You are on page 1of 7

PANELBOARD

LOCATION
FED FROM
MAIN SWITCH
FEEDER CONDUCTOR
Ckt
1
2
3
4
5
6
7
8
9

: SUB-PANELBOARD 3F
: CONTROL ROOM (3F)
: MAIN DISTRIBUTION PANELBOARD (GF)
: 100A 2P ISOLATOR
2
2
: 2-30mm THHN + 1-22mm TW EARTH CONDUCTOR in 100mm NMC
# of
outlet

Connected
Load (VA)

Current
(A)

Circuit Breaker

900

3.91

15AT/100AF 2P, 1,230-V

800

3.48

15AT/100AF 2P, 1,230-V

T/B 4, Living Room 3,


Hallway

10

1000

4.35

15AT/100AF 2P, 1,230-V

Bed Room 3, Hallway,


Living Room 3

2520

10.96

15AT/100AF 2P, 1,230-V

Control Room

1080

4.70

25AT/100AF 2P, 1,230-V

Fitness Room

1080

4.70

25AT/100AF 2P, 1,230-V

Study Room

1800

7.83

15AT/100AF 2P, 1,230-V

Bed Room 4

1080

4.70

15AT/100AF 2P, 1,230-V

Living Room 3,
Hallway

1440

6.26

15AT/100AF 2P, 1,230-V

2000

17

25AT/100AF 2P, 1,230-V

2000

17

2000

17

2000

17

4000

2.17

Load Description
Lighting ( 2-Circular Lamp, 4Fluorescent Lamp)
Lighting ( 2-Circular Lamp, 2Fluorescent Lamp)
Lighting ( 2-Circular Lamp, 1Chandelier, 1-Weather-Proof
Fluorescent Lamp, 1-Fan)
Convenience Outlet ( 7-Double
outlet at 180V)
Convenience Outlet ( 3-Double
outlet at 180V)
Convenience Outlet ( 3-Double
outlet at 180V)
Convenience Outlet ( 5-Double
outlet at 180V)
Convenience Outlet ( 3-Double
outlet at 180V)
Convenience Outlet ( 4-Double
outlet at 180V)

Location
Study Room, Bed
Room 4
Bedroom 3, Fitness
Room, Control Room

10

ACU

Bed Room 3

11

ACU

Living Room 3

12

ACU

Study Room

13

ACU

Bedroom 4

14

WH

T/B 4

TOTAL CONNECTED LOAD

22980

25AT/100AF 2P, 1,230-V


25AT/100AF 2P, 1,230-V
25AT/100AF 2P, 1,230-V
25AT/100AF 2P, 1,230-V

Conductor/ Conduit
2-2mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-2mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2
2-3.5mm THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC

Feeder Conductor Rating:


Total Lighting and Convenience Outlet Load
900+800+1000+2520+1080+1080+1080+1080+1440 = 10980
First 3000 VA at 100% DF
3000
Rem 9660VA at 35% DF
2793
Lighting and Convenience Outlet Load after application of Demand Factor
Refrigerator and Cooking Range Outlet at 80% DF
Water Heater and ACU at 100% DF
TOTAL:
19980VA/230V = 86.87A
Use 2-30mm2THHN + 1-14mm2 TW Earth Conductor in 32mm NMC
Use 100A 2P ISOLATOR (as subpanel disconnecting switch)

=
=
=

7980
0
12000
19980

PANELBOARD
LOCATION
FED FROM
MAIN SWITCH
FEEDER CONDUCTOR
Ckt
#

: SUB-PANELBOARD 2F
: LIVING ROOM 2 (2F)
: MAIN DISTRIBUTION PANELBOARD (GF)
: 100A 2P ISOLATOR
: 2-30mm2THHN + 1-22mm2 TW EARTH CONDUCTOR in 100mm NMC

Lighting (4-Pinlight, 1-Chandelier,


1-Fluorescent Lamp, 1-WeatherProof Fluorescent Lamp, 1-Fan)
Lighting ( 3-Circular Lamp, 2Weather-Proof Fluorescent Lamp,
1-Chandelier, 1-Fan)
Convenience Outlet (5-Double
Outlet at 180V, 1-Weather-Proof
Double Outlet at 180V)
Convenience Outlet ( 6-Double
outlet at 180V)
Convenience Outlet ( 3-Double
outlet at 180V)
ACU

ACU

ACU

WH

10

WH

11
12
13
14

Spare
Spare
Spare
Spare

1
2

4
5

Location

# of
outlet

Connected
Load (VA)

Current
(A)

Circuit Breaker

Conductor/ Conduit

Masters Bedroom,
T/B 2, Balcony

13

1300

5.65

15AT/100AF 2P, 1,230-V

2-2mm2 THHN + 1-2mm2 TW Earth Conductor in


20mm NMC

Bedroom2, Living
Room 2, T/B 3, Stairs

13

1300

5.65

15AT/100AF 2P, 1,230-V

2-2mm2 THHN + 1-2mm2 TW Earth Conductor in


20mm NMC

Load Description

Masters Bedroom,
Balcony
Living Room 2,
Hallway
Bed Room 2

2160

9.39

15AT/100AF 2P, 1,230-V

2160

9.39

15AT/100AF 2P, 1,230-V

1080

4.70

2000

17

Masters Bedroom

Bedroom 2

Living Room 2

T/B 2

T/B 3

TOTAL CONNECTED LOAD

2000
2000

17
17

4000

2.17

4000

2.17

22000

15AT/100AF 2P, 1,230-V


15AT/100AF 2P, 1,230-V
25AT/100AF 2P, 1,230-V
25AT/100AF 2P, 1,230-V
25AT/100AF 2P, 1,230-V
25AT/100AF 2P, 1,230-V

2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in


20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2
2
2-3.5mm THHN + 1-2mm TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC

Feeder Conductor Rating:


Total Lighting and Convenience Outlet Load
1300+1300+2160+2160+1080 = 8000
First 3000 VA at 100% DF
3000
Rem 5400VA at 35% DF
1750
Lighting and Convenience Outlet Load after application of Demand Factor
Refrigerator and Cooking Range Outlet at 80% DF
Water Heater and ACU at 100% DF
TOTAL:
19000VA/230V = 82.61 A
Use 2-30mm2THHN + 1-14mm2 TW Earth Conductor in 32mm NMC
Use 100A 2P ISOLATOR (as subpanel disconnecting switch)

=
=
=

5000
0
14000
19000

PANELBOARD
LOCATION
FED FROM
MAIN SWITCH
FEEDER CONDUCTOR
Ckt
1
2
3
4
5
6
7
8
9

: SUB-PANELBOARD 1F
: DINING AREA BESIDE TOILET (1F)
: MAIN DISTRIBUTION PANELBOARD (1F)
: 100A 2P ISOLATOR
2
2
: 2-30mm THHN + 1-22mm TW EARTH CONDUCTOR in 100mm NMC
Location

# of
outlet

Connected
Load (VA)

Current
(A)

Circuit Breaker

Conductor/ Conduit

Kitchen, Dining Room

13

1300

5.65

15AT/100AF 2P, 1,230-V

2-2mm2 THHN + 1-2mm2 TW Earth Conductor in


20mm NMC

Bedroom 1, T/B 1,
Hallway

10

1000

4.35

15AT/100AF 2P, 1,230-V

2-2mm2 THHN + 1-2mm2 TW Earth Conductor in


20mm NMC

Garage

400

1.74

15AT/100AF 2P, 1,230-V

Living Room 1

900

3.91

15AT/100AF 2P, 1,230-V

Stairs

200

0.87

1800

7.83

720

3.13

2160

9.39

25AT/100AF 2P, 1,230-V

1440

16.26

25AT/100AF 2P, 1,230-V

2000

17

2000

17

500

2.17

Load Description
Lighting (1-Fan, 2-Fluorescent
Lamp, 4-Pinlight, 1-Chandelier)
Lighting (3-Circular Fluorescent
Lamp, 1-Fan, 1-Weather-Proof
Fluorescent Lamp)
Lighting (2- Weather-Proof
Fluorescent Lamp)
Lighting (4-Pinlight, 1-Chandilier)
Lighting (1- Weather-Proof
Fluorescent Lamp)
Convenience Outlet ( 5-Double
Outlet at 180V)
Convenience Outlet ( 2-WeatherProof Double Outlet at 180V)
Convenience Outlet ( 6-Double
outlet at 180V)
Convenience Outlet ( 4-Double
outlet at 180V)

Living Room 1
Garage
Kitchen, Bedroom 1
Dining Room, Hallway

10

ACU

Living Room 1

11

ACU

Dining Room

Kitchen

12
13
14

REF
Spare
Spare
TOTAL CONNECTED LOAD

14420

15AT/100AF 2P, 1,230-V


15AT/100AF 2P, 1,230-V
25AT/100AF 2P, 1,230-V

25AT/100AF 2P, 1,230-V


25AT/100AF 2P, 1,230-V
25AT/100AF 2P, 1,230-V

2-3.5mm THHN + 1-2mm TW Earth Conductor in


20mm NMC
2
2-3.5mm THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC
2-3.5mm2 THHN + 1-2mm2 TW Earth Conductor in
20mm NMC

Feeder Conductor Rating:


Total Lighting and Convenience Outlet Load
1300+1000+400+900+200+1800+720+2160+1440= 9920
First 3000 VA at 100% DF
3000
Rem 5740VA at 35% DF
2422
Lighting and Convenience Outlet Load after application of Demand Factor
Refrigerator and Cooking Range Outlet at 80% DF
Water Heater and ACU at 100% DF
TOTAL:
11420VA/230V = 49.65 A
Use 2-30mm2THHN + 1-14mm2 TW Earth Conductor in 32mm NMC
Use 100A 2P ISOLATOR (as subpanel disconnecting switch)

=
=
=

6920
500
4000
11420

PANEL BOARD
LOCATION
FED FROM
MAIN PROTECTION
SERVICE ENTRANCE CONDUCTOR

Ckt

Load Description

: MAIN DISTRIBUTION PANELBOARD


: DINING AREA BESIDE TOILET (GF)
: SERVICE ENTRANCE (MERALCO 3 WIRE, 1, 230-V SUPPLY)
: 275AT/350AF 2P MCCB
2
2
: 2-250mm THHN + 1-200mm TW EARTH CONDUCTOR in 500mm NMC

Location

# of
outlet

Connected
Load (VA)

Current
(A)

Circuit Breaker

SUB-PANEL BOARD 1F

1st floor

14420

49.65

110AT/200AF 2P, 1,230-V

SUB-PANEL BOARD 2F

2nd floor

22000

82.61

110AT/200AF 2P, 1,230-V

SUB-PANEL BOARD 3F

3rd floor

22980

86.87

150AT/200AF 2P, 1,230-V

Spare
TOTAL CONNECTED LOAD

59100

Service Entrance Conductor Rating:


Total Lighting and Convenience Outlet Load
12660+8400+8740= 29800
First 3000 VA at 100% DF
3000
Rem 26800VA at 35% DF
9380
Lighting and Convenience Outlet Load after application of Demand Factor
Refrigerator and Cooking Range Outlet at 80% DF
Water Heater and ACU at 100% DF

=
=
=
TOTAL:

50400VA/230V = 219.13 A
Use 2-30mm2THHN + 1-14mm2 TW Earth Conductor in 32mm NMC
Use 100A 2P ISOLATOR (as subpanel disconnecting switch)

19900
500
30000
50400

Conductor/ Conduit
2-30mm2THHN + 1-22mm2 TW Earth Conductor in
100mm NMC
2-30mm2THHN + 1-22mm2 TW Earth Conductor in
100mm NMC
2
2-80mm THHN + 1-60mm2 TW Earth Conductor in
100mm NMC

You might also like