LOCATION
FED FROM
MAIN SWITCH
FEEDER CONDUCTOR
Ckt
1
2
3
4
5
6
7
8
9
: SUB-PANELBOARD 3F
: CONTROL ROOM (3F)
: MAIN DISTRIBUTION PANELBOARD (GF)
: 100A 2P ISOLATOR
2
2
: 2-30mm THHN + 1-22mm TW EARTH CONDUCTOR in 100mm NMC
# of
outlet
Connected
Load (VA)
Current
(A)
Circuit Breaker
900
3.91
800
3.48
10
1000
4.35
2520
10.96
Control Room
1080
4.70
Fitness Room
1080
4.70
Study Room
1800
7.83
Bed Room 4
1080
4.70
Living Room 3,
Hallway
1440
6.26
2000
17
2000
17
2000
17
2000
17
4000
2.17
Load Description
Lighting ( 2-Circular Lamp, 4Fluorescent Lamp)
Lighting ( 2-Circular Lamp, 2Fluorescent Lamp)
Lighting ( 2-Circular Lamp, 1Chandelier, 1-Weather-Proof
Fluorescent Lamp, 1-Fan)
Convenience Outlet ( 7-Double
outlet at 180V)
Convenience Outlet ( 3-Double
outlet at 180V)
Convenience Outlet ( 3-Double
outlet at 180V)
Convenience Outlet ( 5-Double
outlet at 180V)
Convenience Outlet ( 3-Double
outlet at 180V)
Convenience Outlet ( 4-Double
outlet at 180V)
Location
Study Room, Bed
Room 4
Bedroom 3, Fitness
Room, Control Room
10
ACU
Bed Room 3
11
ACU
Living Room 3
12
ACU
Study Room
13
ACU
Bedroom 4
14
WH
T/B 4
22980
Conductor/ Conduit
2-2mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-2mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2
2-3.5mm THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
=
=
=
7980
0
12000
19980
PANELBOARD
LOCATION
FED FROM
MAIN SWITCH
FEEDER CONDUCTOR
Ckt
#
: SUB-PANELBOARD 2F
: LIVING ROOM 2 (2F)
: MAIN DISTRIBUTION PANELBOARD (GF)
: 100A 2P ISOLATOR
: 2-30mm2THHN + 1-22mm2 TW EARTH CONDUCTOR in 100mm NMC
ACU
ACU
WH
10
WH
11
12
13
14
Spare
Spare
Spare
Spare
1
2
4
5
Location
# of
outlet
Connected
Load (VA)
Current
(A)
Circuit Breaker
Conductor/ Conduit
Masters Bedroom,
T/B 2, Balcony
13
1300
5.65
Bedroom2, Living
Room 2, T/B 3, Stairs
13
1300
5.65
Load Description
Masters Bedroom,
Balcony
Living Room 2,
Hallway
Bed Room 2
2160
9.39
2160
9.39
1080
4.70
2000
17
Masters Bedroom
Bedroom 2
Living Room 2
T/B 2
T/B 3
2000
2000
17
17
4000
2.17
4000
2.17
22000
=
=
=
5000
0
14000
19000
PANELBOARD
LOCATION
FED FROM
MAIN SWITCH
FEEDER CONDUCTOR
Ckt
1
2
3
4
5
6
7
8
9
: SUB-PANELBOARD 1F
: DINING AREA BESIDE TOILET (1F)
: MAIN DISTRIBUTION PANELBOARD (1F)
: 100A 2P ISOLATOR
2
2
: 2-30mm THHN + 1-22mm TW EARTH CONDUCTOR in 100mm NMC
Location
# of
outlet
Connected
Load (VA)
Current
(A)
Circuit Breaker
Conductor/ Conduit
13
1300
5.65
Bedroom 1, T/B 1,
Hallway
10
1000
4.35
Garage
400
1.74
Living Room 1
900
3.91
Stairs
200
0.87
1800
7.83
720
3.13
2160
9.39
1440
16.26
2000
17
2000
17
500
2.17
Load Description
Lighting (1-Fan, 2-Fluorescent
Lamp, 4-Pinlight, 1-Chandelier)
Lighting (3-Circular Fluorescent
Lamp, 1-Fan, 1-Weather-Proof
Fluorescent Lamp)
Lighting (2- Weather-Proof
Fluorescent Lamp)
Lighting (4-Pinlight, 1-Chandilier)
Lighting (1- Weather-Proof
Fluorescent Lamp)
Convenience Outlet ( 5-Double
Outlet at 180V)
Convenience Outlet ( 2-WeatherProof Double Outlet at 180V)
Convenience Outlet ( 6-Double
outlet at 180V)
Convenience Outlet ( 4-Double
outlet at 180V)
Living Room 1
Garage
Kitchen, Bedroom 1
Dining Room, Hallway
10
ACU
Living Room 1
11
ACU
Dining Room
Kitchen
12
13
14
REF
Spare
Spare
TOTAL CONNECTED LOAD
14420
=
=
=
6920
500
4000
11420
PANEL BOARD
LOCATION
FED FROM
MAIN PROTECTION
SERVICE ENTRANCE CONDUCTOR
Ckt
Load Description
Location
# of
outlet
Connected
Load (VA)
Current
(A)
Circuit Breaker
SUB-PANEL BOARD 1F
1st floor
14420
49.65
SUB-PANEL BOARD 2F
2nd floor
22000
82.61
SUB-PANEL BOARD 3F
3rd floor
22980
86.87
Spare
TOTAL CONNECTED LOAD
59100
=
=
=
TOTAL:
50400VA/230V = 219.13 A
Use 2-30mm2THHN + 1-14mm2 TW Earth Conductor in 32mm NMC
Use 100A 2P ISOLATOR (as subpanel disconnecting switch)
19900
500
30000
50400
Conductor/ Conduit
2-30mm2THHN + 1-22mm2 TW Earth Conductor in
100mm NMC
2-30mm2THHN + 1-22mm2 TW Earth Conductor in
100mm NMC
2
2-80mm THHN + 1-60mm2 TW Earth Conductor in
100mm NMC