROM Fort Myers, Florida 33901
L THREADED CAP, NOTE: STRAP HANGER SIZE (WIDTH x THICK- L
STRUCTURE Phone: 239-278-3838 Fax: 239-275-5356
HAND TIGHTENED HANGER NESS) AND MAXIMUM HANGER SPACING
ABOVE (TYP)
STRAPS SHALL COMPLY WITH REQUIREMENTS OF 949 Central Ave.
COOLING COIL THREADED CAP WITH EXTENDED OPERATOR 60" MAX SECTION IV SMACNA HVAC DUCT Naples, Florida 34102
[" HOLE DRILLED IN ON BALANCE DAMPER CONSTRUCTION STANDARDS. Phone: 239-643-3103 Fax: 239-643-7435
TOP, HAND
TIGHTENED. SPIN-IN FITTING W/VOLUME Project:
UNION CONTROL DAMPER (INSUL. PER SPEC.) DRAW BAND
INSULATE ALL CONDENSATE PIPING
WITH 3/4" THICK ARMAFLEX SCREWS PUBLIC
DEFENDER'S
INSULATION 1" MIN
K SCREWS MAY BE K
STRAP
OMITTED IF HANGER LOOPS

OFFICE - 5TH
OR

B
A ANGLE ROD, SUPPORT
STRAP HANGER - RECTANGULAR DUCT
DRAIN PAN CONDENSATE DRAIN FLEXIBLE DUCT FROM STRUCTURE
MAX. 8'-0" IN LENGTH ABOVE (TYP)
FLOOR

C
CASING SLEEVE INDIRECT FULLY EXTENDED. ROD, SUPPORT
CONNECTION FROM STRUCTURE
ABOVE (TYP)
4"
NEW FUNNEL DRAIN
ALL CONDENSATE 6 IN. Owner:

Lee County Board


PIPING DRAW BAND SIZE BOLT MAX. (TYP)
J TO BE COPPER FOR LOAD J

FLOOR
BLANK-OFF PLATES
WHERE REQUIRED NOTE: ROD DIMENSIONS, MAXIMUM HANGER SPACING,
of County
DIFFUSER NECK (INSUL. PER SPEC.) AND MAXIMUM ALLOWABLE LOADING OF TRAPEZE ANGLES
SHALL COMPLY WITH REQUIREMENTS OF SECTION
Commissioners
NUTS
DIFFUSER CONE (INSUL. PER SPEC.) IV SMACNA HVAC DUCT CONSTRUCTION STANDARDS
Consultant:
CONDENSATE DRAIN PIPING DIMENSIONS: TO CONDENSATE DRAIN
- 13099 S. Cleveland Ave.
ANGLES
A = FULL SIZE OF UNIT DRAIN CONNECTION FOR CONTINUATION SEE Suite 500
B > 1i TIMES FAN SUCTION STATIC PRESSURE PLUMBING PLANS TRAPEZE HANGER - RECTANGULAR DUCT
CEILING H
Fort Myers, Florida 33907
C > FAN DISCHARGE STATIC PRESSURE PLUS i INCH Phone: 239-275-4240
H
Fax: 239-275-3511
COORDINATE MOUNTING/CURB HEIGHT AS REQUIRED TO PROVIDE PROPER www.tlc-engineers.com
CONDENSATE DRAINAGE. © Copyright 2014 TLC Engineering for Architecture, Inc.
EB #0000015 TLC NO: 714125

Seal:

G
AHU CONDENSATE DRAIN TRAP 3 DIFFUSER MOUNTING 2 TYPICAL RECTANGULAR DUCT SUPPORT 1
G

No Scale No Scale

NOTE: STRAP HANGER SIZE (WIDTH x THICK-


NESS) AND MAXIMUM HANGER SPACING
SHALL COMPLY WITH REQUIREMENTS OF
SECTION IV SMACNA HVAC DUCT SUPPORT FROM
CONSTRUCTION STANDARDS. STRUCTURE ABOVE
F F
AS REQUIRED Project Phase:
STEEL ROD W/THREADED
ENDS (TYP. 4 PLCS.) VIBRATION Construction
ISOLATORS
Documents
SUPPORT FROM STRUCTURE Project #: 0118.22
ABOVE
CHWS/R MODULATING Project Issued: 11/05/14
1\" WIDE 18 GA.
PIPING CHILLED FLEX CONN. Sheet Issued:
SUPPORT STRAP WATER
10'-0" MAXIMUM (TYP.)
ROUND DUCT VALVE
E E
SPACING. No. Date Revision
N.C.
M

CHW COIL
SA

RA

FILTER
GALVANIZED STEEL SADDLE 3-SPEED ROUTE MAIN CONDENSATE
FAN LINE TO CONDENSATE DRAIN
IN MECHANICAL ROOM
D D
FLOAT SWITCH
CEILIING
SUPPORT FROM STRUCTURE
ABOVE
1\" WIDE GALVANIZED
STEEL HANGER STRAP FLEXIBLE DUCT 8'-0"
3'-0" MAXIMUM SPACING MAXIMUM LENGTH GALVANIZED SHEET METAL SECONDARY
DRAIN PAN TO EXTEND 3" BEYOND UNIT
ON ALL SIDES BY 1\" DEEP

C C
NOTE
NO FABRIC DUCT
GALVANIZED STEEL SADDLE SUPPORTS PERMITTED

Copyright © 2014. BSSW Architects, Inc.


reserves copyright and other rights
restricting these documents to the original
site or purpose for which they were

B TYPICAL ROUND/FLEX DUCT SUPPORT 5 FAN COIL UNIT INSTALLATION 4 B


prepared. Reproductions, changes or
assignments are prohibited.
No Scale No Scale Sheet Title:

Lawrin T. Ellis, P.E. HVAC DETAILS


Florida License #66383

Sheet No.
A A

Seal
M202
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

C:\Users\mark.hauser\Documents\714125_LCJC ANNEX 5TH FL_MEP CENTRAL_R14_mark.hauser.rvt 1/8/2015 8:09:37 AM


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

M M

CONCRETE OR MASONRY
CONSTRUCTION A R C H I T E C T S I N C
RETAINING ANGLES RETAINING ANGLES 1\"x 1\"x w" MIN. FIRE RESISTIVE MATERIAL (TYP.) License # AA C001863
1\"x1\"xw" ALL
MIN. ALL SIDES (SEE CLEARANCE w" PER SIDES. (SEE NOTE #2)
LINEAR FOOT BOTH 1500 Jackson Street, Suite 200
NOTE # 2) 4" MIN. Fort Myers, Florida 33901
L CONCRETE OR MASONRY DIMENSIONS. L
MANUFACTURER OR FIELD Phone: 239-278-3838 Fax: 239-275-5356
CONSTRUCTION. FABRICATED STEEL SLEEVE
1" MIN. CAULKING (TYP. OF 2)
NOTE# 2 16 949 Central Ave.
U.L. LABELED FIRE DAMPER, GA. MIN. Naples, Florida 34102
DUCT MOUNTED SMOKE DETECTOR
CAULK BEAD AROUND MANUF. OR FIELD (555) SECURE TO SLEEVE Phone: 239-643-3103 Fax: 239-643-7435
NOTE #5 TO BE INSTALLED WITHIN
EDGE BETWEEN DUCT AND WALL FABRICATED STEEL 5'-0" OF DAMPER PER
SLEEVE 16 GA. MIN. MANUFACTURER'S Project:
165°F FUSIBLE LINK RECOMMENDATIONS,
SPACE AT CORNERS 1/8".
SHEET METAL
WRAPPED SHEET METAL DUCT
U.L. (555S) LABELED
WITH NO AIR INLETS OR OUTLETS
BETWEEN THE DETECTOR AND THE
DAMPER.
PUBLIC
DUCT
DEFENDER'S
PLAIN "S" SLIP FIRE/SMOKE DAMPER,
K MAXIMUM COMPRESSION OF SECURE TO SLEEVE K
INSULATION IS 1/8" THICK. 165°F DUCT SIZE

OFFICE - 5TH
COMPRESS INSULATION MAXIMUM ALLOWABLE SPACE FUSIBLE CLEARANCE w" PER LINEAR
BETWEEN DUCTS AND NON RATED WRAPPED SHEET FOOT,
AGAINST PARTITION LINK NOTE #1
WALLS IS 1/4". METAL DUCT BOTH DIMENSIONS
NOTE # 1 PLAIN "S" SLIP (TYP.) BREAK-
AWAY
DUCT WRAP W/VAPOR BARRIER (TYP.)
FLOOR
CONNECTION CLOSURE TAPE
FASTENER W/WASHER
METAL DUCT MOUNTING ANGLE 1" MIN. OVERLAP
DUCT WRAP W/VAPOR ALL
6" MAXIMUM BARRIER (TYP.) SIDES METAL STUD CONSTRUCTION Owner:
EACH SIDE 6" MAX.
J J Lee County Board
CLOSURE TAPE (TYP.)
FIRE RESISTIVE
NOTES:
1. PROVIDE ACCESS DOOR & LABEL ON SIDE OR BOTTOM OF DUCT AS FOLLOWS:
of County
MATERIAL (TYP.)
EXTERNAL THERMAL
INSULATION
METAL STUD CONSTRUCTION DUCT WIDTH DOOR SIZE
Commissioners
CAULK BEAD AROUND EDGE 10" THRU 12" 8" x 8"
BETWEEN DUCT AND WALL 14" THRU 20" 12" x 12"
22" AND ABOVE 18" x 18" Consultant:
METAL STUD NOTES:
CONSTRUCTION 1. PROVIDE ACCESS DOOR & LABEL ON SIDE OR BOTTOM OF DUCT AS FOLLOWS: 2. 1\" x 1\" x w" RETAINING ANGLES SHALL LAP STRUCTURAL OPENING 1" MIN. & COVER 13099 S. Cleveland Ave.
CORNERS OF OPENINGS. ANGLES ATTACH TO SLEEVE ONLY AND MUST NOT BE ATTACHED Suite 500
DUCT WIDTH DOOR SIZE
TO EACH OTHER AT CORNERS OR TO WALL.
H
Fort Myers, Florida 33907
10" THRU 12" 8" x 8"
H WOOD STUD CONSTRUCTION OPENING Phone: 239-275-4240
14" THRU 20" 12" x 12" 3. ALL ATTACHMENTS PER MANUFACTURER'S APPROVED INSTALLATION INSTRUCTION.
Fax: 239-275-3511
TO BE LINED W/FIRE RESISTIVE FIRE RESISTIVE 22" AND ABOVE 18" x 18" www.tlc-engineers.com
4. VERTICAL POSITION SHOWN. HORIZONTAL INSTALLATION SIMILAR.
MATERIAL OF RATING EQUAL TO THAT MATERIAL (TYP.) © Copyright 2014 TLC Engineering for Architecture, Inc.
2. 1\"x1\"xw" RETAINING ANGLES SHALL LAP STRUCTURAL OPENING 1" MIN. & 5. ACTUATOR TO BE MOUNTED ON OUTSIDE OF DAMPER SLEEVE ON ACCESIBLE SIDE.
ON WALL.
COVER CORNERS OF OPENINGS. ANGLES ATTACH TO SLEEVE ONLY AND MUST NOT ACTUATOR SHALL NOT INTERFERE WITH "S" JOINT. ACTUATOR ASSEMBLY TO BE U.L. EB #0000015 TLC NO: 714125
BE ATTACHED TO EACH OTHER AT CORNERS OR TO WALL. LABELED. PROVIDE WITH MODULATING ACTUATOR AND REMOTE
3. ALL ATTACHMENTS PER MANUFACTURER'S APPROVED INSTALLATION INSTRUCTION. MOUNTED TEST STATION.
4. VERTICAL POSITION SHOWN. HORIZONTAL INSTALLATION SIMILAR. DAMPER TO BE Seal:
6. VERIFY THAT ACCESS IS PROVIDED ON THE ACTUATOR SIDE OF THE WALL/FLOOR SO
SPRING LOADED WHEN HORIZONTAL.
THAT THE LINK MAY BE SERVICED WITH THE DAMPER IN CLOSED POSITION.

G
DUCT PENETRATION THROUGH NON-RATED WALLS. 3 FIRE DAMPER INSTALLATION 2 FIRE & SMOKE DAMPER INSTALLATION 1
G

No Scale No Scale No Scale

F F
Project Phase:

Construction
Documents
Project #: 0118.22
Project Issued: 11/05/14
Sheet Issued:

E E
No. Date Revision

D D

C C

Copyright © 2014. BSSW Architects, Inc.


reserves copyright and other rights
restricting these documents to the original
site or purpose for which they were
prepared. Reproductions, changes or
B B assignments are prohibited.

Sheet Title:

Lawrin T. Ellis, P.E. HVAC DETAILS


Florida License #66383

Sheet No.
A A

Seal
M203
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

C:\Users\mark.hauser\Documents\714125_LCJC ANNEX 5TH FL_MEP CENTRAL_R14_mark.hauser.rvt 1/8/2015 8:09:37 AM


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

AIR HANDLING UNIT SCHEDULE CHW/HW


M M
COOLING COIL FILTER REQUIREMENTS SOUND DATA
UNIT COMPONENTS AIR FLOWS FAN AND MOTOR DATA
DESIGN CONDITIONS CAPACITY AIR DATA WATER DATA FILTER
PLAN MODEL UNIT IN DIRECTION OF AIR FLOW DISCHARGE RADIATED FROM CASING
TOTAL OA EXT. WHEEL FAN MOTOR VOLTS/ MOTOR MOTOR COIL AIR FLOW EAT LAT SEN. TOTAL MAX. MIN. TEMP. °F FLOW
MARK NO. TYPE SEE LEGEND BELOW VFD VEL. TYPE EFF.
CFM CFM SP TYPE RPM HP PHASE RPM TYPE DB WB DB WB MBH MBH FPM ROWS ENT. LVG. GPM 63 125 250 500 1K 2K 4K 8K 63 125 250 500 1K 2K 4K 8K

AHU-6S PCC SIZE 30 VERTICAL VAV DRAW-THRU FLT, CCL, FAN 16,000 2040 3.0 25" AF 1479 20 460/3 1800 BELT YES 16,000 75.0 63.0 53.0 52.7 386.9 481.1 500 6 42 57 63.92 PLEAT MERV 8 93 83 81 76 70 68 62 57 86 78 70 73 71 54 38 44 A R C H I T E C T S I N C
License # AA C001863
COMPONENTS LEGEND NOTES:
1500 Jackson Street, Suite 200
CCL - COOLING COIL 1. INDOOR UNIT MODEL NUMBERS AND EQUIPMENT SELECTIONS BASED ON TRANE 5. FILTER EFFICIENCY BASED ON ASHRAE 52.1-1992 TEST METHOD. Fort Myers, Florida 33901
L L
FAN - FAN Phone: 239-278-3838 Fax: 239-275-5356
2. AIR PRESSURE DROP FOR FILTERS SHALL INCLUDE A 0.5" DIRTY FILTER ALLOWANCE. 6. MAX. CHW COIL APD SHALL BE 0.9 IN W.G.
FLT - PRE-FILTERS
3. CAPACITIES SHOWN ARE MINIMUM. AIR AND WATER PRESSURE DROPS ARE MAXIMUM. 7. MAX. CHW COIL WPD SHALL BE 10.0 FT. 949 Central Ave.
Naples, Florida 34102
4. FILTER MODEL NUMBERS AND SELECTIONS BASED ON FARR. 8. DISCONNECT BY DIVISION 26. Phone: 239-643-3103 Fax: 239-643-7435

Project:

PUBLIC
K
TABLE 4-2
K
DEFENDER'S
VARIABLE AIR VOLUME TERMINAL UNIT SCHEDULE AIR DISTRIBUTION SCHEDULE
MINIMUM HANGER SIZES FOR ROUND DUCT
MARK CFM
NECK FACE SIZE
DESCRIPTION
OFFICE - 5TH
FLOOR
MAX. SIZE LENGTH
HEATER COIL DATA
DIA. MAXIMUM WIRE/ ROD STRAP PLAN DESIGN MINIMUM INLET NC
SPACING A
DIA. APD EAT LAT HEATING BASIS OF DESIGN: TITUS TMS-AA
MARK CFM CFM SIZE RATING KW POWER STEPS 000-125 6 24x24
10" DN. 12' ONE 12 GA. 1/4" 1"x 22 GA.
(IN WG) (°F) (°F) CFM 126-250 8 24x24 COLOR: WHITE
250 MM DN 3.7 M ONE 2.75 MM 6.4 MM 25.4 x 0.85 MM
251-325 10 24x24 MATERIAL: ALUMINUM
TWO 12 GA. VAV-3-1 950 285 10 < 20 0.10 4 277/1 2 55 81.6 475 326-450 12 24x24 OPPOSED BLADE DAMPERS: NO Owner:
11-18" 12' 1/4" 1"x 22 GA.
J
460 MM 3.7 M
OR ONE 8 GA.
ONE 4.27 MM 6.4 MM 25.4 x 0.85 MM
VAV-3-2 700 210 8 < 20 0.10 3 277/1 1 55 82.1 350
SUPPLY
B
451-625 14 24x24
J Lee County Board
19-24" 12' TWO 10 GA. 1/4" 1"x 22 GA.
VAV-3-3 1875 562 12 < 20 0.10 8 277/1 2 55 81.6 950
000-120 6 24x24 BASIS OF DESIGN: TITUS 50F of County
VAV-3-4 800 240 8 < 20 0.10 4 277/1 2 55 86.6 400
Commissioners
610 MM 3.7 M TWO 3.51 MM 6.4 MM 25.4 x 0.85 MM 121-225 8 24x12 COLOR: WHITE
226-350 10 24x12 MATERIAL: ALUMINUM
25-36" 12' TWO 8 GA. 3/8" 1"x 20 GA. VAV-3-5 475 142 8 < 20 0.10 2 277/1 1 55 80.3 250
RETURN 351-500 12 24x12
900 MM 3.7 M TWO 2.7 MM 9.5 MM 25.4 x 0.85 MM OPPOSED BLADE DAMPERS: NO
VAV-3-6 1200 360 10 < 20 0.10 5 277/1 2 55 81.3 600 501-800 14 24x12
PROVIDE WITH SQUARE TO ROUND Consultant:
37-50" 12' TWO 3/8" TWO 1"x 20 GA. VAV-3-7 675 210 8 < 20 0.10 3 277/1 1 55 82.1 300 TRANSITION WHERE ROUND DUCT
1270 MM 3.7 M TWO 9.5 MM (2) 25.4 x 1.00 MM CONNECTION IS SHOWN.
13099 S. Cleveland Ave.
VAV-3-8 175 52 5 < 20 0.10 1 277/1 1 55 91.3 100 Suite 500
51-60" 12' TWO 3/8" TWO 1"x 18 GA. VAV-3-9 425 120 6 < 20 0.10 2 277/1 1 55 86.6 200 H
Fort Myers, Florida 33907
H 1520 MM 3.7 M TWO 9.5 MM (2) 25.4 x 1.31 MM C BASIS OF DESIGN: TITUS 300FS Phone: 239-275-4240
VAV-3-10 625 187 8 < 20 0.10 3 277/1 1 55 84.2 325 COLOR: WHITE Fax: 239-275-3511
61-84" 12' TWO 3/8" TWO 1"x 16 GA. MATERIAL: ALUMINUM www.tlc-engineers.com
2130 MM 3.7 M TWO 9.5 MM (2) 25.4 x 1.61 MM VAV-3-11 275 82 6 < 20 0.10 1.5 277/1 1 55 86.6 150 © Copyright 2014 TLC Engineering for Architecture, Inc.
000-100 6 8x8
OPPOSED BLADE DAMPERS: NO
VAV-3-12 350 105 5 < 20 0.10 1.5 277/1 1 55 82.1 175 PROVIDE WITH SQUARE TO ROUND EB #0000015 TLC NO: 714125
NOTES SUPPLY
VAV-3-13 675 202 8 < 20 0.10 3 277/1 1 55 82.1 350 TRANSITION WHERE ROUND DUCT
1. STRAPS ARE GALVANIZED STEEL; RODS ARE UNCOATED OR GALVANIZED STEEL; WIRE IS BLACK ANNEALED, CONNECTION IS SHOWN.
VAV-3-14 725 217 8 < 20 0.10 3 277/1 1 55 80.3 375 Seal:
BRIGHT BASIC, OR GALVANIZED STEEL. ALL ARE ALTERNATIVES
VAV-3-15 550 165 8 < 20 0.10 3 277/1 1 55 89.5 275 D 000-120 6 8x8 BASIS OF DESIGN: TITUS 50F
2. REFER TO SMACNA DUCT STANDARDS - SECOND EDITION: FIG. 4-4 FOR LOWER SUPPORTS.
COLOR: WHITE
3. REFER TO SMACNA DUCT STANDARDS - SECOND EDITION: FIG. 4-2 AND 4-3 FOR UPPER ATTACHMENTS. VAV-3-16 750 225 8 < 20 0.10 3 277/1 1 55 80.3 375
MATERIAL: ALUMINUM
G 4. TABLE ALLOWS FOR CONVENTIONAL WALL THICKNESS, AND JOINT SYSTEMS PLUS ONE LB/SF INSULATION WEIGHT. VAV-3-17 200 60 5 < 20 0.10 1 277/1 1 55 86.6 100 G
OPPOSED BLADE DAMPERS: NO
IF HEAVIER DUCTS ARE TO BE INSTALLED, ADJUST HANGER SIZES TO BE WITHIN THEIR LOAD LIMITS; REFER TO EXHAUST PROVIDE WITH SQUARE TO ROUND
VAV-3-18 NOT USED - - - - - - - - - -
SMACNA DUCT STANDARDS - SECOND EDITION: ALLOWABLE LOADS WITH TABLE 4-1. HANGER SPACING MAY BE TRANSITION WHERE ROUND DUCT
ADJUSTED BY SPECIAL ANALYSIS. VAV-3-19 1200 360 10 < 20 0.10 5 277/1 2 55 81.3 600 CONNECTION IS SHOWN.
5. DESIGNERS: FOR INDUSTRIAL GRADE SUPPORTS, INCLUDING SADDLES, SINGLE LOAD TRAPEZE LOADS, LONGER SPANS VAV-3-20 450 135 8 < 20 0.10 2 277/1 1 55 83.1 225 BASIS OF DESIGN: TITUS 300FL
E 000-300 12x8 12x8 COLOR: WHITE
AND FLANGE JOINT LOADS, SEE SMACNA'S ROUND INDUSTRIAL DUCT CONSTRUCTION STANDARDS. 101-600 18x10 18x10
VAV-3-21 525 157 8 < 20 0.10 3 277/1 1 55 89.5 275 MATERIAL: PLASTIC
6. REFER TO SMACNA DUCT STANDARDS - SECOND EDITION: FIGS.3-9 AND 3-10 FOR FLEXIBLE DUCT SUPPORTS. OPPOSED BLADE DAMPERS: NO
VAV-3-22 200 60 5 < 20 0.10 1 277/1 1 55 86.6 100
COPYRIGHT: HVAC DUCT CONSTRUCTION STANDARDS METAL AND FLEXIBLE - SECOND EDITION.
VAV-3-23 625 187 8 < 20 0.10 3 277/1 1 55 84.2 325 SIDEWALL
SUPPLY
F VAV-3-24 775 232 8 < 20 0.10 4 277/1 2 55 86.6 400 BASIS OF DESIGN: TITUS 50F F
F 000-300 12x8 12x8 COLOR: WHITE Project Phase:
VAV-3-25
VAV-3-26
1125
1675
340
502
10
12
< 20
< 20
0.10
0.10
5
7
277/1
277/1
2
2
55
55
84.4
81.5
575
850
101-600 18x10 18x10 MATERIAL: PLASTIC
OPPOSED BLADE DAMPERS: NO Construction
TABLE 4-1
RECTANGULAR DUCT HANGERS
VAV-3-27 950 285 10 < 20 0.10 4 277/1 2 55 81.6 475 SIDEWALL
RETURN
PROVIDE WITH SQUARE TO ROUND
TRANSITION WHERE ROUND DUCT
CONNECTION IS SHOWN.
Documents
NOTES: Project #: 0118.22
MINIMUM SIZE BASIS OF DESIGN: TITUS TBD-10
1. BASIS OF DESIGN: ENVIROTEC. 4. 3/4" FIBERGLASS - DOUBLE WALL. G 000-225 8 4 FEET COLOR: WHITE Project Issued: 11/05/14
MAXIMUM PAIR AT 10 FT SPACING PAIR AT 8 FT SPACING PAIR AT 5 FT SPACING PAIR AT 4 FT SPACING 2. PROVIDE WITH INTEGRAL DISCONNECT. 5. FIELD-MOUNTED CONTROLS. MATERIAL: ALUMINUM
Sheet Issued:
HALF OF 3. SEE SPECIFICATIONS FOR ADDITIONAL 6. ELECTRONIC CONTROL PACKAGE AND
OPPOSED BLADE DAMPERS: YES
DUCT 2 SLOT, 1" SLOTS
E STRAP WIRE/ STRAP WIRE/ STRAP WIRE/ STRAP WIRE/ INFORMATION. DISCONNECT (FUSED). LINEAR 8" CONNECTION E
PERIMETER ROD ROD ROD ROD SUPPLY No. Date Revision
10 GA. 10 GA. 12 GA. 12 GA.
P/2 = 30" 1"x 22 GA. 1"x 22 GA. 1"x 22 GA. 1"x 22 GA. PROVIDE W/INSULATED PLENUM.
(.135") (.135") (.106") (.106")
BASIS OF DESIGN: TITUS TBD-10
H 000-225 8 4 FEET
P/2 = 72" 1"x 18 GA. 3/8" 1"x 20 GA. 1/4" 1"x 22 GA. 1/4" 1"x 22 GA. 1/4" COLOR: WHITE
MATERIAL: ALUMINUM
P/2 = 96" 1"x 16 GA. 3/8" 1"x 18 GA. 3/8" 1"x 20 GA. 3/8" 1"x 22 GA. 1/4" SOUND ATTENUATOR SCHEDULE OPPOSED BLADE DAMPERS: NO
2 SLOT, 1" SLOTS
P/2 = 120" 1\" x 16 GA 1/2" 1"x 16 GA. 3/8" 1"x 18 GA. 3/8" 1"x 20 GA. 1/4" PLAN AIR FACE PRESS. SIZE MINIMUM DYNAMIC INSERTION LOSS, dB MAXIMUM SELF GENERATED NOISE, dB LINEAR 8" CONNNECTION
FLOW VEL. DROP WxHxL OCTAVE BAND OCTAVE BAND RETURN
P/2 = 168" 1\" x 16 GA 1/2" 1\" x 16 GA 1/2" 1"x 16 GA. 3/8" 1"x 18 GA. 3/8" MARK PROVIDE W/ INSULATED PLENUM.
MODEL CFM FPM IN. WG. INCHES 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
D NOTES: D
P/2 = 192" NOT GIVEN 1/2" 1\" x 16 GA 1/2" 1"x 16 GA. 3/8" 1"x 16 GA. 3/8" SA-1 ES NOTE 3 1778 0.70 36 x 18 x 60 6 12 19 35 49 49 35 24 63 57 54 50 49 53 53 50
1. AIR DISTRIBUTION DEVICES LOCATED WITHIN ACOUSTICAL TILE CEILINGS SHALL BE
NOTES: PROVIDED WITH BORDER TYPE 3 FOR LAY-IN MOUNTING. AIR DISTRIBUTION DEVICES
P/2 = 193" UP SPECIAL ANALYSIS REQUIRED
1. OCTAVE BAND CENTER FREQUENCY (HZ) 1-63, 2-125, 3-250, 4-500, 5-1000, 6-2000, 7-4000, 8-8000. LOCATED WITHIN GYPSUM BOARD CEILINGS OR WALLS SHALL BE PROVIDED WITH
PLASTER FRAME. REFER TO ARCHITECTURAL DOCUMENTS FOR CEILING TYPES.
WHEN STRAPS ARE LAP JOINED SINGLE HANGER MAXIMUM ALLOWABLE LOAD 2. SELECTIONS ARE BASED ON INDUSTRIAL ACOUSTICS QUIET DUCT SILENCERS RECTANGULAR FILM LINED.
USE THESE MINIMUM FASTENERS: 3. REQUIRES (2) 36x18 SILENCERS IN TANDEM - 8000 CFM PER SILENCER FOR A TOTAL OF 16,000 CFM.
STRAP WIRE OR ROD (DIA.) 2. AIR DISTRIBUTION DEVICES LOCATED IN SMALL ROOMS WHERE FULL 24"x24" GRID ARE
4. ACCEPTABLE ALTERNATE MANUFACTURER IS VIBRO-ACOUSTICS. NOT AVAILABLE SHALL BE PROVIDED WITH SURFACE MOUNTING BORDERS IN LIEU OF
1"x 18, 20, 22 GA.-TWO #10 OR ONE 1/4" BOLT 1"x 22 GA.-260 LBS. 0.016".-80 LBS. LAY-IN. SECURE EACH DEVICE TO CEILING GRID WITH FIELD-FABRICATED SUPPORTS.
1"x 16 GA.-TWO 1/4" DIA. 1"x 20 GA.-320 LBS. 0.135"- 120 LBS.
1 1/2"x 16 GA. -TWO 3/8" DIA. 1"x 18 GA.-420 LBS. 0.162"- 160 LBS.
C PLACE FASTENERS IN SERIES, NOT SIDE BY SIDE. 1"x 16 GA.-700 LBS. 1/4"- 270 LBS. C
1 1/2"x 16 GA. -1100 LBS. 3/8"- 680 LBS.
1/2"- 1250 LBS.
5/8"- 2000 LBS.
3/4"- 3000 LBS. CHILLED WATER FAN COIL UNIT
AIRFLOW COOLING COIL DATA FAN & MOTOR DATA
NOTES PLAN MODEL
1. DIMENSIONS OTHER THAN GAGE ARE IN INCHES. CFM / MIN.SEN. MIN.TOT. EAT LAT WATER TEMP. °F FLOW DRIVE FAN #1 FAN #1 FAN #2 FAN #2 VOLTS/ SERVICE Copyright © 2014. BSSW Architects, Inc.
MARK NO. reserves copyright and other rights
2. TABLES ALLOW FOR DUCT WEIGHT, 1 LB./SF INSULATION WEIGHT AND NORMAL REINFORCEMENT AND TRAPEZE WEIGHT, EXT SP MBH MBH DB WB DB WB ENT. LVG. GPM TYPE HP RPM HP RPM MCA MOCP PHASE restricting these documents to the original
BUT NO EXTERNAL LOADS. site or purpose for which they were
FC-1 FCCB12 SIZE 120 600/0.40" 11.9 14.0 75 63 55 54.9 42 57 2.6 DIRECT 0.13 1279 0.24 1224 2.65 15.0 208/1 IT ROOM 347 prepared. Reproductions, changes or
B 3. FOR CUSTOM DESIGN OF HANGERS, DESIGNERS MAY CONSULT SMACNA'S RECTANGULAR INDUSTRIAL DUCT STANDARDS, B assignments are prohibited.
THE AISI COLD FORMED STEEL DESIGN MANUAL AND THE AISC STEEL CONSTRUCTION MANUAL. FC-2 FCCB12 SIZE 120 300/0.50" 5.8 7.1 75 63 55 54.9 42 57 1.3 DIRECT 0.13 1279 0.24 1224 2.65 15.0 208/1 ELEC RM 307
Sheet Title:
4. STRAPS ARE GALVANIZED STEEL; OTHER MATERIALS ARE UNCOATED STEEL.
5. ALLOWABLE LOADS FOR P/2 ASSUME THAT DUCTS ARE 16 GA. MAXIMUM, EXCEPT THAT WHEN MAXIMUM DUCT DIMENSION (W)
IS OVER 60" THEN P/2 MAXIMUM IS 1.25W.
NOTES:
1. MODEL NUMBERS AND EQUIPMENT SELECTIONS BASED ON TRANE
Lawrin T. Ellis, P.E. HVAC SCHEDULES
2. MAX APD ACROSS CHW COIL SHALL BE 0.5".
Florida License #66383
6. FOR UPPER ATTACHMENTS REFER TO SMACNA DUCT STANDARDS - SECOND EDITION: FIG. 4-2
3. MAX WPD ACROSS CHW COIL SHALL BE 3.0 FT.
7. FOR LOWER ATTACHMENTS REFER TO SMACNA DUCT STANDARDS - SECOND EDITION: FIG. 4-4
4. SINGLE POINT POWER CONNECTION.
8. FOR TRAPEZE SIZES REFER TO SMACNA DUCT STANDARDS - SECOND EDITION: TABLE 4-3 AND FIG. 4-5. 5. DISCONNECT BY DIV 26.
9. 12, 10, OR 8 GA. WIRE IS STEEL OF BLACK ANNEALED, BRIGHT BASIC, OR GALVANIZED TYPE. 6. PROVIDE WITH MERV 8 FILTERS.
7. PROVIDE WITH VALVING PACKAGE. Sheet No.
A COPYRIGHT: HVAC DUCT CONSTRUCTION STANDARDS METAL AND FLEXIBLE - SECOND EDITION. A
8. PROVIDE CONTROLLER TO INTERFACE WITH EXISTING EMS SYSTEM.

Seal
M301
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

C:\Users\mark.hauser\Documents\714125_LCJC ANNEX 5TH FL_MEP CENTRAL_R14_mark.hauser.rvt 1/8/2015 8:09:36 AM


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

AHU-OA (EXIST.) DO
C
WIRE TO
FILTER FSD-6LB START AHU-OA
M THIS DAMPER IS TO BE M
C INSTALLED BUT REMAIN SD R-1
N.C. OUTSIDE AIR CLOSED INTERLOCK
C RELAY

2HR. RATED
DUCT CHASE
ROOF
SD A R C H I T E C T S I N C
NEW DUCT TIE IN
License # AA C001863

EXISTING EXHAUST 1500 Jackson Street, Suite 200


L DUCT L Fort Myers, Florida 33901
FSD-6LC COMM. LINE TO NEXT COMM. LINE FROM ADJ.
RISER IN RATED CHASE Phone: 239-278-3838 Fax: 239-275-5356
OUTSIDE AIR TERMINAL UNIT TERMINAL UNIT ELECTRIC HEAT
N.C. NEW DUCT TIE IN
24 VAC
949 Central Ave.
DM-9FLR Naples, Florida 34102
LOCATED IN 9TH FLOOR MECHANICAL ROOM
V.F.D. FOR AHU-OA Phone: 239-643-3103 Fax: 239-643-7435
(EXIST.) EXISTING TOILET SUPPLY AIR
FROM AHU
N.O.
SUPPLY AIR
TO SPACE
Project:
EXHAUST DUCT RISER
DUCT
N.C. OUTSIDE AIR
STAND-ALONE FACTORY MOUNTED
TS-1
PUBLIC
DM-8FLR
DEFENDER'S
SHAFT DDC CONTROLLER WITH VOLUME
K REGULATOR, PITOT TUBES, ETC K
RETURN AIR AI

OFFICE - 5TH
MANUAL RESET DO
HIGH STATIC
DAMPER PRESSURE

FLOOR
N.C. OUTSIDE AIR AO POSITION SENSOR
FSD
DM-7FLR
SMOKE DETECTOR
SHUT-DOWN CKT. FSD-6FLG
DI SPACE TEMPERATURE/HUMIDITY SENSOR W/
DPS-3 SMOKE DETECTOR PS-2 Owner:
DATA-PORT FOR PORTABLE LAPTOP
Lee County Board
SHUT-DOWN CKT.
J N.C. OUTSIDE AIR AO MERV 8 CONNECTION, AND OVERRIDE BUTTON. J
BD FILTER TS-1 FURNISH ONE SENSOR PER UNIT
DM-6FLR
BD
of County
C
RETURN AIR AHU-3S SUPPLY AIR Commissioners
C (NEW)

OUTSIDE AIR Consultant:


N.C.
FSD-6FLH AUXILLIARY DRAIN PAN TS-5
FSD TS-4 DPT-1 FOR SCWP-7 & 8 13099 S. Cleveland Ave.
DM-5FLR BD BI LOCATED AT AHU-9S Suite 500
AI AI
MOISTURE V.F.D. (SHOWN
H
Fort Myers, Florida 33907
H AI DETECTOR AI DI AI FOR REFERENCE) Phone: 239-275-4240
DPT-1 (EXIST) Fax: 239-275-3511
TS-3 www.tlc-engineers.com
DAMPER OUTDOOR MOISTURE DETECTOR AO AI
N.C. OUTSIDE AIR
VARIABLE AIR VOLUME TERMINAL BOXES WITH ELECTRIC REHEAT: © Copyright 2014 TLC Engineering for Architecture, Inc.
POSITION AIRFLOW INTERLOCKED
DM-4FLR AO AI W/ CHILLED WATER VALVE TO T EB #0000015 TLC NO: 714125
FSD-6XF

T
CLOSE STATIC PRESSURE SENSOR LOC. 1. MODULATE THE VAV BOX DAMPER TO MAINTAIN THE SPACE SET-POINT TEMPERATURE VIA THE ASSOCIATED SPACE WALL MOUNTED
VALVE IF MOISTURE IS DETECTED IN CHWR 2/3 DOWNSTREAM OF THE AHU TEMPERATURE SENSOR. MODULATE BETWEEN THE SCHEDULED REQUIRED MAXIMUM CFM AND MINIMUM CFM FLOW TO MAINTAIN
M M DRAIN PAN. Seal:
REFER TO SHEET M101 FOR LOCATION THE SPACE SET-POINT TEMPERATURE.
CHWS
2. WHEN THE VAV BOX REACHES ITS MINIMUM CFM SET-POINT AND A THE SPACE TEMPERATURE FALLS BELOW THE ROOM SET-POINT,
AFMS

OUTSIDE AIR AO
NEW HIGH POINT TIE IN TO ENABLE THE STAGES OF ELECTRIC REHEAT IN THE VAV BOX TO REACH THE SPACE TEMPERATURE SET-POINT. PROVIDE PROOF OF
AIR EXTISING FLOW ACROSS VAV BOX HEATING COIL BEFORE ALLOWING THE COIL TO ENERGIZE.
G VENT IN CHW PIPING CV-3S 3" CHWR VALVES G
(TYP 2) 3. ALL SET-POINTS SHALL BE ADJUSTABLE FROM THE BAS.
FSD
SMOKE DETECTOR
SHUT-DOWN CKT. 4. SET UNOCCUPIED HIGH TEMPERATURE LIMIT TO 80°F. SET UNOCCUPIED LOW TEMPERATURE TO 65°F. WHEN SPACE TEMPERATURE
TIE IN TO EXISTING OA CHASE SPACE R/H CARBON DIOXIDE IS OUTSIDE OF SETPOINTS, VAV BOX DAMPER SHOULD MOVE TO THE APPROPRIATE POSITION AND ENERGIZED THE AIR HANDLING
N.C. OUTSIDE AIR FIRE/SMOKE DAMPER W/ AI AI UNIT.
MODULATING SEE FLOOR SEE FLOOR
DM-2FLR OPERATOR 3" CHWS PLAN FOR PLAN FOR
(TYP) LOCATIONS LOCATIONS
H C
LOW POINT DRAIN
W/ EXISTING CHWS/R
F RISER F
VALVE & 3/4" HOSE Project Phase:

Construction
N.C. OUTSIDE AIR THREAD W/CAP UP AND DOWN
NOTE:
DM-1FLR SEE DETAIL 2 ON SHEET M201 FOR
PIPING COMPONENTS.
Documents
Project #: 0118.22
Project Issued: 11/05/14
DUAL PATH AHU CONTROL FOR AHU-3S 2 VARIABLE VOLUME TERMINAL W/ REHEAT 1 Sheet Issued:
No Scale
E E
No. Date Revision

SEQUENCE OF CONTROL:
NOTE:
CHILLED WATER SYSTEM SEE DETAIL 2 ON SHEET M201 FOR
3. UNOCCUPIED HOURS: PIPING COMPONENTS.
1. START LEAD SECONDARY CHWS PUMP (SCWP-7 OR 8 LOCATED IN THE CENTRAL PLANT) ON CALL
FOR COOLING FROM ANY VAV BOX. THE LAG PUMP SHALL BE STARTED IN THE CASE OF FAILURE A. STOP AHU-3S SUPPLY FAN. FAN START/STOP
OF THE LEAD PUMP. PUMP SPEED SHALL BE CONTROLLED BY INDIVIDUAL VARIABLE FREQUENCY
LEAVING AIR TEMP
AI BO FAN STATUS
BI CURRENT
MOTOR DRIVES VIA A DIFFERENTIAL PRESSURE TRANSDUCER LOCATED IN THE SUNTRUST 9TH B. CLOSE FLOOR OUTSIDE AIR SUPPLY DAMPER FSD-6LF, RETURN AIR DAMPERS FSD-6LG, FSD-6LF AND EXHAUST AIR DAMPERS FSD-6LC. TRANSFORMER
FLOOR MECHANICAL ROOM.
C. START AND STOP AHU-3S TO MEET UNOCCUPIED SPACE TEMPERATURE SETPOINT. USE INDIVIDUAL SPACE
D EXISTING CHWS/R D
2. CHILLED WATER IS PROVIDED FROM THE CENTRAL CHILLER PLANT. TEMPERATURES TO DETERMINE THE START / STOP OF AHU-3S. RETURN AIR RISER UP/DN

SINGLE PATH VARIABLE AIR VOLUME AIR HANDLING UNIT AHU-3S AND AHU-OA 5. SAFETIES
BI
1. MORNING BUILDING COOL-DOWN: A. STOP AHU SUPPLY FANS AND CLOSE RETURN AIR DAMPERS ON DETECTION OF SMOKE. COORDINATE WITH THE ELECTRICAL HOT TAPPED TIE
VALVE IN
START AHU-3S BASED UPON OPTIMAL START PROGRAMMING THAT CALCULATES THE PROPER TIME OF START-UP TO CONTRACTOR. POSITION
AO WITH NEW 1"
COOL SPACE WITH THE HIGHEST TEMPERATURE READING BEFORE THE TIME OF BUILDING OCCUPANCY. THE PROGRAMMING CHWS/R W/VALVE
SHALL USE HISTORICAL TRENDS AS WELL AS OUTSIDE AIR AND SPACE TEMPERATURE IN DETERMINING THE ACTUAL B. PROVIDE HIGH STATIC PRESSURE LIMIT SHUT-DOWN OF THE AIR HANDLING SYSTEM. PROVIDE WITH MANUAL RESET. M
START TIME. DURING MORNING COOL-DOWN THE OUTSIDE DAMPER SHALL BE CLOSED AND THE RETURN AIR DAMPER SET PRESSURE AT 4" W.C. AUX. DRAIN PAN W/ MOISTURE
SHALL BE 100% OPEN. START AHU-3S SUPPLY FAN. MODULATE THE 2-WAY CHILLED WATER CONTROL VALVE FOR DETECTIOR INTERLOCKED W/
AHU-3S TO MAINTAIN A MINIMUM 55 DEGREES F SUPPLY AIR TEMPERATURE DOWN STREAM OF THE SUPPLY FAN. CHILLED
C WATER VALVE C
2. OCCUPIED HOURS:
A. START SUPPLY AIR FAN AHU-3S. OPEN THE OUTSIDE AIR DAMPER. SPACE TEMP
AI NEW HIGH POINT
B. MODULATE THE ASSOCIATED 2-WAY CHILLED WATER CONTROL VALVE FOR AHU-3S CHILLED WATER COILS AIR
TO MAINTAIN 55°F D.B. (ADJ) LEAVING AIR TEMPERATURE FROM THE CHILLED WATER COIL. VENT (TYP) LOW POINT DRAIN W/
T VALVE & 3/4" HOSE
C. AHU-3S SUPPLY AIR FAN SHALL BE CONTROLLED VIA THE ASSOCIATED VARIABLE FREQUENCY MOTOR DRIVE TO MAINTAIN THREAD W/CAP (TYP) Copyright © 2014. BSSW Architects, Inc.
THE SUPPLY DUCT STATIC PRESSURE SET-POINT. reserves copyright and other rights
restricting these documents to the original
D. PROVIDE LEAVING AIR TEMPERATURE (L.A.T.) RESET STRATEGY TO CONTROL L.A.T. BASED ON POSITION OF VAV BOX DAMPERS. site or purpose for which they were
prepared. Reproductions, changes or
B RAISE L.A.T. 1° F. EVERY 15 MINUTES B assignments are prohibited.
UNTIL ANY VAV BOX IS AT FULL OPEN AND SPACE TEMPERATURE AT ANY SENSOR IS ABOVE SETPOINT OR UNTIL SPACE R/H RISES
ABOVE 60% R/H. LOWER THE L.A.T. 1° F. EVERY 15 MINUTES ANY VAV BOX IS AT MIN. POSITION AND SPACE TEMPERATURE IS SEQUENCE OF OPERATION Sheet Title:
BELOW THE SPACE TEMPERATURE SETPOINT.

E. IN NORMAL OPERATION, MODULATING FIRE/SMOKE DAMPERS FSD-6LF, FSD-6LG AND FSD-6LH SHALL BE CONTROLLED TO
1. SUPPLY FAN WILL CYCLE ON A CALL FOR COOLING.

2. MODULATING CHILLED WATER VALVE (NORMALLY CLOSED) WILL BE


Lawrin T. Ellis, P.E. HVAC CONTROL
Florida License #66383
MAINTAIN THE DESIGN OUTDOOR AIR AND RETURN MINIMUM REQUIRED OUTDOOR AIR SETPOINT AND BE CONTROLLED BY
SPACE C02 SENSORS. IN ALL ALARM CONDITION, DUCT SMOKE DETECTORS SHALL SHUT DOWN THE SUPPLY FAN AND
POSITIONED TO MAINTAIN 55°F (ADJ) LAT DURING OPERATION.
DIAGRAMS
CLOSE THE FIRE/SMOKE DAMPERS. 3. IF SPACE TEMPERATURE EXCEEDS 80°F OR IS LESS THAN 60°F, AN ALARM SHALL BE SENT TO THE EMS FRONT END

Sheet No.
A A

CHILLED WATER FAN COIL UNIT FC-1 / FC-2


No Scale
3
Seal
M401
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

C:\Users\mark.hauser\Documents\714125_LCJC ANNEX 5TH FL_MEP CENTRAL_R14_mark.hauser.rvt 1/8/2015 8:09:34 AM


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

M M
PLUMBING GENERAL NOTES:
PLUMBING FIXTURE SCHEDULE PLUMBING SYMBOL LEGEND
1. READ THE SPECIFICATIONS AND ALL NOTES ON PLANS.

WC-1 WALL HUNG ACCESSIBLE WATER CLOSET


2. UTILITIES AND SERVICES INDICATED ARE TAKEN FROM VARIOUS OLD AND NEW WC-2 WALL HUNG WATER CLOSET CD -CONDENSATE
SURVEYS, AS-BUILT RECORDS AND FIELD INVESTIGATIONS. UNFORSEEN CONDITIONS A R C H I T E C T S I N C
VITREOUS CHINA, 1.6 GALLON, WALL HUNG, SIPHON JET, ELONGATED CLOSET BOWL WITH 1-1/2" TOP CO -CLEANOUT
PROBABLY EXIST AND NEW WORK MAY NOT BE FIELD LOCATED EXACTLY AS SHOWN ON VITREOUS CHINA, 1.6 GALLON, WALL HUNG, SIPHON JET, ELONGATED CLOSET BOWL WITH 1-1/2" TOP SPUD.
License # AA C001863
DRAWINGS. COOPERATION WITH OTHER TRADES IN ROUTING AND PIPE DEPTHS, AS CW -COLD WATER
SPUD.
DETERMINED DURING CONSTRUCTION WILL BE NECESSARY. CONT -CONTINUATION 1500 Jackson Street, Suite 200
1.6 GALLON CHROME PLATED FLUSH VALVE(EXPOSED), 1-INCH I.P.S. SCREW DRIVER ANGLE STOP
L 1.6 GALLON CHROME PLATED FLUSH VALVE(EXPOSED), 1-INCH I.P.S. SCREW DRIVER ANGLE STOP DN -DOWN L Fort Myers, Florida 33901
WITH PROTECTIVE CAP, ADJUSTABLE TAILPIECE, VACUUM BREAKER FLUSH CONNECTION AND SPUD
3. PROVIDE ALL OFFSETS AND FITTINGS AND MAKE CONNECTION TO EXISTING UTILITIES. WITH PROTECTIVE CAP, ADJUSTABLE TAILPIECE, VACUUM BREAKER FLUSH CONNECTION AND SPUD FU -FIXTURE UNITS Phone: 239-278-3838 Fax: 239-275-5356
COUPLING FOR 1-1/2" TOP SPUD, DIE CAST WALL FLANGE WITH SET SCREW, SPUD FLANGE, SOLID
COUPLING FOR 1-1/2" TOP SPUD, DIE CAST WALL FLANGE WITH SET SCREW, SPUD FLANGE AND SOLID RING PIPE SUPPORT AND ADA HANDLE. HW -HOT WATER
4. CONCEAL PIPING ABOVE CEILINGS, WITHIN WALLS OR CHASES EXCEPT IN MECHANICAL RING PIPE SUPPORT. 949 Central Ave.
IE -INVERT ELEVATION Naples, Florida 34102
ROOMS OR AS SPECIFICALLY NOTED. PROVIDE ACCESS PANELS FOR ALL VALVES SEAT SHALL BE EXTRA HEAVY SOLID PLASTIC WITH STAINLESS STEEL SELF SUSTAINING CHECK
SEAT SHALL BE EXTRA HEAVY SOLID PLASTIC WITH STAINLESS STEEL SELF SUSTAINING CHECK SAN -SANITARY Phone: 239-643-3103 Fax: 239-643-7435
CONCEALED IN WALLS OR ABOVE NON-ACCESSABLE CEILINGS. HINGE, OPEN FRONT LESS COVER.
HINGE, OPEN FRONT LESS COVER. ST -STORM
Project:
5. SLEEVE AND FIRE STOP PENETRATIONS OF RATED WALLS, FLOORS, CEILINGS AND FULLY ADJUSTABLE CLOSET CARRIER ADJUSTED TO ACCESSIBLE HEIGHT, SEE SPECS. SF -SQUARE FEET
FULLY ADJUSTABLE CLOSET CARRIER ADJUSTED TO STANDARD HEIGHT.
PUBLIC
ROOFS. FLASH AND COUNTERFLASH ROOF PENETRATIONS. TYP -TYPICAL
NOTE: FLUSH VALVE HANDLE SHALL FACE WIDE SIDE OF STALL. VTR -VENT THRU ROOF
BASIS OF DESIGN

DEFENDER'S
6. WHEN BEAM SLEEVE PENETRATIONS ARE NECESSARY, COORDINATE PENETRATIONS WITH BASIS OF DESIGN -HOSE BIBB
K K
ALL TRADES, THE ARCHITECT AND THE STRUCTURAL ENGINEER. CHINA - AMERICAN STANDARD - 2257.103
FLUSH VALVE - SLOAN ROYAL 111-XL-YK -BALANCING VALVE

OFFICE - 5TH
CHINA - AMERICAN STANDARD - 2257.103
7. NOT USED. SEAT - BEMIS - 1655-SS/C FLUSH VALVE - SLOAN ROYAL 111-XL-YK -CLEANOUT
CARRIER - ZURN - Z-1200 SERIES SEAT - BEMIS - 1655-SS/C

FLOOR
CARRIER - ZURN - Z-1200 SERIES -COLD WATER PIPING
8. SEE ARCHITECTURAL DRAWINGS FOR EXACT PLUMBING FIXTURE EWC-1 ACCESSIBLE ELECTRIC WATER COOLER -HOT WATER PIPING
LOCATIONS AND MOUNTING HEIGHTS. U-1 WALL HUNG ACCESSIBLE URINAL -HW RECIRCULATING PIPING
TYPE 304 STAINLESSS STEEL DRINKING FOUNTAIN POLISHED TO A #4 SATIN FINISH WITH S -SANITARY PIPING
9 . PROVIDE CLEANOUTS AT BASE OF ALL RISER STACKS AND DUAL HEIGHT RECEPTOR, SELF CLOSING FRONT MOUNTED PUSH BUTTON TYPE BUBBLERS, VITREOUS CHINA, 1.0 GALLON WALL HUNG, SIPHON JET URINAL WITH INTEGRAL FLUSHING RIM, S -UNDERGROUND SANITARY PIPING
IN ACCORDANCE WITH APPROPRIATE CODES AND REGULATIONS. STRAINER AND TAILPIECE. SURFACE MOUNTED REFRIGERANT CHILLER UNIT CAPABLE OF 8 INTEGRAL TRAP, WALL HANGERS, AND 2 INCH FEMALE FLANGED OUTLET CONNECTION. Owner:
GPH OF 50 °F AT AN AMBIEMT TEMPERATURE OF 90 °F. ELECTRICAL CHARACTERISTICS - -SANITARY VENT PIPING
J
10.
115V AC, 60HZ, SINGLE PHASE. 1.0 GALLON CHROME PLATED FLUSH VALVE(EXPOSED), 3/4-INCH I.P.S. SCREWDRIVER CHECK ANGLE CD -CONDENSATE PIPING J Lee County Board
WHERE POTABLE WATER STUBS OUT OF WALL OR IS EXPOSED, THE PLUMBING
CONTRACTOR SHALL TRANSITION TO COPPER (FOR WC OR URINALS) AND CHROME PLATED WATERSENTRY VII FILTER WITH 1,500 GALLON CAPACITY TO REMOVE CYSTS, LEAD AND
STOP WITH PROTECTIVE CAP, ADJUSTABLE TAILPIECE, VACUUM BREAKER FLUSH CONNECTION AND
SPUD COUPLING FOR 3/4" TOP SPUD, DIE CAST WALL FLANGE WITH SET SCREW, SPUD FLANGE AND
of County
Commissioners
UNDER LAV'S & SINKS. CHLORINE. -CONNECT TO EXISTING
SOLID RING PIPE SUPPORT.
CHROME PLATED 17 GAUGE 1-1/4 X 1-1/2 BRASS P-TRAP WITH CLEANOUT. FULLY ADJUSTABLE URINAL CARRIER ADJUSTED TO ACCESSIBLE HEIGHT, SEE SPECS.
11. THIS CONTRACTOR MUST REFER TO THE ARCHITECTURAL DRAWINGS FOR
ADDITIONAL WORK SCOPE COVERED BY THE ARCHITECT. COORDINATE WITH Consultant:
THE GENERAL CONTRACTOR AND ALL THE SUB-CONTRACTORS INVOLVED.
3/8 INCH I.P.S. CHROME PLATED SUPPLY WITH LOOSE KEY STRAIGHT STOP AND WALL
FLANGE.
BASIS OF DESIGN
COMPLIANCE STATEMENT 13099 S. Cleveland Ave.
CHINA - AMERICAN STANDARD - 6501.010 Suite 500
12. APPLICABLE CODES INCLUDE, BUT ARE NOT LIMITED TO: BASIS OF DESIGN FLUSH VALVE - SLOAN ROYAL 186-1-XL-YK Fort Myers, Florida 33907
THESE PLANS HAVE BEEN PREPARED IN COMPLIANCE WITH H
H CARRIER - ZURN ZR-1222 THE 2007 FLORIDA BUILDING CODE - PLUMBING. Phone: 239-275-4240
A. FLORIDA BUILDING CODE, 2007 EDITION PLUMBING . FOUNTAIN - ELKAY - LZSTL-8-C Fax: 239-275-3511
TRAP - MCGUIRE - 8902 L-1 ACCESSIBLE WALL HUNG LAVATORY www.tlc-engineers.com
B NFPA 101, LIFE SAFETY CODE, 2007 EDITION
SUPPLY - MCGUIRE- 158LK © Copyright 2014 TLC Engineering for Architecture, Inc.
VITREOUS CHINA LAVATORY, 20" X 18", PUNCHED FOR 4"CENTERSET FITTING AND CONCEALED ARM EB #0000015 TLC NO: 714125
C. AMENDMENTS TO ANY OF THE ABOVE CODES WHICH ARE ENFORCED BY CARRIER SUPPORT.
MS-1 MOP SINK
THE LOCAL AUTHORITY HAVING JURISDICTION OVER THIS PROJECT.
4" CENTERSET CHROME PLATED BRASS FAUCET, VANDAL RESISTANT 0.5 GPM FLOW REGULATOR, Seal:
13. FIELD VERIFY EXISTING INSTALLATIONS. MODIFY EXISTING PLUMBING SYSTEMS, FLOOR MOUNTED PRECAST TERRAZO WITH STAINLESS STEEL CAP, 24" X 24" X 12", DRAIN BODY CHROME PLATED WRISTBLADE HANDLES WITH HOT AND COLD WATER CODED INDEXES.
WHICH ARE TO REMAIN ACTIVE, TO FACILITATE RECONNECTION AND EXTENSION OF SHALL BE STAINLESS STEEL CAST INTEGRAL, AND SHALL PROVIDE FOR A CAULKED LEAD
THE NEW WORK. CONNECTION AND NOT LESS THAN 1" DEEP TO A 3" PIPE. PROVIDE WITH STAINLESS STEEL WALL PRE-INSULATED CHROME PLATED WHEELCHAIR LAVATORY STRAINER, CAST GRID DRAIN PLUG WITH
GUARD. STRAINER AND OFFSET DRAIN ASSEMBLY WITH 1-1/4 INCH O.D. TAILPIECE, CHROME PLATED 17
G GAUGE 1-1/4 X 1-1/2" BRASS P-TRAP WITH CLEANOUT. G
14. NOTIFY OWNER AT LEAST 24 HOURS PRIOR TO INTERRUPTING EXISTING SERVICE.
SERVICE FAUCET SHALL BE CHROME PLATED WITH RENEWABLE SEATS IN MONEL, VACUUM
SCHEDULE DISCONNECTION AND TIE-INS TO MINIMIZE DISRUPTION OF SERVICES.
BREAKER, INTEGRAL STOPS, ADJUSTABLE WALL BRACE, PAIL HOOK, AND 3/4" HOSE THREAD ON PRE-INSULATED 1/2" COMPRESSION X 3/8 INCH COMPRESSION CHROME PLATED ANGLE SUPPLY
SERVICES ARE NOT TO BE LEFT DISRUPTED DURING NON-NORMAL CONTRACTOR WORKING SPOUT. STOPS WITH CHROME PLATED 12" FLEXIBLE RISERS AND ESCUTCHEONS.
HOURS.
36" HOSE WITH 3/4" CHROME COUPLING AND WALL BRACKET. FULLY ADJUSTABLE LAVATORY CARRIER ADJUSTED TO ACCESSIBLE HEIGHT, SEE SPECS.
15. PLENUM CEILINGS OCCUR THROUGHOUT, CONTRACTOR TO EITHER VERIFY REQUIRED
FIRE BASIS OF DESIGN BASIS OF DESIGN
RATINGS ARE MET OR WRAP ALL PVC AND/OR CPVC PIPING WITHIN CEILING SPACE WITH
3M SINK - WILLIAMS SBC-1700 - BP CHINA - AMERICAN STANDARD - 0356.012
FIRE WRAP. FAUCET - CHICAGO - 897 FAUCET - CHICAGO - 802A-317-E2805
HOSE - WILLIAMS - T-35 STRAINER/TRAP/STOPS - MCGUIRE - 2125WC
F F
CARRIER - ZURN ZR-1200 SERIES Project Phase:
S-2 SINK Construction
SINK
Documents
S-1
DOUBLE COMPARTMENT SELF RIMMING SINK CONSTRUCTED OF TYPE 304 18-8 STAINLESS STEEL 33"
X 19" X 7-1/2" DEEP. INTERIOR AND TOP SURFACES SHALL BE POLISHED TO A HIGH LUSTER FINISH.
SINGLE COMPARTMENT SELF RIMMING SINK CONSTRUCTED OF TYPE 304
PROVIDE SINK WITH CRUMB CUP STRAINER.
18-8 STAINLESS STEEL 22" X 19" X 7-1/2" DEEP. INTERIOR AND TOP Project #: 0118.22
SURFACES SHALL BE POLISHED TO A HIGH LUSTER FINISH. PROVIDE SINK WITH CRUMB CUP
8" CHROME PLATED BRASS FAUCET, VANDAL RESISTANT 2.0 GPM FLOW REGULATOR, SINGLE LEVER Project Issued: 11/05/14
FINISHED WALL STRAINER.
HANDLE AND 10" SPOUT. Sheet Issued:
8" CHROME PLATED BRASS FAUCET, VANDAL RESISTANT 2.0 GPM FLOW REGULATOR, SINGLE LEVER
1/2" COMPRESSION X 3/8" COMPRESSION CHROME PLATED ANGLE SUPPLY STOPS WITH CHROME
E HANDLE AND 10" SPOUT. E
PLATED 12" FLEXIBLE RISERS AND ESCUTCHEONS. No. Date Revision
1/2" COMPRESSION X 3/8" COMPRESSION CHROME PLATED ANGLE SUPPLY STOPS WITH CHROME
CHROME PLATED 17 GAUGE 1-1/2" TWO COMPARTMENT CONTINUOUS WASTE.
PLATED 12" FLEXIBLE RISERS AND ESCUTCHEONS.
GRAB BAR CHROME PLATED 17 GAUGE 1-1/2" X 1-1/2" P-TRAP WITH CLEANOUT.
VENT LINE
CHROME PLATED 17 GAUGE 1-1/2" X 1-1/2" P-TRAP WITH CLEANOUT.
FLUSH VALVE BASIS OF DESIGN
WATER SUPPLY BASIS OF DESIGN
SINK - ELKAY - LR-3319
SINK - ELKAY - LR-2219
FAUCET - CHICAGO - 2300-8
PIPE SUPPORT (TYP.) FAUCET - CHICAGO - 2300-8
11 1/2"

SUPPLIES - MCGUIRE - 2165CC


SUPPLIES - MCGUIRE - 2165CC
D CONTINUOUS WASTE - ELKAY - LK-53
TRAP - MCGUIRE - 8912 D
TRAP - MCGUIRE - 8912
33"
30"

WATER CLOSET SEAT


19" AFF ADA

CD-1 CONDENSATE DRAIN

COATED CAST IRON BODY WITH BOTTOM OUTLET, COMBINATION INVERTIBLE MEMBRANE CLAMP AND
WATER CLOSET ADJUSTABLE TYPE "I" NICKEL BRONZE STRAINER, 6" ROUND TOP, WITH 1" RAISED LIP.

CARRIER BASIS OF DESIGN


SEE SCHEDULE FOR TYPES
SAN. LINE
ZURN - Z-415
C CONCRETE ANCHOR C

THE HANDLE OF THE FLUSH VALVE


SHALL FACE THE WIDE SIDE OF
THE STALL (NO EXCEPTIONS). PLUMBING FIXTURE CONNECTION SCHEDULE
MARK DESCRIPTION SOIL WASTE VENT CW HW Copyright © 2014. BSSW Architects, Inc.
reserves copyright and other rights
restricting these documents to the original
WC-1&2 ACCESSIBLE WATER CLOSET 3" 2" 1" site or purpose for which they were

B WATER CLOSET 1 ACCESSIBLE LAVATORY 1\" 1\" \" \" B


prepared. Reproductions, changes or
assignments are prohibited.
No Scale L-1
Sheet Title:

PLUMBING SYMBOL
EWC-1 ELECT WATER COOLER 1\" 1\" \"
Lawrin T. Ellis, P.E.
U-1 ACCESSIBLE URINAL ]" Florida License #66383
LEGEND, GENERAL
2" 2"

S-1 SINGLE BOWL SINK 2" 1\" \" \"

S-2 DOUBLE BOWL SINK 2" 1\" \" \" NOTES & INDEX
MS-1 MOP SINK 3" 2" \" \"
Sheet No.
A A

Seal
P001
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

C:\Users\mark.hauser\Documents\714125_LCJC ANNEX 5TH FL_MEP CENTRAL_R14_mark.hauser.rvt 1/8/2015 8:09:33 AM


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

DEMOLITION NOTES:
M M

1 THE CONTRACTOR SHALL PROVIDE PROTECTION FOR ALL PARTS OF THE BUILDING. 7 UNLESS INDICATED OTHERWISE, ALL EXISTING SANITARY WASTE & VENT, AND DOMESTIC
ITS CONTENTS AND OCCUPANTS WHEREVER WORK UNDER THIS CONTRACT IS PERFORMED. HOT AND COLD WATER PIPING SHALL BE CAPPED OR PLUGGED BELOW SLAB, ABOVE
CEILING, OR WITHIN WALL CAVITIES. REFER TO THE ARCHITECTURAL DEMOLITION PLANS.
2 DEMOLITION SHALL INCLUDE REMOVAL OF EXISTING BUILDING CONSTRUCTION TO CONSULT WITH THE OWNER AND OBTAIN OWNERS APPROVAL PRIOR TO DISPOSAL
EXTENT REQUIRED TO PERFORM CONSTRUCTION ACTIVITIES INDICATED. OF REMOVED MATERIAL.
3 THE DEMOLITION PROCEDURES SHALL PROVIDE FOR SAFE CONDUCT OF THE WORK,
PROTECTION OF PERSONNEL, CAREFUL REMOVAL AND DISPOSITION OF MATERIALS
8. THE EXISTING PIPING INDICATED ON THESE DRAWINGS WAS COMPILED FROM ORIGINAL CONSTRUCTION A R C H I T E C T S I N C
SPECIFIED TO BE SALVAGED, PROTECTION OF PROPERTY TO REMAIN UNDISTURBED,
DRAWINGS, "AS-BUILT" DRAWINGS AND ENGINEERS FIELD OBSERVATIONS. THE EXISTING PIPING INDICATED License # AA C001863
REPRESENTS A BEST FAITH EFFORT BY THE ENGINEER TO DEMONSTRATE THE CONDITIONS UNDER WHICH THE WORK
COORDINATION WITH OTHER WORK IN PROGRESS, AND TIMELY DISCONNECTION OF
IS TO BE EXECUTED. THE CONTRACTOR SHALL VISIT SITE AND REVIEW EXISTING CONDITIONS TO THE DEGREE AND
UTILITY SERVICES.
EXTENT NECESSARY TO PREPARE A PROPER AND ADEQUATE BID FOR THE WORK INDICATED. SUBMISSION OF A BID 1500 Jackson Street, Suite 200
L 4 EXISTING WORK TO REMAIN SHALL BE PROTECTED FROM DAMAGE. WORK DAMAGED WILL BE INTERPRETED AS MEANING THE CONTRACTOR HAS REVIEWED EXISTING CONDITIONS AND UNDERSTANDS THE L Fort Myers, Florida 33901
BY THE CONTRACTOR SHALL BE REPAIRED TO MATCH EXISTING WORK OR WORK DIFFICULTIES AND CHALLENGES UNDER WHICH THE WORK IS TO BE ACCOMPLISHED. Phone: 239-278-3838 Fax: 239-275-5356
INSTALLED UNDER THIS CONTRACT DEPENDING ON CONTRACT REQUIREMENTS.
9. DRAWINGS INDICATE INSTALLATION OF NEW FIXTURES TIED TO EXISTING SANITARY WASTE AND VENT PIPING.
5 EXISTING WORK SHALL BE CUT, DRILLED, ALTERED, REMOVED OR TEMPORARILY
SCOPE OF WORK INCLUDES CUTTING AND REMOVAL OF EXISTING FLOOR SLAB FOR THE PURPOSE OF INSTALLING NEW 949 Central Ave.
REMOVED AND REPLACED FOR PERFORMANCE OF WORK UNDER THE CONTRACT.
U.G. SANITARY PIPING. SLAB CUT AND TRENCH WIDTH SHALL BE KEPT TO A MINIMUM. IN NO INSTANCE SHALL SLAB Naples, Florida 34102
WORK REPLACED SHALL MATCH SIMILAR EXISTING WORK. STRUCTURAL MEMBERS OF
CUT/TRENCH WIDTH EXCEED 36 INCHES WITHOUT PRIOR APPROVAL OF ARCHITECT. Phone: 239-643-3103 Fax: 239-643-7435
D101 CONCRETE OR STRUCTURAL STEEL SHALL NOT BE CUT OR ALTERED, EXCEPT AS SHOWN
WITHOUT AUTHORIZATION OF THE OWNER. WORK REMAINING IN PLACE DAMAGED
TYP. OR DEFACED DURING THIS CONTRACT SHALL BE RESTORED TO THE CONDITION AT 10. REMOVE ALL EXISTING DOMESTIC WATER COPPER PIPING/FITTINGS ON THIS FLOOR AND REPLACE WITH CPVC PIPING AND FITTINGS. Project:
TIME OF AWARD OF CONTRACT. CUT, ALTER, REMOVE OR TEMPORARILY REMOVE

PUBLIC
AND REPLACE EXISTING WORK FOR THE INSTALLATION OF MECHANICAL, PLUMBING
AND ELECTRICAL WORK AND OTHER CONSTRUCTION.

DEFENDER'S
6 PROPERLY REMOVE AND DISPOSE OF ALL EXISTING FIXTURES AS REQUIRED
K TO ACCOMODATE NEW PLAN. REFER TO THE ARCHITECTURAL DEMOLITION PLANS. K
CONSULT WITH THE OWNER AND OBTAIN OWNERS APPROVAL PRIOR TO
DISPOSAL OF REMOVED MATERIAL.
D103
TYP.
OFFICE - 5TH
DEMOLITION KEY NOTES:
FLOOR
A FIXTURE TO BE REMOVED.
FIXTURE, FAUCET AND FITTINGS TO BE Owner:

J
PEDESTRIAN BRIDGE
BELOW
TURNED OVER TO CM FOR DEMOLITION .
CAP ALL ASSOCIATED PIPING J Lee County Board
D110
D111 ABOVE CEILING/BELOW SLAB AS
NECESSARY. of County
B FIXTURE TO REMAIN AT SAME LOCATION. Commissioners
CLEAN AND PREPARE AS NEW.

C EXISTING 3" CONDENSATE RISER FROM Consultant:


ABOVE. OFFSET BELOW 4TH FLOOR TO
DROP AS SHOWN, THAN OFFSET BACK 13099 S. Cleveland Ave.
TO ORIGINAL LOCATION BELOW 3RD FLOOR. Suite 500
H
Fort Myers, Florida 33907
H Phone: 239-275-4240
D111 Fax: 239-275-3511
www.tlc-engineers.com
© Copyright 2014 TLC Engineering for Architecture, Inc.
EB #0000015 TLC NO: 714125

D105 D102 Seal:


D104
TYP.
D102
D102
G G
D102
STAIR No. 1 STAIR No. 2
D102
D110

D102
D102
D102

D107
D109
F F
D107 D107 D102 Project Phase:

Construction
D109 D102 D109

D102

D102
Documents
Project #: 0118.22
D102 Project Issued: 11/05/14
Sheet Issued:

E E
D105 No. Date Revision

D104
TYP.

D111

D D

D106 TYP.
D108 TYP.

C C

Copyright © 2014. BSSW Architects, Inc.


reserves copyright and other rights
restricting these documents to the original
site or purpose for which they were
prepared. Reproductions, changes or
B B assignments are prohibited.

Sheet Title:

Lawrin T. Ellis, P.E. 5TH FLOOR


Florida License #66383
DEMOLITION PLAN -
PLUMBING
Sheet No.
A A

1
P101
5TH FLOOR - PLUMBING - DEMOLITION
1/8" = 1'-0" Seal
P101
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

C:\Users\mark.hauser\Documents\714125_LCJC ANNEX 5TH FL_MEP CENTRAL_R14_mark.hauser.rvt 1/8/2015 8:09:32 AM


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 8.9 9 10 GENERAL NOTES:


M M
1. ALL WORK DESCRIBED ON THE "TECHNOLOGY" DRAWINGS ARE PART OF A
"STRUCTURED CABLING" SYSTEM. THE WORK PERTAINING TO THIS SYSTEM CAN
ONLY BE PROVIDED AND INSTALLED BY ONE OF THE PRE-QUALIFIED STRUCTURED
CABLING SYSTEM (SCS) CONTRACTORS LISTED IN THE DIVISION 17
SPECIFICATIONS.

2. ALL CABLING SHALL BE PLENUM RATED A R C H I T E C T S I N C


License # AA C001863

1500 Jackson Street, Suite 200


A Fort Myers, Florida 33901
L L
IMO KEY Phone: 239-278-3838 Fax: 239-275-5356

F40 TV 949 Central Ave.


F40 Naples, Florida 34102
ADP 14 BREAK ROOM ADP 13
Phone: 239-643-3103 Fax: 239-643-7435
72 35 47 X = MOUNTING (F)LUSH, (S)URFACE, (M)ODULAR
FURNITURE ADAPTOR (P)OLE, (FL)LOOR, & (R)ACEWAY Project:
F40 N = # OF DATA JACKS

PUBLIC
F40
ALIGN ALIGN B N = # OF CATV JACKS
APD 15

DEFENDER'S
APD 12
K 70 COMMUNICATIONS "INFORMATION OUTLET" MTD. AT K
44
RECEPTACLE HEIGHT UNLESS OTHERWISE NOTED.
X N N
OFFICE - 5TH
REFER TO SPECIFICATIONS FOR MANUFACTURER'S
PART NUMBER.
APD 16 APD 11
FLOOR
C = ABOVE COUNTER
F40 73 P 64 F40 C
W = WALL MOUNTED

F40 F40

APD 10 Owner:
APD 17
J 71
L4 45
D
# KEYNOTES: J Lee County Board
of County
1. 3RD FLOOR IT ROOM. PROVIDE 3/4" PLYWOOD BACKBOARD, 8'-0" HIGH, WHERE
TRAINING
38
WAP
APD 9 INDICATED. SEE ENLARGED TECHNOLOGY ROOM PLAN FOR DETAILS. CONTRACTOR Commissioners
F40 APD 18 STOR / EQUIP STOR/EQUIP F40 TO
WAP-1 23
PROVIDE AND INSTALL A 100 PR UTP FOR VOICE TO THE SECOND FLOOR MDF AND A
69 WAP 39 FS 40 12 Consultant:
STRAND SM/24 STRAND MM FOC FROM THIS LOCATION TO THE SECOND FLOOR MDF
WAP-2 2. TYPICAL FLUSH MOUNTED VOICE/DATA OUTLET. CABLING, OUTLETS, AND TERMINATIONS 13099 S. Cleveland Ave.
BY Suite 500
F40 APD 19 F40 F40 F40 F40 F40 F40 F40 F40 APD 8
F40 PRE-QUALIFIED DIV. 17 CONTRACTOR. Fort Myers, Florida 33907
68 INVEST. 2 INVEST. 3 INVEST. 4 INVEST. 5 INVEST. 6 INVEST. 7 INVEST. 8 INVEST. 9 22 3. TYPICAL MODULAR FURNITURE CONNECTION, COORDINATE REQUIRED CONNECTIONS H
H Phone: 239-275-4240
43 34 33 36 61 41 60 63 TO Fax: 239-275-3511
F40 F40 MODULAR FURNITURE WITH SUPPLIER/INSTALLER. CABLING, OUTLETS, AND www.tlc-engineers.com
E TERMINATIONS BY PRE-QUALIFIED DIV. 17 CONTRACTOR. © Copyright 2014 TLC Engineering for Architecture, Inc.
APD 20 4. PROVIDE TELECOM CONNECTION TO OVERHEAD PROJECTOR. COORDINATE A/V
APD7 CONDUIT EB #0000015 TLC NO: 714125
67 21 AND WIRING REQUIREMENTS WITH OWNER PRIOR TO INSTALLATION.
5. TELECOMMUNICATIONS GROUND BUS. SEE DETAIL #4 ON DRAWING `T202'. PROVIDE #6
CU Seal:
ALIGN ALIGN ALIGN APD 6 FROM GROUND BUS BACK TO ELECTRICAL PANEL SERVING THIS EQUIPMENT.
20 6. SEE A/V WALL PLATE DETAIL #5 ON DRAWING `T202' FOR MORE DETAIL.
APD 21
F40 66 F40 E.5
7. DEDICATED LOCATION FOR COMCAST CABLE TAP. COORDINATE WITH OWNER.
G CR G

INVEST. 1 MEN'S INVEST. 10


F40 MECH. F40
88 89 87
SS/10 91
APD 22 F40 SS/9 APD 5
F40
65 SS/9 19
M40
M40

FIX
M40 C40 ELEVATOR C40
SS/11 FIX FIX
M40
LOBBY (E) WORKROOM
SS/8 F
F F

CR

FIX
501E 24
SS/8 Project Phase:

ADP 23
F40
C40
ELEC.
92
C40 C40
APD 4 Construction
18 F40 F.3
Documents
58 C40

CR
WORKROOM WOMENS
M40
29 90
M40 M40
CR

SS/12 C40 IDE Project #: 0118.22


C40 94 JAN.
Project Issued:

CR
SS/6 SS/7 11/05/14
F40 APD 24 93 APD 3 F40
SS/6 SS/7 Sheet Issued:
76 17

E ALIGN ALIGN
F.7 E
C40 No. Date Revision

APD 25 APD 2
F40 WAP F40
75 SS/2 16
C40 C40 M40 M40
WAP-4 M40 M40
RECEPT. D COPY/ WAP
PRINT/
2 M40 WORK AREA SS/3 SS/4 SS/5 WAP-3
APD 1 G
F40 ADP 26 CONF. ROOM F40
74
3 95 F41

D Work Stations F40 D


ADP 27
CR

SS/1 501F
78 ADMIN.
F40 F40
15

F41 G.8
ADMIN.
14
PUBLIC CONFERENCE CHIEF ASSIT.
DEFENDER ROOM PD ADMIN. ADMIN. H
F41 7 12 13
4 6 D F40
C F40 C
L4 F41
D
CR

CR

F40 F40

Copyright © 2014. BSSW Architects, Inc.


reserves copyright and other rights
restricting these documents to the original
site or purpose for which they were
prepared. Reproductions, changes or
B B assignments are prohibited.

Sheet Title:

Brett L. Sands, P.E. 5TH FLOOR PLAN -


Florida License #48477
TECHNOLOGY
3.5 3.9 4.8 6.2 6.9 7.5
Sheet No.
A A

1
T101
5TH FLOOR - TECHNOLOGY
1/8" = 1'-0" Seal
T101
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

C:\Users\mark.hauser\Documents\714125_LCJC ANNEX 5TH FL_MEP CENTRAL_R14_mark.hauser.rvt 1/8/2015 8:09:25 AM


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

M M

A R C H I T E C T S I N C
INTERMEADIATE DISTRIBUTION FRAME NOTES 3 License # AA C001863

TO AND ABOVE HUNG CEILING. 1500 Jackson Street, Suite 200


# CABLING NOTES (SHOWN FOR REFERENCE ONLY) 3 3
L CONDUIT SHALL TURN-OUT L Fort Myers, Florida 33901
Phone: 239-278-3838 Fax: 239-275-5356
(1) 200 PAIR TELEPHONE/VOICE TIE CABLE FROM BUILDING MDF ON SECOND FLOOR. AT 00 RU
1.
MDF 9 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

01 RU 949 Central Ave.


TERMINATE CABLE ON EXISTING XLBET RACK, AT 3RD FLOOR IDF TERMINATE ON S210 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48

02 RU
Naples, Florida 34102
TOWER Phone: 239-643-3103 Fax: 239-643-7435
7 7 10 03 RU
2. SC MULTIMODE FIBER OPTIC PATCH CORDS FOR OWNER'S ACTIVE HUBS, LENGTH AS REQUIRED. REFER
SYSTEM. 04 RU
TO Project:
SPECIFICATIONS FOR MORE DETAIL. 9 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

05 RU

PUBLIC
(#) 4 PAIR CAT 6 PLENUM RATED VOICE/DATA STATION CABLE TO INFORMATION OUTLET. TERMINATE DATA
25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48

06 RU
3.
CABLES AT DATA STATION PATCH PANEL, AND VOICE CABLES AT 110 PUNCHDOWN BLOCKS. 7 7 07 RU
08 RU

K # = REFER TO RESPECTIVE FLOOR PLANS FOR QUANTITY OF PORTS PER OULET, TO DETERMINE THE
NUMBER OF 4 PAIR STATION CABLE REQUIRED AT EACH LOCATION.
9 1

25
2

26
3

27
4

28
5

29
6

30
7

31
8

32
9

33
10

34
11

35
12

36
13

37
14

38
15

39
16

40
17

41
18

42
19

43
20

44
21

45
22

46
23

47
24

48
09 RU
10 RU
K
DEFENDER'S
OFFICE - 5TH
7 2 7 11 11 RU
# DIVISION 17 CONTRACTOR'S KEYNOTES 12 RU
9 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

13 RU

1. ELEVATION INDICATES ALL EQUIPMENT AND CABLING REQUIRED TO BE PROVIDED FOR THIS 7
25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48

7
14 RU
15 RU FLOOR
RELAY RACK BASE LOCATION. 16 RU
FIBER OPTIC, COPPER, AND BONDING/GROUNDING BACKBONES ARE PROVIDED BY SCS 12 9
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

17 RU
CONTRACTOR. 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48

18 RU
MOUNTING BOLT 2. TELECOMMUNICATIONS GROUNDING BUSBAR (TGB). SEE DETAIL 7 19 RU
Owner:

J
WITH ISOLATED
WASHERS 3. ALL VERTICAL RACKS TO BE PROVIDED WITH VERTICAL AND HORIZONTAL CABLE MANAGEMENT.
9
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
20 RU
21 RU
J Lee County Board
RUBBER GROUNDING MAT 4. RACK MOUNTED POWER STRIP.
25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48

22 RU of County
7 23 RU
5. RACK MOUNTED UPS UNIT. 30A/120V, 2880VA MINIMUM 24 RU Commissioners
25 RU
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

9
6. VERTICAL CABLE MANAGEMENT 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 AREA RESERVED FOR 26 RU
OWNER PROVIDED Consultant:
7 27 RU
7. ACTIVE ELECTRONICS
HORIZONTAL CABLE MANAGEMENT 28 RU
13099 S. Cleveland Ave.
29 RU Suite 500
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

NOT USED 1 9
8. 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48

30 RU
H
Fort Myers, Florida 33907
7 31 RU
H 9. 48 PORT CAT 6, VOICE/DATA PATCH PANEL. Phone: 239-275-4240
32 RU
Fax: 239-275-3511
33 RU www.tlc-engineers.com
10. (2) 24 PORT FIBER OPTIC PATCH PANEL/DISTRIBUTION CENTERS. (1) FOR SINGLEMODE FIBER AND (1)
FOR 34 RU © Copyright 2014 TLC Engineering for Architecture, Inc.
MULTIMODE FIBER. PROVIDE AND INSTALL (1) 24SM/24MM FOC FROM MDF ON SECOND FLOOR TO THIS VOICE/DATA
35 RU
EB #0000015 TLC NO: 714125
LOCATION. CONNECTIONS TO BE TYPE SC WITH FUSION SPLICE PIGTAILS OUTLET
36 RU
37 RU
11. (2) 24 PORT FIBER OPTIC PATCH PANEL/DISTRIBUTION CENTERS. (1) FOR SINGLEMODE FIBER AND (1) #6 Cu GROUND TO 38 RU Seal:
FOR BUILDING SERVICE 39 RU
MULTIMODE FIBER. PROVIDE AND INSTALL (1) 24SM/24MM FOC FROM PUBLIC DEFENDER'S SERVER GROUND 40 RU
ROOM 41 RU
4
TO THIS LOCATION. CONNECTIONS TO BE TYPE SC WITH FUSION SPLICE PIGTAILS. 42 RU
G 2 43 RU G
12. 110 PUNCHDOWN BLOCKS (QUANTITY AS REQUIRED) FOR TELEPHONE/VOICE TIE CABLES 5
44 RU
MDF 45 RU

NOTE:
ALL WORK SHOWN ON THIS DRAWING, UNLESS SPECIFICALLY NOTED OTHERWISE IS TO BE PROVIDED BY THE #6 Cu GROUND TO
DIVISION 17 CONTRACTOR. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THESE DOCUMENTS AND THE VERTICAL RACKS 6
ASSOCIATED SPECIFICATIONS.

F
RACK MOUNTING ON CONCRETE 1 INTERMEADIATE DISTRIBUTION FRAME RISER ELEVATION 1
2
F
Project Phase:
No Scale No Scale Construction
Documents
Project #: 0118.22
IDF# - PP #-PORT#
3/4" , 6" AFF, 8' H. Project Issued: 11/05/14
CONDUIT SLEEVES PENETRATE PLYWOOD BACKBOARD Sheet Issued:
THROUGH ACCESSIBLE CEILING PAINTED W/ FIRE
OR FLOOR WHERE APPLICABLE RESISTANT PAINT.
E E
BY DIV 16. BY DIV. 16 (1) 4PR UTP CAT- No. Date Revision
6
PLENUM RATED
CABLE FROM IDF

"A" MEASURED FROM END OF (1) RJ45 CAT-6 JACK


STRINGER TO MIDDLE OF CROSS SLAT. MODULE
CABLE RUNWAY RADIUS DROP
TUBULAR RUNWAY FASTENED OR-63750030
TO CEILING AND/OR WALL "B" MEASURED FROM MIDDLE OF CROSS SLATS.
CABLE RUNWAY RADIUS DROP SHALL
BE USED AT ALL CABLE DROP
LOCATIONS
#6 TO GROUND BAR SINGLE GANG FACEPLATE PP #-PORT#
D BY DIV. 17 FRAME D
B
OR-40300549

VERTICAL CABLE OUTLET DESIGNATOR SELF ADHESIVE LABELS


ORGANIZERS ON BOTH SIDES LEN
G TH

IDF # : IDF WHERE OUTLET IS CONNECTED TO


PP # : PATCH PANEL IN IDF
WID PORT #: PORT # ON PATCH PANEL
TH

C C

#6 INSULATED COPPER GROUND


BY DIV. 17 FOR THE OTHER JACK COUNT IN OUTLET
CHATSWORTH TUBULAR RUNWAY PROVIDE
UNIVERSAL RUNWAY SYSTEM AS FOLLOWS
# OF RJ45 CAT-6
# OF UTP CAT-6
# OF JACKS FACE PLATE JACKS
CABLES FROM IDF
OR-63750030 Copyright © 2014. BSSW Architects, Inc.
2 OR-40300548 2 2 reserves copyright and other rights
3 OR-40300547 3 3 restricting these documents to the original
site or purpose for which they were
4 OR-40300546 4 4 prepared. Reproductions, changes or
B 6 OR-40300545 6 6 B assignments are prohibited.

Sheet Title:

Brett L. Sands, P.E. TECHNOLOGY


Florida License #48477
TYPICAL RACK ISOMETRIC VIEW TUBULAR RUNWAY ABOVE RACKS TYPICAL DATA OUTLET DETAILS
No Scale
3 No Scale
4 No Scale
5
Sheet No.
A A

Seal
T201
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16