0118 018 1 04 - JC 2nd Floor MEP Progress Set 01 08 15
0118 018 1 04 - JC 2nd Floor MEP Progress Set 01 08 15
BASIC MATERIALS BASIC MATERIALS CONT. TELEPHONE/COMPUTER RACEWAY SYSTEM GENERAL NOTES:
SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION
1. LIGHT SWITCHES SHALL BE MOUNTED 48 INCHES ABOVE FINISHED FLOOR TO CENTER LINE OF A R C H I T E C T S I N C
Sa SINGLE POLE SWITCH AUTOMATIC TRANSFER SWITCH DEVICE, UNLESS OTHERWISE NOTED. License # AA C001863
(SUBSCRIPT INDICATES ITEM CONTROLLED)
S3 30AR NON-FUSED DISCONNECT SWITCH, SIZE & # OF POLES COMMUNICATIONS "INFORMATION OUTLET" MTD. AT
THREE-WAY SWITCH 1500 Jackson Street, Suite 200
NF RECEPTACLE HEIGHT UNLESS OTHERWISE NOTED. DIVISION
L NF DENOTES NON-FUSED RECEPTACLES SHALL BE LOCATED 18 INCHES ABOVE FINISHED FLOOR TO CENTER LINE OF L Fort Myers, Florida 33901
S4 FOUR-WAY SWITCH 16 CONTRACTOR TO PROVIDE 4" SQUARE WITH SINGLE GANG 2. DEVICE, UNLESS OTHERWISE NOTED. ABOVE-COUNTER RECEPTACLES SHALL BE MOUNTED Phone: 239-278-3838 Fax: 239-275-5356
AR DENOTES AMP RATING OF SWITCH RAISED MUD RING. CONTRACTOR TO STUB UP (2) 1"
SP SINGLE POLE SWITCH WITH PILOT LIGHT 6" ABOVE BACK SPLASH TO CENTERLINE OF DEVICE.
CONDUITS AT EACH LOCATION TO ABOVE CEILING AND TURN
SWP SINGLE POLE SWITCH WITH WEATHERPROOF COVER 30AR TO ACCESSIBLE CEILING SPACE. CONTRACTOR TO PROVIDE 949 Central Ave.
FUSED DISCONNECT BUSHING ON END OF CONDUIT AND PULLSTRING WITHIN. 3. EQUIPMENT SHALL BE OF MATERIALS SUITABLE FOR AND RATED FOR THE ENVIRONMENT IN Naples, Florida 34102
20AF
WHICH THEY ARE TO BE INSTALLED. Phone: 239-643-3103 Fax: 239-643-7435
SWPL SINGLE POLE SWITCH WITH WEATHERPROOF LOCKING COVER AR DENOTES AMP RATING OF SWITCH
MCP AF DENOTES AMP FUSE SIZE
SK SINGLE POLE KEY SWITCH SIZE TV TELEDATA/TV OUTLET - 4" SQUARE 2 GANG BOX WITH A. WORKING CLEARANCES FOR ELECTRICAL EQUIPMENT SHALL BE IN COMPLIANCE WITH Project:
# OF POLES (2) 1" CONDUITS PER ABOVE. 4.
NEC 110.
Lee County
S3K THREE-WAY KEY SWITCH 30/3 COMBINATION MAGNETIC MOTOR STARTER, SIZE & # OF POLES
0 3R
S4K FOUR-WAY KEY SWITCH 4'
3 POLE UNLESS OTHERWISE NOTED B. THE EXCLUSIVELY-DEDICATED SPACE EXTENDING FROM FLOOR TO STRUCTURAL
Justice Center
3'-6"
3'
ENCLOSURE NEMA RATING. TELEPHONE OUTLET FLOOR MOUNTED CEILING WITH A WIDTH AND DEPTH OF THE PANELBOARD OR SWITCHBOARD MUST BE
K SL SINGLE POLE SWITCH WITH SECURITY LOCKING KEY CLEAR OF ALL PIPING, DUCTS OR EQUIPMENT FOREIGN TO THE ELECTRICAL EQUIPMENT K
NEMA STARTER SIZE OR ARCHITECTURAL APPURTENANCES IN ACCORDANCE WITH NEC 408.
Second Floor
SLV
4'
Remodel Pod D
(CLASSIFIED AS FIRE/SMOKE AND SMOKE PARTITIONS), THEY SHALL BE INSTALLED
3'-6"
3'-6"
SD DIMMER SWITCH
3'
SURFACE MOUNTED
(1500 WATTS UNLESS OTHERWISE INDICATED) T A. ALL ELECTRICAL BOXES SHALL BE METALLIC.
TELEPHONE SYSTEM RACEWAY Owner:
BRANCH CIRCUIT PANELBOARD, OVER 250 VOLTS,
J
DUPLEX RECEPTACLE
FLUSH MOUNTED B. BOX OPENING SHALL OCCUR ONLY ON ONE SIDE OF FRAMING SPACE. J Lee County Board
T
TWIST LOCK RECEPTACLE
BRANCH CIRCUIT CONDUIT CONCEALED ABOVE CEILING OR IN WALL.
CONDUIT SHALL INCLUDE PHASE, NEUTRAL AND GROUND CONDUCTORS
C. BOX OPENING SHALL NOT EXCEED 16 SQUARE INCHES. of Commissioners
SURGE PROTECTION TYPE (TVSS) AS REQUIRED FOR CIRCUITS (UNLESS OTHERWISE NOTED). D. ALL CLEARANCES BETWEEN OUTLET BOX AND GYPSUM BOARD SHALL BE
SP DUPLEX RECEPTACLE COMPLETELY FILLED WITH JOINT COMPOUND (OR OTHER APPROVED MATERIAL).
3'
PROVIDE ALL NECESSARY POWER PACKS AND RELAYS FOR A FULLY FUNCTIONAL SYSTEM
DDC DIRECT DIGITAL CONTROL PANEL
Seal
E0.01
NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
M
LIGHTING FIXTURE SCHEDULE M
Required Lamps
Lamp
Type Description Manufacturer Model Voltage Type Quantity Comments A R C H I T E C T S I N C
B RECESSED COMPACT FOURESCENT LIGHTOLIER PH60-132T-277 277 V 42WTT 1 LIMITS OF CONSTRUCTION License # AA C001863
DOWNLIGHT 6" DIA.
1500 Jackson Street, Suite 200
L B2 2x4 PRABOLIC W/18 CELL LIGHTOLIER 2LP3GS332-36AL-277-1/21-EB 277 V F32WT8 2 L Fort Myers, Florida 33901
SEMI-SPECULAR ALUMINUM LOUVER Phone: 239-278-3838 Fax: 239-275-5356
E2 2x2 PRABOLIC W/9 CELL LIGHTOLIER 2LP3GS332-36AL-277-1/21-EB 277 V F32WT8 2 949 Central Ave.
SEMI-SPECULAR ALUMINUM LOUVER POD B Naples, Florida 34102
Phone: 239-643-3103 Fax: 239-643-7435
X EXISTING TO BE REUSED 277 V CLEAN &
RE-LAMP EXISTING Project:
Lee County
CR
GENERAL LIGHTING NOTES :
K 1. ALL FLUORESCENT FIXTURES SHALL USE T8 LAMPS AND ELECTRONIC BALLASTS, UNLESS
OTHERWISE NOTED.
4. IF THERE IS A DISCREPANCY BETWEEN A FIXTURE DESCRIPTION AND GENERAL NOTES, AND
THE CATALOG NUMBER LISTED, THE FIXTURE DESCRIPTION AND GENERAL NOTES SHALL
K
Justice Center
2. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LOCATION OF LIGHT
5.
DICTATE.
FIX
3. COORDINATE TYPE OF CEILING FOR EACH FIXTURE WITH ARCHITECTURAL REFLECTED
Part B
ACT
CEILING PLANS AND PROVIDE FIXTURE TRIM AS REQUIRED. 8' - 6" A.F.F.
Owner:
Design
8' - 0" A.F.F. 8' - 6" A.F.F.
E2 1. SAME AS TYPE A, EXCEPT CIRCUIT IS FED FROM EMERGENCY
GWB 3
GWB E2 8' - 6" A.F.F. E2 E2 DISTRIBUTION TYPICAL.
Development
E2 E2 E2 GWB GWB
8' - 6" A.F.F.
8' - 0" A.F.F. 8' - 0" A.F.F. 2. SAME AS TYPE B, EXCEPT CIRCUIT IS FED FROM EMERGENCY
E2 E2
GWB DISTRIBUTION, TYPICAL.
E2 E2 E2 8' - 0" A.F.F. Project #: 0118.22
ACT (Wood E2 Look) E2
8' - 11 1/2" A.F.F. ACT (Wood Look) Project Issued: 07/01/13
E2 E2 8' - 11 1/2" A.F.F.
E2
ACT ACT Sheet Issued:
E2 E2 E2 8' - 11 1/2" A.F.F. 8' - 6" A.F.F.
E E
POD A
E2 E2 E2 E2 No. Date Revision
GWB
8' - 6" A.F.F. GWB E2 E2
E2 8' - 6" A.F.F. E2 E2
E2
ACT (Wood Look)
E2 E2 EXISTING
ACT APPROX LINE OF CONSTRUCTION
8' - 11 1/2" A.F.F. E2 E2 E2
8' - 11 1/2" A.F.F. EXISTING CLG TO REMAIN
E2 E2 E2 E2 E2
GWB
8' - 0" A.F.F. E2 E2 E2 E2
GWB
E2 8' - 6" A.F.F. GWB
7' - 6" A.F.F.
D E2 ACT (Wood Look)
E2 E2 E2 E2 E2 E2 D
M
E2 ACT
O
8' - 11 1/2" A.F.F. 8' - 0" A.F.F. B2
POD C
NR
ACT
ACT
O
E2 E2 8' - 0" A.F.F.
3 E2 E2
E
8' - 6" A.F.F.
ST
E2 E2 E2 B2
RE
E2 E2 X
ET
B E2 E2 E2
PS
GWB ACT
D
GWB B2
8' - 6" A.F.F. E2 E2
CR
EXISTING ACT
LIMITS OF CONSTRUCTION
POD D POD A
8' - 11 1/2" A.F.F. Copyright © 2014. BSSW Architects, Inc.
reserves copyright and other rights
D2401.A-2 restricting these documents to the original
site or purpose for which they were
prepared. Reproductions, changes or
B B assignments are prohibited.
KEY PLAN Sheet Title:
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
M M
A R C H I T E C T S I N C
License # AA C001863
ELEC/MECH
Lee County
K K
Justice Center
Second Floor
CR Remodel Pod D
D
PS
Part B
CR E-Filing
13 L4
±983 SF Owner:
D
PS
Lee County Board
L4
J J
D
PS
Chair Storage
12 CT CPT L4 L4 of Commissioners
FIX
±380 SF
L4
F2
Consultant:
L4 USB
2 ENLARGED ELEC/MECH ROOM POD D PLAN PHASE II F2
13099 S. Cleveland Ave.
Suite 500
E1.02 USB
1/4" = 1'-0"
UP H
Fort Myers, Florida 33907
H F2 Phone: 239-275-4240
AT 18" Fax: 239-275-3511
USB www.tlc-engineers.com
F USB FS AT 8'-0" © Copyright 2014 TLC Engineering for Architecture, Inc.
Seating Area 2
ETR
Vestibule LIMITS OF CONSTRUCTION 05 EB #0000015 TLC NO: 714124
Men's 10 ±416 SF
11 USB
2 Seal:
E1.02
USB
G G
USB
USB
ELEC/MECH
Women's
09
F F CR F
Project Phase:
Design
D
PS
ETR
"
D
18
Vestibule
PS
"
6
AT
8'-
AT
08
Jury Seating FS
01 Development
±Redundant CR
DPS
Project Issued: 07/16/13
Sheet Issued:
UP
"
18
"
6
Bailiff Queing
AT
8'-
E E
AT
" 6
AT
8'-
AT
FS D
F4
D D
M
O
POD C
"
18
NR
"
F4
6
AT
8'-
O
AT
E
FS
ST
Seating Area 1
RE
ET
04
D
±3935 SF
F4
Break/Lounge
D
Jury Staff 15 POD B
C F4
06 C
±712 SF
USB
PS
Bailiff Queing
D
PS
POD D POD A
D
USB Area F4
03 Supervisor's
USB ±397 SF
Office
07 F4
D
GENERAL NOTES: # KEYNOTES: Copyright © 2014. BSSW Architects, Inc.
reserves copyright and other rights
restricting these documents to the original
F4
site or purpose for which they were
±160 SF 1. REFER TO MECHANICAL DRAWINGS FOR EXACT LOCATION OF ALL MECHANICAL 1. 3/4" C WITH (2) #12, (1) #12 GROUND. TERMINATE ON EXISTING prepared. Reproductions, changes or
B F4 20A/2P CIRCUIT BREAKER. B assignments are prohibited.
KEY PLAN
CR
EQUIPMENT.
2. REFER TO ELECTRICAL DETAIL DRAWINGS FOR MOUNTING HEIGHTS OF ALL WALL 2. NEW FIRE ALARM PULL STATION. Sheet Title:
LIMITS OF CONSTRUCTION
3.
MOUNTED ELECTRICAL DEVICES.
PROVIDE CONDUIT/WIRING AS REQUIRED TO MEET CIRCUITING SHOWN TO
3. CEILING MOUNTED SMOKE DETECTORS FOR SMOKE DOORS.
Brett L. Sands, P.E. SECOND FLOOR POD
Florida License #48477
D PLAN PHASE II -
CONFORM TO N.E.C. REQUIREMENTS. PROVIDE EQUIPMENT GROUND CONDUCTOR 4. MAGNETIC DOOR HOLD OPEN DEVICES.
IN ALL RACEWAYS.
5. LOCATION OF EXISTING PANELS.
E1.02
8. APPROXIMATE LOCATION OF NEW FIRE ALARM DUCT
1 SECOND FLOOR POD D PLAN PHASE II - POWER & SYSTEMS 6. ALL EXISTING CABLE RENDERED "ABANDONED" SHALL BE REMOVED ENTIRELY.
ANY CABLE LEFT IN PLACE (NOT USED) SHALL BE TAGGED WITH LABELS
DETECTORS FOR CONTROL ON NEW FIRE SMOKE DAMPERS.
COORDINATE LOCATION WITH MECHANICAL CONTRACTORS.
E1.02 INDICATING "FUTURE USE" WITH IDENTIFICATION AT BOTH ENDS.
1/8" = 1'-0"
Seal
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
M M
1 PANEL "HPx"
WATT STOPPER WA-200 OR
3 APPROVED EQUIVALENT
A R C H I T E C T S I N C
License # AA C001863
BLUE
2 BLACK 1500 Jackson Street, Suite 200
HOT (BLACK) Fort Myers, Florida 33901
L L
BLACK Phone: 239-278-3838 Fax: 239-275-5356
LINE LOAD
277VAC,60Hz 949 Central Ave.
Naples, Florida 34102
GREEN Phone: 239-643-3103 Fax: 239-643-7435
GROUND
NEUTRAL (WHITE) WHITE Project:
2 CONDUIT - NOM 4" DIA OR SMALLER STEEL ELECTRICAL METALLIC TUBING. A MAX OF ONE CONDUIT IS Part B
PERMITTED IN THE FIRESTOP SYSTEM. CONDUIT TO BE INSTALLED NEAR CENTER OF STUD CAVITY THE NUMBER OF DEVICES POWERED FROM A Owner:
WIDTH AND TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY.
Lee County Board
SINGLE
J POWER PACK VARIES WITH THE TYPE OF DEVICE. J
A SEPARATE POWER PACK IS REQUIRED FOR EACH
of Commissioners
3 FILL VOID OR CAVITY MATERIAL - CAULK FILL MATERIAL BEARING THE UL CLASSIFICATION MARKING
CIRCUIT BEING CONTROLLED.
INSTALLED TO COMPLETELY FILL ANNULAR SPACE BETWEEN PIPE OR CONDUIT AND GYPSUM
WALLBOARD AND WITH A MIN 1/4" DIAM BEAD OF CAULK APPLIED TO PERIMETER OF CONDUIT AT ITS
TYPICAL OVERRIDE SWITCH
EGRESS FROM THE WALL. CAULK INSTALLED SYMMETRICALLY ON BOTH SIDES OF WALL ASSEMBLY. POWER PACK
THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE HOURLY FIRE RATING OF CONTACTS
THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS SHOWN IN THE FOLLOWING TABLE. THE HOURLY T REDRATED FOR 20 AMPS. Consultant:
RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE OF THE CONDUIT AND THE RED
HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS TABULATED BELOW: 13099 S. Cleveland Ave.
BLACK RED 24 VDC Suite 500
BLACK COMMON
WHITE BLUE CONTROL Fort Myers, Florida 33907
H
H CONTROL (BLUE) TO 24 VDC Phone: 239-275-4240
MAX CONDUIT ANNULAR SPACE, F RATING, HR. T RATING, HR. (RED) Fax: 239-275-3511
DIAM, IN. IN. POWER PACK CLOSES OSP CONTACTS. www.tlc-engineers.com
© Copyright 2014 TLC Engineering for Architecture, Inc.
1 0 TO 3/16 1 OR 2 0, 1 OR 2 EB #0000015 TLC NO: 714124
1 1/4 TO 1/2 3 OR 4 3 OR 4
4 0 TO 1-1/2 1 OR 2 0
6 1/4 TO 1/2 3 OR 4 0 PLAN SYMBOL = OS CEILING MOUNTED
DUAL TECHNOLOGY
Seal:
12 3/16 TO 3/8 1 OR 2 0 OCCUPANCY SENSOR
G G
F F
Project Phase:
Design
Development
CENTERED BETWEEN
DOOR & CEILING
CLOCK OUTLET FIRE HORN (OR CHIME) &
(COORDINATE WITH
WALL MOUNTED LIGHT FIXTURES LIGHT 80" AFF Project #:
AS NOTED ON PLANS h EXIT ARCHITECT)
Project Issued:
0118.22
07/16/13
TELEVISION
BOTTOM TV Sheet Issued:
OUTLET
OF DEVICE
E h E
No. Date Revision
h FA PULL F
D D
6" AFC SWITCH STATION 54"
48" DUPLEX
78" MAX. RECEPTACLE
TO TOP DEVICE
1
36" TELE. OUTLET
COMPUTER
AFF OUTLET
h
18"
C AFF C
Sheet Title:
Sheet No.
A A
Seal
E2.01
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
M M
A R C H I T E C T S I N C
License # AA C001863
Justice Center
~
INSTALLATION
K EACH SIDE K
CABLING
Second Floor
ACCESSIBLE CEILING
Remodel Pod D
Part B
8" KINDORF SECTION Owner:
J
EACH SIDE
J Lee County Board
of Commissioners
NOTE: CONTRACTOR SHALL RESTORE THE INTEGRITY OF RATED WALLS PENETRATED PER SPECIFICATIONS.
1" CONCELED CONDUIT ANY NEW PENETRATIONS SHALL FOLLOW THIS GUIDELINE.
IF ADDITIONAL SLEEVES ARE NEEDED OR REQUESTED USE FOLLOWING 13099 S. Cleveland Ave.
WALL SLEEVE SIZING TABLE EQUIVALENT TO CAT. 5 CABLES Suite 500
FACEPLATE ADJUST COUNT BASED ON CABLE SIZES Fort Myers, Florida 33907
H
H Phone: 239-275-4240
# OF CABLES SLEEVE SIZE Fax: 239-275-3511
www.tlc-engineers.com
1-8 1" © Copyright 2014 TLC Engineering for Architecture, Inc.
9-14 1 1/4"
EB #0000015 TLC NO: 714124
15-18 1 1/2"
19-26 2"
FLOOR SLAB Seal:
27-40 2 1/2"
41-60 3"
UNLESS OTHERWISE NOTED ON DRAWINGS
G G
F F
Project Phase:
Design
Development
IDF# - PP #-PORT#
Project #: 0118.22
Project Issued: 07/16/13
Sheet Issued:
(1) 4PR UTP CAT-
6
E CABLE FROM IDF E
No. Date Revision
C C
Sheet Title:
Sheet No.
A A
Seal
E2.02
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
M M
SCOPE OF WORK 61G15 FAC COMPLIANCE NOTES FIRE PROTECTION LEGEND GENERAL NOTES
SYMBOL DESCRIPTION
SCOPE OF WORK: THE SPRINKLER CONTRACTOR SHALL RELOCATE EXISTING SPRINKLER HEADS TO ACCOMMODATE (2) ACCEPTANCE TEST CRITERIA IDENTIFIED. 1. FIRE PROTECTION SYSTEM TO COMPLY WITH NFPA 13, 14, 20, 24 AND ALL APPLICABLE STATE
FOR NEW WALL AND CEILING LAYOUT. CONTRACTOR SHALL PROVIDE HYDRAULIC CALCULATION TO VERIFY THAT THE THE ACCEPTANCE TESTING FOR ABOVE GROUND WET-PIPE FIRE SPRINKLER SYSTEM AND ALL RELATED OR - CONTROL VALVE W/TAMPER SWITCH CODES.
SPRINKLER SYSTEM WILL FUNCTION PROPERLY WITH THE NEW SPRINKLER HEAD LAYOUT/ PROVIDE ALL NEW PIPING, COMPONENTS SHALL CONSIST OF ALL APPLICABLE ITEMS SHOWN ON FORMS: NFPA 13, 2002, CHAPTER 16, FIGURE A R C H I T E C T S I N C
FITTINGS AND SPRINKLER HEADS FOR NEW LAYOUT. CONTRACTOR SHALL COORDINATE DOWN-TIME WITH OWNER AND 16.1, CONTRACTOR'S MATERIAL AND TEST CERTIFICATE FOR ABOVEGROUND PIPING, AND NFPA 13, 2002 EDITION, - CHECK VALVE 2. FINAL INSPECTION AND APPROVAL BY LOCAL FIRE MARSHAL AND ARCHITECT/ENGINEER.
THE LOCAL AHJ. CHAPTER 10, FIGURE 10.10.1, CONTRACTOR'S MATERIAL AND TEST CERTIFICATE FOR UNDERGROUND PIPING. NFPA 13,
License # AA C001863
- FLOW SWITCH
2002 “ INSTALLATION OF SPRINKLER SYSTEMS” AND NFPA 24, “INSTALLATION OF PRIVATE FIRE SERVICE MAINS 3. SPRINKLER SHOP DRAWINGS AND MATERIAL SUBMITTALS SHALL BE SUBMITTED TO THE
AND THEIR APPURTENANCES” REQUIREMENTS ARE APPLICABLE IN THEIR ENTIRETY RELATING TO DESIGN, 1500 Jackson Street, Suite 200
FDC - FIRE DEPARTMENT CONNECTION ARCHITECT/ENGINEER AND STATE FIRE MARSHAL AND SHALL BE APPROVED PRIOR TO ANY
L INSTALLATION AND ACCEPTANCE TESTING CRITERIA. L Fort Myers, Florida 33901
PIV - POST INDICATOR VALVE W/TAMPER SWITCH INSTALLATION. Phone: 239-278-3838 Fax: 239-275-5356
(3) STRUCTURAL SUPPORT AND STRUCTURAL OPENINGS REQUIRED BY THE FIRE PROTECTION SYSTEM ARE SHOWN ON
FVC - FIRE VALVE CABINET 4. PIPE ROUTING SHOWN IS SCHEMATIC ONLY. IT IS THE RESPONSIBILITY OF THIS CONTRACTOR 949 Central Ave.
THE DOCUMENTS THE EXISTING STRUCTURAL SUPPORT SYSTEM FOR THIS BUILDING HAS BEEN DESIGNED BY A STATE
OF FLORIDA LICENSED STRUCTURAL ENGINEER IN ACCORDANCE WITH THE FLORIDA ADMINISTRATIVE CODE. NO
TO PROVIDE ANY ADDITIONAL OFFSETS REQUIRED FOR PROPER INSTALLATION AND Naples, Florida 34102
FDV - STANDPIPE WITH FIRE DEPARTMENT VALVE COORDINATION WITH OTHER TRADES.
ADDITIONAL DEAD LOADS ARE REQUIRED FOR THE MODIFICATION OF THIS STANDPIPE SYSTEM. Phone: 239-643-3103 Fax: 239-643-7435
- SPRINKLER AND DRAIN RISER
B) APPLICABLE NFPA STANDARD TO BE APPLIED 5. PIPING IN AREAS WITH EXPOSED STRUCTURE SHALL BE INSTALLED AS HIGH AS POSSIBLE TO
NFPA 13, AND FLORIDA FIRE PREVENTION CODE LATEST EDITION. - BACKFLOW PREVENTOR W/TAMPER SWITCHES Project:
ALLOW THE OWNER MAXIMUM USE OF THE SPACE.
Lee County
(A) POINT OF SERVICE
- ROOF MANIFOLD
THE POINT OF SERVICE IS AN EXISTING 8" SPRINKLER MAIN THAT BEGINS AT THE NEW BACKFLOW THAT 6. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR CEILING DESCRIPTIONS AND
IS LOCATED APPROX. 30' FROM THE BUILDING SPRINKLER RISER. - HYDRAULIC REFERENCE NODE HEIGHTS.
K
(C) CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR AREA
- NEW SPRINKLER PIPING 7. SPRINKLERS ARE TO BE COORDINATED WITH ALL DIFFUSERS, SPEAKERS, LIGHTING FIXTURES
K
Justice Center
Second Floor
F.C. - FLUSHING CONNECTION AND CEILING SYSTEMS. SPACING OF SPRINKLERS SHALL BE IN ACCORDANCE WITH NFPA 13
LIGHT HAZARD: OPEN OFFICE SPACE, RESTROOMS AND CONFERENCE ROOMS AND THE LISTING OF THE SPRINKLER.
ORDINARY HAZARD GROUP 1: STORAGE AREAS, MECHANICAL ROOMS, MATERIAL STORAGE AND - EXISTING \" UPRIGHT SPRINKLER
CONCRETE FASTENER
(U.L. LISTED OR F.M. APPROVED)
ELECTRICAL ROOMS - EXISTING \" RECESSED SPRINKLER
- EXISTING \" CONCEALED SPRINKLER
8. SPRINKLER LOCATIONS SHALL BE CENTERED IN THE TILE. PROVIDE ARMOVER OR SWING JOINT
AS REQUIRED. Remodel Pod D
(D) DESIGN APPROACH:
LIGHT HAZARD : - EXISTING CONTROL VALVE W/TAMPER SWITCH
9. SPRINKLERS IN AREAS WITH EXPOSED STRUCTURE (OBSTRUCTED CONSTRUCTION) SHALL BE
INSTALLED WITH DEFLECTOR 1" BELOW THE BOTTOM OF THE BEAM (MAXIMUM 22" BELOW
Part B
SPRINKLER SYSTEM TO BE ATTACHED AND SUPPLIED FROM SPRINKLER RISER STANDPIPE. SYSTEM SHALL
ALL THREAD ROD ROOF DECK). EXPOSED BAR JOISTS THAT HAVE SPRAY-ON FIRE PROOFING THAT MAKES THE Owner:
BE EXTENDED INTO ENTIRE BUILDING IN ACCORDANCE WITH NFPA-13. U.L, LIGHT HAZARD. LISTED AND - EXISTING SPRINKLER PIPING
J APPROVED UPRIGHTS & PENDANTS (5.6 K-FACTOR) SPRINKLER HEADS TO BE USED. HEADS SHALL BE
- EXISTING SPRINKLER PIPING TO BE REMOVED
JOIST SOLID SHALL BE TREATED LIKE A BEAM WITH THE SPRINKLERS 1" BELOW THE BOTTOM
OF THE FIRE PROOFING. J Lee County Board
RATED AT 155 DEGREES. MAX. SPRINKLER HEAD SPACING SHALL NOT EXCEED 225 SQ FT WITH A .10
DENSITY. SPRINKLER CONTRACTOR SHALL PROVIDE HYDRAULIC CALCULATION. 1500 SQ. FT. SHALL BE - CONNECT TO EXISTING
10. SLEEVE AND/OR FIRESTOP ALL PENETRATIONS THROUGH RATED WALLS, CEILINGS, AND FLOORS
of Commissioners
USED WHEN PERFORMING HYDRAULIC CALCULATION
- DEMOLISH TO POINT INDICATED WITH U/L LISTED ASSEMBLIES. FIRESTOP ASSEMBLIES SHALL BE EQUAL OR EXCEED THE
ORDINARY HAZARD GROUP 1 : RATING OF THE WALL, CEILING OR FLOOR. SEE ARCHITECTURAL DRAWINGS FOR FINAL FINISHES.
1 - REVISION REFERENCE
SPRINKLER SYSTEM TO BE ATTACHED AND SUPPLIED FROM SPRINKLER RISER STANDPIPE. SYSTEM SHALL
BE EXTENDED INTO ENTIRE BUILDING IN ACCORDANCE WITH NFPA-13. U.L, ORDINARY HAZARD. LISTED AND 1
11. PROVIDE ACCESS PANELS TO ALL VALVES ABOVE NON-ACCESSIBLE CEILINGS AND CHASES. Consultant:
- DETAIL REFERENCE: TOP-DETAIL#,
APPROVED UPRIGHTS & PENDANTS (5.6 K-FACTOR) SPRINKLER HEADS TO BE USED. HEADS SHALL BE FP-1 BOTTOM-DRAWING# SHOWN ON 13099 S. Cleveland Ave.
RATED AT 155 DEGREES. MAX. SPRINKLER HEAD SPACING SHALL NOT EXCEED 130 SQ FT WITH A .15 12. PROVIDE A PERMANENTLY ATTACHED NAME TAG TO THE RISER STATING THE REQUIRED DESIGN
CRITERIA FOR EACH HYDRAULICALLY-DESIGNED SYSTEM. Suite 500
DENSITY SPRINKLER CONTRACTOR SHALL PROVIDE HYDRAULIC CALCULATION. 1500 SQ FT SHALL BE
USED WHEN PERFORMING HYDRAULIC CALCULATIONS . NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT H
Fort Myers, Florida 33907
H PIPE HANGER RING 13. PROVIDE SPRINKLERS UNDERNEATH ALL EXPOSED DUCTWORK WHICH IS OVER 48" WIDE AND Phone: 239-275-4240
Fax: 239-275-3511
(U.L. LISTED OR F.M. APPROVED) (F) FLOW TEST DATA: SPRINKLER CONTRACTOR SHALL PROVIDE A CURRENT FLOW TEST
THAT SHALL BE INCLUDED WITH SHOP DRAWING SUBMITTAL. FIRE SPRINKLER LEGEND SPACE HEADS AROUND ALL OBSTRUCTIONS IN ACCORDANCE WITH NFPA 13. HEADS UNDER
DUCTS ARE NOT INDICATED ON THE DRAWINGS BUT ARE REQUIRED AND SHALL BE PROVIDED
IN ACCORDANCE WITH NFPA 13. SPRINKLER LOCATIONS UNDER DUCTWORK AND AROUND
www.tlc-engineers.com
© Copyright 2014 TLC Engineering for Architecture, Inc.
MODEL PLATE OBSTRUCTIONS SHALL BE GOVERNED BY FINAL INSTALLED LOCATIONS. EB #0000015 TLC NO: 714124
(G) VALVING AND ALARM REQUIREMENTS TO MINIMIZE POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED SYMBOL ORF TEMP RESPONSE K-FAC FINISH STYLE MFG.
FLOW OF WATER
14. PROVIDE SPRINKLER GUARDS ON ALL HEADS IN ELECTRIC ROOMS, TELEPHONE ROOMS, Seal:
5.6" 135° QUICK 5.5 CHROME F4FR CONCEALED CHROME RELIABLE
THE EXISTING FIRE SPRINKLER RISER FOR THIS BUILDING IS EQUIPPED WITH A WATER FLOW SWITCH WITH A LOCAL ELEVATOR ROOMS, ELEVATOR SHAFTS AND ON ANY HEADS LESS THAN 7'-0" ABOVE THE
ALARM AND OFF-SITE MONITORING. 5.6" 155° QUICK 5.62 BRASS F1FR UPRIGHT NONE RELIABLE
FLOOR.
5.6" 155° QUICK 5.62 BRASS F1FR UPRIGHT HD/GD RELIABLE
(I) BACKFLOW PREVENTION AND METERING SPECIFICATIONS: 15. IF SYSTEM PRESSURE EXCEEDS 100 PSI, ALL HANGERS ON END HEADS IN PENDANT POSITION
G G
SHALL BE WITHIN 12" OF END OF LINE IN ACCORDANCE WITH NFPA 13.
THE BACKFLOW PREVENTION DEVICE ASSEMBLY AND METERING EQUIPMENT ARE EXISTING AND MEET THE
REQUIREMENTS OF THE LOCAL WATER PURVEYOR. THE MAX. PRESSURE LOSS SHALL NOT EXCEED -8 P.S.I, @
1000 GPM
APPLICABLE CODES AND STANDARDS 16. COORDINATE PIPING WITH ALL ELECTRICAL EQUIPMENT (PANELS, TRANSFORMERS, ETC.) PRIOR
TO ANY INSTALLATION. DO NOT ROUTE ANY PIPING OVER ANY ELECTRICAL PANELS UNDER ANY
FLORIDA BUILDING CODE 2010 EDITION CIRCUMSTANCES. ANY PIPING RUN OVER ELECTRICAL SHALL BE REROUTED AT NO ADDITIONAL
(J) QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD AND INTERIOR FIRE PROTECTION FLORIDA FIRE PREVENTION CODE 2010 EDITION COST.
COMPONENTS FLORIDA ADMINISTRATION CODE 61G15 FAC
HANGER - CONCRETE 2 ALL NEW YARD AND INTERIOR FIRE PROTECTION EQUIPMENT SHALL BE UL LISTED AND FM APPROVED. NFPA 13, 2007 EDITION
NFPA 14, 2007 EDITION
17. SPRINKLERS IN ELEVATOR SHAFTS AND EQUIPMENT ROOMS ARE TO BE INTERMEDIATE
TEMPERATURE 200°F SPRINKLERS PER NFPA 13.
No Scale
E E
No. Date Revision
BRANCH LINE
1" NPT MALE
D COUPLING D
INLET MAX. REDUCER
ADJUSTMENT
1" NIPPLE
4 7/8" ± 3/4"
FACE OF FITTING
TO FACE OF 1" 90° ELL 1" 90° ELL
CEILING DIMENSION
1" DROP
C REDUCER C
CEILING
SPRINKLER HEAD
Copyright © 2014. BSSW Architects, Inc.
reserves copyright and other rights
restricting these documents to the original
site or purpose for which they were
3/16" prepared. Reproductions, changes or
B MAX. COVER B assignments are prohibited.
ADJUSTMENT
Sheet Title:
Seal
FP0.01
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
M M
A R C H I T E C T S I N C
License # AA C001863
LIMITS OF CONSTRUCTION
1500 Jackson Street, Suite 200
L L Fort Myers, Florida 33901
Phone: 239-278-3838 Fax: 239-275-5356
Project:
Lee County
K K
Justice Center
Second Floor
Remodel Pod D
ACT
8' - 6" A.F.F.
Part B
Owner:
Consultant:
GWB 13099 S. Cleveland Ave.
GWB 8' - 0" A.F.F. GWB
8' - 0" A.F.F. 8' - 0" A.F.F. Suite 500
ACT
8' - 6" A.F.F. H
Fort Myers, Florida 33907
H Phone: 239-275-4240
Fax: 239-275-3511
www.tlc-engineers.com
ACT (Wood Look) © Copyright 2014 TLC Engineering for Architecture, Inc.
8' - 11 1/2" A.F.F. EB #0000015 TLC NO: 714124
OPEN OFFICE AREA
GWB
GWB ACT 8' - 6" A.F.F. Seal:
8' - 0" A.F.F. 8' - 6" A.F.F.
GWB
GWB GWB 8' - 0" A.F.F.
ACT (Wood Look) 8' - 6" A.F.F. 8' - 0" A.F.F.
F 8' - 11 1/2" A.F.F. F
Project Phase:
Design
GWB ACT
8' - 0" A.F.F. 8' - 6" A.F.F.
GWB
GWB
8' - 6" A.F.F.
8' - 6" A.F.F.
GWB
8' - 0" A.F.F.
GWB
8' - 0" A.F.F.
Development
GWB Project #: 0118.22
ACT (Wood Look) 8' - 0" A.F.F. Project Issued: 07/29/13
8' - 11 1/2" A.F.F. ACT (Wood Look) Sheet Issued:
8' - 11 1/2" A.F.F. ACT ACT
8' - 11 1/2" A.F.F. 8' - 6" A.F.F.
E E
No. Date Revision
GWB
8' - 6" A.F.F. OPEN OFFICEGWB
AREA
8' - 6" A.F.F.
NEW UPRIGHT
ACT (Wood Look) SPRINKLER HEAD
8' - 11 1/2" A.F.F. ACT LOCATION TYP.
8' - 11 1/2" A.F.F.
GWB
8' - 0" A.F.F.
GWB
8' - 6" A.F.F. GWB
D 7' - 6" A.F.F. D
LIGHT HAZARD LIGHT HAZARD
M
O
ACT (Wood Look) ACT
POD C
NR
8' - 11 1/2" A.F.F. 8' - 0" A.F.F.
O
ACT
ACT
E
8' - 0" A.F.F.
ST
8' - 6" A.F.F.
RE
ET
GWB ACT
8' - 0" A.F.F.
NEW UPRIGHT
8' - 0" A.F.F.
POD B
C GWB SPRINKLER HEAD C
8' - 0" A.F.F. LOCATION TYP.
GWB
8' - 6" A.F.F.
1
FP1.01
SECOND FLOOR POD D PLAN PHASE II - FIRE PROTECTION
1/8" = 1'-0"
Seal
FP1.01
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
M
MECHANICAL SYMBOL LEGEND MECHANICAL ABBREVIATIONS PLUMBING GENERAL NOTES HVAC GENERAL NOTES M
SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION
1. FIELD VERIFY EXISTING INSTALLATIONS. MODIFY EXISTING PLUMBING SYSTEMS, WHICH ARE TO 1. CONNECTION TO EQUIPMENT SHALL BE VERIFIED WITH MANUFACTURER'S CERTIFIED
REMAIN ACTIVE, TO FACILITATE RECONNECTION AND EXTENSION OF THE NEW WORK. DRAWINGS. TRANSITIONS TO ALL EQUIPMENT SHALL BE VERIFIED AND PROVIDED
-CEILING DIFFUSER, ROUND NECK AFD -ADJUSTABLE FREQUENCY DRIVE LD -LINEAR DIFFUSER FOR EQUIPMENT FURNISHED.
(CEILING DIFFUSERS ARE 4-WAY THROW UNO) -FLEXIBLE DUCT 2. NOTIFY OWNER AT LEAST 24 HOURS PRIOR TO INTERRUPTING EXISTING SERVICE. SCHEDULE
AFF -ABOVE FINISHED FLOOR MBH -THOUSAND BTUs PER HOUR DISCONNECTION AND TIE-INS TO MINIMIZE DISRUPTION OF SERVICES. SERVICES ARE NOT TO BE 2. DIMENSIONS SHALL BE FIELD-VERIFIED AND COORDINATED PRIOR TO PROCUREMENT OR
AFR -ABOVE FINISHED ROOF MCA -MINIMUM CIRCUIT AMPS LEFT DISRUPTED DURING NON-NORMAL CONTRACTOR WORKING HOURS. FABRICATION. COORDINATE THE WORK WITH OTHER TRADES INVOLVED. FIELD MODIFICATIONS A R C H I T E C T S I N C
-REVISION REFERENCE -TRANSITION, CONCENTRIC SUCH AS OFFSETS IN PIPING OR DUCTWORK (INCLUDING DIVIDED DUCTWORK) NEEDED DUE TO
1 AHU -AIR HANDLING UNIT MOCP -MAXIMUM OVER CURRENT PROTECTION 3. PIPE ROUTING SHOWN IS SCHEMATIC AND IS NOT INTENDED TO INDICATE EXACT ROUTING AND OBSTRUCTIONS OR INTERFERENCES SHALL BE PROVIDED AT NO ADDITIONAL COST. FOR PROJECTS License # AA C001863
1 AP -ACCESS PANEL ANY ADDITIONAL OFFSETS AND FITTINGS REQUIRED FOR PROPER INSTALLATION AND TO INVOLVING RENOVATION, COORDINATE NEW WORK WITH EXISTING ELEMENTS SUCH AS THE
-DETAIL REFERENCE: TOP-DETAIL#, MOD -MOTOR OPERATED CONTROL DAMPER (MOD) 1500 Jackson Street, Suite 200
MAINTAIN CLEARANCES. VERIFY STRUCTURAL, MECHANICAL AND ELECTRICAL INSTALLATIONS BUILDING STRUCTURE AND ARCHITECTURAL FEATURES, SPRINKLER PIPING, LIGHTS, PLUMBING, AND
M-1 BOTTOM-DRAWING# SHOWN ON -TRANSITION, ECCENTRIC BOP Fort Myers, Florida 33901
L -BOTTOM OF PIPE NC -NORMALLY CLOSED AND OTHER POTENTIAL OBSTRUCTIONS AND ROUTE PIPING TO AVOID INTERFERENCES. ELECTRICAL CONDUIT. L
Phone: 239-278-3838 Fax: 239-275-5356
T -THERMOSTAT/TEMPERATURE SENSOR BHP -BRAKE HORSEPOWER NO 4. CONCEAL PIPING ABOVE CEILINGS, WITHIN WALLS OR CHASES EXCEPT IN MECHANICAL ROOMS 3. DUCT CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE
-NORMALLY OPEN
10x8 8Ø -TRANSITION, SQUARE TO ROUND BTU -BRITISH THERMAL UNIT OR AS SPECIFICALLY NOTED. PROVIDE ACCESS PANELS FOR ALL VALVES CONCEALED IN SMACNA HVAC DUCT CONSTRUCTION STANDARD. 949 Central Ave.
-DUCT SMOKE DETECTOR NTS -NOT TO SCALE WALLS OR ABOVE NON-ACCESSABLE CEILINGS. Naples, Florida 34102
h -CENTER LINE OA 4. SEE SPECIFICATIONS FOR GAUGES, THICKNESS, BRACING, REQUIREMENTS, ETC., OF DUCTWORK. Phone: 239-643-3103 Fax: 239-643-7435
-OUTSIDE AIR
-CONNECT TO EXISTING c 5. SLEEVE AND FIRE STOP PENETRATIONS OF RATED WALLS, FLOORS, CEILINGS AND ROOFS.
-SQUARE THROAT TEE -CFM (CUBIC FEET PER MINUTE) OAL -OUTSIDE AIR LOUVER FLASH AND COUNTERFLASH ROOF PENETRATIONS. 5. PROVIDE AIR TURNING VANES IN ALL 90 DEGREE RECTANGULAR DUCT ELBOWS.
Project:
-DEMOLISH TO POINT INDICATED CD -CEILING DIFFUSER PRV -PRESSURE REDUCING VALVE
Lee County
6. WHEN BEAM SLEEVE PENETRATIONS ARE NECESSARY, COORDINATE PENETRATIONS WITH ALL 6. DUCT SIZES AND ALL OPENINGS THROUGH BUILDING CONSTRUCTION SHALL SUIT EQUIPMENT
CT -COOLING TOWER PRS TRADES, THE ARCHITECT AND THE STRUCTURAL ENGINEER. FURNISHED.
1 -SHEET NOTE CALLOUT -PRESSURE REDUCING STATION
CV -CONSTANT AIR VOLUME
Justice Center
PSI -POUNDS PER SQUARE INCH 7. SEE ARCHITECTURAL DRAWINGS FOR FIXTURE LOCATIONS AND MOUNTING HEIGHTS. 7. COORDINATE DIFFUSER, GRILLE AND REGISTER LOCATIONS WITH ARCHITECTURAL
K P -CHANGE IN PRESSURE ALL EXPOSED PIPE AND FITTINGS IN FINISHED AREAS SHALL BE CHROME PLATED. REFLECTED CEILING PLANS AND EQUIPMENT OF ALL TRADES. K
PSIG -PSI GAUGE
-SQUARE THROAT ELBOW
Second Floor
T -CHANGE IN TEMPERATURE PTAC 8. PROVIDE CLEANOUTS IN ACCORDANCE WITH APPROPRIATE CODES AND REGULATIONS. 8. LOCATE THERMOSTATS, TEMPERATURE SENSORS, HUMIDISTATS, AND HUMIDITY SENSORS AT 48"
W/TURNING VANES -RECTANGLE-TO-ROUND TAKE-OFF -PACKAGED TERMINAL AIR CONDITIONER
CFM ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE. COORDINATE LOCATIONS WITH OTHER
-CUBIC FEET PER MINUTE PVC -POLYVINYL CHLORIDE PIPE 10. COORDINATE PIPING WITH ALL ELECTRICAL EQUIPMENT(PANELS, TRANSFORMERS, ETC.) PRIOR EQUIPMENT, FURNITURE, AND DOOR SWINGS.
G 24x12 19. ALL EQUIPMENT, DUCTWORK, ETC., TO BE REMOVED SHALL REMAIN PROPERTY OF THE OWNER OR G
-DUCT ELBOW, POSITIVE PRESSURE (SUPPLY), FIRST DISPOSED OF LEGALLY, AS DIRECTED BY OWNER.
DIMENSION INDICATES SIDE TO WHICH ARROW IS
UP W/IN FLOOR POINTING 20. MAINTAIN CLEARANCE OF A MINIMUM OF 6" BETWEEN DUCTWORK, PIPING, EQUIPMENT, ETC., AND ALL
DOWN
FIRE RATED AND FIRE/SMOKE RATED PARTITIONS, TO ALLOW FOR INSPECTIONS OF RATED WALLS.
-DUCT ELBOW, NEGATIVE PRESSURE, RETURN
21. DUCT RUNOUTS TO DIFFUSERS SHALL MATCH THE SIZE OF THE DIFFUSER NECK.
-DUCT ELBOW UP THROUGH ROOF OR SLAB ABOVE 22. SLEEVE AND SEAL ALL PIPING PENETRATIONS THROUGH BUILDING PARTITIONS.
23. PIPING, DUCTWORK, LEAK PROTECTION APPARATUS, OR OTHER EQUIPMENT FOREIGN TO ELECTRICAL
SWITCHBOARDS, PANELBOARDS, DISTRIBUTION BOARDS, OR MOTOR CONTROL CENTERS SHALL NOT
-VOLUME WITH ELECTRIC HEAT BE INSTALLED WITHIN THE REQUIRED SPACE FOR WORKING CLEARANCES OR DEDICATED SPACES OF
F THE ELECTRICAL EQUIPMENT, EXTENDING IN FRONT OF AND FROM FLOOR TO STRUCTURAL CEILING F
Project Phase:
Design
WITH A WIDTH AND DEPTH OF THE ELECTRICAL EQUIPMENT IN ACCORDANCE WITH NEC-110.26.
Development
Project #: 0118.22
Project Issued: 07/10/13
Sheet Issued:
SYMBOL DESCRIPTION
D
- BALL VALVE
HVAC EQUIPMENT TAGS MECHANICAL DRAWING INDEX D
-VALVE ON RISER Sheet Number Sheet Name Issued
TAG
-CAP M0.01 LEGEND, GENERAL NOTES AND INDEX - MECHANICAL
A 200 -AIR DISTRIBUTION DEVICE M1.01 SECOND FLOOR POD D PLAN PHASE II - MECHANICAL
-CONNECTION, BOTTOM
CFM
M3.01 MECHANICAL DETAILS AND SCHEDULES
-CONNECTION, TOP
M6.01 MECHANICAL SPECIFICATIONS
-COUPLING
AHU NUMBER
-ELBOW, 90°
C AHU-1 -AIR HANDLING UNIT C
-ELBOW, 45°
Sheet Title:
Seal
M0.01
1 2 3 4
NOTE: SOME SYMBOLS SHOWN5ON THIS LEGEND MAY NOT PERTAIN
6 TO THIS PROJECT 7 8 9 10 11 12 13 14 15 16
M M
A R C H I T E C T S I N C
LIMITS OF CONSTRUCTION License # AA C001863
Project:
Chair Storage
Second Floor
12
±380 SF
CT CPT
Remodel Pod D
Part B
Owner:
Seating Area 2
Vestibule 05 Consultant:
Men's 10 ±416 SF 13099 S. Cleveland Ave.
11 EX. 66X12 RA
Suite 500
H
Fort Myers, Florida 33907
H Phone: 239-275-4240
Fax: 239-275-3511
www.tlc-engineers.com
© Copyright 2014 TLC Engineering for Architecture, Inc.
EB #0000015 TLC NO: 714124
Seal:
Women's
G 09 G
Vestibule
08
Jury Seating
01
±Redundant
Room
Area
02
±353 SF Development
Project #: 0118.22
Project Issued: 07/11/13
Sheet Issued:
E E
No. Date Revision
EX. 30X14 SA
Seating Area 1
04
±3935 SF
D Break/Lounge D
M
O
Jury Staff 15
POD C
NR
06
O
E
±712 SF
ST
RE
ET
EX. 18X10 SA
Bailiff Queing
Area
03
±397 SF
Supervisor's
Office POD B
C 24X12 TAD 07 C
±160 SF
POD D POD A
Copyright © 2014. BSSW Architects, Inc.
reserves copyright and other rights
restricting these documents to the original
LIMITS OF CONSTRUCTION site or purpose for which they were
prepared. Reproductions, changes or
B B assignments are prohibited.
KEY PLAN Sheet Title:
1
M1.01
SECOND FLOOR POD D PLAN PHASE II - MECHANICAL
1/8" = 1'-0"
Seal
M1.01
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1. SELECT UNDAMAGED DEVICES FROM THOSE REMOVED DURING DEMOLITION. THROUGHLY CLEAN EACH UNIT BEFORE INSTALLATION.
K
Justice Center
Second Floor
EXISTING VAV UNIT SCHEDULE
Remodel Pod D
Nominal Design Air Min. Air Heating Air Static Part B
Mark Inlet Size Flow Flow Flow Pressure Owner:
J
VAV 232C 0' - 6" 360 CFM 225 CFM 225 CFM 0.25 in-wg J Lee County Board
VAV 234C 0' - 6" 360 CFM 225 CFM 225 CFM 0.25 in-wg
of Commissioners
Consultant:
Seal:
G G
Design
FIRE RESISTIVE MATERIAL (TYP.)
NOTE #1
CLEARANCE 1/8" PER LINEAR FOOT
BOTH DIMENSIONS. FLEXIBLE DUCT MAX.
PLAIN "S" SLIP (TYP.) BREAK-AWAY 8'-0" IN LENGTH 1. Wall Assembly — The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be
CONNECTION FULLY EXTENDED. constructed of the materials and in the manner specified in the individual U400 or V400
DUCT WRAP W/VAPOR BARRIER Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the
D (TYP.) 1A following construction features: D
CLOSURE TAPE A A. Studs — Wall framing may consist of steel channel studs. Steel studs to be min 3-1/2 in.
MOUNTING ANGLE 1" MIN. 6" MAX. 3A 3A
OVERLAP ALL SIDES. 2 (89 mm) wide and spaced max 24 in. (610 mm) OC. Additional steel studs shall be used to
METAL STUD CONSTRUCTION completely frame the opening.
B. Wallboard, Gypsum* — Thickness, type, number of layers and fasteners as required in
the individual Wall and Partition Design. Max size of opening is 9,800 in2 (6.32 m2) with a
NOTES: max dimension of 100 in. (254 cm).
The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall
1. PROVIDE ACCESS DOOR & LABEL ON SIDE OR BOTTOM OF DUCT AS FOLLOWS: assembly in which it is installed.
DUCT WIDTH DOOR SIZE 2. Steel Duct — Nom 96 by 96 in. (244 by 244 cm, or smaller) galv steel duct to be installed
DRAW BAND within the opening. The duct shall be constructed and reinforced in accordance with
10" THRU 12" 8"X8"
14" THRU 20" 12"X12" SMACNA construction standards and provided with 2 in. (51 mm) standing seams. The
22" AND ABOVE 18"X18" BLANK-OFF PLATES annular space between the duct and the periphery of opening shall be a min 1 in.(25 mm) to
C WHERE REQUIRED DIFFUSER NECK (INSUL. PER SPEC.) a max 2 in. (51 mm) with the exception that the standing seams which shall be installed at C
2. 1-1/2" x 1-1/2" x 1/8" RETAINING ANGLES SHALL LAP STRUCTURAL OPENING 1" MIN. & COVER CORNERS OF OPENINGS. ANGLES ATTACH TO SLEEVE point contact to the framing of the opening. Duct to be rigidly supported on both sides of
CEILING TEE DIFFUSER CONE (INSUL. PER SPEC.) A 3B 3B 1B opening.
ONLY AND MUST NOT BE ATTACHED TO EACH OTHER AT CORNERS OR TO WALL.
The hourly T Rating of the firestop system is 0 hr except that when the thickness of the steel
3. ALL ATTACHMENTS PER MANUFACTURER'S APPROVED INSTALLATION INSTRUCTION. SECTION A-A duct is 18 ga, the T Rating is ¾ hr.
3. Firestop System — The firestop system shall consist of the following.
4. VERTICAL POSITION SHOWN. HORIZONTAL INSTALLATION SIMILAR. A. Fill, Void or Cavity Material* - Intumescent Caulk or Sealant — Min 5/8 in. (16 mm)
thickness of caulk applied within annulus, flush with both surfaces of wall assembly.
5. ACTUATOR TO BE MOUNTED ON OUTSIDE OF DAMPER SLEEVE ON ACCESIBLE SIDE. ACTUATOR SHALL NOT INTERFERE WITH "S" JOINT. ACTUATOR B. Steel Retaining Angles — Min 16 gauge galv steel angles sized to lap duct a min of 2 in. Copyright © 2014. BSSW Architects, Inc.
ASSEMBLY TO BE U.L. LABELED. (51 mm) and lap wall surface a min of 1 in. (25 mm). Angles attached to the duct on both reserves copyright and other rights
sides of wall with No. 10 (or larger) steel sheet metal screws 1 in. (25 mm) from each end, restricting these documents to the original
and 6 in. (152 mm) OC. On the opposite side of wall, the screw pattern to be staggered. site or purpose for which they were
6. VERIFY THAT ACCESS IS PROVIDED ON THE ACTUATOR SIDE OF THE WALL/FLOOR SO THAT THE LINK MAY BE SERVICED WITH THE DAMPER IN prepared. Reproductions, changes or
LIGHT *Bearing the UL Classification Mark
B CLOSED POSITION. B assignments are prohibited.
Sheet Title:
FIRE & SMOKE DAMPER INSTALLATION DIFFUSER MOUNTING 1 HOUR WALL - DUCT PENETRATION DETAIL Lawrin T. Ellis, P.E. MECHANICAL DETAILS
3 2 1 Florida License #66383
No Scale No Scale No Scale
AND SCHEDULES
Sheet No.
A A
Seal
M3.01
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
HVAC SPECIFICATIONS: HVAC SPECIFICATIONS: (CONT.) FIRE PROTECTION SPECIFICATIONS: PLUMBING SPECIFICATIONS:
1.00 - GENERAL PROVISIONS 1.00 - GENERAL PROVISIONS
2.7 SHEET METAL DUCT INSULATION 1.00 - GENERAL PROVISIONS
M M
1.1 SUMMARY A. ALL PRODUCTS, INCLUDING VAPOR BARRIERS AND ADHESIVES, SHALL CONFORM TO NFPA
A. PROVIDE ALL LABOR AND MATERIALS NECESSARY FOR COMPLETE AND OPERATIONAL 90A. FOR ALL PRODUCTS, THE FLAME SPREAD RATING SHALL NOT EXCEED 25 AND THE SMOKE 1.1 PROVIDE ALL LABOR, MATERIAL AND EQUIPMENT FOR A COMPLETE AND PROPERLY 1.1 PROVIDE ALL LABOR, MATERIAL AND EQUIPMENT FOR A COMPLETE AND PROPERLY
HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS. DEVELOPED RATING SHALL NOT EXCEED 50. OPERATING FIRE PROTECTION SYSTEM. OPERATING PLUMBING SYSTEM.
1.2 EXAMINATION OF DOCUMENTS B. DUCT INSULATION SHALL BE A MINIMUM 1-INCH THICK, 1-1/2 LB. DENSITY FIBERGLASS 1.2 CODES AND STANDARDS: THE FIRE SPRINKLER PROTECTION SYSTEMS INSTALLATION, 1.2 CODES AND STANDARDS: ALL PLUMBING WORK SHALL BE IN STRICT COMPLIANCE WITH
A. THE INTENT OF THE DRAWINGS AND SPECIFICATIONS IS TO ESTABLISH TYPE AND QUALITY OF BLANKET; MAXIMUM THERMAL CONDUCTIVITY OF 0.31 BTUH/°F/SQ.FT. AT 75 DEG F WITH FACTORY FLUSHING AND TESTING SHALL COMPLY WITH THE REQUIREMENTS OF NFPA 13 AND 24, 2007 THE FLORIDA PLUMBING CODE 2010 AND ALL LOCAL CODES HAVING JURISDICTION.
MATERIALS, SIZES AND CAPACITIES OF COMPONENTS, AND A GENERAL LAYOUT AND LOCATION APPLIED REINFORCED-FOIL-KRAFT FACING. SEAL ALL JOINTS AND SEAMS USING NYLON FINISH AND ALL LOCAL CODES HAVING JURISDICTION.
1.3 ALL PLUMBING WORK SHALL BE DONE IN A NEAT AND WORKMANLIKE MANNER.
OF COMPONENTS THAT COMPRISE THE HVAC SYSTEMS. FABRIC AND MASTIC. A R C H I T E C T S I N C
1.3 PIPE THREAD PATTERN: ALL THREADS SHALL BE IN ACCORDANCE WITH LOCAL FIRE
B. CONTRACTOR SHALL PROVIDE IN HIS BID: C. DUCT INSULATION MASTIC SHALL BE LOW ODOR, FIRE AND VAPOR RETARDANT, WITH DEPARTMENT SPECIFICATIONS AND NFPA 1963, 1998 REVISION. 1.4 CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS AND FEES, ETC., REQUIRED License # AA C001863
1. ALL LABOR, TOOLS, MATERIALS, PLANT, TRANSPORTATION, TAXES, RELATED ITEMS, ETC., PERMEANCE NOT EXCEEDING 0.08 PERMS INACCORDANCE WITH ASTM E96. MASTIC COATING FOR THE EXECUTION OF THIS WORK.
ESSENTIAL FOR INSTALLATION AND OPERATION OF THE WORK. SHALL BE NONFLAMMABLE IN BOTH WET AND DRY STATES. 1.4 UL/FM APPROVAL: ALL EQUIPMENT, VALVES, COUPLINGS, HANGERS AND DEVICES SHALL 1500 Jackson Street, Suite 200
1.5 CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL OTHER TRADES BEFORE Fort Myers, Florida 33901
L 2. ALL SYSTEMS SHALL BE COMPLETE AND LEFT IN OPERATING CONDITION. BE APPROVED BY UNDERWRITERS' LABORATORY (UL) OR FACTORY MUTUAL (FM) FOR L
D. DUCT INSULATION ADHESIVE SHALL ADHERE FIBERGLASS BLANKET TO METAL DUCTWORK. USE IN FIRE PROTECTION SERVICE. FABRICATION OR INSTALLATION. OFFSETS AND/OR TRANSITIONS REQUIRED SHALL BE Phone: 239-278-3838 Fax: 239-275-5356
1.3 WARRANTY WHERE DUCT WIDTH IS 24-INCHES OR GREATER, THE INSULATION SHALL BE ADDITIONALLY PROVIDED WITHOUT ADDITIONAL COST. CONTRACTOR SHALL COORDINATE AND INSTALL
A. ALL PRODUCTS AND WORKMANSHIP SHALL BE WARRANTED FOR A MINIMUM OF (1) ONE YEAR SECURED TO THE BOTTOM OF THE DUCT USING MECHANICAL FASTENERS SPACED 1-FOOT ON 1.5 LICENSURE: THE FIRE PROTECTION SYSTEMS SHALL BE INSTALLED BY A STATE OF HIS WORK IN A TIMELY MANNER TO PREVENT DELAYS IN THE CONSTRUCTION.
949 Central Ave.
FROM DATE OF SUBSTANTIAL COMPLETION. CENTER TO PREVENT SAGGING OF THE INSULATION. FLORIDA CERTIFIED FIRE PROTECTION CONTRACTOR. Naples, Florida 34102
1.6 CONTRACTOR SHALL BE RESPONSIBLE TO REPAIR OR REPLACE DAMAGED EQUIPMENT
AND/OR MATERIAL. Phone: 239-643-3103 Fax: 239-643-7435
1.4 CODES AND STANDARDS 2.8 COMBINATION FIRE AND SMOKE DAMPERS 1.6 ALL FIRE PROTECTION WORK SHALL BE DONE IN A NEAT AND WORKMAN-LIKE MANNER.
A. FURNISH AND INSTALL HVAC SYSTEMS TO MEET ALL CURRENT REQUIREMENTS OF THE A. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE PRODUCTS BY
1.7 PROVIDE ALL MATERIALS REQUIRED TO PROPERLY SUPPORT ALL PIPING AND Project:
FLORIDA BUILDING CODE 2010, THE FLORIDA MECHANICAL CODE 2010, AND ALL LOCAL CODES THE FOLLOWING: 1.7 CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS AND FEES, ETC., REQUIRED
EQUIPMENT. PIPE HANGERS SHALL BE ADJUSTABLE TYPE AND BE SPACED IN
Lee County
HAVING JURISDICTION.. 1. AIR BALANCE INC.; A DIVISION OF MESTEK, INC. FOR THE EXECUTION OF THIS WORK.
2. CESCO PRODUCTS; A DIVISION OF MESTEK, INC. ACCORDANCE WITH THE STANDARD PLUMBING CODE. PROVIDED PLASTIC COATED RING
1.5 PERMITS AND INSPECTIONS 3. GREENHECK FAN CORPORATION. 1.8 CONTRACTOR SHALL COORDINATE WORK WITH OTHER TRADES BEFORE ON HANGERS FOR COPPER PIPING TO PROVIDE DIELECTRIC ISOLATION.
Justice Center
A. SECURE AND PAY FOR ALL PERMITS AND LICENSES BEFORE ACTUAL WORK IS STARTED AND 4. NAILOR INDUSTRIES INC. FABRICATION OR INSTALLATION. OFFSETS AND/OR TRANSITIONS REQUIRED SHALL BE
K OBSERVE ANY REQUIREMENT STIPULATED THEREON. 5. POTTORFF. PROVIDED WITHOUT ADDITIONAL COST. CONTRACTOR SHALL COORDINATE AND INSTALL 1.8 PROVIDE DIELECTRIC UNIONS OR FLANGES BETWEEN COPPER AND STEEL PIPING AND K
6. RUSKIN COMPANY. WORK IN A TIMELY MANNER TO PREVENT DELAYS IN THE CONSTRUCTION. BETWEEN BRASSWARE AND STEEL. DO NOT USE STEEL AND COPPER PIPING IN THE
SAME SYSTEM WITHOUT SUCH ISOLATION.
Second Floor
B. THE INSTALLATION SHALL BE MADE IN A NEAT AND WORKMANLIKE MANNER BY PERSONNEL
LICENSED AND SKILLED IN THE TRADE. THE WORK WILL BE INSPECTED BY AN AGENT OF THE B. TYPE: DYNAMIC; RATED AND LABELED ACCORDING TO UL 555 AND UL 555S BY AN NRTL. 1.9 CONTRACTOR SHALL BE RESPONSIBLE TO REPAIR OR REPLACE DAMAGED EQUIPMENT
GOVERNMENTAL AUTHORITY HAVING JURISDICTION. AND/OR MATERIAL. 1.9 PROVIDE REDUCING FITTINGS (REDUCING BUSHINGS SHALL NOT BE USED) WHERE
Remodel Pod D
C. CLOSING RATING IN DUCTS UP TO 4-INCH WG (1-KPA) STATIC PRESSURE CLASS AND MINIMUM CHANGES IN PIPE SIZES OCCUR.
1.6 CUTTING AND PATCHING 2000-FPM (10-M/S) VELOCITY. 1.10 PIPING SHOP DRAWINGS: SUBMIT 1/8" SCALE PIPING SHOP DRAWINGS. SHOP DRAWINGS
A. PROVIDE ALL NECESSARY CUTTING AND PATCHING REQUIRED IN CONNECTION WITH SHALL INCLUDE SPRINKLER PIPING CUT LENGTHS, OFFSETS, FITTINGS AND DEVICES, 1.10 THIS CONTRACTOR SHALL SUPPLY AND INSTALL ALL SERVICES THROUGHOUT THE
Part B
MECHANICAL WORK. D. FIRE RATING: 1-1/2 HOURS. ELEVATIONS, HANGER LOCATIONS, SPRINKLER HEAD COUNT BY TYPE, ELEVATION REMODELED PORITION OF THE BUILDING AND MAKE CONNECTION TO NEAREST UTILITIES.
SECTIONS AND OTHER INSTALLATION INFORMATION. SUBMIT HYDRAULIC CALCULATIONS CONTRACTOR SHALL SUPPLY AND INSTALL FIXTURES, FITTINGS, VALVING AND
1.7 SUBMITTALS E. FRAME: HAT-SHAPED, 0.094-INCH- (2.4-MM-) THICK, GALVANIZED SHEET STEEL, WITH PROVING THE VIABILITY OF THE MOST HYDRAULICALLY-REMOTE AREAS OF THE PROJECT. TRIM AND MAKE READY FOR USE ALL FIXTURES, EQUIPMENT, ETC.
Owner:
A. FINAL REVIEW OF EQUIPMENT AND MATERIALS WILL BE BASED ON THE MANUFACTURER'S MECHANICALLY ATTACHED CORNERS AND MOUNTING FLANGE. INDICATE HYDRAULIC REFERENCE POINTS AND SUBMIT COMPUTER ANALYZED NODAL
Lee County Board
CATALOG CUTS, BROCHURES AND PERFORMANCE DATA. FOUR (4) SETS OF EACH ITEM SHALL CALCULATIONS IN BOTH TABULAR AND GRAPHICAL FORMATS. HYDRAULIC IMBALANCE 1.11 SEE ARCHITECTURAL DRAWINGS FOR FIXTURE LOCATIONS AND MOUNTING HEIGHTS.
J J
BE SUBMITTED FOR REVIEW. F. HEAT-RESPONSIVE DEVICE: REPLACEABLE, 165 DEG F (74 DEG C) RATED, FUSIBLE LINKS. SHALL NOT EXCEED 0.01 GPM AT ANY NODE, AND WATER VELOCITY SHALL NOT EXCEED
of Commissioners
1. AIR GRILLES, REGISTERS, AND DIFFUSERS 20 FEET PER SECOND. DEMONSTRATE COMPLIANCE WITH THE REQUIREMENTS OF NFPA- 2.00 - BASIC MATERIALS AND METHODS
2. DAMPERS G. HEAT-RESPONSIVE DEVICE: ELECTRIC RESETTABLE DEVICE AND SWITCH PACKAGE, FACTORY 13 REGARDING DENSITY, AREA OF APPLICATION, SELECTION OF HYDRAULICALLY-REMOTE
3. DUCT MATERIAL INSTALLED, 250 DEG F (121 DEG C) RATED. AREAS, AND MAXIMUM COVERAGE PER SPRINKLER. 2.1 ABOVEGROUND WATER PIPE AND FITTINGS - TYPE "L" COPPER.
4. DUCT INSULATION
H. SMOKE DETECTOR: INTEGRAL, FACTORY WIRED FOR SINGLE-POINT CONNECTION. 1.11 COORDINATE ALL PIPE ROUTING WITH ALL OTHER TRADES PRIOR TO INSTALLATION. 2.2 PROVIDE UNIONS OR FLANGES IN ALL DOMESTIC WATER SERVICE LINES AT EACH PIECE
1.8 CLEANING ROUTE ALL PIPING TO AVOID DUCTWORK, PIPING, AND BUILDING STRUCTURE. OF EQUIPMENT, SPECIALTY VALVES OR AT OTHER LOCATIONS REQUIRED FOR READY
A. CLEAR AWAY ALL DEBRIS, SURPLUS MATERIALS, ETC., (AND DISPOSE BY LEGAL I. BLADES: ROLL-FORMED, HORIZONTAL, OVERLAPPING, 0.063-INCH- (1.6-MM-) THICK, GALVANIZED DISCONNECT. Consultant:
PROCEDURE) RESULTING FROM WORK AND OPERATIONS, LEAVING THE JOB AND EQUIPMENT SHEET STEEL.
PROVIDED UNDER CONTRACT IN A CLEAN AND FIRST-CLASS CONDITION. 2.00 - BASIC MATERIALS AND METHODS 2.3 WATER HAMMER ARRESTORS SHALL BE INSTALLED AT THE LOCATIONS ON THE PLANS 13099 S. Cleveland Ave.
J. LEAKAGE: CLASS II. AND IN ACCORDANCE WITH PDI STANDARD WH-201. PRODUCTS SHALL BE EQUAL TO Suite 500
1.9 RECORD DOCUMENTS THOSE MANUFACTURED BY PRECISION PLUMBING PRODUCTS OR SIOUX CHIEF. Fort Myers, Florida 33907
H
H A. PROVIDE "AS-BUILT" DRAWINGS INCLUDING DUCT SYSTEMS ROUTING, AND INSTALLED K. RATED PRESSURE AND VELOCITY TO EXCEED DESIGN AIRFLOW CONDITIONS. 2.1 GENERAL: ONLY THE FOLLOWING MATERIALS DESIGNED FOR 175 PSIG CWP SHALL BE Phone: 239-275-4240
ACCESSORIES AND DEVICES. USED FOR FIRE PROTECTION PIPING UNLESS SPECIFICALLY INDICATED OTHERWISE. ALL 2.4 VALVES: PROVIDE VALVES TO ISOLATE EACH RISER, BRANCH LINE AND PIECE OF
Fax: 239-275-3511
L. MOUNTING SLEEVE: FACTORY-INSTALLED, 0.05-INCH- (1.3-MM-) THICK, GALVANIZED SHEET PIPING MATERIALS SHALL HAVE A CORROSION RESISTANCE RATING (CCR) OF 1.0 OR EQUIPMENT.
www.tlc-engineers.com
1.10 CONTRACTOR QUALIFICATIONS STEEL; LENGTH TO SUIT WALL OR FLOOR APPLICATION. GREATER. © Copyright 2014 TLC Engineering for Architecture, Inc.
A. CONTRACTOR SHALL PROVIDE QUALIFIED EXPERIENCE INSTALLING AND SERVICING 2.5 ABOVEGROUND SANITARY WASTE, SANITARY VENT AND STORM PIPING - SERVICE WEIGHT
CAST IRON WITH NO-HUB COUPLINGS - ("HUSKEY 4000" OR "CLAMPALL" ONLY). EB #0000015 TLC NO: 714124
COMMERCIAL HVAC EQUIPMENT FOR A MINIMUM OF 5 YEARS. M. MASTER CONTROL PANEL FOR USE IN DYNAMIC SMOKE-MANAGEMENT SYSTEMS. 2.2 PIPE: 2 INCH OR SMALLER PIPE, AND ALL THREADED PIPING SHALL BE BLACK STEEL,
SCHEDULE 40, ASTM A-53. 2-1/2 INCH AND LARGER PIPE MAY BE BLACK STEEL, SCHEDULE
B. CONTRACTOR SHALL BE RESPONSIBLE TO COVER THE SERVICE FEES FOR ANY AND ALL N. DAMPER MOTORS: TWO-POSITION ACTION. 10, ASTM A-135. 2.6 ABOVEGROUND SANITARY WASTE ARMS - SERVICE WEIGHT CAST IRON WITH NO-HUB
SUBSEQUENT SITE VISITS NECESSARY TO ENSURE THAT EQUIPMENT IS INSTALLED AND COUPLINGS OR DWV COPPER. Seal:
OPERATING PROPERLY. CONTRACTOR'S WORK SHALL NOT BE CONSIDERED COMPLETE UNTIL O. COMPLY WITH NEMA DESIGNATION, TEMPERATURE RATING, SERVICE FACTOR, ENCLOSURE 2.3 FITTINGS: SCHEDULE 40 BLACK STEEL PIPE SHALL BE JOINED BY MECHANICAL
TEST AND BALANCE REPORT INDICATES THAT THE EQUIPMENT COMPONENTS ARE PROPERLY TYPE, AND EFFICIENCY REQUIREMENTS FOR MOTORS SPECIFIED IN SECTION 230513 "COMMON COUPLINGS, THREADED OR WELDED FITTINGS; SCHEDULE 10 BLACK STEEL PIPE SHALL 2.7 INSTALL GRAVITY LINES SLOPED AT 1/8" PER FOOT FOR PIPE 3" AND LARGER AND 1/4" PER
INSTALLED AND OPERATING PER DESIGN DOCUMENTS AND MANUFACTURER'S WRITTEN MOTOR REQUIREMENTS FOR HVAC EQUIPMENT." BE JOINED BY ROLLED GROOVE COUPLINGS OR WELDED FITTINGS ONLY. WELDED FOOT FOR PIPE SMALLER THAT 3". VERIFY INVERT ELEVATION WITH SITE PIPING PRIOR TO
INSTALLATION RECOMMENDATIONS. 1. MOTOR SIZES: MINIMUM SIZE AS INDICATED. IF NOT INDICATED, LARGE ENOUGH SO DRIVEN BRANCH CONNECTIONS WHICH ARE AT LEAST 2 NOMINAL PIPE SIZES SMALLER THAN THE ANY PIPE BEING INSTALLED.
G LOAD WILL NOT REQUIRE MOTOR TO OPERATE IN SERVICE FACTOR RANGE ABOVE 1.0. MAINS ARE PERMITTED. THREADED FITTINGS ARE ACCEPTABLE ONLY FOR PIPING 2 INCHES G
2.00 - PRODUCTS 2. CONTROLLERS, ELECTRICAL DEVICES, AND WIRING: COMPLY WITH REQUIREMENTS FOR AND SMALLER. 3.00 - PLUMBING FIXTURES AND TRIM
ELECTRICAL DEVICES AND CONNECTIONS SPECIFIED IN SECTION 230900 "INSTRUMENTATION
2.1 METAL DUCTWORK AND CONTROL FOR HVAC." 2.4 HANGERS: ALL HANGER SPACING SHALL COMPLY WITH THE REQUIREMENTS OF NFPA-13. 3.1 ALL PLUMBING FIXTURES SHALL BE "FIRST QUALITY" AS DEFINED AND SET FORTH IN
A. MATERIALS: UNLESS NOTED OTHERWISE, ALL DUCTWORK SHALL BE GALVANIZED SHEET 3. PERMANENT-SPLIT-CAPACITOR OR SHADED-POLE MOTORS: WITH OIL-IMMERSED AND COMMERCIAL STANDARD CS77-28 AS PROMULGATED BY THE U.S. DEPARTMENT OF
METAL. FIBERGLASS DUCT BOARD SHALL BE PROHIBITED. SEALED GEAR TRAINS. 2.5 SPRINKLER HEAD LOCATION: INSTALL SPRINKLER HEADS IN THE CENTER OF THE CEILING COMMERCE.
1. GALVANIZED SHEET STEEL: LOCK-FORMING QUALITY, ASTM A527, COATING DESIGNATION G 4. SPRING-RETURN MOTORS: EQUIP WITH AN INTEGRAL SPIRAL-SPRING MECHANISM WHERE TILES FOR SUSPENDED CEILING APPLICATIONS.
90. INDICATED. ENCLOSE ENTIRE SPRING MECHANISM IN A REMOVABLE HOUSING DESIGNED FOR 3.2 FIXTURES AND FITTINGS PROPOSED SHALL BE FROM ONE MANUFACTURER AND OF
SERVICE OR ADJUSTMENTS. SIZE FOR RUNNING TORQUE RATING OF 150 IN. X LBF (17 N X M) 2.6 SPRINKLER CAGE GUARD: PROVIDE HEAD GUARDS ON ALL HEADS IN ELECTRICAL ROOMS SIMILAR CHARACTER IN ANY ROOM OR LOCATION. ESCUTCHEONS, HANDLES, ETC., ON
B. SEALING MATERIALS AND BREAKAWAY TORQUE RATING OF 150 IN. X LBF (17 N X M). AND ON ALL HEADS LESS THAN 7'-0" ABOVE FINISHED FLOOR. THE DIFFERENT FIXTURES SHALL BE OF THE SAME DESIGN.
1. JOINT AND SEAM SEALANT: ONE-PART, NONSAG, SOLVENT-RELEASE-CURING, 5. OUTDOOR MOTORS AND MOTORS IN OUTDOOR-AIR INTAKES: EQUIP WITH O-RING GASKETS
POLYMERIZED BUTYL SEALANT COMPLYING WITH FS TT-S-001657, TYPE I; FORMULATED DESIGNED TO MAKE MOTORS WEATHERPROOF. EQUIP MOTORS WITH INTERNAL HEATERS TO 2.7 GAUGES: PROVIDE GAUGES AND GAUGE VALVES AS REQUIRED BY NFPA 13. GAUGE 3.3 PROVIDE FIXTURE CARRIERS AS RECOMMENDED BY FIXTURE MANUFACTURER AND/OR
WITH A MINIMUM OF 75 PERCENT SOLIDS. TAPING IS NOT PERMITTED. SEALANT IS NOT TO PERMIT NORMAL OPERATION AT MINUS 40 DEG F (MINUS 40 DEG C). SCALE SHALL BE 0-300 PSI UNLESS OTHERWISE INDICATED. CONSTRUCTION METHOD.
F BE VISIBLE. 6. NONSPRING-RETURN MOTORS: FOR DAMPERS LARGER THAN 25 SQ. FT. (2.3 SQ. M), SIZE F
3.4 PROVIDE ACCESS PANELS TO ALL VALVES WITHIN CHASES OR ABOVE NON-ACCESSIBLE Project Phase:
Design
MOTOR FOR RUNNING TORQUE RATING OF 150 IN. X LBF (17 N X M) AND BREAKAWAY TORQUE 2.8 ACCESS PANELS: PROVIDE ACCESS PANELS TO ALL VALVES WITHIN CHASES OR ABOVE
C. HANGERS AND SUPPORTS RATING OF 300 IN. X LBF (34 N X M). NON-ACCESSIBLE CEILINGS. REFER TO ARCHITECTURAL DRAWINGS FOR CEILING TYPES. CEILINGS. REFER TO ARCHITECTURAL DRAWINGS FOR CEILING TYPES.
1. BUILDING ATTACHMENTS: PROVIDE INSERTS AS APPROPRIATE FOR BUILDING MATERIALS. 7. ELECTRICAL CONNECTION: 115 V, SINGLE PHASE, 60 HZ.
Development
2. HANGERS: GALVANIZED SHEET STEEL. CONFORM WITH TABLE 4-1 IN SMACNA HVAC DUCT 2.9 HYDROSTATIC TESTS: ABOVE GROUND AND BELOW GROUND PIPING SYSTEMS SHALL BE 4.00 - VALVES AND COCKS
CONSTRUCTION STANDARDS, CURRENT EDITION, FOR SHEET STEEL WIDTH AND GAGE. P. ACCESSORIES: HYDROSTATICALLY TESTED AT NOT LESS THAN 200 PSI PRESSURE, OR AT 50 PSI IN
3. DUCT ATTACHMENTS: SHEET METAL SCREWS, BLIND RIVETS, OR SELF-TAPPING METAL 1. AUXILIARY SWITCHES FOR SIGNALING OR POSITION INDICATION. EXCESS OF THE MAXIMUM PRESSURE, WHICHEVER IS GREATER, FOR A PERIOD OF 2 4.1 VALVES 2" AND SMALLER SHALL BE BALL VALVES, 150 PSI SWP, 400 PSI WOG. STANDARD
PORT BALL, BRONZE TRIM, CAST BRONZE BODY, CHROMIUM-PLATED BRASS BALL,
SCREWS; COMPATIBLE WITH DUCT MATERIALS. 2. TEST AND RESET SWITCHES, DAMPER MOUNTED. HOURS. THE TEST PRESSURE SHALL BE READ FROM A GAUGE LOCATED AT THE LOW Project #: 0118.22
ELEVATION POINT OF THE INDIVIDUAL SYSTEM OR PORTION OF THE SYSTEM BEING BRONZE NON-BLOWOUT STEM, TEFLON SEAT, DOUBLE O-RING STEM SEALS, ZINC-COATED
STEEL HANDLE WITH PLASTIC COATED HAND GRIP, 90 DEGREE OPERATION FROM FULL Project Issued: 07/16/13
D. DUCT FABRICATION: CONSTRUCT IN ACCORDANCE WITH SMACNA REQUIREMENTS. 3.1 METAL DUCTWORK AND INSULATION TESTED. THE SPRINKLER PIPING SHALL NOT HAVE LEAKAGE EXCEEDING THE AMOUNTS
A. GENERAL: SELECT DUCTWORK ACCORDING TO THE FOLLOWING APPLICATIONS: SPECIFIED IN NFPA 24. LEAKAGE QUANTITIES SHALL BE DETERMINED BY PUMPING AT THE OPEN TO TIGHT SHUT-OFF - STOCKHAM S214-BR-T-T, STOCKHAM S216-BR-T-S OR EQUAL. Sheet Issued:
E. DUCTWORK SHALL COMPLY WITH THE FOLLOWING MINIMUM PRESSURE REQUIREMENTS: 1. CONCEALED SUPPLY AND RETURN AIR: GALVANIZED SHEET METAL, EXTERNALLY SPECIFIED TEST PRESSURE FROM A CALIBRATED CONTAINER. REPAIR LEAKING JOINTS
1. SUPPLY DUCTWORK FROM TERMINAL UNIT TO AIR DEVICE: 2 INCH W.G. INSULATED AND RETEST AS NECESSARY UNTIL ALL SYSTEMS HAVE BEEN TESTED. TEST THE PIPING 5.00 - STERILIZATION
E E
2. EXHAUST AIR DUCTWORK: -1 INCH W.G. 2. CONCEALED SUPPLY RUNOUTS: UL181 FLEXIBLE DUCTWORK BETWEEN THE CHECK VALVE IN THE FIRE DEPARTMENT INLET PIPE AND THE OUTSIDE No. Date Revision
3. SUPPLY AIR THE FIRST 10 FEET OF RETURN AIR DUCTS EXPOSED IN FINISHED AREAS: CONNECTION THE SAME AS THE BALANCE OF THE SYSTEM. 5.1 DOMESTIC WATER PIPING SHALL BE THOROUGHLY FLUSHED OUT AND STERILIZED IN
F. ALL LONGITUDINAL SEAMS SHALL COMPLY WITH SMACNA. SEAMS SHALL BE SELECTED GALVANIZED SHEET METAL READY FOR PAINT,INTERNALLY LINED. ACCORDANCE WITH THE STANDARD PLUMBING CODE.
BASED ON THE SPECIFIED PRESSURE CLASSIFICATION. THE INSIDE FACING OF ALL
LONGITUDINAL SEAMS ANDTRANSVERSE JOINTS SHALL BE FLAT AND SMOOTH. SEALANT B. SEAM AND JOINT SEALING 3.00 - FIRE PROTECTION PRODUCTS AND ACCESSORIES
SHALL BE APPLIED OVER THE CONTINUOUS LENGTH OF ALL SEAMS. 1. SEAL ALL TRANSVERSE JOINTS AND LONGITUDINAL SEAMS.
2.2 DUCT ACCESSORIES C. HANGING AND SUPPORTING 3.1 QUICK-RESPONSE UPRIGHT SPRINKLERS: SPRINKLER HEADS SHALL BE MANUFACTURED
A. FLEXIBLE DUCTS 1. INSTALL METAL DUCT WITH SUPPORT SYSTEMS INDICATED IN SMACNA HVAC DUCT WITH UPRIGHT DEFLECTORS FOR INSTALLATION ABOVE THE BRANCH LINE WITH BRASS
1. GENERAL: COMPLY WITH UL 181, CLASS 1. CONSTRUCTION STANDARDS. FINISH - CENTRAL GB-QR OR VIKING MICROFAST MODEL M.
2. FLEXIBLE DUCTS - INSULATED: FACTORY-FABRICATED, INSULATED, ROUND DUCT, WITH AN
OUTER JACKET ENCLOSING 1-INCH-THICK, GLASS FIBER INSULATION AROUND A CONTINUOUS D. CLEANING 3.2 QUICK RESPONSE SEMI-RECESSED SPRINKLERS: SPRINKLER HEADS SHALL BE
D INNER LINER. 1. REMOVE DUST AND DEBRIS FROM INSIDE DUCTS AND FITTINGS. MANUFACTURED WITH PENDANT DEFLECTOR FOR INSTALLATION BELOW THE BRANCH D
a. REINFORCEMENT: STEEL-WIRE HELIX ENCAPSULATED IN THE INNER LINER. 2. CLEAN EXTERIOR OF INSULATION TO REMOVE DUST AND DIRT. LINE WITH CHROME-PLATED FINISH - CENTRAL GB-QR OR VIKING MICROFAST MODEL M
b. OUTER JACKET: GLASS-REINFORCED, REINFORCED METALIZED POLYESTER JACKET. WITH MODEL F-1 ESCUTCHEON.
c. INNER LINER: POLYETHYLENE FILM. 3.2 TESTING, ADJUSTING, AND BALANCING HVAC SYSTEMS
3. FLEXIBLE DUCT CLAMPS: NYLON BAND INSTALLED WITH USE OF TENSION CLAMPING TOOL. A. SUMMARY:
1. TEST, ADJUST, AND BALANCE THE AIR SYSTEMS.
2.3 AIR INLETS AND OUTLETS 2. VERIFY TEMPERATURE CONTROL SYSTEM OPERATION.
A. GENERAL: EXCEPT AS OTHERWISE INDICATED, PROVIDE MANUFACTURER'S STANDARD 3. PROVIDE COPY OF BALANCE REPORT TO OWNER AND ARCHITECT.
CEILING AIR DIFFUSERS WHERE SHOWN; OF SIZE, SHAPE, CAPACITY AND TYPE INDICATED;
CONSTRUCTED OF MATERIALS AND COMPONENTS AS INDICATED, AND AS REQUIRED FOR
COMPLETE INSTALLATION. PROVIDE CEILING AIR DIFFUSERS THAT HAVE, AS MINIMUM,
TEMPERATURE AND VELOCITY TRAVERSES, THROW AND DROP, AND NOISE CRITERIA RATINGS
FOR EACH SIZE DEVICE AS LISTED INMANUFACTURER'S CURRENT DATA. PROVIDE DIFFUSERS
C WITH BORDER STYLES THAT ARE COMPATIBLEWITH ADJACENT CEILING SYSTEMS, AND THAT C
ARE SPECIFICALLY MANUFACTURED TO FIT INTO CEILINGMODULE WITH ACCURATE FIT AND
ADEQUATE SUPPORT. PROVIDE CEILING DIFFUSERS OF TYPE, CAPACITY, AND WITH
ACCESSORIES AND FINISHES AS LISTED ON DIFFUSER SCHEDULE.
Sheet No.
A A
Seal
M6.01
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
M M
A R C H I T E C T S I N C
License # AA C001863
PUBLIC
AFTER WIRE INSTALLATION
PIPE CLAMP CONDUIT
~
EACH SIDE
K CABLING K
DEFENDER'S
OFFICE - 5TH
ACCESSIBLE CEILING
FLOOR
8" KINDORF SECTION
EACH SIDE
Owner:
G G
Construction
Documents
Project #: 0118.22
STRUCTURE
Project Issued: 11/05/14
TO MAIN SERVICE GROUND Sheet Issued:
COMMUNICATIONS GROUND BAR 4 A/V PLATE DETAIL 5 PROJECTOR MOUNTING 6 Brett L. Sands, P.E. TECHNOLOGY
No Scale Florida License #48477
DETAILS
No Scale No Scale
Sheet No.
A A
Seal
T202
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
M
ELECTRICAL SYMBOL LEGEND M
BASIC MATERIALS BASIC MATERIALS CONT. TELEPHONE/COMPUTER RACEWAY SYSTEM GENERAL NOTES:
SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION
Sa SINGLE POLE SWITCH AUTOMATIC TRANSFER SWITCH A R C H I T E C T S I N C
1. LIGHT SWITCHES SHALL BE MOUNTED 48 INCHES ABOVE FINISHED FLOOR TO CENTER LINE OF DEVICE,
(SUBSCRIPT INDICATES ITEM CONTROLLED) UNLESS OTHERWISE NOTED. License # AA C001863
S3 THREE-WAY SWITCH 30AR NON-FUSED DISCONNECT SWITCH, SIZE & # OF POLES COMMUNICATIONS "INFORMATION OUTLET" MTD. AT RECEPTACLE
NF NF DENOTES NON-FUSED HEIGHT UNLESS OTHERWISE NOTED. DIVISION 16 CONTRACTOR 1500 Jackson Street, Suite 200
S4 FOUR-WAY SWITCH TO PROVIDE 4" SQUARE WITH SINGLE GANG RAISED MUD RING. 2. RECEPTACLES SHALL BE LOCATED 18 INCHES ABOVE FINISHED FLOOR TO CENTER LINE OF DEVICE, Fort Myers, Florida 33901
L AR DENOTES AMP RATING OF SWITCH L
SP SINGLE POLE SWITCH WITH PILOT LIGHT CONTRACTOR TO STUB UP (2) 1" CONDUITS AT EACH LOCATION UNLESS OTHERWISE NOTED. ABOVE-COUNTER RECEPTACLES SHALL BE MOUNTED 6" ABOVE BACK Phone: 239-278-3838 Fax: 239-275-5356
TO SPLASH TO CENTERLINE OF DEVICE.
SWP SINGLE POLE SWITCH WITH WEATHERPROOF COVER 30AR ABOVE CEILING AND TURN TO ACCESSIBLE CEILING SPACE.
FUSED DISCONNECT 949 Central Ave.
20AF CONTRACTOR TO PROVIDE BUSHING ON END OF CONDUIT AND 3. EQUIPMENT SHALL BE OF MATERIALS SUITABLE FOR AND RATED FOR THE ENVIRONMENT IN WHICH
SWPL SINGLE POLE SWITCH WITH WEATHERPROOF LOCKING COVER AR DENOTES AMP RATING OF SWITCH Naples, Florida 34102
PULLSTRING WITHIN. THEY ARE TO BE INSTALLED.
MCP Phone: 239-643-3103 Fax: 239-643-7435
AF DENOTES AMP FUSE SIZE
SK SINGLE POLE KEY SWITCH SIZE
# OF POLES TV TELEDATA/TV OUTLET - 4" SQUARE 2 GANG BOX 4. A. WORKING CLEARANCES FOR ELECTRICAL EQUIPMENT SHALL BE IN COMPLIANCE WITH NEC 110.
S3K WITH Project:
THREE-WAY KEY SWITCH 30/3 COMBINATION MAGNETIC MOTOR STARTER, SIZE & # OF POLES
(2) 1" CONDUITS PER ABOVE.
0 3R
S4K
SL
FOUR-WAY KEY SWITCH
OFFICE - 5TH
SF FAN SWITCH SURFACE MOUNTED TELEPHONE/COMPUTER TERMINAL BOARD
5. WHEN ELECTRICAL BOXES ARE LOCATED IN VERTICAL FIRE-RESISTIVE ASSEMBLIES,
SM MANUAL MOTOR STARTER WITH OVERLOAD HEATERS BRANCH CIRCUIT PANELBOARD, UNDER 250 VOLTS, (CLASSIFIED AS FIRE/SMOKE AND SMOKE PARTITIONS), THEY SHALL BE INSTALLED WITHOUT
TTC AFFECTING THE FIRE CLASSIFICATION. ALL OF THE FOLLOWING CONDITIONS SHALL BE MET:
FLOOR
FLUSH MOUNTED
SMP MANUAL MOTOR STARTER WITH OVERLOAD HEATERS AND PILOT LIGHT TELEPHONE TERMINAL CABINET
BRANCH CIRCUIT PANELBOARD, OVER 250 VOLTS,
SD DIMMER SWITCH SURFACE MOUNTED
(1500 WATTS UNLESS OTHERWISE INDICATED) T A. ALL ELECTRICAL BOXES SHALL BE METALLIC.
BRANCH CIRCUIT PANELBOARD, OVER 250 VOLTS, TELEPHONE SYSTEM RACEWAY
DUPLEX RECEPTACLE
FLUSH MOUNTED B. BOX OPENING SHALL OCCUR ONLY ON ONE SIDE OF FRAMING SPACE. Owner:
J T
TWIST LOCK RECEPTACLE BRANCH CIRCUIT CONDUIT CONCEALED ABOVE CEILING OR IN WALL.
CONDUIT C. BOX OPENING SHALL NOT EXCEED 16 SQUARE INCHES. J Lee County Board
SP
SURGE PROTECTION TYPE (TVSS)
DUPLEX RECEPTACLE
SHALL INCLUDE PHASE, NEUTRAL AND GROUND CONDUCTORS AS
REQUIRED D. ALL CLEARANCES BETWEEN OUTLET BOX AND GYPSUM BOARD SHALL BE COMPLETELY of County
Commissioners
FOR CIRCUITS (UNLESS OTHERWISE NOTED). FILLED WITH JOINT COMPOUND (OR OTHER APPROVED MATERIAL).
BRANCH CIRCUIT CONDUIT CONCEALED IN SLAB,
PEDESTAL MOUNTED RECEPTACLE UNDERGROUND OR UNDER FLOOR. FIRE ALARM/DETECTION SYSTEM E. PROVIDE A WALL AROUND OUTLETS LARGER THAT 16 SQUARE INCHES. THE INTEGRITY OF THE
WALL RATING SHALL BE MAINTAINED.
FLOOR OUTLET BOX AND DUPLEX RECEPTACLE BRANCH CIRCUIT CONDUIT EXPOSED Consultant:
WITH APPROPRIATE FLANGE.
SYMBOL DESCRIPTION
GROUND OR GROUND ROD AS NOTED F. THE TOTAL AGGREGATE SURFACE AREA OF THE BOXES SHALL NOT EXCEED 100 SQUARE
INCHES PER 100 SQUARE FEET. 13099 S. Cleveland Ave.
FLOOR OUTLET BOX WITH DUPLEX RECEPTACLE F MANUAL PULL STATION Suite 500
EM EMERGENCY BRANCH CONDUIT G. OUTLET BOXES LOCATED ON OPPOSITE SIDES OF FIRE-RESISTIVE ASSEMBLIES SHALL BE
AND ONE COMBINATION W/ VOICE/DATA OUTLET
H
Fort Myers, Florida 33907
CEILING SMOKE DETECTOR, PHOTO-ELECTRIC SEPARATED BY A MINIMUM HORIZONTAL DISTANCE OF 24 INCHES.
H Phone: 239-275-4240
FLOOR OUTLET BOX WITH TWO DUPLEX RECEPTACLES CONDUIT TURNING UP TYPE UNLESS OTHERWISE NOTED Fax: 239-275-3511
UP H. OUTLET BOXES SHALL BE SECURELY FASTENED TO WALL FRAMING MEMBERS.
AND ONE COMBINATION W/ VOICE/DATA OUTLET E = ELEVATOR WITH RECALL CONTACTS www.tlc-engineers.com
CONDUIT TURNING DOWN I = IONIZATION I. THE OPENING IN THE GYPSUM BOARD FACING SHALL BE CUT NOT TO EXCEED 1/8 INCH © Copyright 2014 TLC Engineering for Architecture, Inc.
FLOOR POKE THRU - WITH POWER AND TELECOMM DEVICES DN
BETWEEN THE EDGES OF THE OUTLET BOX AND THE EDGES OF THE OPENING. EB #0000015 TLC NO: 714125
CONDUIT STUB DUCT SMOKE DETECTOR
PP POWER POLE R = RETURN
6. ALL DEVICES SHALL BE MOUNTED VERTICAL, UNLESS OTHERWISE NOTED.
CONDUIT CONTINUED S = SUPPLY Seal:
DUPLEX RECEPTACLE WIRED TO COMPUTER PANEL FLEXIBLE CONDUIT 7. ALL RECEPTACLES SHALL BE MOUNTED SUCH THAT THE GROUND PIN IS MOUNTED DOWN.
R SUPERVISED CONTROL RELAY
*
COVERPLATES WITH SPANNER HEAD SCREWS
EXISTING AFFECTED BY THIS PROJECT RT REMOTE INDICATING LAMP FIRE ALARM WITH TEST SWITCH (R) = EXISTING TO BE REMOVED)
WALL MOUNTED 72" AFF
SIMPLEX RECEPTACLE (EWC DENOTES FUTURE (ER) = EXISTING TO BE RELOCATED)
EWC ELECTRIC WATER COOLER. COORDINATE WITH EWC
INSTALLER FOR MOUNTING HEIGHT) NEW F COMBINATION AUDIBLE/VISUAL
NOTIFICATION DEVICE
GFI RECEPTACLE. WP DENOTES WEATHERPROOF COVER.
WP SS FIRE ALARM SPEAKER - CEILING MOUNTED
DDC
VARIABLE FREQUENCY DRIVE
Seal
E001
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
M # KEYNOTES: M
3. THE EXTENT OF THE DEMOLITION WITHIN THIS EXISTING ELECTRICAL ROOM, IS CONFINED
TO ANY WORK ASSOCIATED WITH THE REMOVAL OF THE EXISTING CONDUIT AND WIRING A R C H I T E C T S I N C
WHICH IS TO BE ABANDONED (EITHER HIGH VOLTAGE. LOW VOLTAGE, OR STRUCTURED License # AA C001863
CABLING). NOTE: ONLY THE CONDUIT AND CABLING ASSOCIATED WITH THE ABANDONED
SYSTEMS IS TO BE REMOVED. THERE ARE EXISTING SYSTEMS BOTH LIFE SAFETY AND FOR 1500 Jackson Street, Suite 200
L OTHER TENANTS WHICH MUST REMAIN IN SERVICE. DEMOLITION IN THIS AREA TO BE VERY L Fort Myers, Florida 33901
SELECTIVE. Phone: 239-278-3838 Fax: 239-275-5356
4. DEMOLITION WITHIN THIS SPACE IS CALLED OUT ON THE POWER AND SYSTEMS FLOOR 949 Central Ave.
PLAN, AND IS RELATED TO THE RELOCATION/UPGRADE OF ELECTRICAL SERVICE TO THE Naples, Florida 34102
NEW AIR HANDLER. Phone: 239-643-3103 Fax: 239-643-7435
D101
5. DEMOLITION WITHIN THIS SPACE IS SELECTIVE AND LIMITED TO THE REPLACEMENT OF Project:
TYP.
SOME OF THE EXISTING LIGHT FIXTURES AND THE RELOCATION OF ROOM LIGHTING
CONTROL.
PUBLIC
DEFENDER'S
6. DEMOLITION WITHIN THIS SPACE IS SELECTIVE AND LIMITED REMOVAL OF SOME EXISTING
K WALLS AND CEILINGS. COORDINATE IN FIELD. K
D103
7. UNLESS SPECIFICALLY NOTED OTHERWISE IN #1 - #6 ABOVE, ALL OTHER DEVICES AND
CABLING WHICH SERVES THIS FLOOR ARE TO BE REMOVED. ALL CABLING AND CONDUIT OFFICE - 5TH
NOT SCHEDULED TO BE RE-USED, IS TO BE REMOVED ALL THE WAY BACK TO THE
TYP.
EXISTING PANELBOARD OR TERMINAL CABINET FROM WHICH IT ORIGINATED. IF CONDUIT
AND CABLING RUNNING THROUGH THE THIRD FLOOR IS SERVING OTHER AREAS OF THE
FLOOR
BUILDING, CONTRACTOR SHALL RE-ROUTE SAID CONDUIT AND CABLING TO MAINTAIN
EXISTING SYSTEMS WHICH SERVE OTHER FLOORS, ESPECIALLY LIFE SAFETY SYSTEMS.
Owner:
J
PEDESTRIAN BRIDGE
J Lee County Board
D110
D111
BELOW
of County
Commissioners
Consultant:
Seal:
D105 D102
D104
TYP.
D102
G D102 G
D102
STAIR No. 1 STAIR No. 2
D102
D110
D102
D102
D102
D107
F D109 F
Project Phase:
D107
D109 D102
D107
D109
D102
Construction
D102
Documents
D102 Project #: 0118.22
Project Issued: 11/05/14
D102
Sheet Issued:
E E
No. Date Revision
D105
D104
TYP.
D111
D D
D106 TYP.
D108 TYP.
C C
Sheet Title:
1
E101
5TH FLOOR - DEMOLITION - ELECTRICAL E101
1/8" = 1'-0" Seal
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
3. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT TYPE AND HEIGHT
OF CEILING IN EACH ROOM. COORDINATE WITH ARCHITECT/ENGINEER PRIOR TO A R C H I T E C T S I N C
ROUGH-IN OF ANY FIXTURES. COORDINATE ALL CONTROL JOINTS LOCATIONS WITH
LIGHT FIXTURES PRIOR TO ANY ROUGH-IN OF FIXTURES.
License # AA C001863
PUBLIC
E2 BELOW SWITCH LOCATIONS.
E2
B
B2
DEFENDER'S
B2 E2 B2 E2
K K
B2
# KEYNOTES:
OFFICE - 5TH
B2
1. EXISTING AREA LIGHTING TO REMAIN. (NO WORK)
N1 N1
E2 E2
FLOOR
2. EXISTING ELECTRICAL ROOM. PANEL LOCATIONS ARE SHOWN IN THE ROOM
B2 C ENLARGEMENT ON E102.
B2 3. ALL CORRIDOR AND OPEN OFFICE AREA FIXTURES TO BE WIRED THRU LIGHTING
B2 CONTACTOR CONTROLLED BY BUILDING EMS SYSTEM. PROVIDE OVER-RIDE
B2 E2 E2 SWITCHES IN LOCATIONS NOTED. SEE PANEL SCHEDULES AND DETAIL DRAWINGS
FOR MORE INFORMATION. SHADED FIXTURES ARE ON EMERGENCY LIGHTING
B2 CIRCUITS. PROVIDE "EM" BYPASS RELAY FOR SWITCH OVERRIDE IN EMERGENCY MODE Owner:
J
B2
E2
N1 N1
E2 D
DURING POWER LOSS.
J Lee County Board
B2 4. PROVIDE SEPARATE SLIDER DIMMER(S) AS INDICATED. DIMMERS TO BE SIZED
B2
E2 E2
APPROPRIATELY FOR LOAD SERVED. COLOR TO MATCH OTHER DEVICES. MOUNT
DIMMERS IN SEPARATE BOXES TO ACCOMMODATE HEAT.
of County
5. NEW BATHROOM LIGHTING TO REPLACE EXISTING AS INDICATED. CONNECT TO
CIRCUITS INDICATED AND SWITCH AS SHOWN.
Commissioners
B2 B2 B2
B2 6. ALL DOWNLIGHTS SHOWN ON THIS PLAN ARE TO BE TYPE "D" UNLESS NOTED
E2 E2 OTHERWISE. SEE FIXTURE SCHEDULE ON DRAWING `E301'. Consultant:
B2
B2 7. ALL EXIT LIGHT FIXTURES SHOWN ON THIS PLAN ARE TO BE CIRCUITED TO PANEL 13099 S. Cleveland Ave.
`HE3-4'.
Suite 500
B2 B2 B2 B2 B2 B2 8. EXISTING BATHROOM SCONCES TO REMAIN, CLEAN & RELAMP FIXTURES. CONNECT TO Fort Myers, Florida 33907
B2 CIRCUITS INDICATED AND SWITCH AS SHOWN. H
H B2 E2 E2 Phone: 239-275-4240
B2 B2
Fax: 239-275-3511
B2 B2 B2 B2 B2 B2 B2 www.tlc-engineers.com
B2
E © Copyright 2014 TLC Engineering for Architecture, Inc.
B2 B2 B2 EB #0000015 TLC NO: 714125
B2 E2 E2
B2
B2 Seal:
B2 B2 B2 B2 B2 B2 B2 B2 B2
B2
E2 E2 B2
E2 B2 E.5
G B2 E2 G
N1
OPEN TO
B2 E2 ABOVE E2 B2
B2 B2 B2
N1 N1 N1
B2 B2 B2 B2
B2 B2
B2 E2 N1 N1 N1 E2
E2 B2
OPEN TO OPEN TO
ABOVE EXISTING ABOVE
CEILING
TO REMAIN
F
F B2 E2 B2 B2 E2 B2 F
Project Phase:
Construction
B2
OPEN TO N1 N1 N1
B2 ABOVE
B2 B2
Documents
B2 B2
F.3
B2 E2 N1 N1 N1 E2 B2
B2
OPEN TO Project #: 0118.22
ABOVE OPEN TO N1 E2 B2 B2 Project Issued: 11/05/14
B2 ABOVE
B2 B2 Sheet Issued:
B2 B2 B2 E2 E2 B2
E F.7 E
No. Date Revision
E2 B2 B2 B2 B2 B2 B2 B2 B2 B2 B2 B2 E2
B2
B2
B2 B2 B2
E2 B2 B2 B2 B2 E2
B2
B2 G
B2
B2 B2 B2
B2 B2 B2 E2 B2
D E2 D
B2 B2 B2
B2 B2
B2 B2
E2 B2
B2
B2
G.8
E2 B2 B2 B2
B2
B2 B2 B2
E2
H
E2 B2 B2 B2 B2
C B2 B2 B2 C
E2 B2 B2 B2 B2
B2 B2
Sheet Title:
1
E102
5TH FLOOR - LIGHTING
1/8" = 1'-0" Seal
E102
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
APD 15
ALIGN ALIGN B PUBLIC
DEFENDER'S
APD 12
K 70 K
44 # KEYNOTES:
APD 16
1. FLUSH, WALL MOUNTED J-BOX, FOR NORMAL POWER CONNECTION TO MODULAR OFFICE - 5TH
APD 11 FURNITURE.
73 J 64 C
2. FLUSH, WALL MOUNTED J-BOX, FOR VOICE/DATA CABLING. PROVIDE (1) 1" CONDUIT TO
FLOOR
ABOVE CEILING SPACE. PROVIDE BUSHING ON END OF CONDUIT WITH PULL STRING.
APD 10 3. FLUSH, WALL MOUNTED J-BOX, FOR VOICE/DATA CABLING CONNECTION TO MODULAR Owner:
APD 17
J 71
45
D
FURNITURE. PROVIDE (2) 1" CONDUITS TO ABOVE CEILING SPACE. PROVIDE BUSHING ON
END OF CONDUIT WITH PULL STRING. J Lee County Board
4. TELECOMM. SERVICES TO POKE-THRUS REQUIRES (2) 3/4" CONDUITS
of County
TRAINING
38
APD 9 5. 20A/125V. SIMPLEX OUTLET FOR COPIER/FAX UNIT, COORDINATE DEVICE
Commissioners
APD 18 STOR / EQUIP STOR/EQUIP 23 REQUIREMENTS WITH OWNER.
69 39 40 Consultant:
6. FURNITURE MOUNTED DEVICE. CIRCUIT AS INDICATED ON THIS PLAN. LOCATION AND
AMOUNT OF DEVICES SET BY SYSTEM FURNITURE SUPPLIER. COORDINATE FURNITURE 13099 S. Cleveland Ave.
WIRING ACCESS LOCATIONS WITH VENDOR PRIOR TO ROUGH-IN. Suite 500
APD 19 APD 8
H
Fort Myers, Florida 33907
68 INVEST. 2 INVEST. 3 INVEST. 4 INVEST. 5 INVEST. 6 INVEST. 7 INVEST. 8 INVEST. 9 22
H 7. SWITCH FOR MOTORIZED PROJECTION. VERIFY REQUIREMENTS WITH SUPPLIER/ Phone: 239-275-4240
43 34 33 36 61 41 60 63 INSTALLER. Fax: 239-275-3511
www.tlc-engineers.com
8.E COORDINATE LOCATION OF DETECTORS WITH OTHER CEILING DEVICES. © Copyright 2014 TLC Engineering for Architecture, Inc.
APD 20 APD7 EB #0000015 TLC NO: 714125
67 21 9. PROVIDE SINGLE GANG J-BOX WITH BLANK COVER PLATE AT 48" A.F.F. FOR FUTURE
SECURITY ACCESS CONTROL. (BY OTHERS) RUN 3/4"C IN WALL TO J-BOX ABOVE DOOR
HEADER. Seal:
ALIGN ALIGN ALIGN APD 6
10. PROVIDE FIRE ALARM RELAY TO INTERFACE WITH THE ACCESS CONTROL SYSTEM.
APD 21 20
COORDINATE LOCATION OF AND CONNECITON TO RELAY WITH THE SECURITY SYSTEM
66 E.5 SUPPLIER/INSTALLER. PROVIDE (4) 20A CIRCUITS FOR SECURITY EQUIP.
G J
J G
11. PROVIDE J-BOX RECESSED UNDER COUNTER FOR OVER RIDE BUTTON. RUN 3/4"C. BACK
INVEST. 1 TO ELECTRICAL ROOM.
MECH. MEN'S INVEST. 10
88 89 87 12. PROVIDE J-BOX RECESSED UNDER COUNTER FOR SECURITY ASSISTANCE
SS/10 91
APD 22 SS/9 APD 5
NOTIFICATION. RUN 3/4"C BACK TO ELECTRICAL ROOM.
65 SS/9 19
13. ALL EQUIPMENT, INCLUDING FIRE ALARM SYSTEM PANEL & TRANSFORMER
SUSPENDED FROM STRUCTURE OVERHEAD, IS EXISTING TO REMAIN U.O.N., SEE
DRAWING `E301' FOR PANEL INFORMATION.
ELEVATOR 14.
SS/11 PROVIDE CEILING RECEPTACLE AND J-BOX FOR TELECOM CONNECTION TO
LOBBY (E) WORKROOM
SS/8 F OVERHEAD PROJECTOR. COORDINATE ADDITIONAL A/V CONDUIT REQUIREMENTS
F 501E 24 WITH OWNER. F
SS/8 Project Phase:
ELEC.
Construction
J
APD 4 15. PROVIDE NEW 15KVA TRANSFORMER AND 120/208V PANEL `L3E'. SEE PANEL
ADP 23
J
92 SCHEDULES FOR MORE DETAILS.
F.3
Documents
58 WOMENS 18
WORKROOM J J J
29 90 16. OUTLETS MOUNTED LOW IN WALL BELOW GLAZING.
SS/12 IDE 17. J-BOXES ABOVE CEILING FOR VOICE, DATA AND POWER FEED INTO MODULAR Project #: 0118.22
94 JAN. FURNITURE VIA POWER POLE.
SS/6 SS/7 Project Issued: 11/05/14
APD 24 93 APD 3
SS/6 SS/7 Sheet Issued:
76 17
E ALIGN ALIGN
F.7 E
No. Date Revision
APD 25 APD 2
75 SS/2 16
J J
RECEPT. COPY/
PRINT/
2 WORK AREA SS/3 SS/4 SS/5 APD 1 G
ADP 26 CONF. ROOM
J
74
3 95
J
D Work Stations D
ADP 27
SS/1 501F
78 ADMIN.
15
G.8
ADMIN.
14
PUBLIC CONFERENCE CHIEF ASSIT.
DEFENDER ROOM PD ADMIN. ADMIN. H
4 6 7 12 13
C C
Sheet Title:
1
E103
5TH FLOOR - POWER
1/8" = 1'-0" Seal
E103
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
M M
A R C H I T E C T S I N C
License # AA C001863
1 0 TO 3/16 1 OR 2 0, 1 OR 2
1 1/4 TO 1/2 3 OR 4 3 OR 4
4 0 TO 1-1/2 1 OR 2 0
G 6 1/4 TO 1/2 3 OR 4 0 PLAN SYMBOL = OS CEILING MOUNTED
DUAL TECHNOLOGY
G
12 3/16 TO 3/8 1 OR 2 0 OCCUPANCY
SENSOR
FLOOR POKE THRU OUTLET 1 CONDUIT PENETRATION OF FIREWALL 2 TYPICAL OCCUPANCY SENSOR WIRING DIAGRAM 3
No Scale UL SYSTEM NO. W-L-1001 No Scale
F F
3/4" CONDUIT TO LOCAL 4 HR. OVER-RIDE Project Phase:
SWITCHES LOCATED AT MAIN ENTRIES.
REFER TO LIGHTING FLOOR PLAN
FOR EXACT LOCATION.
Construction
Documents
EMS PANEL Project #: 0118.22
PANEL `H3' CENTERED BETWEEN
Project Issued: 11/05/14
DOOR & CEILING
N CLOCK OUTLET FIRE HORN (OR CHIME) & Sheet Issued:
20A C (COORDINATE WITH
LIGHT 80" AFF
E
TYP.
2 TO CORRIDOR/OPEN OFFICE AREA LIGHTS
WALL MOUNTED LIGHT FIXTURES
AS NOTED ON PLANS CL EXIT ARCHITECT)
E
No. Date Revision
TELEVISION
4 TO CORRIDOR/OPEN OFFICE AREA LIGHTS BOTTOM TV
OUTLET
OF DEVICE
6 TO CORRIDOR/OPEN OFFICE AREA LIGHTS
CL
8 TO CORRIDOR/OPEN OFFICE AREA LIGHTS
SPARE
SPARE CENTERED OVER DOOR RT REMOTE TEST VOLUME CONTROL VC
(WHERE APPLICABLE) 80"
PANELBOARD
90"
600V RATED LIGHTING CONTACTOR "LC-1" N.O. 20A, 277V. CONTACTS, DUPLEX CL
277V RECEPTACLE
D W D
COIL. NEMA 1 ENCLOSURE SQ.'D' CLASS 8903 'LG1200-VO4'
CL TELE. OUTLET
CL FA PULL F
6" AFC SWITCH STATION 54"
3/4" CONDUIT TO LOCAL 4 HR. OVER-RIDE
SWITCHES LOCATED AT MAIN ENTRIES.
48" DUPLEX
REFER TO LIGHTING FLOOR PLAN
FOR EXACT LOCATION. 78" MAX. RECEPTACLE
TO TOP DEVICE
1
36" TELE. OUTLET
COMPUTER
EMS PANEL AFF OUTLET
C PANEL `HE3' C
CL
20A N 18"
C
TYP. AFF
2 TO CORRIDOR/OPEN OFFICE AREA LIGHTS
SPARE
1 42" A.F.F. W/ 36" COUNTER, FINISHED FLOOR
SPARE 39" A.F.F. W/ 30" COUNTER, SPECIAL POWER OUTLET
48" A.F.F. WITHOUT COUNTER Copyright © 2014. BSSW Architects, Inc.
SPARE reserves copyright and other rights
OR AS NOTED ON PLANS
restricting these documents to the original
site or purpose for which they were
600V RATED LIGHTING CONTACTOR "LC-2" N.O. 20A, 277V. CONTACTS, prepared. Reproductions, changes or
B B assignments are prohibited.
277V
COIL. NEMA 1 ENCLOSURE SQ.'D' CLASS 8903 'LG1200-VO4' Sheet Title:
Sheet No.
A A
Seal
E201
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
M
FIRE PROTECTION LEGEND GENERAL NOTES M
APPLICABLE CODES AND STANDARDS SYMBOL DESCRIPTION 1. FIRE PROTECTION SYSTEM TO COMPLY WITH NFPA 13, 14, 20, 24 AND ALL APPLICABLE STATE CODES.
FIRE PROTECTION SYSTEM 2. FINAL INSPECTION AND APPROVAL BY LOCAL FIRE MARSHAL AND ARCHITECT/ENGINEER.
OR - CONTROL VALVE W/TAMPER SWITCH
- CHECK VALVE 3. SPRINKLER SHOP DRAWINGS AND MATERIAL SUBMITTALS SHALL BE SUBMITTED TO THE
FLORIDA ADMINISTRATIVE CODE 61G15 (2) (B) 1/06/05 A R C H I T E C T S I N C
ARCHITECT/ENGINEER AND STATE FIRE MARSHAL AND SHALL BE APPROVED PRIOR TO ANY
FLORIDA BUILDING CODE, 2007 EDITION - FLOW SWITCH License # AA C001863
INSTALLATION.
NFPA-13, 2007 EDITION
FDC - FIRE DEPARTMENT CONNECTION
NFPA-24, 2007 EDITION 1500 Jackson Street, Suite 200
4. PIPE ROUTING SHOWN IS SCHEMATIC ONLY. IT IS THE RESPONSIBILITY OF THIS CONTRACTOR TO
L PIV - POST INDICATOR VALVE W/TAMPER SWITCH L Fort Myers, Florida 33901
PROVIDE ANY ADDITIONAL OFFSETS REQUIRED FOR PROPER INSTALLATION AND COORDINATION WITH Phone: 239-278-3838 Fax: 239-275-5356
FVC - FIRE VALVE CABINET OTHER TRADES.
61G15 FAC COMPLIANCE NOTES FDV - STANDPIPE WITH FIRE DEPARTMENT VALVE
- SPRINKLER AND DRAIN RISER
5. PIPING IN AREAS WITH EXPOSED STRUCTURE SHALL BE INSTALLED AS HIGH AS POSSIBLE TO ALLOW THE
OWNER MAXIMUM USE OF THE SPACE.
949 Central Ave.
Naples, Florida 34102
Phone: 239-643-3103 Fax: 239-643-7435
- BACKFLOW PREVENTOR W/TAMPER SWITCHES 6. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR CEILING DESCRIPTIONS AND HEIGHTS.
61G15-32.003 Project:
- ROOF MANIFOLD
PUBLIC
7. SPRINKLERS ARE TO BE COORDINATED WITH ALL DIFFUSERS, SPEAKERS, LIGHTING FIXTURES AND
(2) ACCEPTANCE TEST CRITERIA - HYDRAULIC REFERENCE NODE CEILING SYSTEMS. SPACING OF SPRINKLERS SHALL BE IN ACCORDANCE WITH NFPA 13 AND THE LISTING
SHALL COMPLY WITH N.F.P.A. 13 2007 CHAPTER 16. SYSTEM ACCEPTANCE OF THE SPRINKLER.
DEFENDER'S
SECTION: - NEW SPRINKLER PIPING
K K
16.1 APPROVAL OF SPRINKLER SYSTEM. F.C. - FLUSHING CONNECTION 8. SPRINKLER LOCATIONS SHALL BE CENTERED IN THE TILE. PROVIDE ARMOVER OR SWING JOINT AS
16.2 ACCEPTANCE REQUIREMENTS.
OFFICE - 5TH
REQUIRED.
16.3 CIRCULATING CLOSED LOOP SYSTEM
16.4 INSTRUCTION 1 - REVISION REFERENCE
16.5 HYDRAULIC DESIGN INFORMATION SIGNS 9. SPRINKLERS IN AREAS WITH EXPOSED STRUCTURE (OBSTRUCTED CONSTRUCTION) SHALL BE INSTALLED
FLOOR
1 - DETAIL REFERENCE: TOP-DETAIL#, WITH DEFLECTOR 1" BELOW THE BOTTOM OF THE BEAM (MAXIMUM 22" BELOW ROOF DECK). EXPOSED
10.10.1 CONTRACTORS MATERIAL & TEST CERTIFICATE FOR UNDERGROUND
PIPING FP-1 BOTTOM-DRAWING# SHOWN ON BAR JOISTS THAT HAVE SPRAY-ON FIRE PROOFING THAT MAKES THE JOIST SOLID SHALL BE TREATED
LIKE A BEAM WITH THE SPRINKLERS 1" BELOW THE BOTTOM OF THE FIRE PROOFING.
(5) STRUCTURAL SUPPORT COORDINATION: NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT 10. SLEEVE AND/OR FIRESTOP ALL PENETRATIONS THROUGH RATED WALLS, CEILINGS, AND FLOORS WITH
THIS IS AN EXISTING STRUCTURE THERE ARE NO ADDITIONAL LIVE AND DEAD LOADS THAT ARE REQUIRED FOR THE U/L LISTED ASSEMBLIES. FIRESTOP ASSEMBLIES SHALL BE EQUAL OR EXCEED THE RATING OF THE WALL, Owner:
(G) VALVING AND ALARM REQUIREMENTS TO MINIMIZE POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF WATER:
THE EXISTING FIRE SPRINKLER RISER IS EQUIPPED WITH A WATER FLOW SWITCH WITH A LOCAL ALARM AND OFF-
F SITE F
Project Phase:
Construction
MONITORING. THE BACKFLOW PREVENTION DEVICE IS EXISTING.
(H) MICROBIAL INDUCED CORROSION (MIC):
THE LOCAL WATER PURVEYOR, LEE COUNTY PUBLIC UTILITIES, ACKNOWLEDGES THAT THE WATER SERVICE
PROVIDED MEETS OR EXCEEDS STATE AND FEDERAL CORROSION WATER CONTROL QUALITY PARAMETERS.
ADDITIONALLY, THE PURVEYOR ACKNOWLEDGES THAT NO SPECIFIC TESTING GUIDELINES FOR MIC PRESENTLY
Documents
EXIST. AS SUCH THE INSTALLING FIRE SPRINKLER CONTRACTOR SHALL MAKE PIPE AND FITTING SELECTIONS Project #: 0118.22
BASED ON THIS INFORMATION AND IN ACCORDANCE WITH NFPA 13, (2002 EDITION), CHAPTER 8, SUBSECTION
8.15.3.2.2; CHAPTER 15, SUBSECTION 15.1.5; AND ANNEX A, SUBSECTION A.15.1.5. Project Issued: 11/05/14
Sheet Issued:
(J) QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD AND INTERIOR FIRE PROTECTION COMPONENTS:
ALL NEW YARD AND INTERIOR FIRE PROTECTION EQUIPMENT SHALL BE UL LISTED AND FM APPROVED.
SCOPE OF WORK: THIS BUILDING HAS WITH A EXISTING SPRINKLER AND STANDPIPE SYSTEM PER NFPA 13 AND 14. THE
SPRINKLER SYSTEM SHALL BE MODIFIED ON THE 3RD FLOOR TO ACCOMMODATE THE NEW WALLS AND CEILINGS. THE
SYSTEM SHALL BE HYDRAULICALLY CALCULATED BY THE SPRINKLER CONTRACTOR. SHOP DRAWING ARE REQUIRED TO
BE APPROVED PRIOR TO INSTALLING BY THE OWNER, AHJ, ARCHITECT AND THE ENGINEERS. UPON COMPELLATION THE
SYSTEM SHALL BE HYDROSTATICALLY TESTED PER THE LOCAL AHJ.
D D
C C
Sheet Title:
Seal
F001
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
M
HVAC SYMBOL LEGEND HVAC ABBREVATIONS GENERAL NOTES M
SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION
1. CONNECTION TO EQUIPMENT SHALL BE VERIFIED WITH MANUFACTURER'S CERTIFIED
AFD -ADJUSTABLE FREQUENCY DRIVE MCA -MINIMUM CIRCUIT AMPS
-EXHAUST DUCT UP THROUGH SLAB W/FAN UP DN DRAWINGS. TRANSITIONS TO ALL EQUIPMENT SHALL BE VERIFIED AND PROVIDED FOR
ON ROOF ABOVE -FIRE DAMPER AFF -ABOVE FINISHED FLOOR MOCP -MAXIMUM OVER CURRENT PROTECTION EQUIPMENT FURNISHED.
-CHANGE OF ELEVATION
(WITH ACCESS PANEL)
AFR -ABOVE FINISHED ROOF MOD -MOTOR OPERATED CONTROL DAMPER (MOD) 2. DIMENSIONS SHALL BE FIELD-VERIFIED AND COORDINATED PRIOR TO PROCUREMENT OR
-EXHAUST FAN ON ROOF W/DUCT DOWN -FLEXIBLE DUCT FABRICATION. COORDINATE THE WORK WITH OTHER TRADES INVOLVED. FIELD
A R C H I T E C T S I N C
AHU -AIR HANDLING UNIT
THROUGH ROOF -FIRE & SMOKE DAMPER NC -NORMALLY CLOSED MODIFICATIONS SUCH AS OFFSETS IN PIPING OR DUCTWORK (INCLUDING DIVIDED License # AA C001863
(WITH ACCESS PANEL) AP -ACCESS PANEL DUCTWORK) NEEDED DUE TO OBSTRUCTIONS OR INTERFERENCES SHALL BE PROVIDED AT
-TRANSITION, CONCENTRIC NO -NORMALLY OPEN
-OUTSIDE AIR DUCT UP THROUGH SLAB W/FAN
BOP -BOTTOM OF PIPE NO ADDITIONAL COST. FOR PROJECTS INVOLVING RENOVATION, COORDINATE NEW WORK 1500 Jackson Street, Suite 200
L ON ROOF ABOVE NTS -NOT TO SCALE WITH EXISTING ELEMENTS SUCH AS THE BUILDING STRUCTURE AND ARCHITECTURAL L Fort Myers, Florida 33901
-EXISTING FIRE DAMPER TO REMAIN -TRANSITION, ECCENTRIC BHP -BRAKE HORSEPOWER FEATURES, SPRINKLER PIPING, LIGHTS, PLUMBING, AND ELECTRICAL CONDUIT. Phone: 239-278-3838 Fax: 239-275-5356
OA -OUTSIDE AIR
-OUTSIDE AIR FAN ON ROOF W/DUCT DOWN
BTU -BRITISH THERMAL UNIT
THROUGH ROOF 10x8 8 -TRANSITION, SQUARE TO ROUND OAL -OUTSIDE AIR LOUVER 949 Central Ave.
-EXISTING FIRE & SMOKE DAMPER TO REMAIN
h -CENTER LINE
3. Naples, Florida 34102
PRV -PRESSURE REDUCING VALVE DUCT CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE
Phone: 239-643-3103 Fax: 239-643-7435
-SQUARE THROAT ELBOW c -CFM (CUBIC FEET PER MINUTE) SMACNA HVAC DUCT CONSTRUCTION STANDARD.
-CEILING DIFFUSER, ROUND NECK PRS -PRESSURE REDUCING STATION
(CEILING DIFFUSERS ARE 4-WAY THROW UNO)
W/TURNING VANES
SA-1 -SOUND ATTENUATOR CD -CEILING DIFFUSER 4. SEE SPECIFICATIONS FOR GAUGES, THICKNESS, BRACING, REQUIREMENTS, ETC., OF Project:
PSI -POUNDS PER SQUARE INCH
DUCTWORK.
PUBLIC
CT -COOLING TOWER
PSIG -PSI GAUGE
-ROUND DIFFUSER -MOTOR OPERATED CONTROL DAMPER (MOD) CV -CONSTANT AIR VOLUME 5. PROVIDE AIR TURNING VANES IN ALL LOW PRESSURE 90 DEGREE RECTANGULAR
-RADIUS ELBOW PTAC -PACKAGED TERMINAL AIR CONDITIONER DUCT ELBOWS.
K
-CEILING RETURN
M
UC
(VERTICAL MOUNT, SIDEWALL) -UNDERCUT DOOR SA -SUPPLY AIR
J FD -FIRE DAMPER SP -STATIC PRESSURE
SPECIFIED. PROVIDE ADDITIONAL SUPPORTS AS REQUIRED TO PROVIDE A
VIBRATION-FREE, RIGID INSTALLATION. J Lee County Board
-RETURN/EXHAUST REGISTER OR GRILLE
(VERTICAL MOUNT, SIDEWALL)
-ACCESS DOORS, VERTICAL OR HORIZONTAL
12x8 -RADIUS TEE FF -FINAL FILTERS
TSP -TOTAL STATIC PRESSURE 10. ALL DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS. of County
FLA -FULL LOAD AMPS UNO -UNLESS NOTED OTHERWISE 11. DAMPERS AND INSIDES OF DUCTS VISIBLE THROUGH GRILLES, REGISTERS AND Commissioners
1 -REVISION REFERENCE -STAINLESS STEEL DUCTWORK FPM -FEET PER MINUTE DIFFUSERS SHALL BE PAINTED FLAT BLACK.
V/PH -VOLTS/PHASE
1 -DETAIL REFERENCE: TOP - DETAIL#; -RECTANGLE-TO-ROUND TAKE-OFF GPM -GALLONS PER MINUTE 12. REFER TO TYPICAL DETAILS FOR PIPING, DUCTWORK AND INSTALLATION OF EQUIPMENT. Consultant:
-FLEXIBLE CONNECTION VAV -VARIABLE AIR VOLUME
M-1 BOTTOM - DRAWING# SHOWN ON
KW -KILOWATT 13. TRAPPED CONDENSATE DRAINS FROM ALL MECHANICAL EQUIPMENT SHALL BE 13099 S. Cleveland Ave.
VFD -VARIABLE FREQUENCY DRIVE
T -THERMOSTAT/TEMPERATURE SENSOR 12x8 LAT -LEAVING AIR TEMPERATURE PROVIDED FOR PROPER DRAINAGE TO SUIT EQUIPMENT FURNISHED. Suite 500
-FLAT OVAL DUCT -STANDARD BRANCH TAKE-OFF P -CHANGE IN PRESSURE
-LEAVING WATER TEMPERATURE 14. ACCESS PANELS IN DUCTWORK AND CEILINGS SHALL BE PROVIDED WHERE H
Fort Myers, Florida 33907
H -HUMIDISTAT/HUMIDITY SENSOR LWT
H 24x12 T -CHANGE IN TEMPERATURE REQUIRED FOR OPERATION, BALANCING OR MAINTENANCE OF ALL MECHANICAL Phone: 239-275-4240
-NEW DUCTWORK, FIRST DIMENSION IS SIDE SHOWN
-SPIN-IN TAKE-OFF LD -LINEAR DIFFUSER EQUIPMENT. Fax: 239-275-3511
-DUCT SMOKE DETECTOR www.tlc-engineers.com
24x12 -EXISTING DUCTWORK TO REMAIN MBH -THOUSAND BTUs PER HOUR © Copyright 2014 TLC Engineering for Architecture, Inc.
15. ALL DUCTWORK AND PIPING IS SHOWN SCHEMATICALLY. PROVIDE ALL TRANSITIONS,
-CONNECT TO EXISTING
TURNING VANES, ELBOWS, FITTINGS, ETC., TO ALLOW SMOOTH FLOWS. ALL SPLIT DUCT EB #0000015 TLC NO: 714125
24x12 -EXISTING DUCTWORK TO BE REMOVED FITTINGS SHALL TRANSITION TO FULL SIZE OF THE SUM OF BOTH BRANCHES, UPSTREAM
-DEMOLISH TO POINT INDICATED OF SPLIT.
Seal:
M -MOTORIZED CONTROL DAMPER 16. VERIFY FINISH WITH ARCHITECT PRIOR TO PURCHASING GRILLES, REGISTERS,
-DUCT ELBOW, POSITIVE PRESSURE (SUPPLY)
TS -TEMPERATURE SENSOR DOWN UP W/IN FLOOR HVAC EQUIPMENT TAGS 17.
DIFFUSERS, LOUVERS AND OTHER AIR DISTRIBUTION DEVICES.
-THERMOMETER -TEE, OUTLET UP COMPLIANCE STATEMENT Lawrin T. Ellis, P.E. HVAC SYMBOL
Florida License #66383
LEGEND, GENERAL
D D
-TWO-WAY CHECK VALVE -45° PIPE RISE (R) / DROP (D)
Seal
M001
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
M KEYNOTES: M
PUBLIC
K
DEMOLITION NOTES K
DEFENDER'S
D103
TYP.
1 THE CONTRACTOR SHALL PROVIDE PROTECTION FOR ALL PARTS OF THE BUILDING.
ITS CONTENTS AND OCCUPANTS WHEREVER WORK UNDER THIS CONTRACT IS PERFORMED.
OFFICE - 5TH
2 DEMOLITION SHALL INCLUDE REMOVAL OF EXISTING BUILDING CONSTRUCTION TO
EXTENT REQUIRED TO PERFORM CONSTRUCTION ACTIVITIES INDICATED.
FLOOR
3 THE DEMOLITION PROCEDURES SHALL PROVIDE FOR SAFE CONDUCT OF THE WORK,
PROTECTION OF PERSONNEL, CAREFUL REMOVAL AND DISPOSITION OF MATERIALS
SPECIFIED TO BE SALVAGED, PROTECTION OF PROPERTY TO REMAIN UNDISTURBED, Owner:
of County
D110
D111 4 EXISTING WORK TO REMAIN SHALL BE PROTECTED FROM DAMAGE. WORK DAMAGED
BY THE CONTRACTOR SHALL BE REPAIRED TO MATCH EXISTING WORK OR WORK
INSTALLED UNDER THIS CONTRACT DEPENDING ON CONTRACT REQUIREMENTS. Commissioners
5 EXISTING WORK SHALL BE CUT, DRILLED, ALTERED, REMOVED OR TEMPORARILY
REMOVED AND REPLACED FOR PERFORMANCE OF WORK UNDER THE CONTRACT. Consultant:
WORK REPLACED SHALL MATCH SIMILAR EXISTING WORK. STRUCTURAL MEMBERS OF
CONCRETE OR STRUCTURAL STEEL SHALL NOT BE CUT OR ALTERED, EXCEPT AS SHOWN 13099 S. Cleveland Ave.
WITHOUT AUTHORIZATION OF THE OWNER. WORK REMAINING IN PLACE DAMAGED Suite 500
OR DEFACED DURING THIS CONTRACT SHALL BE RESTORED TO THE CONDITION AT Fort Myers, Florida 33907
TIME OF AWARD OF CONTRACT. CUT, ALTER, REMOVE OR TEMPORARILY REMOVE H
H AND REPLACE EXISTING WORK FOR THE INSTALLATION OF MECHANICAL, PLUMBING Phone: 239-275-4240
D111 AND ELECTRICAL WORK AND OTHER CONSTRUCTION. Fax: 239-275-3511
www.tlc-engineers.com
PROPERLY REMOVE AND DISPOSE OF ALL EXISTING FIXTURES AS REQUIRED © Copyright 2014 TLC Engineering for Architecture, Inc.
6
TO ACCOMODATE NEW PLAN. REFER TO THE ARCHITECTURAL DEMOLITION PLANS. EB #0000015 TLC NO: 714125
CONSULT WITH THE OWNER AND OBTAIN OWNERS APPROVAL PRIOR TO
DISPOSAL OF REMOVED MATERIAL.
Seal:
D105 D102 7 UNLESS INDICATED OTHERWISE, ALL EXISTING MECHANICAL EQUIPMENT, DUCTWORK, PIPING,
D104 WIRING, HANGERS AND SUPPORTS SHALL BE REMOVED BACK TO BELOW SLAB, ABOVE
TYP. CEILING, OR WITHIN WALL CAVITIES AS INDICATED ON THE DRAWINGS.
D102 REFER TO THE ARCHITECTURAL DEMOLITION PLANS.
D102 CONSULT WITH THE OWNER AND OBTAIN OWNERS APPROVAL PRIOR TO DISPOSAL
G OF REMOVED MATERIAL. G
D102
STAIR No. 1 STAIR No. 2 8 THE EXISTING EQUIPMENT INDICATED ON THESE DRAWINGS REPRESENTS A BEST FAITH EFFORT BY THE
D102 ENGINEER TO DEMONSTRATE THE CONDITIONS UNDER WHICH THE WORK IS TO BE EXECUTED. THE
D110
CONTRACTOR SHALL VISIT SITE AND REVIEW EXISTING CONDITIONS TO THE DEGREE AND EXTENT
D102 NECESSARY TO PREPARE A PROPER AND ADEQUATE BID FOR THE WORK INDICATED. SUBMISSION OF
D102 A BID WILL BE INTERPRETED AS MEANING THE CONTRACTOR HAS REVIEWED EXISTING CONDITIONS AND
D102 UNDERSTANDS THE DIFFICULTIES AND CHALLENGES UNDER WHICH THE WORK IS TO BE ACCOMPLISHED.
D107
D109
F F
D107 D107 D102 Project Phase:
D109 D102 D109
Construction
Documents
D102
D102
Project #: 0118.22
D102 Project Issued: 11/05/14
Sheet Issued:
E E
No. Date Revision
D105
D104
TYP.
D111
D D
D106 TYP.
D108 TYP.
C C
Sheet Title:
1
M101
5TH FLOOR - DUCTWORK - DEMOLITION M101
1/8" = 1'-0" Seal
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
M M
A R C H I T E C T S I N C
License # AA C001863
PRESSURE GAUGE & COCK (TYP.)
1500 Jackson Street, Suite 200
L TWO WAY CONTROL VALVE L Fort Myers, Florida 33901
MANUAL AIR VENT W/AUTO Phone: 239-278-3838 Fax: 239-275-5356
AUTOMATIC FLOW CONTROL SHUT-OFF COCK
DEVICE PRESET BY MANUF. 949 Central Ave.
COIL
W/ P & T TEST PORTS, Naples, Florida 34102
STRAINER, AND DRAIN. Phone: 239-643-3103 Fax: 239-643-7435
(PRE-MANUF. SINGLE
ASSEMBLY ACCEPTABLE) STRAIGHT SECTION OF METAL INLET DUCT IN SIZE Project:
BALANCING DAMPER EQUAL TO INLET COLLAR. MIN. LENGTH SHALL
SHEET METAL DUCT WITH
INTERIOR DUCT LINING
RETURN BE 4 TIMES DUCT DIAMETER
INLET COLLAR, ROUND OR OVAL.
PUBLIC
K
SEE SCHEDULE FOR SIZES
AIRFLOW SENSOR
K
DEFENDER'S
12" MINIMUM OR AS
INDICATED PER SPEC.
SUPPLY
OFFICE - 5TH
SHUT-OFF VALVE (TYP.)
SUPPORT STRAP HANGERS, SECURE
FLOOR
P/T TEST PORTS TO STRUCTURE. (TYP. OF 4)
STRAINER W / BLOWDOWN
Owner:
Seal:
G G
TYPICAL RETURN AIR BOOT 3 2-WAY COIL PIPING DIAGRAM 2 VARIABLE VOLUME TERMINAL W/ELECTRIC HEAT 1
No Scale No Scale No Scale
PIPE HANGER
(SEE SPECS.) ROUND MEDIUM
AIRFLOW
PRESSURE DUCT
D D
PIPE SADDLE HAS FLARED
EDGES NOTCHED TO FIT
45 DEGREE DIVERGING
PIPE HANGER.
CORNERS ARE WYE FITTING
CLIPPED
45 DEGREE ROUND
ELBOW
B TYPICAL LOW PRESSURE DUCTWORK 6 INSULATED PIPE HANGER - INDOORS 5 MEDIUM PRESSURE DUCT BRANCH TAKE-OFF 4 B
prepared. Reproductions, changes or
assignments are prohibited.
Sheet No.
A A
Seal
M201
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
M M
A R C H I T E C T S I N C
License # AA C001863
OFFICE - 5TH
OR
B
A ANGLE ROD, SUPPORT
STRAP HANGER - RECTANGULAR DUCT
DRAIN PAN CONDENSATE DRAIN FLEXIBLE DUCT FROM STRUCTURE
MAX. 8'-0" IN LENGTH ABOVE (TYP)
FLOOR
C
CASING SLEEVE INDIRECT FULLY EXTENDED. ROD, SUPPORT
CONNECTION FROM STRUCTURE
ABOVE (TYP)
4"
NEW FUNNEL DRAIN
ALL CONDENSATE 6 IN. Owner:
FLOOR
BLANK-OFF PLATES
WHERE REQUIRED NOTE: ROD DIMENSIONS, MAXIMUM HANGER SPACING,
of County
DIFFUSER NECK (INSUL. PER SPEC.) AND MAXIMUM ALLOWABLE LOADING OF TRAPEZE ANGLES
SHALL COMPLY WITH REQUIREMENTS OF SECTION
Commissioners
NUTS
DIFFUSER CONE (INSUL. PER SPEC.) IV SMACNA HVAC DUCT CONSTRUCTION STANDARDS
Consultant:
CONDENSATE DRAIN PIPING DIMENSIONS: TO CONDENSATE DRAIN
- 13099 S. Cleveland Ave.
ANGLES
A = FULL SIZE OF UNIT DRAIN CONNECTION FOR CONTINUATION SEE Suite 500
B > 1i TIMES FAN SUCTION STATIC PRESSURE PLUMBING PLANS TRAPEZE HANGER - RECTANGULAR DUCT
CEILING H
Fort Myers, Florida 33907
C > FAN DISCHARGE STATIC PRESSURE PLUS i INCH Phone: 239-275-4240
H
Fax: 239-275-3511
COORDINATE MOUNTING/CURB HEIGHT AS REQUIRED TO PROVIDE PROPER www.tlc-engineers.com
CONDENSATE DRAINAGE. © Copyright 2014 TLC Engineering for Architecture, Inc.
EB #0000015 TLC NO: 714125
Seal:
G
AHU CONDENSATE DRAIN TRAP 3 DIFFUSER MOUNTING 2 TYPICAL RECTANGULAR DUCT SUPPORT 1
G
No Scale No Scale
CHW COIL
SA
RA
FILTER
GALVANIZED STEEL SADDLE 3-SPEED ROUTE MAIN CONDENSATE
FAN LINE TO CONDENSATE DRAIN
IN MECHANICAL ROOM
D D
FLOAT SWITCH
CEILIING
SUPPORT FROM STRUCTURE
ABOVE
1\" WIDE GALVANIZED
STEEL HANGER STRAP FLEXIBLE DUCT 8'-0"
3'-0" MAXIMUM SPACING MAXIMUM LENGTH GALVANIZED SHEET METAL SECONDARY
DRAIN PAN TO EXTEND 3" BEYOND UNIT
ON ALL SIDES BY 1\" DEEP
C C
NOTE
NO FABRIC DUCT
GALVANIZED STEEL SADDLE SUPPORTS PERMITTED
Sheet No.
A A
Seal
M202
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
M M
CONCRETE OR MASONRY
CONSTRUCTION A R C H I T E C T S I N C
RETAINING ANGLES RETAINING ANGLES 1\"x 1\"x w" MIN. FIRE RESISTIVE MATERIAL (TYP.) License # AA C001863
1\"x1\"xw" ALL
MIN. ALL SIDES (SEE CLEARANCE w" PER SIDES. (SEE NOTE #2)
LINEAR FOOT BOTH 1500 Jackson Street, Suite 200
NOTE # 2) 4" MIN. Fort Myers, Florida 33901
L CONCRETE OR MASONRY DIMENSIONS. L
MANUFACTURER OR FIELD Phone: 239-278-3838 Fax: 239-275-5356
CONSTRUCTION. FABRICATED STEEL SLEEVE
1" MIN. CAULKING (TYP. OF 2)
NOTE# 2 16 949 Central Ave.
U.L. LABELED FIRE DAMPER, GA. MIN. Naples, Florida 34102
DUCT MOUNTED SMOKE DETECTOR
CAULK BEAD AROUND MANUF. OR FIELD (555) SECURE TO SLEEVE Phone: 239-643-3103 Fax: 239-643-7435
NOTE #5 TO BE INSTALLED WITHIN
EDGE BETWEEN DUCT AND WALL FABRICATED STEEL 5'-0" OF DAMPER PER
SLEEVE 16 GA. MIN. MANUFACTURER'S Project:
165°F FUSIBLE LINK RECOMMENDATIONS,
SPACE AT CORNERS 1/8".
SHEET METAL
WRAPPED SHEET METAL DUCT
U.L. (555S) LABELED
WITH NO AIR INLETS OR OUTLETS
BETWEEN THE DETECTOR AND THE
DAMPER.
PUBLIC
DUCT
DEFENDER'S
PLAIN "S" SLIP FIRE/SMOKE DAMPER,
K MAXIMUM COMPRESSION OF SECURE TO SLEEVE K
INSULATION IS 1/8" THICK. 165°F DUCT SIZE
OFFICE - 5TH
COMPRESS INSULATION MAXIMUM ALLOWABLE SPACE FUSIBLE CLEARANCE w" PER LINEAR
BETWEEN DUCTS AND NON RATED WRAPPED SHEET FOOT,
AGAINST PARTITION LINK NOTE #1
WALLS IS 1/4". METAL DUCT BOTH DIMENSIONS
NOTE # 1 PLAIN "S" SLIP (TYP.) BREAK-
AWAY
DUCT WRAP W/VAPOR BARRIER (TYP.)
FLOOR
CONNECTION CLOSURE TAPE
FASTENER W/WASHER
METAL DUCT MOUNTING ANGLE 1" MIN. OVERLAP
DUCT WRAP W/VAPOR ALL
6" MAXIMUM BARRIER (TYP.) SIDES METAL STUD CONSTRUCTION Owner:
EACH SIDE 6" MAX.
J J Lee County Board
CLOSURE TAPE (TYP.)
FIRE RESISTIVE
NOTES:
1. PROVIDE ACCESS DOOR & LABEL ON SIDE OR BOTTOM OF DUCT AS FOLLOWS:
of County
MATERIAL (TYP.)
EXTERNAL THERMAL
INSULATION
METAL STUD CONSTRUCTION DUCT WIDTH DOOR SIZE
Commissioners
CAULK BEAD AROUND EDGE 10" THRU 12" 8" x 8"
BETWEEN DUCT AND WALL 14" THRU 20" 12" x 12"
22" AND ABOVE 18" x 18" Consultant:
METAL STUD NOTES:
CONSTRUCTION 1. PROVIDE ACCESS DOOR & LABEL ON SIDE OR BOTTOM OF DUCT AS FOLLOWS: 2. 1\" x 1\" x w" RETAINING ANGLES SHALL LAP STRUCTURAL OPENING 1" MIN. & COVER 13099 S. Cleveland Ave.
CORNERS OF OPENINGS. ANGLES ATTACH TO SLEEVE ONLY AND MUST NOT BE ATTACHED Suite 500
DUCT WIDTH DOOR SIZE
TO EACH OTHER AT CORNERS OR TO WALL.
H
Fort Myers, Florida 33907
10" THRU 12" 8" x 8"
H WOOD STUD CONSTRUCTION OPENING Phone: 239-275-4240
14" THRU 20" 12" x 12" 3. ALL ATTACHMENTS PER MANUFACTURER'S APPROVED INSTALLATION INSTRUCTION.
Fax: 239-275-3511
TO BE LINED W/FIRE RESISTIVE FIRE RESISTIVE 22" AND ABOVE 18" x 18" www.tlc-engineers.com
4. VERTICAL POSITION SHOWN. HORIZONTAL INSTALLATION SIMILAR.
MATERIAL OF RATING EQUAL TO THAT MATERIAL (TYP.) © Copyright 2014 TLC Engineering for Architecture, Inc.
2. 1\"x1\"xw" RETAINING ANGLES SHALL LAP STRUCTURAL OPENING 1" MIN. & 5. ACTUATOR TO BE MOUNTED ON OUTSIDE OF DAMPER SLEEVE ON ACCESIBLE SIDE.
ON WALL.
COVER CORNERS OF OPENINGS. ANGLES ATTACH TO SLEEVE ONLY AND MUST NOT ACTUATOR SHALL NOT INTERFERE WITH "S" JOINT. ACTUATOR ASSEMBLY TO BE U.L. EB #0000015 TLC NO: 714125
BE ATTACHED TO EACH OTHER AT CORNERS OR TO WALL. LABELED. PROVIDE WITH MODULATING ACTUATOR AND REMOTE
3. ALL ATTACHMENTS PER MANUFACTURER'S APPROVED INSTALLATION INSTRUCTION. MOUNTED TEST STATION.
4. VERTICAL POSITION SHOWN. HORIZONTAL INSTALLATION SIMILAR. DAMPER TO BE Seal:
6. VERIFY THAT ACCESS IS PROVIDED ON THE ACTUATOR SIDE OF THE WALL/FLOOR SO
SPRING LOADED WHEN HORIZONTAL.
THAT THE LINK MAY BE SERVICED WITH THE DAMPER IN CLOSED POSITION.
G
DUCT PENETRATION THROUGH NON-RATED WALLS. 3 FIRE DAMPER INSTALLATION 2 FIRE & SMOKE DAMPER INSTALLATION 1
G
F F
Project Phase:
Construction
Documents
Project #: 0118.22
Project Issued: 11/05/14
Sheet Issued:
E E
No. Date Revision
D D
C C
Sheet Title:
Sheet No.
A A
Seal
M203
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
AHU-6S PCC SIZE 30 VERTICAL VAV DRAW-THRU FLT, CCL, FAN 16,000 2040 3.0 25" AF 1479 20 460/3 1800 BELT YES 16,000 75.0 63.0 53.0 52.7 386.9 481.1 500 6 42 57 63.92 PLEAT MERV 8 93 83 81 76 70 68 62 57 86 78 70 73 71 54 38 44 A R C H I T E C T S I N C
License # AA C001863
COMPONENTS LEGEND NOTES:
1500 Jackson Street, Suite 200
CCL - COOLING COIL 1. INDOOR UNIT MODEL NUMBERS AND EQUIPMENT SELECTIONS BASED ON TRANE 5. FILTER EFFICIENCY BASED ON ASHRAE 52.1-1992 TEST METHOD. Fort Myers, Florida 33901
L L
FAN - FAN Phone: 239-278-3838 Fax: 239-275-5356
2. AIR PRESSURE DROP FOR FILTERS SHALL INCLUDE A 0.5" DIRTY FILTER ALLOWANCE. 6. MAX. CHW COIL APD SHALL BE 0.9 IN W.G.
FLT - PRE-FILTERS
3. CAPACITIES SHOWN ARE MINIMUM. AIR AND WATER PRESSURE DROPS ARE MAXIMUM. 7. MAX. CHW COIL WPD SHALL BE 10.0 FT. 949 Central Ave.
Naples, Florida 34102
4. FILTER MODEL NUMBERS AND SELECTIONS BASED ON FARR. 8. DISCONNECT BY DIVISION 26. Phone: 239-643-3103 Fax: 239-643-7435
Project:
PUBLIC
K
TABLE 4-2
K
DEFENDER'S
VARIABLE AIR VOLUME TERMINAL UNIT SCHEDULE AIR DISTRIBUTION SCHEDULE
MINIMUM HANGER SIZES FOR ROUND DUCT
MARK CFM
NECK FACE SIZE
DESCRIPTION
OFFICE - 5TH
FLOOR
MAX. SIZE LENGTH
HEATER COIL DATA
DIA. MAXIMUM WIRE/ ROD STRAP PLAN DESIGN MINIMUM INLET NC
SPACING A
DIA. APD EAT LAT HEATING BASIS OF DESIGN: TITUS TMS-AA
MARK CFM CFM SIZE RATING KW POWER STEPS 000-125 6 24x24
10" DN. 12' ONE 12 GA. 1/4" 1"x 22 GA.
(IN WG) (°F) (°F) CFM 126-250 8 24x24 COLOR: WHITE
250 MM DN 3.7 M ONE 2.75 MM 6.4 MM 25.4 x 0.85 MM
251-325 10 24x24 MATERIAL: ALUMINUM
TWO 12 GA. VAV-3-1 950 285 10 < 20 0.10 4 277/1 2 55 81.6 475 326-450 12 24x24 OPPOSED BLADE DAMPERS: NO Owner:
11-18" 12' 1/4" 1"x 22 GA.
J
460 MM 3.7 M
OR ONE 8 GA.
ONE 4.27 MM 6.4 MM 25.4 x 0.85 MM
VAV-3-2 700 210 8 < 20 0.10 3 277/1 1 55 82.1 350
SUPPLY
B
451-625 14 24x24
J Lee County Board
19-24" 12' TWO 10 GA. 1/4" 1"x 22 GA.
VAV-3-3 1875 562 12 < 20 0.10 8 277/1 2 55 81.6 950
000-120 6 24x24 BASIS OF DESIGN: TITUS 50F of County
VAV-3-4 800 240 8 < 20 0.10 4 277/1 2 55 86.6 400
Commissioners
610 MM 3.7 M TWO 3.51 MM 6.4 MM 25.4 x 0.85 MM 121-225 8 24x12 COLOR: WHITE
226-350 10 24x12 MATERIAL: ALUMINUM
25-36" 12' TWO 8 GA. 3/8" 1"x 20 GA. VAV-3-5 475 142 8 < 20 0.10 2 277/1 1 55 80.3 250
RETURN 351-500 12 24x12
900 MM 3.7 M TWO 2.7 MM 9.5 MM 25.4 x 0.85 MM OPPOSED BLADE DAMPERS: NO
VAV-3-6 1200 360 10 < 20 0.10 5 277/1 2 55 81.3 600 501-800 14 24x12
PROVIDE WITH SQUARE TO ROUND Consultant:
37-50" 12' TWO 3/8" TWO 1"x 20 GA. VAV-3-7 675 210 8 < 20 0.10 3 277/1 1 55 82.1 300 TRANSITION WHERE ROUND DUCT
1270 MM 3.7 M TWO 9.5 MM (2) 25.4 x 1.00 MM CONNECTION IS SHOWN.
13099 S. Cleveland Ave.
VAV-3-8 175 52 5 < 20 0.10 1 277/1 1 55 91.3 100 Suite 500
51-60" 12' TWO 3/8" TWO 1"x 18 GA. VAV-3-9 425 120 6 < 20 0.10 2 277/1 1 55 86.6 200 H
Fort Myers, Florida 33907
H 1520 MM 3.7 M TWO 9.5 MM (2) 25.4 x 1.31 MM C BASIS OF DESIGN: TITUS 300FS Phone: 239-275-4240
VAV-3-10 625 187 8 < 20 0.10 3 277/1 1 55 84.2 325 COLOR: WHITE Fax: 239-275-3511
61-84" 12' TWO 3/8" TWO 1"x 16 GA. MATERIAL: ALUMINUM www.tlc-engineers.com
2130 MM 3.7 M TWO 9.5 MM (2) 25.4 x 1.61 MM VAV-3-11 275 82 6 < 20 0.10 1.5 277/1 1 55 86.6 150 © Copyright 2014 TLC Engineering for Architecture, Inc.
000-100 6 8x8
OPPOSED BLADE DAMPERS: NO
VAV-3-12 350 105 5 < 20 0.10 1.5 277/1 1 55 82.1 175 PROVIDE WITH SQUARE TO ROUND EB #0000015 TLC NO: 714125
NOTES SUPPLY
VAV-3-13 675 202 8 < 20 0.10 3 277/1 1 55 82.1 350 TRANSITION WHERE ROUND DUCT
1. STRAPS ARE GALVANIZED STEEL; RODS ARE UNCOATED OR GALVANIZED STEEL; WIRE IS BLACK ANNEALED, CONNECTION IS SHOWN.
VAV-3-14 725 217 8 < 20 0.10 3 277/1 1 55 80.3 375 Seal:
BRIGHT BASIC, OR GALVANIZED STEEL. ALL ARE ALTERNATIVES
VAV-3-15 550 165 8 < 20 0.10 3 277/1 1 55 89.5 275 D 000-120 6 8x8 BASIS OF DESIGN: TITUS 50F
2. REFER TO SMACNA DUCT STANDARDS - SECOND EDITION: FIG. 4-4 FOR LOWER SUPPORTS.
COLOR: WHITE
3. REFER TO SMACNA DUCT STANDARDS - SECOND EDITION: FIG. 4-2 AND 4-3 FOR UPPER ATTACHMENTS. VAV-3-16 750 225 8 < 20 0.10 3 277/1 1 55 80.3 375
MATERIAL: ALUMINUM
G 4. TABLE ALLOWS FOR CONVENTIONAL WALL THICKNESS, AND JOINT SYSTEMS PLUS ONE LB/SF INSULATION WEIGHT. VAV-3-17 200 60 5 < 20 0.10 1 277/1 1 55 86.6 100 G
OPPOSED BLADE DAMPERS: NO
IF HEAVIER DUCTS ARE TO BE INSTALLED, ADJUST HANGER SIZES TO BE WITHIN THEIR LOAD LIMITS; REFER TO EXHAUST PROVIDE WITH SQUARE TO ROUND
VAV-3-18 NOT USED - - - - - - - - - -
SMACNA DUCT STANDARDS - SECOND EDITION: ALLOWABLE LOADS WITH TABLE 4-1. HANGER SPACING MAY BE TRANSITION WHERE ROUND DUCT
ADJUSTED BY SPECIAL ANALYSIS. VAV-3-19 1200 360 10 < 20 0.10 5 277/1 2 55 81.3 600 CONNECTION IS SHOWN.
5. DESIGNERS: FOR INDUSTRIAL GRADE SUPPORTS, INCLUDING SADDLES, SINGLE LOAD TRAPEZE LOADS, LONGER SPANS VAV-3-20 450 135 8 < 20 0.10 2 277/1 1 55 83.1 225 BASIS OF DESIGN: TITUS 300FL
E 000-300 12x8 12x8 COLOR: WHITE
AND FLANGE JOINT LOADS, SEE SMACNA'S ROUND INDUSTRIAL DUCT CONSTRUCTION STANDARDS. 101-600 18x10 18x10
VAV-3-21 525 157 8 < 20 0.10 3 277/1 1 55 89.5 275 MATERIAL: PLASTIC
6. REFER TO SMACNA DUCT STANDARDS - SECOND EDITION: FIGS.3-9 AND 3-10 FOR FLEXIBLE DUCT SUPPORTS. OPPOSED BLADE DAMPERS: NO
VAV-3-22 200 60 5 < 20 0.10 1 277/1 1 55 86.6 100
COPYRIGHT: HVAC DUCT CONSTRUCTION STANDARDS METAL AND FLEXIBLE - SECOND EDITION.
VAV-3-23 625 187 8 < 20 0.10 3 277/1 1 55 84.2 325 SIDEWALL
SUPPLY
F VAV-3-24 775 232 8 < 20 0.10 4 277/1 2 55 86.6 400 BASIS OF DESIGN: TITUS 50F F
F 000-300 12x8 12x8 COLOR: WHITE Project Phase:
VAV-3-25
VAV-3-26
1125
1675
340
502
10
12
< 20
< 20
0.10
0.10
5
7
277/1
277/1
2
2
55
55
84.4
81.5
575
850
101-600 18x10 18x10 MATERIAL: PLASTIC
OPPOSED BLADE DAMPERS: NO Construction
TABLE 4-1
RECTANGULAR DUCT HANGERS
VAV-3-27 950 285 10 < 20 0.10 4 277/1 2 55 81.6 475 SIDEWALL
RETURN
PROVIDE WITH SQUARE TO ROUND
TRANSITION WHERE ROUND DUCT
CONNECTION IS SHOWN.
Documents
NOTES: Project #: 0118.22
MINIMUM SIZE BASIS OF DESIGN: TITUS TBD-10
1. BASIS OF DESIGN: ENVIROTEC. 4. 3/4" FIBERGLASS - DOUBLE WALL. G 000-225 8 4 FEET COLOR: WHITE Project Issued: 11/05/14
MAXIMUM PAIR AT 10 FT SPACING PAIR AT 8 FT SPACING PAIR AT 5 FT SPACING PAIR AT 4 FT SPACING 2. PROVIDE WITH INTEGRAL DISCONNECT. 5. FIELD-MOUNTED CONTROLS. MATERIAL: ALUMINUM
Sheet Issued:
HALF OF 3. SEE SPECIFICATIONS FOR ADDITIONAL 6. ELECTRONIC CONTROL PACKAGE AND
OPPOSED BLADE DAMPERS: YES
DUCT 2 SLOT, 1" SLOTS
E STRAP WIRE/ STRAP WIRE/ STRAP WIRE/ STRAP WIRE/ INFORMATION. DISCONNECT (FUSED). LINEAR 8" CONNECTION E
PERIMETER ROD ROD ROD ROD SUPPLY No. Date Revision
10 GA. 10 GA. 12 GA. 12 GA.
P/2 = 30" 1"x 22 GA. 1"x 22 GA. 1"x 22 GA. 1"x 22 GA. PROVIDE W/INSULATED PLENUM.
(.135") (.135") (.106") (.106")
BASIS OF DESIGN: TITUS TBD-10
H 000-225 8 4 FEET
P/2 = 72" 1"x 18 GA. 3/8" 1"x 20 GA. 1/4" 1"x 22 GA. 1/4" 1"x 22 GA. 1/4" COLOR: WHITE
MATERIAL: ALUMINUM
P/2 = 96" 1"x 16 GA. 3/8" 1"x 18 GA. 3/8" 1"x 20 GA. 3/8" 1"x 22 GA. 1/4" SOUND ATTENUATOR SCHEDULE OPPOSED BLADE DAMPERS: NO
2 SLOT, 1" SLOTS
P/2 = 120" 1\" x 16 GA 1/2" 1"x 16 GA. 3/8" 1"x 18 GA. 3/8" 1"x 20 GA. 1/4" PLAN AIR FACE PRESS. SIZE MINIMUM DYNAMIC INSERTION LOSS, dB MAXIMUM SELF GENERATED NOISE, dB LINEAR 8" CONNNECTION
FLOW VEL. DROP WxHxL OCTAVE BAND OCTAVE BAND RETURN
P/2 = 168" 1\" x 16 GA 1/2" 1\" x 16 GA 1/2" 1"x 16 GA. 3/8" 1"x 18 GA. 3/8" MARK PROVIDE W/ INSULATED PLENUM.
MODEL CFM FPM IN. WG. INCHES 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
D NOTES: D
P/2 = 192" NOT GIVEN 1/2" 1\" x 16 GA 1/2" 1"x 16 GA. 3/8" 1"x 16 GA. 3/8" SA-1 ES NOTE 3 1778 0.70 36 x 18 x 60 6 12 19 35 49 49 35 24 63 57 54 50 49 53 53 50
1. AIR DISTRIBUTION DEVICES LOCATED WITHIN ACOUSTICAL TILE CEILINGS SHALL BE
NOTES: PROVIDED WITH BORDER TYPE 3 FOR LAY-IN MOUNTING. AIR DISTRIBUTION DEVICES
P/2 = 193" UP SPECIAL ANALYSIS REQUIRED
1. OCTAVE BAND CENTER FREQUENCY (HZ) 1-63, 2-125, 3-250, 4-500, 5-1000, 6-2000, 7-4000, 8-8000. LOCATED WITHIN GYPSUM BOARD CEILINGS OR WALLS SHALL BE PROVIDED WITH
PLASTER FRAME. REFER TO ARCHITECTURAL DOCUMENTS FOR CEILING TYPES.
WHEN STRAPS ARE LAP JOINED SINGLE HANGER MAXIMUM ALLOWABLE LOAD 2. SELECTIONS ARE BASED ON INDUSTRIAL ACOUSTICS QUIET DUCT SILENCERS RECTANGULAR FILM LINED.
USE THESE MINIMUM FASTENERS: 3. REQUIRES (2) 36x18 SILENCERS IN TANDEM - 8000 CFM PER SILENCER FOR A TOTAL OF 16,000 CFM.
STRAP WIRE OR ROD (DIA.) 2. AIR DISTRIBUTION DEVICES LOCATED IN SMALL ROOMS WHERE FULL 24"x24" GRID ARE
4. ACCEPTABLE ALTERNATE MANUFACTURER IS VIBRO-ACOUSTICS. NOT AVAILABLE SHALL BE PROVIDED WITH SURFACE MOUNTING BORDERS IN LIEU OF
1"x 18, 20, 22 GA.-TWO #10 OR ONE 1/4" BOLT 1"x 22 GA.-260 LBS. 0.016".-80 LBS. LAY-IN. SECURE EACH DEVICE TO CEILING GRID WITH FIELD-FABRICATED SUPPORTS.
1"x 16 GA.-TWO 1/4" DIA. 1"x 20 GA.-320 LBS. 0.135"- 120 LBS.
1 1/2"x 16 GA. -TWO 3/8" DIA. 1"x 18 GA.-420 LBS. 0.162"- 160 LBS.
C PLACE FASTENERS IN SERIES, NOT SIDE BY SIDE. 1"x 16 GA.-700 LBS. 1/4"- 270 LBS. C
1 1/2"x 16 GA. -1100 LBS. 3/8"- 680 LBS.
1/2"- 1250 LBS.
5/8"- 2000 LBS.
3/4"- 3000 LBS. CHILLED WATER FAN COIL UNIT
AIRFLOW COOLING COIL DATA FAN & MOTOR DATA
NOTES PLAN MODEL
1. DIMENSIONS OTHER THAN GAGE ARE IN INCHES. CFM / MIN.SEN. MIN.TOT. EAT LAT WATER TEMP. °F FLOW DRIVE FAN #1 FAN #1 FAN #2 FAN #2 VOLTS/ SERVICE Copyright © 2014. BSSW Architects, Inc.
MARK NO. reserves copyright and other rights
2. TABLES ALLOW FOR DUCT WEIGHT, 1 LB./SF INSULATION WEIGHT AND NORMAL REINFORCEMENT AND TRAPEZE WEIGHT, EXT SP MBH MBH DB WB DB WB ENT. LVG. GPM TYPE HP RPM HP RPM MCA MOCP PHASE restricting these documents to the original
BUT NO EXTERNAL LOADS. site or purpose for which they were
FC-1 FCCB12 SIZE 120 600/0.40" 11.9 14.0 75 63 55 54.9 42 57 2.6 DIRECT 0.13 1279 0.24 1224 2.65 15.0 208/1 IT ROOM 347 prepared. Reproductions, changes or
B 3. FOR CUSTOM DESIGN OF HANGERS, DESIGNERS MAY CONSULT SMACNA'S RECTANGULAR INDUSTRIAL DUCT STANDARDS, B assignments are prohibited.
THE AISI COLD FORMED STEEL DESIGN MANUAL AND THE AISC STEEL CONSTRUCTION MANUAL. FC-2 FCCB12 SIZE 120 300/0.50" 5.8 7.1 75 63 55 54.9 42 57 1.3 DIRECT 0.13 1279 0.24 1224 2.65 15.0 208/1 ELEC RM 307
Sheet Title:
4. STRAPS ARE GALVANIZED STEEL; OTHER MATERIALS ARE UNCOATED STEEL.
5. ALLOWABLE LOADS FOR P/2 ASSUME THAT DUCTS ARE 16 GA. MAXIMUM, EXCEPT THAT WHEN MAXIMUM DUCT DIMENSION (W)
IS OVER 60" THEN P/2 MAXIMUM IS 1.25W.
NOTES:
1. MODEL NUMBERS AND EQUIPMENT SELECTIONS BASED ON TRANE
Lawrin T. Ellis, P.E. HVAC SCHEDULES
2. MAX APD ACROSS CHW COIL SHALL BE 0.5".
Florida License #66383
6. FOR UPPER ATTACHMENTS REFER TO SMACNA DUCT STANDARDS - SECOND EDITION: FIG. 4-2
3. MAX WPD ACROSS CHW COIL SHALL BE 3.0 FT.
7. FOR LOWER ATTACHMENTS REFER TO SMACNA DUCT STANDARDS - SECOND EDITION: FIG. 4-4
4. SINGLE POINT POWER CONNECTION.
8. FOR TRAPEZE SIZES REFER TO SMACNA DUCT STANDARDS - SECOND EDITION: TABLE 4-3 AND FIG. 4-5. 5. DISCONNECT BY DIV 26.
9. 12, 10, OR 8 GA. WIRE IS STEEL OF BLACK ANNEALED, BRIGHT BASIC, OR GALVANIZED TYPE. 6. PROVIDE WITH MERV 8 FILTERS.
7. PROVIDE WITH VALVING PACKAGE. Sheet No.
A COPYRIGHT: HVAC DUCT CONSTRUCTION STANDARDS METAL AND FLEXIBLE - SECOND EDITION. A
8. PROVIDE CONTROLLER TO INTERFACE WITH EXISTING EMS SYSTEM.
Seal
M301
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
AHU-OA (EXIST.) DO
C
WIRE TO
FILTER FSD-6LB START AHU-OA
M THIS DAMPER IS TO BE M
C INSTALLED BUT REMAIN SD R-1
N.C. OUTSIDE AIR CLOSED INTERLOCK
C RELAY
2HR. RATED
DUCT CHASE
ROOF
SD A R C H I T E C T S I N C
NEW DUCT TIE IN
License # AA C001863
OFFICE - 5TH
MANUAL RESET DO
HIGH STATIC
DAMPER PRESSURE
FLOOR
N.C. OUTSIDE AIR AO POSITION SENSOR
FSD
DM-7FLR
SMOKE DETECTOR
SHUT-DOWN CKT. FSD-6FLG
DI SPACE TEMPERATURE/HUMIDITY SENSOR W/
DPS-3 SMOKE DETECTOR PS-2 Owner:
DATA-PORT FOR PORTABLE LAPTOP
Lee County Board
SHUT-DOWN CKT.
J N.C. OUTSIDE AIR AO MERV 8 CONNECTION, AND OVERRIDE BUTTON. J
BD FILTER TS-1 FURNISH ONE SENSOR PER UNIT
DM-6FLR
BD
of County
C
RETURN AIR AHU-3S SUPPLY AIR Commissioners
C (NEW)
T
CLOSE STATIC PRESSURE SENSOR LOC. 1. MODULATE THE VAV BOX DAMPER TO MAINTAIN THE SPACE SET-POINT TEMPERATURE VIA THE ASSOCIATED SPACE WALL MOUNTED
VALVE IF MOISTURE IS DETECTED IN CHWR 2/3 DOWNSTREAM OF THE AHU TEMPERATURE SENSOR. MODULATE BETWEEN THE SCHEDULED REQUIRED MAXIMUM CFM AND MINIMUM CFM FLOW TO MAINTAIN
M M DRAIN PAN. Seal:
REFER TO SHEET M101 FOR LOCATION THE SPACE SET-POINT TEMPERATURE.
CHWS
2. WHEN THE VAV BOX REACHES ITS MINIMUM CFM SET-POINT AND A THE SPACE TEMPERATURE FALLS BELOW THE ROOM SET-POINT,
AFMS
OUTSIDE AIR AO
NEW HIGH POINT TIE IN TO ENABLE THE STAGES OF ELECTRIC REHEAT IN THE VAV BOX TO REACH THE SPACE TEMPERATURE SET-POINT. PROVIDE PROOF OF
AIR EXTISING FLOW ACROSS VAV BOX HEATING COIL BEFORE ALLOWING THE COIL TO ENERGIZE.
G VENT IN CHW PIPING CV-3S 3" CHWR VALVES G
(TYP 2) 3. ALL SET-POINTS SHALL BE ADJUSTABLE FROM THE BAS.
FSD
SMOKE DETECTOR
SHUT-DOWN CKT. 4. SET UNOCCUPIED HIGH TEMPERATURE LIMIT TO 80°F. SET UNOCCUPIED LOW TEMPERATURE TO 65°F. WHEN SPACE TEMPERATURE
TIE IN TO EXISTING OA CHASE SPACE R/H CARBON DIOXIDE IS OUTSIDE OF SETPOINTS, VAV BOX DAMPER SHOULD MOVE TO THE APPROPRIATE POSITION AND ENERGIZED THE AIR HANDLING
N.C. OUTSIDE AIR FIRE/SMOKE DAMPER W/ AI AI UNIT.
MODULATING SEE FLOOR SEE FLOOR
DM-2FLR OPERATOR 3" CHWS PLAN FOR PLAN FOR
(TYP) LOCATIONS LOCATIONS
H C
LOW POINT DRAIN
W/ EXISTING CHWS/R
F RISER F
VALVE & 3/4" HOSE Project Phase:
Construction
N.C. OUTSIDE AIR THREAD W/CAP UP AND DOWN
NOTE:
DM-1FLR SEE DETAIL 2 ON SHEET M201 FOR
PIPING COMPONENTS.
Documents
Project #: 0118.22
Project Issued: 11/05/14
DUAL PATH AHU CONTROL FOR AHU-3S 2 VARIABLE VOLUME TERMINAL W/ REHEAT 1 Sheet Issued:
No Scale
E E
No. Date Revision
SEQUENCE OF CONTROL:
NOTE:
CHILLED WATER SYSTEM SEE DETAIL 2 ON SHEET M201 FOR
3. UNOCCUPIED HOURS: PIPING COMPONENTS.
1. START LEAD SECONDARY CHWS PUMP (SCWP-7 OR 8 LOCATED IN THE CENTRAL PLANT) ON CALL
FOR COOLING FROM ANY VAV BOX. THE LAG PUMP SHALL BE STARTED IN THE CASE OF FAILURE A. STOP AHU-3S SUPPLY FAN. FAN START/STOP
OF THE LEAD PUMP. PUMP SPEED SHALL BE CONTROLLED BY INDIVIDUAL VARIABLE FREQUENCY
LEAVING AIR TEMP
AI BO FAN STATUS
BI CURRENT
MOTOR DRIVES VIA A DIFFERENTIAL PRESSURE TRANSDUCER LOCATED IN THE SUNTRUST 9TH B. CLOSE FLOOR OUTSIDE AIR SUPPLY DAMPER FSD-6LF, RETURN AIR DAMPERS FSD-6LG, FSD-6LF AND EXHAUST AIR DAMPERS FSD-6LC. TRANSFORMER
FLOOR MECHANICAL ROOM.
C. START AND STOP AHU-3S TO MEET UNOCCUPIED SPACE TEMPERATURE SETPOINT. USE INDIVIDUAL SPACE
D EXISTING CHWS/R D
2. CHILLED WATER IS PROVIDED FROM THE CENTRAL CHILLER PLANT. TEMPERATURES TO DETERMINE THE START / STOP OF AHU-3S. RETURN AIR RISER UP/DN
SINGLE PATH VARIABLE AIR VOLUME AIR HANDLING UNIT AHU-3S AND AHU-OA 5. SAFETIES
BI
1. MORNING BUILDING COOL-DOWN: A. STOP AHU SUPPLY FANS AND CLOSE RETURN AIR DAMPERS ON DETECTION OF SMOKE. COORDINATE WITH THE ELECTRICAL HOT TAPPED TIE
VALVE IN
START AHU-3S BASED UPON OPTIMAL START PROGRAMMING THAT CALCULATES THE PROPER TIME OF START-UP TO CONTRACTOR. POSITION
AO WITH NEW 1"
COOL SPACE WITH THE HIGHEST TEMPERATURE READING BEFORE THE TIME OF BUILDING OCCUPANCY. THE PROGRAMMING CHWS/R W/VALVE
SHALL USE HISTORICAL TRENDS AS WELL AS OUTSIDE AIR AND SPACE TEMPERATURE IN DETERMINING THE ACTUAL B. PROVIDE HIGH STATIC PRESSURE LIMIT SHUT-DOWN OF THE AIR HANDLING SYSTEM. PROVIDE WITH MANUAL RESET. M
START TIME. DURING MORNING COOL-DOWN THE OUTSIDE DAMPER SHALL BE CLOSED AND THE RETURN AIR DAMPER SET PRESSURE AT 4" W.C. AUX. DRAIN PAN W/ MOISTURE
SHALL BE 100% OPEN. START AHU-3S SUPPLY FAN. MODULATE THE 2-WAY CHILLED WATER CONTROL VALVE FOR DETECTIOR INTERLOCKED W/
AHU-3S TO MAINTAIN A MINIMUM 55 DEGREES F SUPPLY AIR TEMPERATURE DOWN STREAM OF THE SUPPLY FAN. CHILLED
C WATER VALVE C
2. OCCUPIED HOURS:
A. START SUPPLY AIR FAN AHU-3S. OPEN THE OUTSIDE AIR DAMPER. SPACE TEMP
AI NEW HIGH POINT
B. MODULATE THE ASSOCIATED 2-WAY CHILLED WATER CONTROL VALVE FOR AHU-3S CHILLED WATER COILS AIR
TO MAINTAIN 55°F D.B. (ADJ) LEAVING AIR TEMPERATURE FROM THE CHILLED WATER COIL. VENT (TYP) LOW POINT DRAIN W/
T VALVE & 3/4" HOSE
C. AHU-3S SUPPLY AIR FAN SHALL BE CONTROLLED VIA THE ASSOCIATED VARIABLE FREQUENCY MOTOR DRIVE TO MAINTAIN THREAD W/CAP (TYP) Copyright © 2014. BSSW Architects, Inc.
THE SUPPLY DUCT STATIC PRESSURE SET-POINT. reserves copyright and other rights
restricting these documents to the original
D. PROVIDE LEAVING AIR TEMPERATURE (L.A.T.) RESET STRATEGY TO CONTROL L.A.T. BASED ON POSITION OF VAV BOX DAMPERS. site or purpose for which they were
prepared. Reproductions, changes or
B RAISE L.A.T. 1° F. EVERY 15 MINUTES B assignments are prohibited.
UNTIL ANY VAV BOX IS AT FULL OPEN AND SPACE TEMPERATURE AT ANY SENSOR IS ABOVE SETPOINT OR UNTIL SPACE R/H RISES
ABOVE 60% R/H. LOWER THE L.A.T. 1° F. EVERY 15 MINUTES ANY VAV BOX IS AT MIN. POSITION AND SPACE TEMPERATURE IS SEQUENCE OF OPERATION Sheet Title:
BELOW THE SPACE TEMPERATURE SETPOINT.
E. IN NORMAL OPERATION, MODULATING FIRE/SMOKE DAMPERS FSD-6LF, FSD-6LG AND FSD-6LH SHALL BE CONTROLLED TO
1. SUPPLY FAN WILL CYCLE ON A CALL FOR COOLING.
Sheet No.
A A
M M
PLUMBING GENERAL NOTES:
PLUMBING FIXTURE SCHEDULE PLUMBING SYMBOL LEGEND
1. READ THE SPECIFICATIONS AND ALL NOTES ON PLANS.
DEFENDER'S
6. WHEN BEAM SLEEVE PENETRATIONS ARE NECESSARY, COORDINATE PENETRATIONS WITH BASIS OF DESIGN -HOSE BIBB
K K
ALL TRADES, THE ARCHITECT AND THE STRUCTURAL ENGINEER. CHINA - AMERICAN STANDARD - 2257.103
FLUSH VALVE - SLOAN ROYAL 111-XL-YK -BALANCING VALVE
OFFICE - 5TH
CHINA - AMERICAN STANDARD - 2257.103
7. NOT USED. SEAT - BEMIS - 1655-SS/C FLUSH VALVE - SLOAN ROYAL 111-XL-YK -CLEANOUT
CARRIER - ZURN - Z-1200 SERIES SEAT - BEMIS - 1655-SS/C
FLOOR
CARRIER - ZURN - Z-1200 SERIES -COLD WATER PIPING
8. SEE ARCHITECTURAL DRAWINGS FOR EXACT PLUMBING FIXTURE EWC-1 ACCESSIBLE ELECTRIC WATER COOLER -HOT WATER PIPING
LOCATIONS AND MOUNTING HEIGHTS. U-1 WALL HUNG ACCESSIBLE URINAL -HW RECIRCULATING PIPING
TYPE 304 STAINLESSS STEEL DRINKING FOUNTAIN POLISHED TO A #4 SATIN FINISH WITH S -SANITARY PIPING
9 . PROVIDE CLEANOUTS AT BASE OF ALL RISER STACKS AND DUAL HEIGHT RECEPTOR, SELF CLOSING FRONT MOUNTED PUSH BUTTON TYPE BUBBLERS, VITREOUS CHINA, 1.0 GALLON WALL HUNG, SIPHON JET URINAL WITH INTEGRAL FLUSHING RIM, S -UNDERGROUND SANITARY PIPING
IN ACCORDANCE WITH APPROPRIATE CODES AND REGULATIONS. STRAINER AND TAILPIECE. SURFACE MOUNTED REFRIGERANT CHILLER UNIT CAPABLE OF 8 INTEGRAL TRAP, WALL HANGERS, AND 2 INCH FEMALE FLANGED OUTLET CONNECTION. Owner:
GPH OF 50 °F AT AN AMBIEMT TEMPERATURE OF 90 °F. ELECTRICAL CHARACTERISTICS - -SANITARY VENT PIPING
J
10.
115V AC, 60HZ, SINGLE PHASE. 1.0 GALLON CHROME PLATED FLUSH VALVE(EXPOSED), 3/4-INCH I.P.S. SCREWDRIVER CHECK ANGLE CD -CONDENSATE PIPING J Lee County Board
WHERE POTABLE WATER STUBS OUT OF WALL OR IS EXPOSED, THE PLUMBING
CONTRACTOR SHALL TRANSITION TO COPPER (FOR WC OR URINALS) AND CHROME PLATED WATERSENTRY VII FILTER WITH 1,500 GALLON CAPACITY TO REMOVE CYSTS, LEAD AND
STOP WITH PROTECTIVE CAP, ADJUSTABLE TAILPIECE, VACUUM BREAKER FLUSH CONNECTION AND
SPUD COUPLING FOR 3/4" TOP SPUD, DIE CAST WALL FLANGE WITH SET SCREW, SPUD FLANGE AND
of County
Commissioners
UNDER LAV'S & SINKS. CHLORINE. -CONNECT TO EXISTING
SOLID RING PIPE SUPPORT.
CHROME PLATED 17 GAUGE 1-1/4 X 1-1/2 BRASS P-TRAP WITH CLEANOUT. FULLY ADJUSTABLE URINAL CARRIER ADJUSTED TO ACCESSIBLE HEIGHT, SEE SPECS.
11. THIS CONTRACTOR MUST REFER TO THE ARCHITECTURAL DRAWINGS FOR
ADDITIONAL WORK SCOPE COVERED BY THE ARCHITECT. COORDINATE WITH Consultant:
THE GENERAL CONTRACTOR AND ALL THE SUB-CONTRACTORS INVOLVED.
3/8 INCH I.P.S. CHROME PLATED SUPPLY WITH LOOSE KEY STRAIGHT STOP AND WALL
FLANGE.
BASIS OF DESIGN
COMPLIANCE STATEMENT 13099 S. Cleveland Ave.
CHINA - AMERICAN STANDARD - 6501.010 Suite 500
12. APPLICABLE CODES INCLUDE, BUT ARE NOT LIMITED TO: BASIS OF DESIGN FLUSH VALVE - SLOAN ROYAL 186-1-XL-YK Fort Myers, Florida 33907
THESE PLANS HAVE BEEN PREPARED IN COMPLIANCE WITH H
H CARRIER - ZURN ZR-1222 THE 2007 FLORIDA BUILDING CODE - PLUMBING. Phone: 239-275-4240
A. FLORIDA BUILDING CODE, 2007 EDITION PLUMBING . FOUNTAIN - ELKAY - LZSTL-8-C Fax: 239-275-3511
TRAP - MCGUIRE - 8902 L-1 ACCESSIBLE WALL HUNG LAVATORY www.tlc-engineers.com
B NFPA 101, LIFE SAFETY CODE, 2007 EDITION
SUPPLY - MCGUIRE- 158LK © Copyright 2014 TLC Engineering for Architecture, Inc.
VITREOUS CHINA LAVATORY, 20" X 18", PUNCHED FOR 4"CENTERSET FITTING AND CONCEALED ARM EB #0000015 TLC NO: 714125
C. AMENDMENTS TO ANY OF THE ABOVE CODES WHICH ARE ENFORCED BY CARRIER SUPPORT.
MS-1 MOP SINK
THE LOCAL AUTHORITY HAVING JURISDICTION OVER THIS PROJECT.
4" CENTERSET CHROME PLATED BRASS FAUCET, VANDAL RESISTANT 0.5 GPM FLOW REGULATOR, Seal:
13. FIELD VERIFY EXISTING INSTALLATIONS. MODIFY EXISTING PLUMBING SYSTEMS, FLOOR MOUNTED PRECAST TERRAZO WITH STAINLESS STEEL CAP, 24" X 24" X 12", DRAIN BODY CHROME PLATED WRISTBLADE HANDLES WITH HOT AND COLD WATER CODED INDEXES.
WHICH ARE TO REMAIN ACTIVE, TO FACILITATE RECONNECTION AND EXTENSION OF SHALL BE STAINLESS STEEL CAST INTEGRAL, AND SHALL PROVIDE FOR A CAULKED LEAD
THE NEW WORK. CONNECTION AND NOT LESS THAN 1" DEEP TO A 3" PIPE. PROVIDE WITH STAINLESS STEEL WALL PRE-INSULATED CHROME PLATED WHEELCHAIR LAVATORY STRAINER, CAST GRID DRAIN PLUG WITH
GUARD. STRAINER AND OFFSET DRAIN ASSEMBLY WITH 1-1/4 INCH O.D. TAILPIECE, CHROME PLATED 17
G GAUGE 1-1/4 X 1-1/2" BRASS P-TRAP WITH CLEANOUT. G
14. NOTIFY OWNER AT LEAST 24 HOURS PRIOR TO INTERRUPTING EXISTING SERVICE.
SERVICE FAUCET SHALL BE CHROME PLATED WITH RENEWABLE SEATS IN MONEL, VACUUM
SCHEDULE DISCONNECTION AND TIE-INS TO MINIMIZE DISRUPTION OF SERVICES.
BREAKER, INTEGRAL STOPS, ADJUSTABLE WALL BRACE, PAIL HOOK, AND 3/4" HOSE THREAD ON PRE-INSULATED 1/2" COMPRESSION X 3/8 INCH COMPRESSION CHROME PLATED ANGLE SUPPLY
SERVICES ARE NOT TO BE LEFT DISRUPTED DURING NON-NORMAL CONTRACTOR WORKING SPOUT. STOPS WITH CHROME PLATED 12" FLEXIBLE RISERS AND ESCUTCHEONS.
HOURS.
36" HOSE WITH 3/4" CHROME COUPLING AND WALL BRACKET. FULLY ADJUSTABLE LAVATORY CARRIER ADJUSTED TO ACCESSIBLE HEIGHT, SEE SPECS.
15. PLENUM CEILINGS OCCUR THROUGHOUT, CONTRACTOR TO EITHER VERIFY REQUIRED
FIRE BASIS OF DESIGN BASIS OF DESIGN
RATINGS ARE MET OR WRAP ALL PVC AND/OR CPVC PIPING WITHIN CEILING SPACE WITH
3M SINK - WILLIAMS SBC-1700 - BP CHINA - AMERICAN STANDARD - 0356.012
FIRE WRAP. FAUCET - CHICAGO - 897 FAUCET - CHICAGO - 802A-317-E2805
HOSE - WILLIAMS - T-35 STRAINER/TRAP/STOPS - MCGUIRE - 2125WC
F F
CARRIER - ZURN ZR-1200 SERIES Project Phase:
S-2 SINK Construction
SINK
Documents
S-1
DOUBLE COMPARTMENT SELF RIMMING SINK CONSTRUCTED OF TYPE 304 18-8 STAINLESS STEEL 33"
X 19" X 7-1/2" DEEP. INTERIOR AND TOP SURFACES SHALL BE POLISHED TO A HIGH LUSTER FINISH.
SINGLE COMPARTMENT SELF RIMMING SINK CONSTRUCTED OF TYPE 304
PROVIDE SINK WITH CRUMB CUP STRAINER.
18-8 STAINLESS STEEL 22" X 19" X 7-1/2" DEEP. INTERIOR AND TOP Project #: 0118.22
SURFACES SHALL BE POLISHED TO A HIGH LUSTER FINISH. PROVIDE SINK WITH CRUMB CUP
8" CHROME PLATED BRASS FAUCET, VANDAL RESISTANT 2.0 GPM FLOW REGULATOR, SINGLE LEVER Project Issued: 11/05/14
FINISHED WALL STRAINER.
HANDLE AND 10" SPOUT. Sheet Issued:
8" CHROME PLATED BRASS FAUCET, VANDAL RESISTANT 2.0 GPM FLOW REGULATOR, SINGLE LEVER
1/2" COMPRESSION X 3/8" COMPRESSION CHROME PLATED ANGLE SUPPLY STOPS WITH CHROME
E HANDLE AND 10" SPOUT. E
PLATED 12" FLEXIBLE RISERS AND ESCUTCHEONS. No. Date Revision
1/2" COMPRESSION X 3/8" COMPRESSION CHROME PLATED ANGLE SUPPLY STOPS WITH CHROME
CHROME PLATED 17 GAUGE 1-1/2" TWO COMPARTMENT CONTINUOUS WASTE.
PLATED 12" FLEXIBLE RISERS AND ESCUTCHEONS.
GRAB BAR CHROME PLATED 17 GAUGE 1-1/2" X 1-1/2" P-TRAP WITH CLEANOUT.
VENT LINE
CHROME PLATED 17 GAUGE 1-1/2" X 1-1/2" P-TRAP WITH CLEANOUT.
FLUSH VALVE BASIS OF DESIGN
WATER SUPPLY BASIS OF DESIGN
SINK - ELKAY - LR-3319
SINK - ELKAY - LR-2219
FAUCET - CHICAGO - 2300-8
PIPE SUPPORT (TYP.) FAUCET - CHICAGO - 2300-8
11 1/2"
COATED CAST IRON BODY WITH BOTTOM OUTLET, COMBINATION INVERTIBLE MEMBRANE CLAMP AND
WATER CLOSET ADJUSTABLE TYPE "I" NICKEL BRONZE STRAINER, 6" ROUND TOP, WITH 1" RAISED LIP.
PLUMBING SYMBOL
EWC-1 ELECT WATER COOLER 1\" 1\" \"
Lawrin T. Ellis, P.E.
U-1 ACCESSIBLE URINAL ]" Florida License #66383
LEGEND, GENERAL
2" 2"
S-2 DOUBLE BOWL SINK 2" 1\" \" \" NOTES & INDEX
MS-1 MOP SINK 3" 2" \" \"
Sheet No.
A A
Seal
P001
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
DEMOLITION NOTES:
M M
1 THE CONTRACTOR SHALL PROVIDE PROTECTION FOR ALL PARTS OF THE BUILDING. 7 UNLESS INDICATED OTHERWISE, ALL EXISTING SANITARY WASTE & VENT, AND DOMESTIC
ITS CONTENTS AND OCCUPANTS WHEREVER WORK UNDER THIS CONTRACT IS PERFORMED. HOT AND COLD WATER PIPING SHALL BE CAPPED OR PLUGGED BELOW SLAB, ABOVE
CEILING, OR WITHIN WALL CAVITIES. REFER TO THE ARCHITECTURAL DEMOLITION PLANS.
2 DEMOLITION SHALL INCLUDE REMOVAL OF EXISTING BUILDING CONSTRUCTION TO CONSULT WITH THE OWNER AND OBTAIN OWNERS APPROVAL PRIOR TO DISPOSAL
EXTENT REQUIRED TO PERFORM CONSTRUCTION ACTIVITIES INDICATED. OF REMOVED MATERIAL.
3 THE DEMOLITION PROCEDURES SHALL PROVIDE FOR SAFE CONDUCT OF THE WORK,
PROTECTION OF PERSONNEL, CAREFUL REMOVAL AND DISPOSITION OF MATERIALS
8. THE EXISTING PIPING INDICATED ON THESE DRAWINGS WAS COMPILED FROM ORIGINAL CONSTRUCTION A R C H I T E C T S I N C
SPECIFIED TO BE SALVAGED, PROTECTION OF PROPERTY TO REMAIN UNDISTURBED,
DRAWINGS, "AS-BUILT" DRAWINGS AND ENGINEERS FIELD OBSERVATIONS. THE EXISTING PIPING INDICATED License # AA C001863
REPRESENTS A BEST FAITH EFFORT BY THE ENGINEER TO DEMONSTRATE THE CONDITIONS UNDER WHICH THE WORK
COORDINATION WITH OTHER WORK IN PROGRESS, AND TIMELY DISCONNECTION OF
IS TO BE EXECUTED. THE CONTRACTOR SHALL VISIT SITE AND REVIEW EXISTING CONDITIONS TO THE DEGREE AND
UTILITY SERVICES.
EXTENT NECESSARY TO PREPARE A PROPER AND ADEQUATE BID FOR THE WORK INDICATED. SUBMISSION OF A BID 1500 Jackson Street, Suite 200
L 4 EXISTING WORK TO REMAIN SHALL BE PROTECTED FROM DAMAGE. WORK DAMAGED WILL BE INTERPRETED AS MEANING THE CONTRACTOR HAS REVIEWED EXISTING CONDITIONS AND UNDERSTANDS THE L Fort Myers, Florida 33901
BY THE CONTRACTOR SHALL BE REPAIRED TO MATCH EXISTING WORK OR WORK DIFFICULTIES AND CHALLENGES UNDER WHICH THE WORK IS TO BE ACCOMPLISHED. Phone: 239-278-3838 Fax: 239-275-5356
INSTALLED UNDER THIS CONTRACT DEPENDING ON CONTRACT REQUIREMENTS.
9. DRAWINGS INDICATE INSTALLATION OF NEW FIXTURES TIED TO EXISTING SANITARY WASTE AND VENT PIPING.
5 EXISTING WORK SHALL BE CUT, DRILLED, ALTERED, REMOVED OR TEMPORARILY
SCOPE OF WORK INCLUDES CUTTING AND REMOVAL OF EXISTING FLOOR SLAB FOR THE PURPOSE OF INSTALLING NEW 949 Central Ave.
REMOVED AND REPLACED FOR PERFORMANCE OF WORK UNDER THE CONTRACT.
U.G. SANITARY PIPING. SLAB CUT AND TRENCH WIDTH SHALL BE KEPT TO A MINIMUM. IN NO INSTANCE SHALL SLAB Naples, Florida 34102
WORK REPLACED SHALL MATCH SIMILAR EXISTING WORK. STRUCTURAL MEMBERS OF
CUT/TRENCH WIDTH EXCEED 36 INCHES WITHOUT PRIOR APPROVAL OF ARCHITECT. Phone: 239-643-3103 Fax: 239-643-7435
D101 CONCRETE OR STRUCTURAL STEEL SHALL NOT BE CUT OR ALTERED, EXCEPT AS SHOWN
WITHOUT AUTHORIZATION OF THE OWNER. WORK REMAINING IN PLACE DAMAGED
TYP. OR DEFACED DURING THIS CONTRACT SHALL BE RESTORED TO THE CONDITION AT 10. REMOVE ALL EXISTING DOMESTIC WATER COPPER PIPING/FITTINGS ON THIS FLOOR AND REPLACE WITH CPVC PIPING AND FITTINGS. Project:
TIME OF AWARD OF CONTRACT. CUT, ALTER, REMOVE OR TEMPORARILY REMOVE
PUBLIC
AND REPLACE EXISTING WORK FOR THE INSTALLATION OF MECHANICAL, PLUMBING
AND ELECTRICAL WORK AND OTHER CONSTRUCTION.
DEFENDER'S
6 PROPERLY REMOVE AND DISPOSE OF ALL EXISTING FIXTURES AS REQUIRED
K TO ACCOMODATE NEW PLAN. REFER TO THE ARCHITECTURAL DEMOLITION PLANS. K
CONSULT WITH THE OWNER AND OBTAIN OWNERS APPROVAL PRIOR TO
DISPOSAL OF REMOVED MATERIAL.
D103
TYP.
OFFICE - 5TH
DEMOLITION KEY NOTES:
FLOOR
A FIXTURE TO BE REMOVED.
FIXTURE, FAUCET AND FITTINGS TO BE Owner:
J
PEDESTRIAN BRIDGE
BELOW
TURNED OVER TO CM FOR DEMOLITION .
CAP ALL ASSOCIATED PIPING J Lee County Board
D110
D111 ABOVE CEILING/BELOW SLAB AS
NECESSARY. of County
B FIXTURE TO REMAIN AT SAME LOCATION. Commissioners
CLEAN AND PREPARE AS NEW.
D102
D102
D102
D107
D109
F F
D107 D107 D102 Project Phase:
Construction
D109 D102 D109
D102
D102
Documents
Project #: 0118.22
D102 Project Issued: 11/05/14
Sheet Issued:
E E
D105 No. Date Revision
D104
TYP.
D111
D D
D106 TYP.
D108 TYP.
C C
Sheet Title:
1
P101
5TH FLOOR - PLUMBING - DEMOLITION
1/8" = 1'-0" Seal
P101
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PUBLIC
F40
ALIGN ALIGN B N = # OF CATV JACKS
APD 15
DEFENDER'S
APD 12
K 70 COMMUNICATIONS "INFORMATION OUTLET" MTD. AT K
44
RECEPTACLE HEIGHT UNLESS OTHERWISE NOTED.
X N N
OFFICE - 5TH
REFER TO SPECIFICATIONS FOR MANUFACTURER'S
PART NUMBER.
APD 16 APD 11
FLOOR
C = ABOVE COUNTER
F40 73 P 64 F40 C
W = WALL MOUNTED
F40 F40
APD 10 Owner:
APD 17
J 71
L4 45
D
# KEYNOTES: J Lee County Board
of County
1. 3RD FLOOR IT ROOM. PROVIDE 3/4" PLYWOOD BACKBOARD, 8'-0" HIGH, WHERE
TRAINING
38
WAP
APD 9 INDICATED. SEE ENLARGED TECHNOLOGY ROOM PLAN FOR DETAILS. CONTRACTOR Commissioners
F40 APD 18 STOR / EQUIP STOR/EQUIP F40 TO
WAP-1 23
PROVIDE AND INSTALL A 100 PR UTP FOR VOICE TO THE SECOND FLOOR MDF AND A
69 WAP 39 FS 40 12 Consultant:
STRAND SM/24 STRAND MM FOC FROM THIS LOCATION TO THE SECOND FLOOR MDF
WAP-2 2. TYPICAL FLUSH MOUNTED VOICE/DATA OUTLET. CABLING, OUTLETS, AND TERMINATIONS 13099 S. Cleveland Ave.
BY Suite 500
F40 APD 19 F40 F40 F40 F40 F40 F40 F40 F40 APD 8
F40 PRE-QUALIFIED DIV. 17 CONTRACTOR. Fort Myers, Florida 33907
68 INVEST. 2 INVEST. 3 INVEST. 4 INVEST. 5 INVEST. 6 INVEST. 7 INVEST. 8 INVEST. 9 22 3. TYPICAL MODULAR FURNITURE CONNECTION, COORDINATE REQUIRED CONNECTIONS H
H Phone: 239-275-4240
43 34 33 36 61 41 60 63 TO Fax: 239-275-3511
F40 F40 MODULAR FURNITURE WITH SUPPLIER/INSTALLER. CABLING, OUTLETS, AND www.tlc-engineers.com
E TERMINATIONS BY PRE-QUALIFIED DIV. 17 CONTRACTOR. © Copyright 2014 TLC Engineering for Architecture, Inc.
APD 20 4. PROVIDE TELECOM CONNECTION TO OVERHEAD PROJECTOR. COORDINATE A/V
APD7 CONDUIT EB #0000015 TLC NO: 714125
67 21 AND WIRING REQUIREMENTS WITH OWNER PRIOR TO INSTALLATION.
5. TELECOMMUNICATIONS GROUND BUS. SEE DETAIL #4 ON DRAWING `T202'. PROVIDE #6
CU Seal:
ALIGN ALIGN ALIGN APD 6 FROM GROUND BUS BACK TO ELECTRICAL PANEL SERVING THIS EQUIPMENT.
20 6. SEE A/V WALL PLATE DETAIL #5 ON DRAWING `T202' FOR MORE DETAIL.
APD 21
F40 66 F40 E.5
7. DEDICATED LOCATION FOR COMCAST CABLE TAP. COORDINATE WITH OWNER.
G CR G
FIX
M40 C40 ELEVATOR C40
SS/11 FIX FIX
M40
LOBBY (E) WORKROOM
SS/8 F
F F
CR
FIX
501E 24
SS/8 Project Phase:
ADP 23
F40
C40
ELEC.
92
C40 C40
APD 4 Construction
18 F40 F.3
Documents
58 C40
CR
WORKROOM WOMENS
M40
29 90
M40 M40
CR
CR
SS/6 SS/7 11/05/14
F40 APD 24 93 APD 3 F40
SS/6 SS/7 Sheet Issued:
76 17
E ALIGN ALIGN
F.7 E
C40 No. Date Revision
APD 25 APD 2
F40 WAP F40
75 SS/2 16
C40 C40 M40 M40
WAP-4 M40 M40
RECEPT. D COPY/ WAP
PRINT/
2 M40 WORK AREA SS/3 SS/4 SS/5 WAP-3
APD 1 G
F40 ADP 26 CONF. ROOM F40
74
3 95 F41
SS/1 501F
78 ADMIN.
F40 F40
15
F41 G.8
ADMIN.
14
PUBLIC CONFERENCE CHIEF ASSIT.
DEFENDER ROOM PD ADMIN. ADMIN. H
F41 7 12 13
4 6 D F40
C F40 C
L4 F41
D
CR
CR
F40 F40
Sheet Title:
1
T101
5TH FLOOR - TECHNOLOGY
1/8" = 1'-0" Seal
T101
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
M M
A R C H I T E C T S I N C
INTERMEADIATE DISTRIBUTION FRAME NOTES 3 License # AA C001863
02 RU
Naples, Florida 34102
TOWER Phone: 239-643-3103 Fax: 239-643-7435
7 7 10 03 RU
2. SC MULTIMODE FIBER OPTIC PATCH CORDS FOR OWNER'S ACTIVE HUBS, LENGTH AS REQUIRED. REFER
SYSTEM. 04 RU
TO Project:
SPECIFICATIONS FOR MORE DETAIL. 9 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
05 RU
PUBLIC
(#) 4 PAIR CAT 6 PLENUM RATED VOICE/DATA STATION CABLE TO INFORMATION OUTLET. TERMINATE DATA
25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
06 RU
3.
CABLES AT DATA STATION PATCH PANEL, AND VOICE CABLES AT 110 PUNCHDOWN BLOCKS. 7 7 07 RU
08 RU
K # = REFER TO RESPECTIVE FLOOR PLANS FOR QUANTITY OF PORTS PER OULET, TO DETERMINE THE
NUMBER OF 4 PAIR STATION CABLE REQUIRED AT EACH LOCATION.
9 1
25
2
26
3
27
4
28
5
29
6
30
7
31
8
32
9
33
10
34
11
35
12
36
13
37
14
38
15
39
16
40
17
41
18
42
19
43
20
44
21
45
22
46
23
47
24
48
09 RU
10 RU
K
DEFENDER'S
OFFICE - 5TH
7 2 7 11 11 RU
# DIVISION 17 CONTRACTOR'S KEYNOTES 12 RU
9 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
13 RU
1. ELEVATION INDICATES ALL EQUIPMENT AND CABLING REQUIRED TO BE PROVIDED FOR THIS 7
25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
7
14 RU
15 RU FLOOR
RELAY RACK BASE LOCATION. 16 RU
FIBER OPTIC, COPPER, AND BONDING/GROUNDING BACKBONES ARE PROVIDED BY SCS 12 9
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
17 RU
CONTRACTOR. 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
18 RU
MOUNTING BOLT 2. TELECOMMUNICATIONS GROUNDING BUSBAR (TGB). SEE DETAIL 7 19 RU
Owner:
J
WITH ISOLATED
WASHERS 3. ALL VERTICAL RACKS TO BE PROVIDED WITH VERTICAL AND HORIZONTAL CABLE MANAGEMENT.
9
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
20 RU
21 RU
J Lee County Board
RUBBER GROUNDING MAT 4. RACK MOUNTED POWER STRIP.
25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
22 RU of County
7 23 RU
5. RACK MOUNTED UPS UNIT. 30A/120V, 2880VA MINIMUM 24 RU Commissioners
25 RU
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
9
6. VERTICAL CABLE MANAGEMENT 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 AREA RESERVED FOR 26 RU
OWNER PROVIDED Consultant:
7 27 RU
7. ACTIVE ELECTRONICS
HORIZONTAL CABLE MANAGEMENT 28 RU
13099 S. Cleveland Ave.
29 RU Suite 500
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
NOT USED 1 9
8. 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
30 RU
H
Fort Myers, Florida 33907
7 31 RU
H 9. 48 PORT CAT 6, VOICE/DATA PATCH PANEL. Phone: 239-275-4240
32 RU
Fax: 239-275-3511
33 RU www.tlc-engineers.com
10. (2) 24 PORT FIBER OPTIC PATCH PANEL/DISTRIBUTION CENTERS. (1) FOR SINGLEMODE FIBER AND (1)
FOR 34 RU © Copyright 2014 TLC Engineering for Architecture, Inc.
MULTIMODE FIBER. PROVIDE AND INSTALL (1) 24SM/24MM FOC FROM MDF ON SECOND FLOOR TO THIS VOICE/DATA
35 RU
EB #0000015 TLC NO: 714125
LOCATION. CONNECTIONS TO BE TYPE SC WITH FUSION SPLICE PIGTAILS OUTLET
36 RU
37 RU
11. (2) 24 PORT FIBER OPTIC PATCH PANEL/DISTRIBUTION CENTERS. (1) FOR SINGLEMODE FIBER AND (1) #6 Cu GROUND TO 38 RU Seal:
FOR BUILDING SERVICE 39 RU
MULTIMODE FIBER. PROVIDE AND INSTALL (1) 24SM/24MM FOC FROM PUBLIC DEFENDER'S SERVER GROUND 40 RU
ROOM 41 RU
4
TO THIS LOCATION. CONNECTIONS TO BE TYPE SC WITH FUSION SPLICE PIGTAILS. 42 RU
G 2 43 RU G
12. 110 PUNCHDOWN BLOCKS (QUANTITY AS REQUIRED) FOR TELEPHONE/VOICE TIE CABLES 5
44 RU
MDF 45 RU
NOTE:
ALL WORK SHOWN ON THIS DRAWING, UNLESS SPECIFICALLY NOTED OTHERWISE IS TO BE PROVIDED BY THE #6 Cu GROUND TO
DIVISION 17 CONTRACTOR. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THESE DOCUMENTS AND THE VERTICAL RACKS 6
ASSOCIATED SPECIFICATIONS.
F
RACK MOUNTING ON CONCRETE 1 INTERMEADIATE DISTRIBUTION FRAME RISER ELEVATION 1
2
F
Project Phase:
No Scale No Scale Construction
Documents
Project #: 0118.22
IDF# - PP #-PORT#
3/4" , 6" AFF, 8' H. Project Issued: 11/05/14
CONDUIT SLEEVES PENETRATE PLYWOOD BACKBOARD Sheet Issued:
THROUGH ACCESSIBLE CEILING PAINTED W/ FIRE
OR FLOOR WHERE APPLICABLE RESISTANT PAINT.
E E
BY DIV 16. BY DIV. 16 (1) 4PR UTP CAT- No. Date Revision
6
PLENUM RATED
CABLE FROM IDF
C C
Sheet Title:
Seal
T201