TUGAS 1 FISIKA BANGUNAN 2

Naufal Ghithrif Rif'at Husodo


18/428547/TK/47049
TUGAS 1 FISIKA BANGUNAN 2 13/03/2020

TUGAS 1 FISIKA BANGUNAN 2 / Table of contents

Table of contents
TUGAS 1 FISIKA BANGUNAN 2
Luminaire parts list.................................................................................................................................................................................................... 3
Views.........................................................................................................................................................................................................................4
TUGAS 1 FISIKA BANGUNAN 2
ES-SYSTEM S.A. - WHY 1S 1465 (1xLED).....................................................................................................................................................6
Site 1
Building 1
Storey 1
Room 1
Room summary....................................................................................................................................................................................... 9
Luminaire layout plan............................................................................................................................................................................ 10
Luminaire parts list.................................................................................................................................................................................11
Views..................................................................................................................................................................................................... 12
Workplane (Room 1) / Perpendicular illuminance (adaptive)................................................................................................................ 13

Page 2
TUGAS 1 FISIKA BANGUNAN 2 13/03/2020

TUGAS 1 FISIKA BANGUNAN 2 / Luminaire parts list

TUGAS 1 FISIKA BANGUNAN 2


Quantity Luminaire (Luminous emittance)
20 ES-SYSTEM S.A. - 2751301 WHY 1S 1465
Luminous emittance 1
Fitting: 1xLED
Light output ratio: 100%
Lamp luminous flux: 5300 lm
Luminaire luminous flux: 5300 lm See our luminaire catalog for
Power: 41.0 W an image of the luminaire.
Luminous efficacy: 129.3 lm/W

Colorimetric data
1x: CCT 4000 K, CRI 80

Total lamp luminous flux: 106000 lm, Total luminaire luminous flux: 106000 lm, Total Load: 820.0 W, Luminous efficacy: 129.3 lm/W

Page 3
TUGAS 1 FISIKA BANGUNAN 2 13/03/2020

TUGAS 1 FISIKA BANGUNAN 2 / Views

TUGAS 1 FISIKA BANGUNAN 2

Room 1 (47)

Page 4
TUGAS 1 FISIKA BANGUNAN 2 13/03/2020

TUGAS 1 FISIKA BANGUNAN 2 / Views

Room 1 (50)

Page 5
TUGAS 1 FISIKA BANGUNAN 2 13/03/2020

Site 1 / Building 1 / Storey 1 / ES-SYSTEM S.A. 2751301 WHY 1S 1465 1xLED / ES-SYSTEM S.A. - WHY 1S 1465 (1xLED)

ES-SYSTEM S.A. 2751301 WHY 1S 1465 1xLED

See our luminaire


catalog for an image of
the luminaire.

Light output ratio: 100%


Lamp luminous flux: 5300 lm
Luminaire luminous flux: 5300 lm
Power: 41.0 W
Luminous efficacy: 129.3 lm/W

Colorimetric data
1x: CCT 4000 K, CRI 80

Luminous emittance 1 / Polar LDC


135° 150° 165° 180° 165° 150° 135°
240

200

120° 160 120°

105° 80 105°

90° 90°

75° 75°

60° 60°

45° 30° 15° 0° 15° 30° 45°

cd/klm η = 100%
C0 - C180 C90 - C270

Page 6
TUGAS 1 FISIKA BANGUNAN 2 13/03/2020

Site 1 / Building 1 / Storey 1 / ES-SYSTEM S.A. 2751301 WHY 1S 1465 1xLED / ES-SYSTEM S.A. - WHY 1S 1465 (1xLED)

Luminous emittance 1 / Linear LDC


240

200

160

120

80

40

180° 135° 90° 45° 0° 45° 90° 135° 180°


cd/klm η = 100%
C0 - C180 C90 - C270

Luminous emittance 1 / Cone diagram

E(0°) 4620
1.6 E(C90) 57.5° 359
0.50 1.5 E(C0) 56.6° 387

E(0°) 1155
3.1 E(C90) 57.5° 90
1.0 3.0 E(C0) 56.6° 97

E(0°) 513
4.7 E(C90) 57.5° 40
1.5 4.5 E(C0) 56.6° 43

E(0°) 289
6.3 E(C90) 57.5° 22
2.0 6.1 E(C0) 56.6° 24

E(0°) 185
7.8 E(C90) 57.5° 14
2.5 7.6 E(C0) 56.6° 15

E(0°) 128
9.4 E(C90) 57.5° 10.0
3.0 9.1 E(C0) 56.6° 11
Distance [m] Cone diameter [m] Illuminance [lx]
C0 - C180 (Beam angle: 113.2°)
C90 - C270 (Beam angle: 115.0°)

Page 7
TUGAS 1 FISIKA BANGUNAN 2 13/03/2020

Site 1 / Building 1 / Storey 1 / ES-SYSTEM S.A. 2751301 WHY 1S 1465 1xLED / ES-SYSTEM S.A. - WHY 1S 1465 (1xLED)

Luminous emittance 1 / Luminance diagram


C225 C180 C135

C270 C90

10000

15000

20000

30000
C315 C0 C45

cd/m²
g = 65.0° g = 75.0° g = 85.0°

Luminous emittance 1 / UGR diagram


Glare evaluation according to UGR
ρ Ceiling 70 70 50 50 30 70 70 50 50 30
ρ Walls 50 30 50 30 30 50 30 50 30 30
ρ Floor 20 20 20 20 20 20 20 20 20 20
Room size Viewing direction at right angles Viewing direction parallel
X Y to lamp axis to lamp axis

2H 2H 21.4 22.4 22.2 23.1 24.0 21.6 22.5 22.3 23.3 24.1
3H 23.1 24.0 23.9 24.7 25.6 23.3 24.2 24.1 24.9 25.8
4H 23.9 24.7 24.6 25.4 26.4 24.1 24.9 24.8 25.6 26.6
6H 24.5 25.2 25.3 26.0 27.0 24.7 25.4 25.5 26.2 27.2
8H 24.8 25.5 25.6 26.3 27.2 24.9 25.6 25.7 26.4 27.4
12H 25.0 25.6 25.8 26.5 27.4 25.1 25.8 26.0 26.6 27.6
4H 2H 22.1 22.9 22.9 23.6 24.6 22.2 23.0 23.0 23.8 24.7
3H 23.9 24.6 24.8 25.4 26.4 24.1 24.8 24.9 25.6 26.6
4H 24.8 25.4 25.7 26.3 27.3 25.0 25.6 25.8 26.4 27.4
6H 25.6 26.1 26.5 27.0 28.0 25.8 26.3 26.6 27.1 28.2
8H 26.0 26.4 26.8 27.3 28.3 26.1 26.6 27.0 27.4 28.5
12H 26.2 26.7 27.1 27.5 28.6 26.4 26.8 27.2 27.6 28.7
8H 4H 25.2 25.6 26.0 26.5 27.6 25.3 25.8 26.2 26.6 27.7
6H 26.1 26.5 27.0 27.4 28.5 26.2 26.6 27.1 27.5 28.6
8H 26.6 26.9 27.5 27.8 28.9 26.7 27.0 27.6 27.9 29.0
12H 27.0 27.3 27.9 28.2 29.3 27.1 27.3 28.0 28.3 29.4
12H 4H 25.2 25.6 26.1 26.5 27.6 25.3 25.7 26.2 26.6 27.7
6H 26.2 26.6 27.1 27.4 28.6 26.3 26.7 27.2 27.6 28.7
8H 26.7 27.0 27.6 27.9 29.0 26.8 27.1 27.7 28.0 29.1
Variation of the observer position for the luminaire distances S
S = 1.0H +0.1 / -0.1 +0.1 / -0.1
S = 1.5H +0.2 / -0.3 +0.2 / -0.3
S = 2.0H +0.3 / -0.5 +0.3 / -0.5

Standard table BK07 BK07

Correction Summand 10.6 10.8

Corrected glare indices referring to 5300lm Total luminous flux

The UGR values are calculated in acc. with CIE Publ. 117. Spacing-
to-height ratio = 0.25

Page 8
TUGAS 1 FISIKA BANGUNAN 2 13/03/2020

Site 1 / Building 1 / Storey 1 / Room 1 / Room summary

Room 1

Clearance height: 3.050 m to 7.750 m, Reflection factors: Ceiling 80.5%, Walls 29.1%, Floor 59.0%, Light loss factor: 0.80

Workplane
Surface Result Average (Target) Min Max Min/average Min/max

1 Workplane (Room 1) Perpendicular illuminance (adaptive) [lx] 310 (≥ 500) 76.1 399 0.25 0.19
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

20 ES-SYSTEM S.A. - 2751301 WHY 1S 1465 5300 41.0 129.3

Total via all luminaires 106000 820.0 129.3

Lighting power density: 4.18 W/m² = 1.35 W/m²/100 lx (Floor area of room 196.00 m²)

Consumption: 1400 - 2250 kWh/a of maximum 6900 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 9
TUGAS 1 FISIKA BANGUNAN 2 13/03/2020

Site 1 / Building 1 / Storey 1 / Room 1 / Luminaire layout plan

Room 1

ES-SYSTEM S.A. 2751301 WHY 1S 1465

No. X [m] Y [m] Mounting height [m] Light loss factor


1 1.400 1.900 4.000 0.80
2 4.200 1.900 4.000 0.80
3 7.000 1.900 4.000 0.80
4 9.800 1.900 4.000 0.80
5 12.600 1.900 4.000 0.80
6 1.400 5.300 4.000 0.80
7 4.200 5.300 4.000 0.80
8 7.000 5.300 4.000 0.80
9 9.800 5.300 4.000 0.80
10 12.600 5.300 4.000 0.80
11 1.400 8.700 4.000 0.80
12 4.200 8.700 4.000 0.80
13 7.000 8.700 4.000 0.80
14 9.800 8.700 4.000 0.80
15 12.600 8.700 4.000 0.80
16 1.400 12.100 4.000 0.80
17 12.600 12.100 4.000 0.80
18 9.800 12.100 4.000 0.80
19 7.000 12.100 4.000 0.80
20 4.200 12.100 4.000 0.80

Page 10
TUGAS 1 FISIKA BANGUNAN 2 13/03/2020

Site 1 / Building 1 / Storey 1 / Room 1 / Luminaire parts list

Room 1
Quantity Luminaire (Luminous emittance)
20 ES-SYSTEM S.A. - 2751301 WHY 1S 1465
Luminous emittance 1
Fitting: 1xLED
Light output ratio: 100%
Lamp luminous flux: 5300 lm
Luminaire luminous flux: 5300 lm See our luminaire catalog for
Power: 41.0 W an image of the luminaire.
Luminous efficacy: 129.3 lm/W

Colorimetric data
1x: CCT 4000 K, CRI 80

Total lamp luminous flux: 106000 lm, Total luminaire luminous flux: 106000 lm, Total Load: 820.0 W, Luminous efficacy: 129.3 lm/W

Page 11
TUGAS 1 FISIKA BANGUNAN 2 13/03/2020

Site 1 / Building 1 / Storey 1 / Room 1 / Views

Room 1

Room 1 (49)

Page 12
TUGAS 1 FISIKA BANGUNAN 2 13/03/2020

Site 1 / Building 1 / Storey 1 / Room 1 / Workplane (Room 1) / Perpendicular illuminance (adaptive)

Workplane (Room 1) / Perpendicular illuminance (adaptive)

Workplane (Room 1): Perpendicular illuminance (adaptive) (Surface)


Light scene: Light scene 1
Average: 310 lx (Target: ≥ 500 lx), Min: 76.1 lx, Max: 399 lx, Min/average: 0.25, Min/max: 0.19
Height: 0.800 m, Wall zone: 0.000 m

Page 13
TUGAS 1 FISIKA BANGUNAN 2 13/03/2020

Site 1 / Building 1 / Storey 1 / Room 1 / Workplane (Room 1) / Perpendicular illuminance (adaptive)

Isolines [lx]

Scale: 1 : 100

Page 14
TUGAS 1 FISIKA BANGUNAN 2 13/03/2020

Site 1 / Building 1 / Storey 1 / Room 1 / Workplane (Room 1) / Perpendicular illuminance (adaptive)

False colors [lx]

Scale: 1 : 100

Page 15
TUGAS 1 FISIKA BANGUNAN 2 13/03/2020

Site 1 / Building 1 / Storey 1 / Room 1 / Workplane (Room 1) / Perpendicular illuminance (adaptive)

Value grid [lx]

Scale: 1 : 100

Page 16